DATE:
.....
SIGN:
.....
Clint:- M/s The Adani Dharma Port company Limited
NAME:
Project:- Thyssenkrupp I. I Pvt. Ltd. .....
3) Housing derating
This shows that bars are capable of working in above condition, without much of
Hence Design is safe.
Note:- Tables were taken as reference from K.C. Agarwal Book.
Tables were taken as reference from K.C. Agarwal Book.
1of4
= = 20
10
From the Table "5" & interploating, we get value of "K" = 1.15
Since, RAC
= K
RDC
here,'S' is space between two bars and 'a' & 'b' are thickness & width of the bar respectivily.
= 1.26 x 95 10
&
10 + 200 200
&
= 0.57 0.05
= 0.06 m/mtr.
m/mtr.
(Due to double layer design, value of "Z" become halved)
Voltage Drop = IxZ
= 3200 x 0.06
= 192 mV/mtr.
2of4
= 0.192 V/mtr.
= 0.096 V/mtr.
( for Phase splitting and interleaved design,volatge drop get halved)
This show's that, the voltage drop is minimum for mtr. Length run
Thisshow'sthat,thevoltagedropisminimumformtr.Lengthrun
Power loss,
PL = Vd x I
= 0.096 x 3200
PL = 307 watts
PL = 0.307 KW
Minium cross section of conductor required to withstand temp rise due to short circuit current
it can be calculate by formula
Hence, Area is
A = 50 x 1000 x 1
2.17 x 10^4 Log 10 200 + 258
85 + 258
A = 6.76 Sq.cm
The cross section area of provided conductor is 40 sqcm which is above the requirement .
3of4
K = Space factor for rectangular conductor's which is function
of size & spacing between two conductor.
a = Thickness of conductor pair( i.e.10mm)
b = Width of conductor (i.e. 200 mm)
S-a = 95 - 10 = 0.4
a+b 10+ 200
And
a = 10 = 0.05
b 200
Each phase having two circuit,hence[ISC = 50KA /2] , So, the force developed during short circuit is given
(Putting in above formula)
Fm = 6842.1 N/m
or Fm = 697.6 Kg/m
The supports used at every 200 mm apart for this total force acting on each support shall be
= 697.6 x 0.2
= 139.5 .."A"
STRESS ON BUS BAR SUPPORT
4of4