Sei sulla pagina 1di 1

Total Area = 35,000 SF

Assumptions: Classroom Area = 35,000 x 80% = 28,000 SF


Support Area = 35,000 x 20% = 7,000 SF

Title 24 Classroom Lighting Power Density (W/SF) = 1.2


Title 24 Support Lighting Power Density (W/SF) = 0.6

Reduce T24 Classroom LPD by 15% (W/SF) = 1.2 x 0.85 = 1.02


Reduce T24 Support LPD by 15% (W/SF) = 0.6 x 0.85 = 0.51

Lighting Load, Classroom = 28,000 x 1.02 = 28,560 W


Lighting Load, Support = 7,000 x 0.51 = 3,570 W

Receptacle Load, Classroom = 28,000 x 1.02 = 28,560 W


Receptacle Load, Support = 7,000 x 0.51 = 3,570 W

Miscellaneous Load, Support = 35,000 x 1.02 = 35,700 W


------------
Sub total 99,960 W
Demand Factor 0.7
------------
Total for Electrical 69,972 W

Total for Mechanical (260 kBTU/SF/year) 854,800 W


------------
(a) Total Load 924,772 W

Building Roof Area = 12,000 SF


Approximate Photovoltaic SF = 12,000 SF x 0.8 = 9,600 SF

Canopy Roof Area = 2,000 SF


Approximate Photovoltaic SF = 2,000 SF x 0.8 = 1,600 SF

Vertical installation, assume Area= 6,000 SF


Approximate Photovoltaic SF = 6,000 SF x 0.8 = 4,800 SF

(b) From PVSYST software, 9,600 SF can have a PV nominal power = 107,000 W
or = 11.15 W per SF
(c) From PVSYST software, 1,600 SF can have a PV nominal power = 15,600 W
or = 9.75 W per SF
(d) From PVSYST software, 4,800 SF can have a PV nominal power = 46,800 W
or = 9.75 W per SF
------------
(e) Total PV nominal power = 169,400 W

Therefore, (e) requires more power to equate it to (a)