Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

SECTION 2 - TECHNICAL DATA (P14X/EN AD/DE6)

MECHANICAL SPECIFICATIONS Rear Communications Port


EIA(RS)485 signal levels, two wire connections
Design located on general purpose block, M4 screw.
For screened twisted pair cable, multi-drop, 1000 m
Modular MiCOM Px40 platform relay, P141/142/P144-
max.
40TE (206 mm (8)) case and P143/P145 (309.6 mm
For K-Bus, IEC-870-5-103, or DNP3 protocol
(12)) case. Mounting is front of panel flush mounting,
(ordering options).
or 19 rack mounted (ordering options).
Isolation to SELV level.
Enclosure Protection
Per IEC 60529: 1992
Optional Second Rear Communications
IP 52 Protection (front panel) against dust and Port
dripping water. EIA(RS)232, 9 pin D-type female connector, socket
IP 50 Protection for the rear and sides of the case SK4.
against dust. Courier protocol: K-Bus, EIA(RS)232, or EIA(RS)485
IP 10 Product safety protection for the rear due to live connection.
connections on the terminal block. Isolation to SELV level.

Weight Optional Rear IRIG-B Interface modulated


Case 40TE: approx. 7.3 kg or un-modulated
Case 60TE: approx. 9.2 kg BNC socket
Isolation to SELV level.
50 ohm coaxial cable.
Optional Rear Fiber Connection for
TERMINALS SCADA/DCS
BFOC 2.5 -(ST)-interface for glass fiber, as per IEC
AC Current and Voltage Measuring Inputs 874-10.
Located on heavy duty (black) terminal block: 850 nm short-haul fibers, one Tx and one Rx. For
Threaded M4 terminals, for ring lug connection. Courier, IEC-870-5-103, DNP3 or MODBUS protocol
CT inputs have integral safety shorting, upon removal (ordering options).
of the terminal block. Optional Rear Ethernet Connection for
General Input/Output Terminals IEC 61850 or DNP3.0
For power supply, opto inputs, output contacts and Optional redundant Rear Ethernet Connection
COM1 rear communications. (optical)
Located on general purpose (grey) blocks:
Threaded M4 terminals, for ring lug connection. 10BaseT/100BaseTX Communications
Interface in accordance with IEEE802.3 and IEC
Case Protective Earth Connection 61850
Two rear stud connections, threaded M4. Isolation: 1.5 kV
Must be earthed (grounded) for safety, minimum earth Connector type: RJ45
wire size 2.5 mm2. Cable type: Screened Twisted Pair (STP)
100 Base FX Interface
Front Port Serial PC Interface Interface in accordance with IEEE802.3 and IEC
EIA(RS)232 DTE, 9 pin D-type female connector.
61850
Courier protocol for interface to MiCOM S1 software.
Wavelength: 1300 nm
Isolation to ELV level.
Fiber: multi-mode 50/125 m or 62.5/125
Maximum cable length 15 m.
m

Front Download/Monitor Port Connector style: BFOC 2.5 -(ST )
EIA(RS)232, 25 pin D-type female connector.
For firmware downloads.
Isolation to ELV level.

Page (AD) -14 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

RATINGS Power Supply Interruption


Per IEC 60255-11: 1979
AC Measuring Inputs The relay will withstand a 20 ms interruption in
the DC auxiliary supply, without de-energizing.
Nominal frequency: 50 and 60 Hz (settable)
Per IEC 61000-4-11: 1994
Operating range: 45 to 65 Hz
The relay will withstand a 20 ms interruption in
Phase rotation: ABC
an AC auxiliary supply, without de-energizing.
AC Current
Nominal current (In): 1 and 5 A dual rated. (1A and 5A
Battery Backup
Front panel mounted
inputs use different transformer tap Connections,
Type AA, 3.6 V (SAFT advanced battery reference
check correct terminals are wired).
LS14250) Battery life (assuming relay energized for
Nominal burden per phase: < 0.15 VA at In
90% time) >10 years
Thermal withstand: continuous 4 In
for 10 s: 30 In Field Voltage Output
for 1 s; 100 In Regulated 48 Vdc
Linear to 64 In (non-offset AC current). Current limited at 112 mA maximum output
AC Voltage Digital (Opto) Inputs
Nominal voltage (Vn): 100 to 120 V or 380 to 480 V Universal opto inputs with programmable voltage
phase-phase (min. 196 Vac, max. 560 Vac). thresholds (24/27, 30/34, 48/54, 110/125, 220/250 V).
Nominal burden per phase: < 0.02 VA at Vn. May be energized from the 48 V field voltage, or the
Thermal withstand: continuous 2 Vn external battery supply.
for 10 s: 2.6 Vn Rated nominal voltage: 24 to 250 Vdc
Operating range: 19 to 265 Vdc
POWER SUPPLY Withstand: 300 Vdc, 300 Vrms.
Peak current of opto input when energized is 3.5 mA
Auxiliary Voltage (Vx) (0-300 V)
Three ordering options: Nominal pick-up and reset thresholds:
(i) Vx: 24 to 48 Vdc Nominal battery 24/27: 60 - 80% DO/PU
Vx: 48 to 110 Vdc, and 40 to 100 Vac (rms) (logic 0) <16.2 (logic 1) >19.2
Vx: 110 to 250 Vdc, and Nominal battery 24/27: 50 - 70% DO/PU
100 to 240 Vac (rms) (logic 0) <12.0 (logic 1) >16.8
Nominal battery 30/34: 60 - 80% DO/PU
Operating Range (logic 0) <20.4 (logic 1) >24.0
19 to 65 V (dc only for this variant) Nominal battery 30/34: 50 - 70% DO/PU
37 to 150 V (dc), 32 to 110 V (ac) (logic 0) <15.0 (logic 1) >21.0
87 to 300 V (dc), 80 to 265 V (ac) Nominal battery 48/54: 60 - 80% DO/PU
With a tolerable ac ripple of up to 12% for a dc supply, (logic 0) <32.4 (logic 1) >38.4
per IEC 60255-11: 1979. Nominal battery 48/54: 50 - 70% DO/PU
Nominal Burden (logic 0) <24.0 (logic 1) >33.6
Quiescent burden: 11 W. (Extra 1.25 W when fitted Nominal battery 110/125: 60 - 80% DO/PU
with second rear Courier) (logic 0) <75.0 (logic 1) >88.0
Additions for energized binary inputs/outputs: Nominal battery 110/125: 50 - 70% DO/PU
Per opto input: 0.09 W (24 to 54 V), (logic 0) <55.0 (logic 1) >77.0
0.12 W (110/125 V), Nominal battery 220/250: 60 - 80% DO/PU
0.19 W (220/120 V). (logic 0) <150.0 (logic 1) >176.0
Per energized output relay: 0.13 W Nominal battery 220/250: 50 - 70% DO/PU
(logic 0) <110 (logic 1) >154
Power-up Time Recognition time:
Time to power up < 11 s. <2 ms with long filter removed,
<12 ms with half cycle ac immunity filter on

P14x/EN AD/Gf7 Page (AD)-15


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

OUTPUT CONTACTS High Break Contacts (Model D only)


Continuous Carry Ratings (Not Switched):
Standard Contacts Maximum continuous current: 10 A
Short duration withstand carry: 30 A for 3 s
General purpose relay outputs for signaling, tripping
250A for 30ms
and alarming:
Rated voltage: 300 V
Continuous Carry Ratings (Not Switched):
Maximum continuous current: 10 A (UL: 8 A) Make & Break Capacity:
Short duration withstand carry: 30 A for 3 s DC: 7500 W resistive
250A for 30ms DC: 2500 W inductive (L/R = 50 ms)
Rated voltage: 300 V
Make, Carry:
Make & Break Capacity: 30 A for 3 secs, dc resistive, 10,000 operations
DC: 50 W resistive (subject to the above limits of make/break
DC: 62.5 W inductive (L/R = 50 ms) capacity & rated voltage)
AC: 2500 VA resistive (cos = unity)
AC: 2500 VA inductive (cos = 0.7) Make, Carry & Break:
30 A for 3 secs, dc resistive, 5,000 operations
Make, Carry: (subject to the above limits of make/break
30 A for 3 secs, dc resistive, 10,000 operations capacity & rated voltage)
(subject to the above limits of make/break 30 A for 200 ms, dc resistive, 10,000 operations
capacity and rated voltage) (subject to the above limits of make/break
capacity & rated voltage)
Make, Carry & Break: 10 A (*), dc inductive, 10,000 operations
30 A for 200 ms, ac resistive, 2,000 operations (subject to the above limits of make/break
(subject to the above limits of make/break capacity & rated voltage)
capacity & rated voltage) *Typical for repetitive shots - 2 minutes idle for
4A for 1.5 secs, dc resistive, 10,000 operations thermal dissipation
(subject to the above limits of make/break
capacity & rated voltage)
No. of Shots in 1
Voltage Current L/R
0.5 A for 1 sec, dc inductive, 10,000 sec
operations (subject to the above limits of 65 V 10 A 40 ms 5
make/break capacity & rated voltage) 150 V 10 A 40 ms 4
10 A for 1.5 secs, ac resistive/inductive,
10,000 operations (subject to the above limits of 250 V 10 A 40 ms 2
make/break capacity & rated voltage) 250 V 10 A 20 ms 4
MOV protection: Max Voltage 330 V dc
Durability:
Loaded contact: 10 000 operations minimum Durability:
Unloaded contact: 100 000 operations minimum Loaded contact: 10 000 operations minimum
Operate Time Less than 5 ms Unloaded contact: 100 000 operations minimum
Reset Time Less than 5 ms Operate Time: Less than 0.2 ms
Reset Time: Less than 8 ms
Watchdog Contacts
Non-programmable contacts for relay healthy/relay fail
indication:
Breaking capacity:
DC: 30 W resistive
DC: 15 W inductive (L/R = 40 ms)
AC: 375 VA inductive (cos = 0.7)

Page (AD) -16 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

IRIG-B 12X Interface (Modulated) TYPE TESTS


External clock synchronization per IRIG standard 200-
98, format B12X. Insulation
Input impedance 6 k at 1000 Hz Per IEC 60255-27: 2005
Modulation ratio: 3:1 to 6:1
Insulation resistance > 100 M at 500 Vdc
Input signal, peak-peak: 200 mV to 20 V
(Using only electronic/brushless insulation tester).
IRIG-B 00X Interface (Un-modulated) Creepage Distances and Clearances
External clock synchronization per IRIG standard 200-
Per EN 61010-1: 2001
98, format B00X.
Pollution degree 2,
Input signal TTL level
Overvoltage category III,
Input impedance at dc 10 k Impulse test voltage 5 kV.
High Voltage (Dielectric) Withstand
EIA(RS)232 ports excepted.
(i) Per IEC 60255-27: 2005, 2 kV rms AC, 1 minute:
Between all case terminals connected together,
ENVIRONMENTAL CONDITIONS and the case earth.
Also, between all terminals of independent
Ambient Temperature Range circuits.
Per IEC 60255-6: 1988 1 kV rms AC for 1 minute, across open
Operating temperature range: watchdog contacts.
-25C to +55C (or -13F to +131F). 1 kV rms AC for 1 minute, across open contacts
Storage and transit: of changeover output relays.
-25C to +70C (or -13F to +158F). (ii) Per ANSI/IEEE C37.90-1989 (reaffirmed 1994):
Tested as per 1.5 kV rms AC for 1 minute, across open
IEC 60068-2-1: 2007 contacts of changeover output relays.
-25C storage (96 hours)
-40C operation (96 hours) Impulse Voltage Withstand Test
IEC 60068-2-2: 2007 Per IEC 60255-27: 2005
+85C storage (96 hours) Front time: 1.2 s, Time to half-value: 50 s,
Peak value: 5 kV, 0.5 J
Ambient Humidity Range Between all terminals, and all terminals and case
Per IEC 60068-2-3: 1969: earth.
56 days at 93% relative humidity and +40C
Per IEC 60068-2-30: 1980:
Damp heat cyclic, six (12 + 12) hour cycles,
93% RH, +25 to +55C

P14x/EN AD/Gf7 Page (AD)-17


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

ELECTROMAGNETIC Immunity to Radiated Electromagnetic


Energy
COMPATIBILITY (EMC) Per IEC 60255-22-3: 2000, Class III:
Test field strength, frequency band 80 to 1000
1 MHz Burst High Frequency Disturbance MHz: 10 V/m,
Test Test using AM: 1 kHz / 80%,
Per IEC 60255-22-1: 1988, Class III, Spot tests at 80, 160, 450, 900 MHz
Common-mode test voltage: 2.5 kV, Per IEEE/ANSI C37.90.2: 1995:
Differential test voltage: 1.0 kV, 25 MHz to 1000 MHz, zero and 100% square wave
Test duration: 2 s, Source impedance: 200 modulated.
EIA(RS)232 ports excepted. Field strength of 35 V/m.
100 kHz Damped Oscillatory Test Radiated Immunity from Digital
Per EN61000-4-18: 2007: Level 3 Communications
Common mode test voltage: 2.5 kV Per EN61000-4-3: 2002, Level 4:
Differential mode test voltage: 1 kV Test field strength, frequency band 800 to 960 MHz,
Immunity to Electrostatic Discharge and 1.4 to 2.0 GHz: 30 V/m,
Per IEC 60255-22-2: 1996, Class 4, Test using AM: 1 kHz / 80%.
15 kV discharge in air to user interface, display, Radiated Immunity from Digital Radio
and exposed metalwork.
Per IEC 60255-22-2: 1996, Class 3,
Telephones
Per ENV 50204: 1995
8 kV discharge in air to all communication ports.
10 V/m, 900 MHz and 1.89 GHz.
6 kV point contact discharge to any part of the
front of the product. Immunity to Conducted Disturbances
Electrical Fast Transient or Burst Induced by Radio Frequency Fields
Requirements Per IEC 61000-4-6: 1996, Level 3,
Disturbing test voltage: 10 V
Per IEC 60255-22-4: 2002. Test severity Class III and
IV: Power Frequency Magnetic Field
Amplitude: 2 kV, burst frequency 5 kHz
Immunity
(Class III),
Per IEC 61000-4-8: 1994, Level 5,
Amplitude: 4 kV, burst frequency 2.5 kHz (Class IV).
100 A/m applied continuously,
Applied directly to auxiliary supply, and applied
1000 A/m applied for 3 s.
to all other inputs. EIA(RS)232 ports excepted.
Per IEC 61000-4-9: 1993, Level 5,
Surge Withstand Capability 1000 A/m applied in all planes.
IEEE/ANSI C37.90.1:2002: Per IEC 61000-4-10: 1993, Level 5,
4 kV fast transient and 2.5 kV oscillatory applied 100 A/m applied in all planes at 100 kHz/1MHz
common mode and differential mode to opto inputs with a burst duration of 2 s.
(filtered), output relays, CTs, VTs, power supply, field
Conducted Emissions
voltage.
Per EN 55022: 1998: Class A:
4 kV fast transient and 2.5 kV oscillatory applied
0.15 - 0.5 MHz, 79 dBV (quasi peak)
common mode to communications, IRIG- B.
66 dBV (average)
Surge Immunity Test 0.5 30 MHz, 73 dBV (quasi peak)
EIA(RS)232 ports excepted. 60 dBV (average).
Per IEC 61000-4-5: 2005 Level 4,
Time to half-value: 1.2/50 s, Radiated Emissions
Amplitude: 4 kV between all groups and case earth, Per EN 55022: 1998: Class A:
Amplitude: 2 kV between terminals of each group. 30 230 MHz, 40 dBV/m at 10 m
measurement distance
230 1 GHz, 47 dBV/m at 10 m measurement
distance.

Page (AD) -18 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

EU DIRECTIVES MECHANICAL ROBUSTNESS


EMC Compliance Vibration Test
Per 89/336/EEC: Per IEC 60255-21-1: 1996
Compliance to the European Commission Directive on Response Class 2
EMC is claimed via the Technical Construction File Endurance Class 2
route. Product Specific Standards were used to
establish conformity: EN50263: 2000 Shock and Bump
Per IEC 60255-21-2: 1995
Product Safety Shock response Class 2
Per 2006/95/EC: Shock withstand Class 1
Compliance to the European Commission Low Bump Class 1
Voltage Directive. (LVD) is demonstrated using a
Technical File. Seismic Test
A product specific standard was used to establish Per IEC 60255-21-3: 1995
conformity. Class 2
EN 60255-27: 2005

R&TTE Compliance P14X THIRD PARTY COMPLIANCES


Radio and Telecommunications Terminal Equipment
(R&TTE) directive 99/5/EC. Underwriters Laboratory (UL)
Compliance demonstrated by compliance to both the
EMC directive and the Low voltage directive, down to
zero volts.
Applicable to rear communications ports.
File Number: E202519
ATEX Compliance Issue Date: 21-04-2005
ATEX Potentially Explosive Atmospheres directive
(Complies with Canadian and US requirements).
94/9/EC, for equipment.
Energy Networks Association (ENA)
The equipment is compliant with Article 1(2) of
European directive 94/9/EC.
It is approved for operation outside an ATEX
hazardous area. It is however approved for
connection to Increased Safety, Ex e, motors with
Certificate Number: 101 Issue 3
rated ATEX protection, Equipment Category 2, to
Assessment Date: 10-12-2004
ensure their safe operation in gas Zones 1 and 2
Type (s): P141, P142, P143 & P145
hazardous areas.
CAUTION - Equipment with this marking is not itself
suitable for operation within a potentially explosive
atmosphere.
Compliance demonstrated by Notified Body
certificates of compliance.

II (2) G

P14x/EN AD/Gf7 Page (AD)-19


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

* Reference conditions TMS = 1, TD = 1 and IN >


PROTECTION FUNCTIONS setting of 100 mA, operating range 2-0 In

Three Phase Overcurrent Protection REF


Accuracy Pick-up: Setting formula 5%
Additional tolerance X/R ratios: 5% over X/R 190 Drop-off: 0.80 x setting formula 5%
Overshoot: <30 ms Operating time: <60 ms
High pick up: Setting 5%
Inverse Time Characteristic High operating time: <30 ms
Accuracy Repeatability: <15%
DT Pick-up: Setting 5% Wattmetric SEF
Minimum IDMT trip level: 1.05 x setting 5% Pick-up For P=0W
Drop-off: 0.95 x setting 5% ISEF> 5% or P> 5%
IDMT shape: 5% or 40 ms whichever is greater Drop off: For P>0W
IEEE reset: 5% or 50 ms whichever is greater (0.95 x ISEF>) 5% or 0.9 x P> 5%
DT operation: 2% or 50 ms, whichever is greater Boundary accuracy: 5% with 1o hysteresis
DT reset: 5% Repeatability: 5%
Directional boundary (RCA 90%): 2% hysteresis 2o SEF Cos(PHI)/
Characteristic: UK curves IEC 60255-3 1998 Pick-up: Setting 5% for angles RCA60o
US curves: IEEEC37.1121996 Drop-off: 0.90 x Setting
IDMT shape: 5% or 50 ms whichever is greater *
Earth/Sensitive Fault Protection IEEE reset: 7.5% or 60 ms whichever is greater
Earth Fault 1 DT operation: 2% or 50 ms whichever is greater
DT Pick-up: Setting 5% DT reset: 5%
Minimum IDMT trip level: 1.05 x Setting 5% Repeatability:2%
Drop-off: 0.95 x Setting 5% * Reference conditions TMS = 1, TD = 1 and IN >
IDMT shape: 5% or 40 ms whichever is greater * setting of 100 mA, operating range 2-0 In
IEEE reset: 5% or 50 ms whichever is greater
DT operation: 2% or 50 ms whichever is greater SEF Sin(PHI)
DT reset: 5% Pick-up: Setting 5% for angles from RCA60o
Repeatability: 2.5% to RCA90o
* Reference conditions TMS = 1, TD = 1 and IN> Drop-off: 0.90 x Setting
setting of 1 A operating range 2-20 In IDMT shape: 5% or 50 ms whichever is greater *
IEEE reset: 7.5% or 60 ms whichever is greater
Earth Fault 2 DT operation: 2% or 50 ms whichever is greater
DT Pick-up: Setting 5% DT reset: 5%
Minimum IDMT Trip level: 1.05 x Setting 5% Repeatability: 2%
Drop-off: 0.95 x Setting 5% Reference conditions TMS = 1, TD = 1 and IN >
IDMT shape: 5% or 40 ms whichever is greater * setting of 100 mA, operating range 2-0 In
IEEE reset: 10% or 40 ms whichever is greater Zero Polarizing
DT operation: 2% or 50 ms whichever is greater Operating pick-up: 2%o of RCA 90%
DT reset: 2% or 50 ms whichever is greater Hysteresis: <3o
Repeatability: 5% VN > Pick-up: Setting 10%
* Reference conditions TMS = 1, TD = 1 and IN > VN > Drop-off: 0.9 x Setting 10%
setting of 1A, operating range 2-20 In Negative Polarizing
Operating Pick-up: 2%o of RCA 90%
SEF Hysteresis: <3o
DT Pick-up: Setting 5% VN 2 > Pick-up: Setting 10%
Minimum IDMT Trip level: 1.05 x Setting 5% VN 2 > Drop-off: 0.9 x Setting 10%
Drop-off: 0.95 x Setting 5% I2 > Pick up: Setting 10%
IDMT shape: 5% or 40 ms whichever is greater * I2 > Drop-off: 0.9 x Setting 10%
IEEE reset: 7.5% or 60 ms whichever is greater
DT operation: 2% or 50 ms whichever is greater
DT reset: 5%
Repeatability: 5%

Page (AD) -20 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Negative Sequence Overcurrent Undervoltage Protection


Accuracy Accuracy
DT Pick-up: Setting 5% DT Pick-up: Setting 5%
Minimum IDMT trip level: 1.05 x Setting 5% IDMT Pick-up: Setting 5%
Drop-off: 0.95 x Setting 5% Drop-off: 1.02 x Setting 5%
IDMT shape: 5% or 40 ms whichever is greater IDMT shape: 2% or 50 ms whichever is greater
IEEE reset: 5% or 50 ms whichever is greater DT operation: 2% or 50 ms whichever is greater
DT operation: 2% or 50 ms, whichever is greater Reset: <75 ms
DT reset: 5% Repeatability: <1%
Directional boundary (RCA 90%): 2% hysteresis 2o
Characteristic: UK curves IEC 60255-3 1998
Overvoltage Protection
US curves: IEEEC37.1121996 Accuracy
DT Pick-up: Setting 5%
Reverse/Low Forward/Overpower IDMT Pick-up: Setting 5%
Protection Drop-off: 0.98 x Setting 5%
Accuracy IDMT shape: 2% or 50 ms whichever is greater
Pick-up: Setting 10% DT operation: 2% or 50 ms whichever is greater
Reverse/Overpower drop off: 0.95 x Setting 10% Reset: <75 ms
Low forward Power drop off: 1.05 x Setting +10% Repeatability: <1%
Angle variation pick-up: Expected pick-up angle 2 Rate of Change of Voltage dv/dt
degree
Angle variation drop-off: Expected drop-off angle 2.5
Protection
degree Accuracy for 110 V VT
Operating time: 2% or 50 ms whichever is greater Tolerance: 1% or 0.07, whichever is greater
Repeatability: <5% Pick-up: Setting tolerance
Disengagement time: <50 ms Drop-off: (Setting - 0.07) tolerance for
tRESET: 5% positive direction
Instantaneous operating time: < 50 ms Drop-off: (Setting + 0.07) tolerance for
negative direction
Sensitive Reverse/Low Operating time@50 Hz: [(Avg.cycle*20)+60]ms
Forward/Overpower (1 Phase) Reset time@50 Hz: 40 ms
Accuracy Neutral Displacement/Residual Voltage
Pick-up: Setting 10%
Reverse/Overpower Drop-off: 0.9 of setting 10% Accuracy
Low forward power Drop-off: 1.1 of Setting 10% Pick-up: Setting 5% or 1.05 x Setting 5%
Angle variation Pick-up: Drop-off: 0.95 x Setting 5%
Expected pick-up angle 2 degree IDMT shape: 5% or 65 ms whichever is greater
Angle variation Drop-off: DT operation: 2% or 20 ms whichever is greater <55
Expected drop-off angle 2.5% degree ms
Operating time: 2% or 50 ms whichever is greater Reset: <35 ms
Repeatability: <5% Repeatability: <10%
Disengagement time: <50 ms
tRESET: 5% Underfrequency Protection
Instantaneous operating time: <50 ms Accuracy
Pick-up: Setting 0.025 Hz
Drop-off: 1.05 x Setting 0.025 Hz
DT operation: 2% or 50 ms whichever is greater *
* The operating time will also include a time for the
relay to frequency track (20 Hz/second)

P14x/EN AD/Gf7 Page (AD)-21


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

Overfrequency Protection Advanced Frequency Supervised Rate of


Accuracy Change of Frequency f+df/dt Protection
Pick-up: Setting 0.025 Hz [81RF]
Drop-off: 0.95 x Setting 0.025 Hz Accuracy
DT operation: 2% or 50 ms whichever is greater * Pick-up:
* The operating will also include a time for the relay to Setting10 mHz (frequency threshold)
frequency track (20 Hz/ second) Setting 3% or 10 mHz/s, whichever is greater
(df/dt threshold)
Advanced Over/Underfrequency f+t Drop-off (frequency threshold):
Protection [81U/81O] Setting +20 mHz, 10 mHz (underfrequency)
Setting -20 mHz, 10 mHz (overfrequency)
Accuracy Drop-off (df/dt threshold, falling frequency):
Pick-up: Setting10 mHz Setting +0.005 Hz/s, 10 mHz/s
Drop-off: Setting +20mHz, 10mHz (underfrequency) (for settings between 0.01 Hz/s and 0.1Hz/s)
Setting -20mHz, 10mHz (overfrequency) Setting +0.05 Hz/s, 5% or 55 mHz/s,
Operating timer: 2% or 50 ms whichever is greater whichever is greater (for settings greater than
Operating & Reset Time 0.1 Hz/s)
Operating time* (underfrequency): Drop-off (df/dt threshold, rising frequency):
<100 ms for Fs/Ff ratios less than 2 Setting -0.005 Hz/s, 10 mHz/s
<160 ms for Fs/Ff ratios less than 6 (for settings between 0.01Hz/s and 0.1 Hz/s)
<230 ms otherwise Setting -0.05 Hz/s, 5% or 55 mHz/s,
Operating time* (overfrequency): whichever is greater (for settings greater than
<125 ms for Fs/Ff ratios less than 2 0.1 Hz/s)
<150 ms for Fs/Ff ratios less than 30 Operating & Reset Time
<200 ms otherwise Instantaneous operating time:
Reset time*: <200 ms <125 ms for Freq.Av.Cycles setting = 0
* Reference conditions: Tested using step Reset time:
changes in frequency with Freq.Av.Cycles <400 ms for df/dt.Av.Cycles setting = 0
setting = 0 and no intentional time delay.
Fs/Ff ratios as stated, where: Advanced Independent Rate of Change of
Fs = start frequency - frequency setting Frequency df/dt+t Protection [81R]
Ff = frequency setting - end frequency
Accuracy
Pick-up:
Setting 3% or 10 mHz/s, whichever is greater
Drop-off (falling frequency):
Setting +0.005 Hz/s, 10 mHz/s (for settings
between 0.01 Hz/s and 0.1Hz/s)
Setting +0.05 Hz/s, 5% or 55 mHz/s,
whichever is greater (for settings greater than
0.1 Hz/s)
Drop-off (rising frequency):
Setting -0.005 Hz/s, 10 mHz/s (for settings
between 0.01 Hz/s and 0.1Hz/s)
Setting -0.05 Hz/s, 5% or 55 mHz/s,
whichever is greater (for settings greater than
0.1 Hz/s)
Operating timer: 2% or 50 ms whichever is greater
Operating & Reset Time
Operating time*:
<200 ms for ramps 2x setting or greater
<300 ms for ramps 1.3x setting or greater
Reset time*: <250 ms
* Reference conditions: Tested with df/dt.Av.Cycles
setting = 0, for df/dt settings greater than 0.1 Hz/s
(positive or negative, as relevant) and no intentional
time delay.

Page (AD) -22 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Advanced Average Rate of Change of Cold Load Pick-up Setting


Frequency f+Df/Dt Protection [81RAV]
Accuracy
Accuracy I> Pick-up: Setting 1.5%
Pick-up:
I> Pick-up: Setting 2.5%
Setting10 mHz (frequency threshold)
IN> Pick-up: Setting 1.5%
Setting 0.1 Hz/s (Df/Dt threshold)*
Drop-off: I> Drop-off: 0.95 x Setting 1.5%
Setting +20 mHz, 10mHz (falling frequency) I> Drop-off: 0.95 x Setting 2.5%
Setting -20 mHz, 10 mHz (rising frequency) IN> Drop-off: 0.95 x Setting 1.5%
Operating timer: DT operation: 0.5% or 40 ms whichever is greater
2% or 30 ms whichever is greater Repeatability: <1%
* Reference conditions: To maintain accuracy
Negative Sequence Overvoltage
the minimum time delay setting, Dt, should be:
Dt > 0.375 x Df + 0.23 (for Df setting < 1 Hz) Protection
Dt > 0.156 x Df + 0.47 (for Df setting 1 Hz) Accuracy
Operating Time Pick-up: Setting 5%
Typically <125 ms with Freq.Av.Cycles = 0 Drop-off: 0.95 x Setting 5%
DT operation: 2% or 50 ms whichever is greater
Repeatability: <5%
Advanced Load Restoration
Accuracy Admittance, Conductance and
Pick-up: Setting10 mHz Susceptance
Drop-off: Setting -20 mHz, 10 mHz Accuracy
Restoration timer: 2% or 50 ms whichever is greater
YN, BN and BN measurements: 5%
Holding timer: 2% or 50 ms whichever is greater
YN, BN, BN Pick-up: Setting 5%
Broken Conductor Logic YN, BN, BN Drop-off: >0.85 x Setting
Operating time:
Accuracy
Start <100 ms Trip Setting 2% or 50 ms
Pick-up: Setting 2.5%
Operating boundary: 2
Drop-off: 0.95 x Setting 2.5%
VN: Setting 5%
DT operation: 2% or 40 ms whichever is greater
Selective Overcurrent Protection
Thermal Overload
Accuracy
Accuracy Fast block operation: <25 ms
Thermal alarm pick-up:
Fast block reset: <30 ms
Calculated trip time 10%
Time delay: Setting 2% or 20 ms whichever is
Thermal overload pick-up:
greater
Calculated trip time 10%
Cooling time accuracy: Voltage Transformer Supervision
15% of theoretical Accuracy
Repeatability: <5% Fast block operation: <25 ms
* Operating time measured with applied current of Fast block reset: <30 ms
20% above thermal setting.
Time delay: Setting 2% or 20 ms whichever is
greater
Voltage Dependent Overcurrent
Current Transformer Supervision
Accuracy
VCO / VRO threshold Pick-up: Setting 5% Accuracy
Overcurrent Pick-up:(K factor x Setting) 5% In> Pick-up: Setting 5%
VCO / VRO threshold Drop-off:1.05 x Setting 5% VN< Pick-up: Setting 5%
Overcurrent Drop-off:0.95 x (K factor x Setting) 5% In> Drop-off: 0.9 x Setting 5%
Operating time:5% or 60 ms whichever is greater VN< Drop-off: (1.05 x Setting 5% or 1 V
Repeatability: <5% whichever is greater
Time delay operation: Setting 2% or 20 ms
whichever is greater
CTS block operation: <1 cycle
CTS reset: <35 ms

P14x/EN AD/Gf7 Page (AD)-23


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

CB fail Disturbance Records


Accuracy Accuracy
I > Pick-up: Setting 5% or 20 mA whichever is Magnitude and relative phases: 5% of applied
greater quantities
I > Drop-off: 100% of setting 5% or 20 mA Duration: 2%
whichever is greater Trigger position: 2% (minimum Trigger 100 ms)
Timers: 2% or 50 ms whichever is greater Line length: 0.011000 kn **
Reset time: <25 ms without DC offset Line impedance (100/110 V): 0.1/In250/In
<35 ms with DC offset Line impedance (380/480 V): 0.4/In1000/In
Line angle: 2085
Programmable Scheme Logic KZN residual: 07.00
KZN res. angle: -90+90
Accuracy
Output conditioner timer: Setting 2% or 50 ms Plant Supervision
whichever is greater
Accuracy
Dwell conditioner timer: Setting 2% or 50 ms
Timers: 2% or 20 ms whichever is greater
whichever is greater
Broken current accuracy: 5%
Pulse conditioner timer: Setting 2% or 50 ms
whichever is greater Timer Accuracy
Timers: 2% or 40 ms whichever is greater
Measurements and Recording Facilities Reset time: <30 ms
Measurements Undercurrent Accuracy
Current: 0.05 3 In Pick-up: 10% or 25 mA whichever is greater
Accuracy: 1.0% of reading Operating time: <20 ms
Voltage: 0.052 Vn Reset: <25 ms
Accuracy: 1.0% of reading
Power (W): 0.22 Vn 0.053 In IEC 61850 Ethernet Data
Accuracy: 5.0% of reading at unity power factor 100 Base FX Interface
Reactive Power (Vars): 0.22 Vn, 0.053 In Transmitter Optical Characteristics
Accuracy: 5.0% of reading at zero power factor (TA = 0C to 70C, VCC = 4.75 V to 5.25 V)
Apparent Power (VA): 0.22 Vn 0.053 In
Accuracy: 5% of reading Parameter Sym Min. Typ. Max Unit
Energy (Wh): 0.22 Vn 0.23 In
Output Optical Power
Accuracy: 5% of reading at zero power factor
BOL -19
Energy (Varh): 0.22 Vn 0.23 In PO -16.8 -14 dBm avg.
62.5/125 m, NA = -20
Accuracy: 5% of reading at zero power factor 0.275 Fiber EOL
Phase accuracy: 036
Output Optical Power
Accuracy: 0.5% BOL -22.5
Frequency: 4565 Hz PO -20.3 -14 dBm avg.
50/125 m, NA = 0.20 -23.5
Accuracy: 0.025 Hz Fiber EOL
Performance Optical Extinction 10
% dB
Year 2000: Compliant Ratio -10
Real time clock accuracy: <2% seconds/day Output Optical Power PO
-45 dBm avg
Modulation ratio: 1/3 or 1/6 at Logic 0 State (0)
Input signal peak-peak amplitude: 200 mV20 V BOL - Beginning of life EOL - End of life
Input impedance at 1000 Hz: 6000
External clock synchronization:
Conforms to IRIG standard 200-98, format B
IRIG-B and Real Time Clock
Accuracy (for modulated and un-modulated
versions)
Real time clock accuracy: < 2 seconds/day

Page (AD) -24 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Receiver Optical Characteristics


(TA = 0C to 70C, VCC = 4.75 V to 5.25 V)
Parameter Sym Min. Typ. Max. Unit
Input Optical Power
PIN Min.
Minimum at Window -33.5 -31 dBm avg.
(W)
Edge
Input Optical Power
PIN Min.
Minimum at Eye -34.5 -31.8 Bm avg.
(C)
Center
Input Optical Power PIN
-14 -11.8 dBm avg.
Maximum Max.

Note The 10BaseFL connection will no


longer be supported as IEC 61850
does not specify this interface

SETTINGS, MEASUREMENTS AND


RECORDS LIST
Settings List Date and Time
IRIG-B Sync: Disabled/Enabled
Global Settings (System Data) Battery Alarm: Disabled/Enabled
Language: English/French/German/Spanish LocalTime Enable: Disabled/Fixed/Flexible
Frequency: 50/60 Hz LocalTime Offset: -720 min720 min
DST Enable: Disabled/Enabled
Circuit Breaker Control DST Offset: 30 min60 min
(CB Control) DST Start: First/Second/Third/
CB Control by: Disabled Fourth/Last
Local DST Start Day: Sun/Mon/Tues/Wed/
Remote Thurs/Fri/Sat
Local+Remote DST Start Month: Jan/Feb/Mar/Apr/May/
Opto Jun/Jul/Aug/Sept/Oct/
Opto+local Nov/Dec
Opto+Remote DST Start Mins: 0min1425 min
Opto+Rem+local DST End: First/Second/Third/
Close Pulse Time: 0.1050.00 s Fourth/Last
Trip Pulse Time: 0.105.00 s DST End Day: Sun/Mon/Tues/Wed/
Man Close t max: 0.019999.00 s Thurs/Fri/Sat
Man Close Delay: 0.01600.00 s DST End Month: Jan/Feb/Mar/Apr/
CB Healthy Time: 0.019999.00 s May/Jun/Jul/Aug/Sept/
Check Sync. Time: 0.019999.00 s Oct/Nov/Dec
Reset Lockout by: User Interface/CB Close DST End Mins: 0min1425 min
Man Close RstDly: 0.10600.00 s RP1 Time Zone: UTC/Local
CB Status Input: None RP2 Time Zone: UTC/Local
52A Tunnel Time Zone: UTC/Local
52B
52A & 52B

P14x/EN AD/Gf7 Page (AD)-25


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

Configuration CT and VT Ratios


Setting Group: Select via Menu Main VT Primary: 100 V...1 MV
Select via Opto Main VT Sec'y: 80...140 V
Active Settings: Group 1/2/3/4 C/S VT Primary2: 100 V...1 MV
Setting Group 1: Disabled/Enabled C/S VT Secondary: 80...140 V
Setting Group 2: Disabled/Enabled NVD VT Primary5: 100 V...1 MV
Setting Group 3: Disabled/Enabled NVD VT Secondary: 80...140 V
Setting Group 4: Disabled/Enabled Phase CT Primary: 1 A30 kA
System Config: Invisible/Visible Phase CT Sec'y: 1 A/5 A
Overcurrent: Disabled/Enabled E/F CT Primary: 1 A30 kA
Negative Sequence O/C: Disabled/Enabled E/F CT Sec'y: 1 A/5 A
Broken Conductor: Disabled/Enabled SEF CT Primary: 1 A30 kA
Earth Fault 1: Disabled/Enabled SEF CT Sec'y: 1 A/5 A
Earth Fault 2: Disabled/Enabled I Derived Phase5: IA / IB / IC / None
1
SEF/REF Prot: Disabled/Enabled C/S Input2: A-N / B-N / C-N
Residual O/V NVD: Disabled/Enabled A-B / B-C / C-A
Thermal Overload: Disabled/Enabled Main VT Location2: Line/Bus
Neg. Sequence O/V: Disabled/Enabled
Cold Load Pick-up: Disabled/Enabled Sequence of Event Recorder
Selective Logic: Disabled/Enabled (Record Control)
Admit. Protection: Disabled/Enabled Alarm Event: Disabled/Enabled
Power Protection: Disabled/Enabled Relay O/P Event: Disabled/Enabled
Volt Protection: Disabled/Enabled Opto Input Event: Disabled/Enabled
Freq. Protection: Disabled/Enabled General Event: Disabled/Enabled
CB Fail: Disabled/Enabled Fault Rec. Event: Disabled/Enabled
Supervision: Disabled/Enabled Maint. Rec. Event: Disabled/Enabled
Fault Locator: Disabled/Enabled Protection Event: Disabled/Enabled
2
System Checks : Disabled/Enabled DDB 31 - 0:(up to): DDB 1279 - 1248:
3
Auto-Reclose : Disabled/Enabled Binary function link strings, selecting which DDB
Input Labels: Invisible/Visible signals will be stored as events, and which will be
Output Labels: Invisible/Visible filtered out
Adv. Freq. Protn: Disabled/Enabled
CT & VT Ratios: Invisible/Visible Oscillography (Disturb. Recorder)
Record Control: Invisible/Visible Duration: 0.1010.50 s
Disturb Recorder: Invisible/Visible Trigger Position: 0.0100.0%
Measuret Setup: Invisible/Visible Trigger Mode: Single/Extended
Comms Settings: Invisible/Visible Analog Channel 1: (up to):
Commission Tests: Invisible/Visible Analog Channel 8: Disturbance channels selected
Setting Values: Primary/Secondary from:
Control Inputs: Invisible/Visible VA/VB/VC/Vchecksync./IA/IB/IC/IN
Ctrl I/P Config: Invisible/Visible /IN Sensitive
Ctrl I/P Labels: Invisible/Visible Digital Input 1: (up to):
Direct Access: Disabled/Enabled Digital Input 32:
InterMiCOM: Disabled/Enabled Selected binary channel assignment from any DDB
4
Function Key : Invisible/Visible status point within the relay (opto input, output
RP1 Read Only: Disabled/Enabled contact, alarms, starts, trips, controls, logic).
RP2 Read Only: Disabled/Enabled Input 1 Trigger: No Trigger/Trigger L/H/Trigger H/L
NIC Read Only: Disabled/Enabled (up to):
LCD Contrast: (Factory pre- Input 32 Trigger: No Trigger/Trigger L/H/
set) Trigger H/L

Page (AD) -26 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Measured Operating Data Optional Additional Second Rear


(Measure't. Setup) Communication (Rear Port2 (RP2))
Default Display: 3Ph + N Current RP2 Protocol: Courier (fixed)
3Ph Voltage RP2 Port Config: Courier over EIA(RS)232
Power Courier over EIA(RS)485
Date and Time K-Bus
Description RP2 Comms. Mode:
Plant Reference IEC60870 FT1.2 Frame
Frequency 10-Bit NoParity
Access Level RP2 Address: 0255
Local Values: Primary/Secondary RP2 InactivTimer: 130 mins
Remote Values: Primary/Secondary RP2 Baud Rate: 9600 bits/s / 19200 bits/s
Measurement Ref: VA/VB/VC/IA/IB/IC 38400 bits/s
Measurement Mode: 0/1/2/3
Fix Dem. Period: 199 mins Optional Ethernet Port
Roll Sub Period: 199 mins NIC Tunl Timeout: 1...30 mins
Num. Sub Periods: 115 NIC Link Report: Alarm/Event/None
Distance Unit: Miles/Kilometers NIC Link Timeout: 0.1...60 s
Fault Location: Distance Commission Tests
Ohms
Monitor Bit 1: (up to):
% of Line
Monitor Bit 8:
Remote2 Values: Primary/Secondary
Binary function link strings, selecting which DDB
signals have their status visible in the Commissioning
Communications menu, for test purposes
RP1 Protocol: Courier Test Mode: Disabled
IEC870-5-103 Test Mode
DNP 3.0 Blocked Contacts
RP1 Address: (Courier or IEC870-5-103): Test Pattern: Configuration of which output
0255 contacts are to be energized when
RP1 Address: (DNP3.0): the contact test is applied.
065519 Static Test Mode: Disabled/Enabled
RP1 InactivTimer: 130 mins
RP1 Baud Rate: (IEC870-5-103): Circuit Breaker Condition Monitoring
9600/19200 bits/s (CB Monitor Setup)
RP1 Baud Rate: (DNP3.0): Broken I^: 1.02.0
1200 bits/s / 2400 bits/s I^ Maintenance: Alarm Disabled/Enabled
4800 bits/s / 9600 bits/s I^ Maintenance: 125000
19200 bits/s / 38400 bits/s I^ Lockout: Alarm Disabled/Enabled
RP1 Parity: Odd/Even/None I^ Lockout: 125000
RP1 Meas Period: 160 s No. CB Ops Maint: Alarm Disabled/Enabled
RP1 PhysicalLink: Copper No. CB Ops Maint: 110000
Fiber Optic (IEC870-5-103, No. CB Ops Lock: Alarm Disabled/Enabled
DNP3.0, Courier, MODBUS) No. CB Ops Lock: 110000
K-Bus (Courier only) CB Time Maint: Alarm Disabled/Enabled
RP1 Time Sync: Disabled/Enabled CB Time Maint: 0.0050.500 s
DNP Need Time: 130 m CB Time Lockout: Alarm Disabled/Enabled
DNP App Fragment: 1002048 CB Time Lockout: 0.0050.500 s
DNP App Timeout: 1120 Fault Freq. Lock: Alarm Disabled/Enabled
DNP SBO Timeout: 110 Fault Freq. Count: 19999
DNP Link Timeout: 0120 Fault Freq. Time: 09999 s
RP1 CS103 Blocking: Disabled
Monitor Blocking
Command Blocking
RP1 Port Config. (Courier): K Bus / EIA(RS)485
RP1 Comms. Mode: IEC60870 FT1.2 Frame
10-Bit No Parity

P14x/EN AD/Gf7 Page (AD)-27


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

Optocoupled Binary Inputs (Opto Config.) Function Keys4


Global threshold: 24 27 V / 30 34 V Fn. Key Status 1: (up to):
48 54 V / 110 125 V Fn. Key Status 10 Disable
220 250 V Lock
Custom Unlock/Enable
Opto Input 1: (up to): Fn. Key 1 Mode: Toggled/Normal (up to):
Opto Input #. (# = max. opto no. fitted): Fn. Key 10 Mode: Toggled/Normal
Custom options allow independent thresholds to be Fn. Key 1 Label: (up to):
set per opto, from the same range as above. Fn. Key 10 Label:
Filter Control: Binary function link string, User defined text string to describe the function of the
selecting which optos will have an particular function key
extra 1/2 cycle noise filter, and
which will not. IED CONFIGURATOR
Characteristics: Standard 60% - 80% Switch Conf. Bank: No Action/Switch Banks
50% - 70%
Time stamping accuracy: + 1 msec IEC61850 GOOSE
GoEna: Disabled/Enabled
Control Inputs into PSL (Ctrl. I/P Config.) Test Mode: Disabled/Pass Through/Forced
Hotkey Enabled: Binary function link string, VOP Test Pattern: 0x00000000... 0xFFFFFFFF
selecting which of the control Ignore Test Flag: No/Yes
inputs will be driven from Hotkeys.
Control Input 1: Latched/Pulsed (up to): Control Input User Labels
Control Input 32: Latched/Pulsed (Ctrl. I/P Labels)
Ctrl Command 1: (up to): Control Input 1: (up to):
Ctrl Command 32: ON/OFF Control Input 32:
SET/RESET User defined text string to describe the function of the
IN/OUT particular control input
ENABLED/DISABLED
EIA(RS)232 Teleprotection Settings in Multiple Groups
(InterMiCOM Comms.) Note: All settings here onwards apply for
Source Address: 110 setting groups # = 1 to 4.
Received Address: 110
Data Rate: 600 Baud / 1200 Baud
2400 Baud / 4800 Baud
9600 Baud / 19200 Baud
Loopback Mode: Disabled/Internal/External
Test Pattern: Configuration of which InterMiCOM
signals are to be energized when
the loopback test is applied.
InterMiCOM Conf.
IM Msg Alarm Lvl: 0100.0%
IM1 Cmd Type: Disabled/Direct/Blocking (up to):
IM4 Cmd Type: Disabled/Direct/Blocking
IM5 Cmd Type: Disabled/Permissive/Direct (up to):
IM8 Cmd Type: Disabled/Permissive/Direct
IM1 FallBackMode: Default/Latched (up to):
IM8 FallBackMode: Default/Latched
IM1 DefaultValue: 0/1 (up to):
IM8 DefaultValue: 0/1
IM1 FrameSyncTim: 10 ms1.50 s (up to):
IM8 FrameSyncTim: 10 ms1.50 s

Page (AD) -28 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

I> Blocking:
PROTECTION FUNCTIONS Binary function link string, selecting which overcurrent
elements (stages 1 to 4) will be blocked if VTS
System Config. detection of fuse failure occurs.
Phase Sequence: Standard ABC Binary function link string, selecting which overcurrent
Reverse ACB elements (stages 1 to 4) will be blocked if 2nd
2NDHARM BLOCKING: Disabled/ Enabled Harmonic Block is enabled with an option of choosing
2ndHarm Thresh: 570 1PH block.
I>lift 2H: 432
Voltage Dependent Overcurrent
Phase Overcurrent (Overcurrent) V DEPENDANT O/C
I>1 Function: Disabled / DT / V Dep OC Status
IEC S Inverse / IEC V Inverse / VCO Disabled
IEC E Inverse / UK LT Inverse / VCO >1
UK Rectifier / RI / IEEE M Inverse VCO >2
IEEE V Inverse / IEEE E Inverse VCO >1 & >2
US Inverse / US ST Inverse / VCO >5
Def User Curve 1 / VCO >1 & >2 & >5
Def User Curve 2 / VCO >1 & >5
Def User Curve 3 / VC0 >2 & >5
Def User Curve 4 VRO I>1
I>1 Direction: Non-Directional VRO I>2
Directional Fwd VRO I>5
Directional Rev VRO >1 & >2
I>1 Current Set: 0.084.00 In VRO >1 & >5
I>1 Time Delay: 0.00100.00 s
VRO >2 & >5
I>1 TMS: 0.0251.200
VRO >1 & >2 & I>5
I>1 Time Dial: 0.01100.00
V Dep OC V<1 Set
I>1 K (RI): 0.1010.00
10120 V (100/120 V)
I>1 DT Adder: 0.00100.00
40480 V (380/440 V)
I>1 Reset Char.: DT/Inverse
V Dep OC V<2 Set
I>1 tRESET: 0.00100.00 s
10120 V (100/120 V)
I>2 Status (up to):
40480 V (380/440 V)
I>2 tRESET All settings and options chosen
from the same ranges as per the Load Blinder
first stage overcurrent, I>1. Blinder Status: Disabled/Enabled
I>3 Status: Disabled Blinder Function: 3Ph/1Ph
Enabled Blinder Mode: Both/Forward/Reverse
I>3 Direction: Non-Directional FWD Z Impedance: 0.1100 ohm
Directional Fwd FWD Z Angle: 585 deg
Directional Rev REV Z Impedance: 0.1100 ohm
I>3 Current Set: 0.0832.00 In REV Z Angle: 585 deg
I>3 Time Delay: 0.00100.00 s Binder V<Block: 10120 V
I>4 Status (up to): Binder I2>Block: 0.84 A
I>4 Time Delay All settings and options chosen PU cycles: 050
from the same ranges as per the DO cycles: 050
third stage overcurrent, I>3.
I> Char Angle: -9595
I>5 Status (up to):
I>5 tRESET
All settings and options chosen from the same ranges
as per the first stage overcurrent, I>1.
I>6 Status (up to):
I>6 Time Delay All settings and options chosen
from the same ranges as per the
third stage overcurrent, I>3.

P14x/EN AD/Gf7 Page (AD)-29


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

Negative Sequence Overcurrent Ground Overcurrent (Earth Fault 1 & 2)


I2>1 Function: Disabled / DT IN1>1 Function Disabled / DT
IEC S Inverse / IEC V Inverse IEC S Inverse / IEC V Inverse
IEC E Inverse / UK LT Inverse IEC E Inverse / UK LT Inverse
IEEE M Inverse / IEEE V Inverse RI / IEEE M Inverse
IEEE E Inverse / US Inverse IEEE V Inverse / IEEE E Inverse
US ST Inverse US Inverse / US ST Inverse
I2>1 Direction: Non-Directional IDG / Def User Curve 1
Directional Fwd Def User Curve 2
Directional Rev Def User Curve 3
I2>1 Current Set: 0.084.00 In Def User Curve 4
I2>1 Time Delay: 0.00100.00 s IN1>1 Directional Non-Directional
I2>1 TMS: 0.0251.200 Directional Fwd
I2>1 Time Dial: 0.01100.00 Directional Rev
I2>1 DT Adder: 0.00100.00 IN1>1 Current Set: 0.084.00 In
I2>1 Reset Char.: DT/Inverse IN1>1 IDG Is: 1.04.0 In
I2>1 tRESET: 0.00100.00 s IN1>1 Time Delay: 0.00200.00 s
I2>2 Status (up to): I2>2 tRESET IN1>1 TMS: 0.0251.200
All settings and options chosen from the same ranges IN1>1 Time Dial: 0.01100.00
as per the first stage overcurrent, I2>1. IN1>1 K(RI): 0.10..10.00
I2>3 Status: Disabled/Enabled IN1>1 IDG Time: 1.002.00
I2>3 Direction: Non-Directional IN1>1 DT Adder: 0.00100.00
Directional Fwd IN1>1 Reset Char.: DT/Inverse
Directional Rev IN1>1 tRESET: 0.00100.00 s
I2>3 Current Set: 0.0832.00 In IN1>2 Status (up to):
I2>3 Time Delay: 0.00100.00 s IN1>2 tRESET
I2>4 Status (up to): I2>4 Time Delay All settings and options chosen from the same ranges
All settings and options chosen from the same ranges as per the first stage ground overcurrent, IN>1.
as per the third stage overcurrent, I2>3. IN1>3 Status: Disabled
I2> VTS Blocking: Enabled
Binary function link string, selecting which Neg. Seq. IN1>3 Directional: Non-Directional
O/C elements (stages 1 to 4) will be blocked if VTS Directional Fwd
detection of fuse failure occurs. Directional Rev
Binary function link string, selecting which Neg. Seq. IN1>3 Current Set: 0.0832.00 In
nd
O/C elements (stages 1 to 4) will be blocked if 2 IN1>3 Time Delay: 0.00200.00 s
Harmonic Block is enabled. IN1>4 Status (up to): IN1>4 Time Delay
I2> Char Angle: -9595 All settings and options chosen from the same ranges
I2> V2pol Set: 0.525.0 (100 110 V): as per the third stage ground overcurrent, IN>3.
2100 (380 480 V):
IN1> Blocking:
Broken Conductor Binary function link string, selecting which ground
Broken Conductor: Disabled/Enabled overcurrent elements (stages 1 to 4) will be blocked if
I2/I1 Setting: 0.201.00 VTS detection of fuse failure occurs.
I2/I1 Time Delay: 0.0100.0 s Binary function link string, selecting which ground
overcurrent elements (stages 1 to 4) will be blocked if
nd
2 Harmonic Block is enabled.
IN1> Char Angle: -9595
IN1> Polarization: Zero Sequence
Neg. Sequence
IN1> VNpol Set: 0.580.0 V (100 110 V)
2320 V (380 480 V)
IN1> V2pol Set: 0.525.0 V (100 110 V)
2100 V (380 480 V)
IN1> I2pol Set: 0.081.00 In

Page (AD) -30 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Sensitive Earth Fault Protection/ WATTMETRIC SEF:


PN> Setting: 020 W (1A, 100/120 V)
Restricted Earth Fault Protection PN> Setting: 0100 W (5A, 100/120 V)
SEF/REF Options: SEF / SEF cos (PHI)
PN> Setting: 0 80 W (1A, 380/440 V)
SEF sin (PHI) / Wattmetric
PN> Setting: 0400 W (5A, 380/440 V)
Hi Z REF / Lo Z REF
Lo Z REF + SEF Restricted Earth-Fault (Low Impedance)
Lo Z REF + Wattmetric IREF > K1: 0 20%
ISEF>1 Function: Disabled / DT IREF > K2: 0 150%
IEC S Inverse / IEC V Inverse IREF > Is1: 0.081.00 In
IEC E Inverse / UK LT Inverse IREF > Is2: 0.11.50 In
RI / IEEE M Inverse Restricted Earth-Fault (High Impedance)
IEEE V Inverse: IEEE E Inverse IREF > K1: 0.051.00 In
US Inverse / US ST Inverse
IDG / Def User Curve 1 Neutral Voltage Displacement
Def User Curve 2 (Residual O/V NVD)
Def User Curve 3 VN>1 Function: Disabled
Def User Curve 4 DT
ISEF>1 Directional: Non-Directional IDMT
Directional Fwd VN>1 Voltage Set: 150 V
Directional Rev. VN>1 Time Delay: 0.00100.00 s
ISEF>1 Current Set: 0.0050.01 In VN>1 TMS: 0.5100.0
ISEF>1 IDG Is: 1.04.0 In VN>1 tReset: 0.00100.00 s
ISEF>1 Time Delay: 0.00200.00 s VN>2 Status: Disabled/Enabled
ISEF>1 TMS: 0.0251.200 VN>2 Voltage Set: 180 V (100/110 V)
ISEF>1 Time Dial: 0.5100.0 4320 V (380/440 V)
IN1>1 K(RI): 0.10..10.00 VN>2 Time Delay: 0.00100.00 s
ISEF>1 IDG Time: 1.00..2.00
ISEF>1 DT Adder: 0.00100.00 Thermal Overload
ISEF>1 Reset Char: DT/Inverse Characteristic: Disabled
ISEF>1 tRESET: 0.00100.00 s Single
ISEF>2 Status (up to): ISEF>2 tRESET Dual
All settings and options chosen from the same ranges Thermal Trip: 0.084.00 In
as per the first stage ground overcurrent, IN>1. Thermal Alarm: 50100%
ISEF>3 Status: Disabled / Enabled Time Constant 1: 1200 mins
ISEF>3 Directional: Non-Directional Time Constant 2: 1200 mins
Directional Fwd Negative Sequence Overvoltage
Directional Rev
ISEF>3 Current Set: 0.005.2.000 In
Protection
V2> Status: Disabled/Enabled
ISEF>3 Time Delay: 0.00200.00 s
V2> Voltage Set: 1V110 V (100/120 V)
ISEF>4 Status (up to):
4V 440 V (380/440 V)
ISEF>4 Time Delay
V2> Time Delay: 0.00100.00 s
All settings and options chosen from the same ranges
as per the third stage ground overcurrent, IN>3. Cold Load Pick-up Setting
ISEF> Blocking: tcold Time Delay: 014 400 s
Binary function link string, selecting which ground tclp Time Delay: 014 400 s
overcurrent elements (stages 1 to 4) will be blocked if
VTS detection of fuse failure occurs.
Binary function link string, selecting which ground
overcurrent elements (stages 1 to 4) will be blocked if
nd
2 Harmonic Block is enabled.
ISEF> Char. Angle: -9595
ISEF> VNpol Set: 0.580.0V (100 110 V)
2320V (380 480 V)

P14x/EN AD/Gf7 Page (AD)-31


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

Overcurrent Neutral Admittance Protection


I>1 Status: Block/Enabled VN Threshold: 140 V (100/120 V)
I>1 Current Set: 0.084.00 In 4160 V (380/440 V)
I>1 Time delay: 0.00100.00 s CT Input Type: SEF CT/E/F CT
I>1 TMS: 0.025.2.000 Correction angle: 3030o
I>1 Time Dial: 0.515.0 Overadmittance
I>2 Status (up to): YN Status: Disabled/Enabled
I>2 Time Dial YN> Set (SEF): 0.110 mS (100/110 V)
All settings and options chosen from the same ranges 0.0252.5 mS (380/440 V)
as per the 1st stage. YN> Set (EF): 1100 mS (100/110 V)
I>3 Status: Block/Enabled 0.2525 mS (380/440 V)
I>3 Current Set: 0.0832.00 In YN> Time Delay: 0.05 s100.00 s
3 Time delay: 0.00100.00 s YN> tRESET: 0.00100.00 s
I>4 Status (up to):
I>4 Time Delay Over Conductance
All settings and options chosen from the same ranges GN Status: Disabled/Enabled
as per the 1st stage. GN>Direction Non-Directional
E/F1 Directional Fwd
IN1>1 Status: Block/Enabled Directional Rev.
IN1>1 Current Set: 0.084.00 In GN> Set (SEF): 0.15 mS (100/110 V)
IN1>1 IDG Is: 1.04.0 In 0.251.25 mS (380/440 V)
IN1>1 Time Delay: 0.00200.00 s GN> Set (E/F): 150 mS (100/110 V)
IN1>1 TMS: 0.025.2.000 0.2512.5 mS (380/440 V)
IN1>1 Time Dial: 0.515.0 GN> Time Delay: 0.05 s100 s
IN1>1 K(RI): 0.10..10.00 GN>tRESET: 0 s100 s
IN1>2 Status (up to): Over Susceptance
IN2> 1 K(RI) BN Status: Disabled/Enabled
All settings and options chosen from the same ranges GN>Direction Non-Directional
as per the E/F1 stage. Directional Fwd
I>5 Status (up to): Directional Rev.
I>5 Time Dial BN> Set (SEF) 0.15 mS (100/110 V)
All settings and options chosen from the same ranges 0.0251.25 mS (380/440 V))
as per the 1st stage. BN> Set (E/F): 150 mS (100/110 V)
I>6 Status (up to): 0.2512.5 mS (380/440 V)
I>6 Time Delay BN> Time Delay: 0.05100 s
All settings and options chosen from the same ranges BN> tRESET: 0 s100 s
as per the 3rd stage.
Undervoltage Protection
V< Measur't. Mode: Phase-Phase / Phase-Neutral
Selective Overcurrent Logic V< Operate Mode: Any Phase / Three Phase
Overcurrent V<1 Function: Disabled / DT / IDMT
I>3 Time Delay: 0.00100.00 s V<1 Voltage Set: 10120 V (100/110 V)
I>4 Time Delay: 0.00100.00 s 40480 V (380/440 V)
Earth Fault1 V<1 Time Delay: 0.00100.00 s
IN1>3 Time Delay: 0.00200.00 s V<1 TMS: 0.5100.0
IN1>4 Time Delay: 0.00200.00 s V<1 Poledead Inh: Disabled/Enabled
Earth Fault2 V<2 Status: Disabled/Enabled
IN2>3 Time Delay: 0.00200.00 s V<2 Voltage Set: 10120 V (100/110 V)
IN2>4 Time Delay: 0.00200.00 s 40480 V (380/440 V)
Sensitive E/F V<2 Time Delay: 0.00100.00 s
ISEF>3 Time Delay: 0.00200.00 s V<2 Poledead Inh: Disabled/Enabled
ISEF>4 Time Delay: 0.00200.00 s
Overcurrent
I>6 Time Delay: 0.00100.00 s

Page (AD) -32 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Overvoltage Protection Advanced Over/Underfrequency


V> Measur't. Mode: Phase-Phase Protection (f+t [81U/81O])
Phase-Neutral Stage 1 f+t Status: Disabled / Enabled
V> Operate Mode: Any Phase 1 (f+t) f: 40.1069.90 Hz
Three Phase 1 (f+t) t: 0.00100.00 s
V>1 Function: Disabled / DT / IDMT Stage 2 f+t Status (up to): 9 (f+t)t
V>1 Voltage Set: 60185 V (100/110 V) All settings and options chosen from the same ranges
240740 V (380/440 V) as per the first stage over/underfrequency, Stage 1
V>1 Time Delay: 0.00100.00 s f+t.
V>1 TMS: 0.5100.0
V>2 Status: Disabled/Enabled Advanced Frequency Supervised Rate of
V>2 Voltage Set: 60185 V (100/110 V) Change of Frequency Protection (f+df/dt
240740 V (380/440 V) [81RF]
V>2 Time Delay: 0.00100.00 s Stage 1 f+df/dt Status: Disabled / Enabled
dv/dt Protection 1 (f+df/dt) f: 40.1069.90 Hz
dv/dt Meas. Mode: Phase-Phase / Phase-Neutral 1 (f+df/dt) df/dt: 0.0110.0 Hz/s
dv/dt1 Function: Disabled / Negative / Stage 2 f+df/dt Status (up to): 9 (f+df/dt) df/dt
Positive / Both All settings and options chosen from the same ranges
dv/dt1 Oper Mode: Any Phase / Three Phase as per the first stage frequency supervized rate of
dv/dt1 AvgCycles: 550 change of frequency, Stage 1 f+df/dt.
dv/dt1 Threshold: 0.5200 Advanced Independent Rate of Change of
dv/dt1 TimeDelay: 0100 s
dv/dt1 tRESET: 0100 s
Frequency Protection (df/dt+t [81R])
Stage 1 df/dt+t Status: Disabled / Negative / Positive
dv/dt2 Function: Disabled / Negative /
1 (df/dt+t) df/dt: 0.0110.00 Hz/s
Positive / Both
1 (df/dt+t) t: 0.00100.00 s
dv/dt2 Oper Mode: Any Phase / Three Phase
Stage 2 df/dt+t Status (up to): 9 (df/dt+t) t
dv/dt2 AvgCycles: 550
All settings and options chosen from the same ranges
dv/dt2 Threshold: 0.5200
as per the first stage independent rate of change of
dv/dt2 TimeDelay: 0100 s
frequency, Stage 1 df/dt+t.
dv/dt2 tRESET: 0100 s
Underfrequency Protection Advanced Average Rate of Change of
F<1 Status: Disabled/Enabled Frequency Protection (f+Df/Dt [81RAV])
F<1 Setting: 45.0065.00 Hz Stage 1 f+Df/Dt Status: Disabled / Enabled
F<1 Time Delay: 0.00100.00 s 1 (f+Df/Dt) f: 40.1069.90 Hz
F<2 Status (up to): F<4 Time Delay 1 (f+Df/Dt) Df: 0.210.0 Hz
All settings and options chosen from the same ranges 1 (f+Df/Dt) Dt: 0.022.00 s
as per the 1st stage. Stage 2 f+Df/Dt Status (up to): 9 (f+Df/Dt) Dt
F> Blocking: All settings and options chosen from the same ranges
Binary function link string, selecting which frequency as per the first stage average rate of change of
elements (stages 1 to 4) will be blocked by the pole- frequency, Stage 1 f+Df/Dt.
dead logic.

Overfrequency Protection
F>1 Status: Disabled/Enabled
F>1 Setting: 45.0065.00 Hz
F>1 Time Delay: 0.00100.00 s
F<2 Status (up to): F<2 Time Delay
All settings and options chosen from the same ranges
as per the 1st stage.

P14x/EN AD/Gf7 Page (AD)-33


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

Advanced Load Restoration Fault Locator


Restore1 Status: Disabled / Enabled Line Length (km): 0.0011000.000 km
Restore1 Freq.: 40.1069.90 Hz Line Length (mi): 0.20625.00 mi
Restore1 Time: 07200 s Line Impedance: 0.10250.00
Restore2 Status (up to): Restore9 Time Line Angle: 2085
All settings and options chosen from the same ranges KZN Residual: 0.007.00
as per the first stage load restoration, Restore1. KZN Res. Angle: -9090
Circuit Breaker Fail Bus-Line Synchronizm and Voltage
CB Fail 1 Status: Disabled/Enabled Checks (System Checks)
CB Fail 1 Timer: 0.0010.00 s
CB Fail 2 Status: Disabled/Enabled VOLTAGE MONITORS
CB Fail 2 Timer: 0.0010.00 s Live Voltage: 1.0132.0 V (100/110 V)
Volt Prot. Reset: I< Only 22528 V (380/440 V)
CB Open & I< Dead Voltage: 1.0132.0 V (100/110 V)
Prot. Reset & I< 22528 V (380/440 V)
Ext Prot. Reset: Synchrocheck (Check Sync.)
I< Only CS1 Status: Disabled/Enabled
CB Open & I< CS1 Phase Angle: 590o
Prot. Reset & I< CS1 Slip Control: None / Timer / Frequency / Both
Undercurrent CS1 Slip Freq.: 0.011.00 Hz
I< Current Set: 0.023.20 In CS1 Slip Timer: 0.099.0 s
IN< Current Set: 0.023.20 In CS2 Status (up to): CS2 Slip Timer
ISEF< Current Set: 0.0010.800 In All settings and options chosen from the same ranges
as per the first stage CS1 element.
BLOCKED O/C CS Undervoltage: 10.0132.0 V (100/110 V)
Remove I> Start: Disabled/Enabled 40528 V (380/440 V)
Remove IN> Start: Disabled/Enabled CS Overvoltage: 40.0185.0 V (100/110 V)
160740 V (380/440 V)
Fuse Failure (VT Supervision) CS Diff Voltage: 1.0132.0 V (100/110 V)
VTS Status: Blocking/Indication 4528 V (380/440 V)
VTS Reset Mode: Manual/Auto CS Voltage Block: None / Undervoltage /
VTS Time Delay: 1.010.0 s Overvoltage / Differential /
VTS I> Inhibit: 0.0832.00 In UV & OV / UV & DiffV /
VTS I2> Inhibit: 0.050.50 In OV & DiffV / UV, OV & DiffV
CT Supervision System Split
CTS Status: Disabled/Enabled SS Status: Disabled/Enabled
CTS VN< Inhibit: 0.522.0 V (100/110 V) SS Phase Angle: 90175
288 V (380/440 V) SS Under V Block: Disabled/Enabled
CTS IN> Set: 0.084.00 In SS Undervoltage: 10.0132.0 V (100/110 V)
CTS Time Delay: 010 s 40528 V (380/440 V)
VTS PickupThresh: 20120 V SS Timer: 0.099.0 s
CB Close Time: 0.0000.500 s

Page (AD) -34 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

SYSTEM CHECKS
Auto-reclose AR with ChkSync: Disabled/Enabled
AR Mode Select: Command Mode AR with SysSync: Disabled/ Enabled
Opto Set Mode Live/Dead Ccts: Disabled/Enabled
User Set Mode No System Checks: Enabled/Disabled
Pulse Set Mode SysChk on Shot 1: Disabled/ Enabled
Number of Shots: 14 I>5: No Action/Initiate Main AR
Number of SEF Shots: 04 I>6: No Action/Initiate Main AR/Block AR
Sequence Co-ord.: Disabled/Enabled
CS AR Immediate: Disabled/Enabled Opto Input Labels
Dead Time 1: 0.01300.00 s Opto Input 1: (up to): Opto Input 24:
Dead Time 2: 0.01300.00 s User defined text string to describe the function of the
Dead Time 3: 0.019999.00 s particular opto input.
Dead Time 4: 0.019999.00 s
CB Healthy Time: 0.01 s9999.00 s
Start Dead on: Protection Resets/CB Trips
Output Labels
Relay 1: (up to): Relay 32:
Reclaim Extend: No Operation/On Prot. Start
User defined text string to describe the function of the
Reclaim Time 1: 1.00600.00 s
particular relay output contact.
Reclaim Time 2: 1.00600.00 s
Reclaim Time 3: 1.00600.00 s
Reclaim Time 4: 1.00600.00 s
AR Inhibit Time: 0.01600.00 s
AR Lockout: No Block/Block Inst. Prot.
EFF Maint. Lock: No Block/Block Inst. Prot.
AR Deselected: No Block/Block Inst. Prot.
Manual close: No Block/Block Inst. Prot.
Trip 1 Main: No Block/Block Inst. Prot.
Trip 2 Main: No Block/Block Inst. Prot.
Trip 3 Main: No Block/Block Inst. Prot.
Trip 4 Main: No Block/Block Inst. Prot.
Trip 5 Main: No Block/Block Inst. Prot.
Trip 1 SEF: No Block/Block Inst. Prot.
Trip 2 SEF: No Block/Block Inst. Prot.
Trip 3 SEF: No Block/Block Inst. Prot.
Trip 4 SEF: No Block/Block Inst. Prot.
Trip 5 SEF: No Block/Block Inst. Prot.
Man. Close on Flt: No Lockout/Lockout
Trip AR Inactive: No Lockout/Lockout
Reset Lockout by: User Interface/Select Non-Auto
AR on Man. Close: Enabled/Inhibited
Sys. Check Time: 0.019999.00 s
AR Skip Shot 1: Enabled/disabled
AR INITIATION
I>1, I>2: No Action/Initiate Main AR
I>3 and I>4: No Action/Initiate Main AR/
Block AR
IN1>1 and IN1>2: No Action/Main AR
IN1>3 and IN1>4: No Action/Initiate Main AR/
Block AR
IN2>1, IN2>2: No Action/Initiate Main AR
IN2>3 and IN2>4: No Action/Initiate Main AR/
Block AR
ISEF>1, ISEF>2, ISEF>3 and ISEF>4:
No Action/Initiate Main AR/
Initiate SEF AR/ Block AR
YN/GN/ BN>: No Action/Initiate Main AR
Ext. Prot.: No Action/Initiate Main AR

P14x/EN AD/Gf7 Page (AD)-35


Update Documentation Section 2 - Technical Data (P14x/EN AD/De6)

MEASUREMENTS LIST Measurements 2


Phase Watts
Measurements 1 Phase VArs
I Magnitude Phase VA All phase segregated power
I Phase Angle measurements, real, reactive and apparent
Per phase ( = A, B, C) current ( = A, B, C)
measurements 3 Phase Watts
IN Measured Mag. 3 Phase VArs
IN Measured Ang. 3 Phase VA
IN Derived Mag. Zero Seq. Power
IN Derived Angle 3Ph Power Factor
ISEF Magnitude Ph Power Factor
ISEF Angle Independent power factor measurements for
I1 Magnitude all three phases ( = A, B, C).
I2 Magnitude 3Ph WHours Fwd
I0 Magnitude 3Ph WHours Rev.
I RMS 3Ph VArHours Fwd
Per phase ( = A, B, C) RMS current 3Ph VArHours Rev.
measurements 3Ph W Fix Demand
3Ph VArs Fix Dem.
V- Magnitude
I Fixed Demand Maximum demand currents
V- Phase Angle
measured on a per phase basis ( = A, B,
V Magnitude
C).
V Phase Angle
3Ph W Roll Dem.
All phase-phase and phase-neutral voltages
3Ph VArs Roll Dem.
( = A, B. C)
I Roll Demand
VN Derived Mag.
Maximum demand currents measured on a
VN Derived Ang.
per phase basis ( = A, B, C).
V1 Magnitude.
3Ph W Peak Dem.
V2 Magnitude
3Ph VAr Peak Dem.
V0 Magnitude
I Peak Demand
V RMS
Maximum demand currents measured on a
All phase-neutral voltages ( = A, B, C)
per phase basis ( = A, B, C).
Frequency
Reset Demand: Yes/No
C/S Voltage Mag.
C/S Voltage Ang. Measurements 3
C/S Bus-line Ang. Highest Phase I
Slip Frequency Thermal State
IM Magnitude Reset Thermal
IM Phase Angle IREF Diff.
I1 Magnitude IREF Bias
I1 Phase Angle Admittance
I2 Magnitude Conductance
I2 Phase Angle Susceptance
I0 Magnitude Admittance
I0 Phase Angle Conductance
V1 Magnitude Susceptance
V1 Phase Angle I2/I1 Ratio
V2 Magnitude SEF Power
V2 Phase Angle IA 2nd Harmonic
V0 Magnitude IB 2nd Harmonic
V0 Phase Angle IC 2nd Harmonic
APh Sen Watts
APh Sen Vars
APh Power Angle
Z1 Imp Mag
Z1 Imp Ang

Page (AD) -36 P14x/EN AD/Gf7


Section 2 - Technical Data (P14x/EN AD/De6) Update Documentation

Phase A Imp Mag U/Voltage Start V< 1 2 AB BC CA


Phase A Imp Ang U/Voltage Trip V< 1 2 AB BC CA
Phase B Imp Mag O/Voltage Start V> 1 2 AB BC CA
Phase B Imp Ang O/Voltage Trip V> 1 2 AB BC CA
Phase C Imp Mag Underfrequency Start F< 1234
Phase C Imp Ang Trip F< 1234
Overfrequency Start F> 1 2
Stage Statistics (Advanced) Trip F> 1 2
StgX f+t Sta Overadmittance YN> Start Trip
StgX f+t Trip Overconductance GN> Start Trip
StgX f+df/dt Trp Oversusceptance BN> Start Trip
StgX df/dt+t Sta Breaker Fail: CB Fail 1 2
StgX df/dt+t Trp Supervision VTS/CTS/VCO/CLP
StgX f+Df/Dt Sta A/R State: Trip 1/2/3/4/5
StgX f+Df/Dt Trp Advanced Freq. Protection Start >123456789
StgX Revn Date Advanced Freq. Protection Trip >123456789
(X = 1, 2, 3, 4, 5, 6, 7, 8, 9) Adv. F+df/dt Protection Trip >123456789
Circuit Breaker Monitoring Statistics Adv. df/dt Protection Start >123456789
Adv. df/dt Protection Trip >123456789
CB Operations
Adv. DelF/DelT Protection Start >123456789
CB Operations
Adv. DelF/DelT Protection Trip >123456789
Circuit breaker operation counters on a per
Faulted Phase: A/B/C
phase basis ( = A, B, C). Start Elements:
Total I Broken Trip Elements: Binary data strings for fast polling
Cumulative breaker interruption duty on a of which protection elements started or
per phase basis ( = A, B, C). tripped for the fault recorded.
CB Operate Time Fault Alarms: Binary data strings for fast polling
CB CONTROL of alarms for the fault recorded.
Total Re-closures Fault Time:
Fault Record Proforma Active Group: 1/2/3/4
The following data is recorded for any relevant System Frequency: Hz
elements that operated during a fault, and can be Fault Duration: s
viewed in each fault record. CB Operate Time: s
Time & Date Relay Trip Time: s
Event Text Fault Location: km/miles//%
Event Value The current magnitudes and phase angles
Select Fault: [0...n] stored before the fault inception.
Started Phase: A/B/C I
Tripped Phase: A/B/C V:
Overcurrent Start I> 123456 Per phase record of the current and voltage
Trip I> 123456 magnitudes during the fault.
Neg. Seq. O/C Start I2> 1234 IN Measured
Trip I2> 1234 IN Derived
IN Sensitive
Broken ConductorTrip IREF Diff.
Earth Fault 1 Start IN1> 1234 IREF Bias
Trip IN1> 1234 VAN
Earth Fault 2 Start IN2> 1234 VBN
Trip IN2> 1234 VCN
Sensitive E/F Start ISEF> 1234 VN Derived
Trip ISEF> 1234 Admittance
Restricted E/F Trip IREF> Conductance
Residual O/V NVD Start VN> 1 2 Susceptance
Trip VN> 1 2
Thermal Overload: Alarm/Trip
Neg. Seq. O/V V2> Start Trip

P14x/EN AD/Gf7 Page (AD)-37