I> Blocking:
PROTECTION FUNCTIONS Binary function link string, selecting which overcurrent
elements (stages 1 to 4) will be blocked if VTS
System Config. detection of fuse failure occurs.
Phase Sequence: Standard ABC Binary function link string, selecting which overcurrent
Reverse ACB elements (stages 1 to 4) will be blocked if 2nd
2NDHARM BLOCKING: Disabled/ Enabled Harmonic Block is enabled with an option of choosing
2ndHarm Thresh: 570 1PH block.
I>lift 2H: 432
Voltage Dependent Overcurrent
Phase Overcurrent (Overcurrent) V DEPENDANT O/C
I>1 Function: Disabled / DT / V Dep OC Status
IEC S Inverse / IEC V Inverse / VCO Disabled
IEC E Inverse / UK LT Inverse / VCO >1
UK Rectifier / RI / IEEE M Inverse VCO >2
IEEE V Inverse / IEEE E Inverse VCO >1 & >2
US Inverse / US ST Inverse / VCO >5
Def User Curve 1 / VCO >1 & >2 & >5
Def User Curve 2 / VCO >1 & >5
Def User Curve 3 / VC0 >2 & >5
Def User Curve 4 VRO I>1
I>1 Direction: Non-Directional VRO I>2
Directional Fwd VRO I>5
Directional Rev VRO >1 & >2
I>1 Current Set: 0.084.00 In VRO >1 & >5
I>1 Time Delay: 0.00100.00 s
VRO >2 & >5
I>1 TMS: 0.0251.200
VRO >1 & >2 & I>5
I>1 Time Dial: 0.01100.00
V Dep OC V<1 Set
I>1 K (RI): 0.1010.00
10120 V (100/120 V)
I>1 DT Adder: 0.00100.00
40480 V (380/440 V)
I>1 Reset Char.: DT/Inverse
V Dep OC V<2 Set
I>1 tRESET: 0.00100.00 s
10120 V (100/120 V)
I>2 Status (up to):
40480 V (380/440 V)
I>2 tRESET All settings and options chosen
from the same ranges as per the Load Blinder
first stage overcurrent, I>1. Blinder Status: Disabled/Enabled
I>3 Status: Disabled Blinder Function: 3Ph/1Ph
Enabled Blinder Mode: Both/Forward/Reverse
I>3 Direction: Non-Directional FWD Z Impedance: 0.1100 ohm
Directional Fwd FWD Z Angle: 585 deg
Directional Rev REV Z Impedance: 0.1100 ohm
I>3 Current Set: 0.0832.00 In REV Z Angle: 585 deg
I>3 Time Delay: 0.00100.00 s Binder V<Block: 10120 V
I>4 Status (up to): Binder I2>Block: 0.84 A
I>4 Time Delay All settings and options chosen PU cycles: 050
from the same ranges as per the DO cycles: 050
third stage overcurrent, I>3.
I> Char Angle: -9595
I>5 Status (up to):
I>5 tRESET
All settings and options chosen from the same ranges
as per the first stage overcurrent, I>1.
I>6 Status (up to):
I>6 Time Delay All settings and options chosen
from the same ranges as per the
third stage overcurrent, I>3.
Overfrequency Protection
F>1 Status: Disabled/Enabled
F>1 Setting: 45.0065.00 Hz
F>1 Time Delay: 0.00100.00 s
F<2 Status (up to): F<2 Time Delay
All settings and options chosen from the same ranges
as per the 1st stage.
SYSTEM CHECKS
Auto-reclose AR with ChkSync: Disabled/Enabled
AR Mode Select: Command Mode AR with SysSync: Disabled/ Enabled
Opto Set Mode Live/Dead Ccts: Disabled/Enabled
User Set Mode No System Checks: Enabled/Disabled
Pulse Set Mode SysChk on Shot 1: Disabled/ Enabled
Number of Shots: 14 I>5: No Action/Initiate Main AR
Number of SEF Shots: 04 I>6: No Action/Initiate Main AR/Block AR
Sequence Co-ord.: Disabled/Enabled
CS AR Immediate: Disabled/Enabled Opto Input Labels
Dead Time 1: 0.01300.00 s Opto Input 1: (up to): Opto Input 24:
Dead Time 2: 0.01300.00 s User defined text string to describe the function of the
Dead Time 3: 0.019999.00 s particular opto input.
Dead Time 4: 0.019999.00 s
CB Healthy Time: 0.01 s9999.00 s
Start Dead on: Protection Resets/CB Trips
Output Labels
Relay 1: (up to): Relay 32:
Reclaim Extend: No Operation/On Prot. Start
User defined text string to describe the function of the
Reclaim Time 1: 1.00600.00 s
particular relay output contact.
Reclaim Time 2: 1.00600.00 s
Reclaim Time 3: 1.00600.00 s
Reclaim Time 4: 1.00600.00 s
AR Inhibit Time: 0.01600.00 s
AR Lockout: No Block/Block Inst. Prot.
EFF Maint. Lock: No Block/Block Inst. Prot.
AR Deselected: No Block/Block Inst. Prot.
Manual close: No Block/Block Inst. Prot.
Trip 1 Main: No Block/Block Inst. Prot.
Trip 2 Main: No Block/Block Inst. Prot.
Trip 3 Main: No Block/Block Inst. Prot.
Trip 4 Main: No Block/Block Inst. Prot.
Trip 5 Main: No Block/Block Inst. Prot.
Trip 1 SEF: No Block/Block Inst. Prot.
Trip 2 SEF: No Block/Block Inst. Prot.
Trip 3 SEF: No Block/Block Inst. Prot.
Trip 4 SEF: No Block/Block Inst. Prot.
Trip 5 SEF: No Block/Block Inst. Prot.
Man. Close on Flt: No Lockout/Lockout
Trip AR Inactive: No Lockout/Lockout
Reset Lockout by: User Interface/Select Non-Auto
AR on Man. Close: Enabled/Inhibited
Sys. Check Time: 0.019999.00 s
AR Skip Shot 1: Enabled/disabled
AR INITIATION
I>1, I>2: No Action/Initiate Main AR
I>3 and I>4: No Action/Initiate Main AR/
Block AR
IN1>1 and IN1>2: No Action/Main AR
IN1>3 and IN1>4: No Action/Initiate Main AR/
Block AR
IN2>1, IN2>2: No Action/Initiate Main AR
IN2>3 and IN2>4: No Action/Initiate Main AR/
Block AR
ISEF>1, ISEF>2, ISEF>3 and ISEF>4:
No Action/Initiate Main AR/
Initiate SEF AR/ Block AR
YN/GN/ BN>: No Action/Initiate Main AR
Ext. Prot.: No Action/Initiate Main AR