** Based on 1/2 inch water (0.12 kPa) external restriction and 1000 ft (300m) altitude.
*** Based on instantaneous voltage dip as defined per NEMA MG-1.
**** See your Caterpillar dealer and/or Spec Sheet for technical information.
***** Package Power Tolerance: +/- 5%
Maximum voltage distortion due to non-linear load calculated to be within specified limits.
Overall dimensions and weight not to be used for installation. Contact your Caterpillar dealer for specific dimension drawings.
Caterpillar makes no express warranties and disclaims all implied warranties including merchantability and fitness for a particular purpose regarding program. Caterpillar shall have no liability in law or
equity for damages consequential or otherwise arising from use of program and related material or any part thereof. The analysis provided from SpecSizer is only for the expected results at the generator
terminals. Analysis of transient conditions of any device downstream is the responsibility of the system designer.
Project Load Report
Modified Date 22-Feb-2017 Rating Type Mission Critical Standby Max Ambient Temperature 50 Deg. C
Customer Name SKCH Fuel Diesel Altitude 152.4 M.A.S.L.
Project Name/Ref # SKCH Fujaira Electricity Supply 50 Hz 400/230 V
Prepared By Husni Khalil
Load Details Permitted Dip Predicted Dip Load Analysis
Load Transient Resultant Cumulative
Load Description Frequency Voltage Frequency Voltage Running Fdip: Vdip 1: Vdip 2:
Step Inrush Peak Running
SkVA SkW kVA kW SkVA SkW kVA kW
Step 1 Step Passed
https://specsizer.cat.com/Project/GeneratorSetDetails/FrequencyVoltageChart.aspx?width=150&height=100&slope=2&slopeMod=1.006&knee=0.4&maxF=1.9298687664042&maxV=2.29199529125584&rtime=2.11955389336658
Step 1 Total 10% 10% 1.9% 3.1% 977.4 919.1 1,414.2 1,313.7
Total Through Step 1 977.4 919.1 1,414.2 1,313.7
Step 2 Step Passed
https://specsizer.cat.com/Project/GeneratorSetDetails/FrequencyVoltageChart.aspx?width=150&height=100&slope=2&slopeMod=1.006&knee=0.4&maxF=1.76251968503937&maxV=3.04513432026264&rtime=1.90376404328365
Step 2 Total 10% 10% 1.8% 3.0% 989.6 839.4 985.5 852.9
Total Through Step 2 2,394.5 2,153.1 2,393.6 2,166.6
Step 3 Step Passed
https://specsizer.cat.com/Project/GeneratorSetDetails/FrequencyVoltageChart.aspx?width=150&height=100&slope=2&slopeMod=1.006&knee=0.4&maxF=2.19695538057743&maxV=2.90017749847553&rtime=2.44951503333483
Step 3 Total 10% 10% 2.2% 3.6% 1,244.5 1,046.3 1,493.5 1,271.8
Total Through Step 3 3,630.8 3,212.9 3,881.2 3,438.4
Load Details Permitted Dip Predicted Dip Load Analysis
Load Transient Resultant Cumulative
Load Description Frequency Voltage Frequency Voltage Running Fdip: Vdip 1: Vdip 2:
Step Inrush Peak Running
SkVA SkW kVA kW SkVA SkW kVA kW
Step 4 Running kW requirements
https://specsizer.cat.com/Project/GeneratorSetDetails/FrequencyVoltageChart.aspx?width=150&height=100&slope=2&slopeMod=1.006&knee=0.4&maxF=0.447874015748032&maxV=0.822125971818837&rtime=0.426095578781649
Step 4 Total 10% 10% 0.4% 0.8% 259.0 213.3 297.0 255.4
Total Through Step 4 4,138.4 3,651.7 4,177.8 3,693.7
Intermittent Step Running kW requirements
https://specsizer.cat.com/Project/GeneratorSetDetails/FrequencyVoltageChart.aspx?width=150&height=100&slope=2&slopeMod=1.006&knee=0.4&maxF=0.0600524934383202&maxV=0.12464444373422&rtime=0.045646634406214
Step 5 Total 10% 10% 0.1% 0.1% 52.0 28.6 45.7 41.2
Total Through Step 5 4,177.7 3,681.2 4,177.8 3,693.7
Modified Date 22-Feb-2017 Electricity Supply 50 Hz 400/230 V Rating Type Mission Critical
Customer Name SKCH Fuel Diesel Standby
Project Name/Ref # SKCH Fujaira Max. Ambient Temperature 50.0 C
Prepared By Husni Khalil Altitude 152.4 M.A.S.L.
Load Scenario
Step 4 Selection Criteria: Running kW requirements
https://specsizer.cat.com/Project/GeneratorSetDetails/FrequencyVoltageChart.aspx?leg=true&slope=2&slopeMod=1.006&knee=0.4&maxF=0.447874015748032&maxV=0.822125971818837&rtime=0.426095578781649
Fdip: Vdip 1: Vdip 2:
* Block Load (only) Transient Response values are at factory conditions. Genset block
Recovery Time (sec)
load capabilities at site conditions may vary from factory transient response test results
due to a variance in site altitude or ambient conditions.
Elevator motors may generate electric power. The regenerative power absorption
capability of this generating set is 65.59 EkW.