GENERAL STRUCTURAL NOTES Engineers


Affiliated Engineers, Inc.


GENERAL REQUIREMENTS: 4. WIND LOADS: 7. LAP ALL WELDED WIRE FABRIC A MINIMUM DISTANCE OF ONE CROSS WIRE SPACING PLUS 2 STRUCTURAL STEEL: 3. ALL MEMBERS SHALL BE FORMED FROM HOT-DIPPED GALVANIZED STEEL, CORRESPONDING TO 3007 SW Williston Rd.
1. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE SPECIFICATIONS AND A. LOADS BASED ON ASCE 7-05 WIND LOAD CRITERIA. INCHES. 1. SEE NOTES ON PRIMARY CODES AND SPECIFICATIONS. THE REQUIREMENTS OF ASTM A653 SQ GRADE 33 (Fy = 33,000 PSI). GALVANIZED Gainesville, Florida 32608
OTHER PROJECT DRAWINGS BY OTHER DISCIPLINES. ALL WORK SHALL CONFORM TO THE BASIC WIND SPEED, 3 SECOND GUST................... 120 MPH COATING SHALL CONFORM TO ASTM A924 WITH COATING DESIGNATION G60. Tel 352.376.5500 Fax 352.375.3479
www.aeieng.com
REQUIREMENTS OF THE CODES LISTED BELOW. HURRICANE PRONE REGION........................... YES 8. ALL REINFORCING STEEL SHALL BE SUPPORTED ON STANDARD ACCESSORIES, HELD RIGIDLY 2. MATERIALS:
FL Cert of Auth - 0005140
WINDBORNE DEBRIS REGION.......................... NO AND ACCURATELY IN PLACE, AND PROTECTED AGAINST DISPLACEMENT BEFORE AND DURING 4. EXTERIOR METAL WALL STUDS:
2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS RELATING TO EXISTING BUILDING CLASSIFICATION CATEGORY.................. III PLACEMENT OF CONCRETE. SUPPORTING ACCESSORY LEGS THAT REST ON CONCRETE W-SHAPES & WT-SHAPES.................................... ASTM A992 A. THE COLD FORMED METAL STUD FRAMING CONTRACTOR IS RESPONSIBLE FOR THE
CONDITIONS BY MAKING FIELD SURVEYS AND MEASUREMENTS PRIOR TO COMMENCING IMPORTANCE FACTOR................................. 1.15 SURFACES THAT WILL BE EXPOSED IN THE FINISHED STRUCTURE SHALL BE FABRICATED OF S-SHAPES, M-SHAPES, HP-SHAPES........................... ASTM A36 DESIGN OF EXTERIOR METAL STUDS. SHOP DRAWINGS SHOWING PLANS, ELEVATIONS,
FABRICATION OR CONSTRUCTION. INTERNAL PRESSURE COEFFICIENT..................... +/- 0.18 STAINLESS STEEL. ST-SHAPES & MT-SHAPES................................... ASTM A36 AND SECTIONS SHALL BE SUBMITTED WITH CALCULATIONS SIGNED AND SEALED BY A
WIND EXPOSURE CATEGORY............................ B C-SHAPES & MC-SHAPES.................................... ASTM A36 LICENSED ENGINEER IN THE STATE OF FLORIDA.
3. THE GENERAL CONTRACTOR SHALL ENSURE THAT ALL CONSTRUCTION METHODS USED WILL NOT WIND TOPOGRAPHIC FACTOR, Kzt....................... 1.0 9. DOWELS AND OTHER MISCELLANEOUS STEEL EMBEDDED ITEMS SHALL BE LOCATED AND HELD ANGLES & PLATES......................................... ASTM A36 B. THE MINIMUM SIZE AND SPACING SHALL BE AS DESCRIBED IN THE CONSTRUCTION
CAUSE DAMAGE TO ADJACENT BUILDINGS, UTILITIES, OR OTHER PROPERTY. THIS IN SPECIFIED POSITION PRIOR TO PLACEMENT OF CONCRETE AND SHALL NOT BE PUSHED HSS SHAPES.............................................. ASTM A500, GRADE B DOCUMENTS.
REQUIREMENT IS PARTICULARLY IMPORTANT DURING FOUNDATION INSTALLATION. B. SEE LOADING NOTES, TABLES AND DIAGRAMS FOR DESIGN FORCES FOR COMPONENTS INTO CONCRETE FOLLOWING CONCRETE POUR. STEEL PIPE................................. ASTM A53 (TYPE E OR S), GRADE B C. DO NOT CUT OR OTHERWISE DAMAGE LOAD BEARING STUDS DURING INSTALLATION OF
DESIGNED BY DELEGATED ENGINEERS. HIGH STRENGTH BOLTS..................................... ASTM A325 WORK BY OTHER TRADES.
4. THE GENERAL CONTRACTOR IS ADVISED TO CONSIDER PERFORMING PHOTOGRAPHIC SURVEYS 10. FOUNDATION AND GRADE BEAM REINFORCING SHALL BE SUPPORTED ON SPECIALLY CAST 3- MACHINE BOLTS........................................... ASTM A307
AND OTHER DOCUMENTATION OF THE CONDITION OF ADJACENT BUILDINGS AND OTHER 5. SEISMIC: NOT CONTROLLING. 1/2 INCH HIGH CONCRETE BLOCKS CAST IN ACCORDANCE WITH DETAILS FURNISHED ON ANCHOR RODS.................................ASTM F1554, GRADE 55 TYPE S1(UNO)
STRUCTURES BEFORE THE START OF CONSTRUCTION. DRAWINGS. SLAB-ON-GRADE REINFORCING, INCLUDING WIRE FABRIC, SHALL BE SUPPORTED WELDED HEADED STUDS..................................... ASTM A108 SUBMITTALS:
FOUNDATIONS: ON PRECAST BLOCKS OR 3000 PSI CONCRETE BRICK OF THE PROPER THICKNESS. DEFORMED BAR ANCHORS.................................... ASTM A496 1. ALL SHOP DRAWINGS MUST BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR
5. THE GENERAL CONTRACTOR SHALL OBTAIN COPIES OF THE LATEST CONTRACT DOCUMENTS, 1. FOUNDATION DESIGN IS BASED ON THE INFORMATION PROVIDED ON THE STRUCTURAL WELDING ELECTRODES...................................... AWS D1.1, E70 SERIES TO SUBMITTAL. SUBMITTAL WITHOUT CONTRACTOR REVIEW WILL RESULT IN DELAYS. THE
INCLUDING ALL ADDENDA, AND PROVIDE THE RELEVANT PORTIONS TO ALL SUB-CONTRACTORS DRAWINGS FOR THE ORIGINAL STRUCTURE BY TK&A ARCHITECTS AND DATED 2/28/03. 11. SOFT METRIC BAR SIZES VS. INCH POUND BAR SIZES: CONTRACTOR SHALL CONFIRM THAT SHOP DRAWINGS HAVE BEEN COMPLETED AND CHECKED BY
AND SUPPLIERS PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND FABRICATION AND ERECTION 3. NON-SHRINK, NON-METALLIC GROUT WITH A 28 DAY STRENGTH OF 5000 PSI SHALL BE USED THE SUPPLIER PRIOR TO SUBMISSION.
OF STRUCTURAL MEMBERS. 2. ALL VEGETATION, TOPSOILS, ROOTS AND ORGANIC ZONES SHALL BE STRIPPED AND REMOVED METRIC INCH-POUND UNDER BASE PLATES AND SHALL CONFORM TO CORPS OF ENGINEERS CRD-C621, FACTORY
FROM THE CONSTRUCTION AREA FOR A DISTANCE OF AT LEAST 5 FEET BEYOND THE PREMIX GROUT. SEE SPECIFICATIONS FOR TESTING REQUIREMENTS. 2. CONTRACTOR IS TO PROVIDE 1 REPRODUCIBLE AND 2 COPIES OF SHOP DRAWINGS. THE 2
6. THE GENERAL CONTRACTOR SHALL COMPARE AND COORDINATE THE DRAWINGS OF ALL EXTERIOR OF BUILDING FOUNDATION LIMITS. THE DEPTH OF STRIPPING SHALL BE THAT #10.....................#3 COPIES WILL BE RETAINED BY THE ARCHITECT AND ENGINEER AND THE REPRODUCIBLE WILL
DISCIPLINES AND REPORT ANY DISCREPANCIES BETWEEN THE DRAWINGS TO THE ARCHITECT REQUIRED TO REMOVE SIGNIFICANT ROOT ZONES, SMALL TREE STUMPS AND OTHER #13.....................#4 4. ENGINEER SHALL BE CONTACTED FOR APPROVAL OF ANY FIELD MODIFICATIONS OF ANCHOR BE RETURNED TO THE CONTRACTOR. ADDITIONAL COPIES WILL BE RETURNED UNMARKED.
AND ENGINEER. UNACCEPTABLE MATERIALS, BUT IN NO CASE LESS THAN 6 INCHES. #16.....................#5 BOLTS OR RODS AND COLUMN BASE PLATES (PER OSHA). CONTRACTOR SHALL MAKE ANY OTHER ADDITIONAL REQUIRED COPIES FROM THE MARKED-UP
#19.....................#6 REPRODUCIBLES. PREFERRED ALTERNATE: PROVIDE ELECTRONIC COPIES (PDF) OF Architecture
7. DETAILS LABELED "TYPICAL" SHALL APPLY TO ALL SITUATIONS THAT ARE THE SAME OR 3. EXCAVATIONS FOR LARGE STUMPS, ABANDONED UTILITIES, UNDERGROUND TANKS, ETC. #22.....................#7 5. TEMPORARY BRACING OF STRUCTURAL STEEL ELEMENTS IS THE RESPONSIBILITY OF THE CONTRACTOR REVIEWED AND STAMPED SHOP DRAWINGS FOR A/E REVIEW AND PROCESSING. Walker Architects, Inc.
SIMILAR TO THOSE SPECIFICALLY DETAILED. SEE DETAIL TITLES FOR APPLICABILITY OF SHALL BE BACKFILLED IN LAYERS WITH COMPACTION AND TESTING OF EACH LAYER AS #25.....................#8 CONTRACTOR. STRUCTURAL STABILITY SHALL BE MAINTAINED AT ALL TIMES DURING THE 4055 NW 43rd St, #28
Gainesville, Florida 32606
A PARTICULAR DETAIL. TYPICAL DETAILS SHALL APPLY WHETHER OR NOT THEY ARE DESCRIBED FOR PLACEMENT AND COMPACTION OF FILL MATERIAL. USE LOOSE BACKFILL #29.....................#9 ERECTION PROCESS. 3. SHOP DRAWING SUBMITTAL REQUIREMENTS SHALL BE IN ACCORDANCE WITH THE STRUCTURAL
Tel 352.672.6448 Fax 352.672.6468
SPECIFICALLY KEYED AT EACH LOCATION. THE ENGINEER SHALL HAVE FINAL AUTHORITY LAYER THICKNESS APPROPRIATE FOR THE SIZE OF COMPACTOR BEING USED. #32.....................#10 SPECIFICATIONS. CHANGES OR ADDITIONS MADE ON RESUBMITTED SHOP DRAWINGS SHALL BE www.walker-arch.com
TO DETERMINE APPLICABILITY OF TYPICAL DETAILS. #36.....................#11 CONTRACTOR MUST PROVIDE NOTIFICATION TO THE ERECTOR THAT, BY TESTING, THE CLEARLY INDICATED, AND THE PURPOSE OF THE RESUBMITTAL SHALL BE NOTED ON THE AA26002009
4. AFTER THE SITE HAS BEEN CLEARED AND PROOF-ROLLED, THE EXPOSED SOILS AT THE #43.....................#14 FOUNDATION AND SUPPORTING WALLS HAVE ATTAINED SUFFICIENT STRENGTH TO SUPPORT TRANSMITTAL. REVIEW OF RESUBMITTED SHOP DRAWINGS SHALL BE LIMITED SPECIFICALLY
8. WHERE CONFLICTS EXIST BETWEEN STRUCTURAL DOCUMENTS THE STRICTEST REQUIREMENTS, STRIPPED SURFACE WITHIN AND TO A POINT 5 FEET OUTSIDE THE BUILDING CONSTRUCTION THE STEEL TO BE ERECTED BEFORE ERECTING STRUCTURAL STEEL. TO THE ITEMS NOTED FOR CORRECTION ON THE PREVIOUS SUBMITTAL.
AS INDICATED BY THE STRUCTURAL ENGINEER SHALL GOVERN. AREA SHALL BE COMPACTED WITH OVERLAPPING PASSES WITH A LIGHT WEIGHT VIBRATORY Structural
DRUM ROLLER. DENSITIES OF AT LEAST 95 PERCENT OF THE MODIFIED PROCTOR MAXIMUM CONCRETE FORMWORK: 6. PROVIDE ONE SHOP COAT OF PRIMER (TT-P-636) ON ALL STEEL EXCEPT FOR ITEMS TO BE 4. THE GENERAL CONTRACTOR SHALL SUBMIT FOR STRUCTURAL ENGINEER REVIEW SHOP Structural Engineers Group, Inc.
9. DELEGATED ENGINEER REQUIREMENTS: THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS DRY DENSITY (ASTM D-1557) SHALL BE UNIFORMLY OBTAINED TO A DEPTH OF AT LEAST 24 1. SEE NOTES ON PRIMARY CODES AND SPECIFICATIONS. HOT DIPPED GALVANIZED OR SPRAY FIREPROOFED. DO NOT PAINT PORTIONS EMBEDDED IN DRAWINGS FOR THE FOLLOWING ITEMS: 4114 Sunbeam Rd, Bldg 200
HAS ISSUED STATEMENTS ON RESPONSIBILITIES OF PROFESSIONAL ENGINEERS, PURSUANT INCHES BELOW THE COMPACTED SURFACE. REGARDLESS OF THE DEGREE OF COMPACTION CONCRETE. Jacksonville, Florida 32257
TO CHAPTERS 61G15-30 AND 61G15-31 OF THE FLORIDA ADMINISTRATIVE CODE. CERTAIN ACHIEVED, A MINIMUM OF EIGHT COMPLETE COVERAGES SHALL BE MADE WITHIN THE 2. ALL FORMWORK SHALL BE DESIGNED, ERECTED, SUPPORTED, BRACED, AND MAINTAINED CONCRETE MIX DESIGNS Tel 904.262.4000 Fax 904.262.4100
COMPONENTS OF THE STRUCTURE REQUIRE THE WORK OF DELEGATED ENGINEERS FOR THE BUILDING AREA. THE ROLLER COVERAGES SHALL BE DIVIDED EVENLY INTO TWO ACCORDING TO ACI 347, RECOMMENDED STANDARD PRACTICE FOR CONCRETE FORMWORK. 7. FRAMING CONNECTIONS NOT DETAILED, OR CONNECTIONS THAT ARE MODIFIED FROM THOSE LIGHT GAGE METAL FRAMING(a) www.segonline.com
Cert of Auth - 6523
S EG
DESIGN OF THOSE COMPONENTS. ALL RELEVANT PROCEDURES PRESENTED IN THE FLORIDA PERPENDICULAR DIRECTIONS. THE CONTRACTOR IS ADVISED NOT TO USE THE VIBRATORY DETAILED, SHALL BE DESIGNED BY SUPPLIER FOR THE END REACTION SHOWN ON THE PLAN. REINFORCING STEEL
ADMINISTRATIVE CODE SHALL APPLY TO THIS PROJECT. MODE OF COMPACTORS IN CLOSE PROXIMITY TO EXISTING STRUCTURES. THE CONTRACTOR 3. RESPONSIBILITY: THE DESIGN, CONSTRUCTION, AND SAFETY OF ALL FORMWORK SHALL BE IF NO REACTION IS PROVIDED, DESIGN FOR 1/2 THE BEAM MAXIMUM UNIFORM LOAD PER STEEL JOISTS (b)
SHALL COORDINATE COMPACTION EFFORTS AND FOUNDATION INSTALLATIONS TO INSURE THAT THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. ALL FORMS, SHORES, BACKSHORES, AISC MANUAL FOR STEEL CONSTRUCTION. SUBMIT SIGNED AND SEALED CALCULATIONS. STEEL ROOF DECK
10. THE GENERAL CONTRACTOR SHALL REVIEW AND DETERMINE THAT DIMENSIONS ARE NO DAMAGE OCCURS TO ADJACENT STRUCTURES. FALSEWORK, BRACING, AND OTHER TEMPORARY SUPPORTS SHALL BE ENGINEERED TO SUPPORT STRUCTURAL STEEL
ENGINEER OF RECORD
COORDINATED BETWEEN ARCHITECTURAL AND STRUCTURAL DRAWINGS PRIOR TO FABRICATION ALL LOADS IMPOSED INCLUDING THE WET WEIGHT OF CONCRETE, CONSTRUCTION EQUIPMENT, 8. ALL WELD OPERATORS SHALL BE CURRENTLY AWS QUALIFIED.
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961
OR START OF CONSTRUCTION. 5. AFTER THE EXISTING CONCRETE SLAB HAS BEEN REMOVED, THE EXPOSED SOILS AT THE LIVE LOADS, LATERAL LOADS DUE TO WIND AND WET CONCRETE IMBALANCE. SEE THE NOTATIONS FOLLOWING SUBMITTAL ITEMS INDICATE THE FOLLOWING:
STRIPPED SURFACE WITHIN THE NEW GANTRY PIT CONSTRUCTION AREA SHALL BE COMPACTED SPECIFICATIONS FOR DETAILED REQUIREMENTS. 9. SHOP CONNECTIONS SHALL BE WELDED OR HIGH STRENGTH BOLTED. USE 3/16" FILLET WELD
11. NO STRUCTURAL MEMBER SHALL BE CUT OR NOTCHED OR OTHERWISE REDUCED IN STRENGTH WITH OVERLAPPING PASSES WITH A WALK-BEHIND VIBRATORY COMPACTOR. DENSITIES OF MINIMUM. (a) CALCULATIONS AND SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A
UNLESS APPROVED BY THE STRUCTURAL ENGINEER. AT LEAST 95 PERCENT OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY (ASTM D 1557) 4. TOLERANCES: UNLESS SPECIFIED OTHERWISE, ALL TOLERANCES FOR CONCRETE FORMWORK PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA.
SHALL BE UNIFORMLY OBTAINED TO A DEPTH OF AT LEAST 12 INCHES BELOW THE SHALL CONFORM TO ACI STANDARD 117, STANDARD TOLERANCES FOR CONCRETE 10. FIELD CONNECTIONS SHALL BE WELDED OR HIGH STRENGTH BOLTED AS DETAILED. NO
12. THE GENERAL CONTRACTOR SHALL COORDINATE ARCHITECTURAL, MECHANICAL, ELECTRICAL COMPACTED SURFACE. REGARDLESS OF THE DEGREE OF COMPACTION ACHIEVED, A MINIMUM CONSTRUCTION AND MATERIALS. THE CONTRACTOR SHALL ENGAGE A LICENSED SURVEYOR TO FIELD WELDING OF HOT DIPPED GALVANIZED MEMBERS WILL BE ALLOWED. USE 3/16" (b) INCLUDE A CERTIFICATE OF COMPLIANCE WITH CONTRACT DOCUMENTS SIGNED AND
AND PLUMBING DRAWINGS FOR ANCHORED, EMBEDDED OR SUPPORTED ITEMS. NOTIFY THE OF EIGHT COMPLETE COVERAGES SHALL BE MADE WITHIN THE PIT AREA. THE COMPACTOR VERIFY THAT WORK IS WITHIN SPECIFIED TOLERANCES UNLESS WRITTEN AUTHORIZATION IS FILLET WELD MINIMUM. SEALED BY THE PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA
ARCHITECT / ENGINEER OF ANY DISCREPANCIES. COVERAGES SHALL BE DIVIDED EVENLY INTO TWO PERPENDICULAR DIRECTIONS. THE OBTAINED FROM THE ARCHITECT TO PROVIDE TOLERANCE CONTROL USING THE CONTRACTOR'S RESPONSIBLE FOR THE DESIGN.
CONTRACTOR SHALL COORDINATE COMPACTION EFFORTS AND FOUNDATION INSTALLATIONS TO OWN FORCES PRIOR TO BEGINNING WORK. 11. DURING THE ERECTION OF STEEL BEAMS AND DIAGONAL BRACING, ALL BOLTING AND
SPECIAL INSPECTIONS: INSURE THAT NO DAMAGE OCCURS TO ADJACENT STRUCTURES. FIELD WELDING SHALL BE COMPLETE BEFORE RELEASING HOISTING CABLES. (c) SUBMIT ONE COPY FOR INFORMATION AND RECORD ONLY.
1. THIS BUILDING IS CLASSIFIED AS A "THRESHOLD BUILDING". SPECIAL INSPECTION OF 5. ALL EXPOSED EDGES OF CONCRETE SHALL BE CHAMFERED WHERE SHOWN ON THE
THE CONSTRUCTION IS REQUIRED BY THE STATE OF FLORIDA IN ACCORDANCE WITH 6. AFTER COMPLETION OF DENSIFICATION OF EXISTING SOILS, STRUCTURAL FILL SHALL THEN ARCHITECTURAL OR STRUCTURAL DRAWINGS. 12. SUBMIT FOR REVIEW SHOP DRAWINGS OF STEEL DETAILS PRIOR TO FABRICATING 5. MANUFACTURER'S LITERATURE: SUBMIT TWO COPIES OF MANUFACTURER'S LITERATURE FOR
CHAPTERS 471 AND 553 OF THE FLORIDA STATUTES. THE COST OF THESE SPECIAL BE PLACED IN LIFTS NOT EXCEEDING 6 INCHES IN LOOSE THICKNESS WHEN USING THE STRUCTURAL STEEL. ALL MATERIALS AND PRODUCTS USED IN CONSTRUCTION ON THE PROJECT.
INSPECTION SERVICES SHALL BE PAID BY THE OWNER. ROLLER PREVIOUSLY DESCRIBED. EACH LIFT SHALL BE THOROUGHLY COMPACTED WITH THE 6. PLUMBING SLEEVE SPACING SHALL BE THE LARGER OF THREE (3) DIAMETERS CENTER
VIBRATORY ROLLER UNTIL DENSITIES EQUIVALENT TO AT LEAST 95 PERCENT OF THE TO CENTER OF THE LARGER SLEEVE, OR 6" CLEAR BETWEEN SLEEVES. SUBMIT SLEEVE 13. ALL EXTERIOR ELEMENTS AND THOSE ELEMENTS NOTED TO BE GALVANIZED SHALL BE HOT 6. THE ENGINEER'S REVIEW OF SHOP DRAWINGS IS FOR GENERAL CONFORMANCE OF THE DESIGN
2. SUBMIT DOCUMENTATION TO THE STRUCTURAL ENGINEER CERTIFYING THAT THE SPECIAL MODIFIED PROCTOR MAXIMUM DRY DENSITY ARE UNIFORMLY OBTAINED. STRUCTURAL FILL LOCATIONS AND SIZES TO ENGINEER FOR REVIEW PRIOR TO CONSTRUCTION. DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A123 AFTER SANDBLAST CLEANING PER CONCEPT. CONTRACTOR SHALL SUBMIT A SCHEDULE OF SHOP DRAWING SUBMITTALS THAT IS
INSPECTOR AND HIS AUTHORIZED REPRESENTATIVE(S) COMPLY WITH THE MINIMUM SHALL CONSIST OF AN INORGANIC, NON-PLASTIC, GRANULAR SOIL CONTAINING LESS THAN SSPC-SP10. USE ASTM A325 BOLTS HOT DIPPED GALVANIZED WITH GALVANIZED HARDENED ACCEPTABLE TO BOTH CONTRACTOR AND ENGINEER. AFTER THE CONTRACTOR HAS REVIEWED
QUALIFICATIONS UNDER THE FLORIDA STATUTES AND THOSE LISTED IN THE STRUCTURAL 10 PERCENT MATERIAL PASSING THE NO. 200 MESH SIEVE, A RELATIVELY CLEAN SAND 7. PENETRATIONS SHALL NOT BE PERMITTED IN ANY STRUCTURAL MEMBERS OTHER THAN WASHERS AND GALVANIZED HEAVY HEX NUTS FOR BOLTING OF GALVANIZED ITEMS. THE SHOP DRAWINGS, PROMPT REVIEW BY THE ENGINEER WILL BE MADE OF ALL
INSPECTION PLAN. DOCUMENTATION SHALL INCLUDE A LIST OF THE NAMES OF PERSONS WITH A UNIFIED SOIL CLASSIFICATION OF SP OR SP-SM. THOSE SPECIFICALLY INDICATED ON THE STRUCTURAL DRAWINGS WITHOUT THE WRITTEN SUBMITTALS. FOR LARGE SUBMITTALS, REASONABLE REVIEW TIME SHALL BE ALLOWED AND
PERFORMING THRESHOLD INSPECTION SERVICES AND PROOF THAT THE SPECIAL INSPECTOR REVIEW OF THE STRUCTURAL ENGINEER OF RECORD. THE CONTRACTOR SHALL SUBMIT 14. STEEL COLUMNS, BASE PLATES AND ALL STEEL BELOW GRADE SHALL HAVE A MINIMUM 3" MAY EXCEED TWO WEEKS. THE CONCURRENT SUBMITTAL OF MULTIPLE SHOP DRAWINGS
IS REGISTERED IN THE STATE OF FLORIDA WHEN AUTHORIZED REPRESENTATIVES ARE USED. 7. FOOTINGS AND MAT HAVE BEEN DESIGNED FOR AN ALLOWABLE BEARING PRESSURE OF 4000 DRAWINGS TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW INDICATING ANY CONCRETE COVER PROTECTION. ("DUMPING") WILL FURTHER EXTEND THE REVIEW PROCESS AND TIME FRAME NECESSARY TO
SUBMIT DOCUMENTATION THAT THEY ARE QUALIFIED BY LICENSURE AS A PROFESSIONAL PSF. THE UPPER 12 INCHES OF SANDY BEARING SOILS IN THE FOOTING EXCAVATION CONCENTRATION OF PIPES, OPENINGS OR PENETRATIONS NOT SHOWN ON THE STRUCTURAL PROPERLY REVIEW EACH SUBMITTAL.
ENGINEER OR ENGINEER INTERN, OR REGISTRATION AS A BUILDING INSPECTOR OR GENERAL BOTTOMS SHALL BE COMPACTED TO DENSITIES EQUIVALENT TO 95 PERCENT OF THE DRAWINGS PRIOR TO CONCRETE POURS. 15. MEMBERS NOTED AS "CONTINUOUS" SHALL BE FULLY WELDED AT ALL BUTT SPLICES OR
CONTRACTOR. MODIFIED PROCTOR MAXIMUM DRY DENSITY. COMPACTION, OR RECOMPACTION OF THE CONNECTIONS SHALL BE DETAILED TO PROVIDE CONTINUITY. 7. REPRODUCTION OF THESE CONTRACT DOCUMENTS BY ANYONE FOR USE IN SHOP DRAWINGS
FOOTING EXCAVATION BEARING LEVEL SOILS LOOSENED BY THE EXCAVATION PROCESS, CONCRETE MASONRY: SHALL SIGNIFY THEIR ACCEPTANCE OF ALL INFORMATION SHOWN AS BEING CORRECT. Revisions
CONSTRUCTION RESPONSIBILITY: SHALL BE ACHIEVED BY MAKING SEVERAL PASSES WITH A RELATIVELY LIGHTWEIGHT, WALK- 1. SEE NOTES ON PRIMARY CODES AND SPECIFICATIONS. STEEL JOISTS: STRUCTURAL ENGINEERS GROUP, INC. SHALL BE INDEMNIFIED AND HELD HARMLESS FROM
1. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE COMPLETED BEHIND VIBRATORY SLED OR ROLLER COMPACTOR. 1. SEE NOTES ON PRIMARY CODES AND SPECIFICATIONS. ALL CLAIMS, DAMAGES, LOSSES, EXPENSES OR LIABILITIES OF ANY KIND, INCLUDING
STRUCTURE, AND ARE NOT INTENDED TO INDICATE THE METHOD OR MEANS OF 2. CONCRETE MASONRY UNITS SHALL BE LOAD BEARING TYPE CONFORMING TO ASTM C-90 ATTORNEYS FEES. THE CONTRACTOR IS RESPONSIBLE FOR PROPER CHECKING AND
CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE 8. UNLESS NOTED, ALL FOOTINGS SHALL BE CENTERED UNDER COLUMNS, PIERS AND WALLS. HAVING A MINIMUM COMPRESSIVE STRENGTH OF 1900 PSI (NET AREA). 2. THE MANUFACTURER OF THE JOISTS SHALL BE A MEMBER OF THE STEEL JOIST INSTITUTE. COORDINATING OF DETAILS, DIMENSIONS, SIZES AND QUANTITIES AS REQUIRED TO
SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, FACILITATE COMPLETE AND ACCURATE FABRICATION AND ERECTION.
SEQUENCES, AND FOR JOB SAFETY. 9. SLAB-ON-GRADE CONSTRUCTION SHALL BE SUPPORTED ON SUBGRADE COMPACTED TO A 3. MORTAR SHALL CONFORM TO ASTM C-270 TYPE S. 3. PROVIDE ONE SHOP COAT OF PRIMER (TT-P-636) EXCEPT ITEMS TO RECEIVE SPRAY
DENSITY OF NO LESS THAN 95% OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY (ASTM FIREPROOFING.
2. THE ENGINEER DOES NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE RESPONSIBLE D-1557) TO A DEPTH OF AT LEAST 12 INCHES. INTERIOR SLABS-ON-GRADE SHALL BE 4. PLAIN END TWO CELLED UNITS SHALL BE USED FOR BLOCKS THAT ARE TO HAVE CELLS POST-INSTALLED ANCHORS:
FOR, CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES, FOR CAST OVER A VAPOR RETARDER. SEE SPECIFICATIONS. REINFORCED AND FILLED. WEB SHELLS ADJACENT TO CELLS THAT ARE TO BE FILLED ARE 4. SEE GENERAL NOTES FOR SPRINKLER PIPE SUPPORT. 1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE DRAWINGS.
SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK, FOR THE ACTS OR TO BE BEDDED IN MORTAR. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORD (EOR) PRIOR TO USING
OMISSIONS OF THE CONTRACTOR, SUBCONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY 10. RETAINING WALLS HAVE BEEN DESIGNED FOR AN ASSUMED LATERAL EARTH PRESSURE OF 5. REFER TO DETAILS FOR SPECIAL TREATMENT OF: POST-INSTALLED ANCHORS FOR MISSINGS OR MISPLACED ANCHORS.
OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN 110 PSF PER FOOT OF DEPTH AND AN ASSUMED SURCHARGE OF 200 PSF. DESIGN ASSUMES 5. FILL CELLS AS NOTED ON DRAWINGS WITH 3000 PSI GROUT, OR GROUT CONFORMING TO SUPPORTING CONCENTRATED LOADS
ACCORDANCE WITH THE CONTRACT DOCUMENTS. WELL GRADED AND DRAINED BACKFILL. ASTM C-476,SPECIFICALLY DESIGNED FOR FILLING OF CELLS. 2. CARE SHALL BE GIVEN TO AVOID CONFLICTS WITH EXISTING REINFORCING WHEN DRILLING
6. JOISTS SHALL BE DESIGNED TO RESIST A NET UPLIFT AS SHOWN ON LOADING DIAGRAMS. HOLES. HOLES SHALL BE DRILLED AND CLEANED PER THE MANUFACTURER'S INSTRUCTIONS.
3. PERIODIC SITE OBSERVATION VISITS MAY BE PROVIDED BY THE STRUCTURAL ENGINEER. CAST-IN-PLACE CONCRETE: 6. IN SPLICING VERTICAL BARS, LAP ENDS, PLACE IN CONTACT AND WIRE-TIE TOGETHER OR ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AT
THE SOLE PURPOSE OF THESE OBSERVATIONS IS TO REVIEW THE GENERAL CONFORMANCE OF 1. THE LATEST EDITION OF THE FOLLOWING ACI STANDARDS APPLY: USE BAR POSITIONERS. LAP BARS SIDE BY SIDE IN THE PLANE OF THE WALL TO 7. CONNECT JOIST BEARING PLATES TO JOIST TOP CHORD FOR 4K. NOT LESS THAN MINIMUM EDGE DISTANCES AND/OR SPACINGS INDICATED IN THE
THE CONSTRUCTION WITH THE STRUCTURAL CONTRACT DOCUMENTS. THESE LIMITED MAINTAIN PROPER COVER. MANUFACTURER'S LITERATURE.
OBSERVATIONS SHOULD NOT BE CONSTRUED AS CONTINUOUS OR EXHAUSTIVE TO VERIFY THAT ACI 318 (CODE) ACI 304 (PLACING) 8. SUBMIT FOR REVIEW SHOP DRAWINGS OF JOIST DETAILS FOR FABRICATION AND ERECTION
ALL CONSTRUCTION IS IN COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS. THE GENERAL ACI 306 (WINTER CONCRETING) ACI 315 (DETAILING) 7. SEE PRIMARY CODES, SPECIFICATIONS AND DRAWINGS FOR GROUTING PROCEDURES. PRIOR TO FABRICATING JOISTS. 3. SPECIAL INSPECTION SHALL BE PROVIDED FOR ALL ADHESIVE AND MECHANICAL ANCHOR
CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING ALL WORK IN COMPLIANCE WITH THE ACI 305 (HOT WEATHER CONCRETING) ACI 347 (FORMWORK) INSTALLATIONS AS REQUIRED BY THE EOR. INDEPENDENT ON-SITE PROOF LOAD TESTING
CONSTRUCTION DOCUMENTS. ACI 211.1 (MIX PROPORTIONING) ACI 301 (SPECIFICATIONS) 8. INSTALLATION OF CONCRETE MASONRY SHALL BE COMPATIBLE WITH ALL APPLIED FINISHES 9. PROVIDE HORIZONTAL OR DIAGONAL TYPE BRIDGING FOR ALL JOISTS AS REQUIRED BY SJI SHALL BE PERFORMED AS REQUIRED BY THE EOR. CONTACT EOR FOR NUMBER OF ANCHORS
SUCH AS STUCCO OR PAINT. DO NOT SPONGE WALLS WITHOUT PROPER CLEANING SPECIFICATION AND AS INDICATED ON THE DRAWINGS. THE ENDS OF ALL BRIDGING LINES REQUIRED TO BE TESTED AND REQUIRED PROOF LOAD MAGNITUDE.
PRIMARY CODES AND SPECIFICATIONS: 2. ALL CONCRETE SHALL BE NORMAL WEIGHT (148 PCF DRY DENSITY, MIN), WITH MIXES COMPATIBLE WITH FINISHES. TERMINATING AT BEAMS SHALL BE ANCHORED THERETO AT TOP AND BOTTOM CHORDS.
1. GENERAL BUILDING CODE: DESIGNED TO MEET THE FOLLOWING CRITERIA FOR USE IN VARIOUS ELEMENTS OF THE PROVIDE ALL REQUIRED BRIDGING ANCHORS. 4. UNLESS NOTED OTHERWISE ON DOCUMENTS, ACCEPTABLE PRODUCTS SHALL BE AS LISTED
A. FLORIDA BUILDING CODE, 2007 EDITION WITH 2009 SUPPLEMENT. STRUCTURE AS FOLLOWS: 9. PROVIDE GALVANIZED WIRE TYPE HORIZONTAL JOINT REINFORCING AT 16" O.C. (MAX) AND BELOW:
28-DAY AS INDICATED ON ARCHITECTURAL DRAWINGS. PROVIDE HOT DIP GALVANIZED HJR ON ALL 10. ALL JOISTS SHALL BE DESIGNED FOR A SINGLE CONCENTRATED TRAVELING PROVISIONAL A. MECHANICAL ANCHORS INTO CONCRETE:
2. CONCRETE CODES: COMPRESSIVE MAX. SLUMP EXTERIOR WALLS. IN ADDITION TO SCHEDULED OR DETAILED LINTEL AND SILL LOAD OF 300 POUNDS ALONG THE TOP CHORD AND 100 POUNDS ALONG THE BOTTOM CHORD 1. USE THE FOLLOWING (UNO):
A. BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318-05). STRENGTH MAX. SIZE W/C RANGE REINFORCING, PROVIDE TWO LAYERS OF HJR AT 8 INCHES ON CENTER ABOVE AND BELOW APPLIED BETWEEN PANEL POINTS. A. HILTI KWIK BOLT TZ CARBON AND STAINLESS STEEL ANCHORS
B. SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301). STRUCTURAL ELEMENT (PSI) AGGREGATE RATIO (IN) ALL LINTELS AND SILLS WHICH SPAN MORE THAN 12 INCHES. EXTEND ADDED HJR 24 (ICC-ES ESR1917)
C. LATEST EDITION OF THE CRSI MANUAL OF STANDARD PRACTICE WITH ALL INCHES BEYOND THE OPENING JAMBS EXCEPT AT WCJ. 11. JOIST DIAGONAL MEMBERS LOCATED IN THE MIDDLE QUARTER OF THE SPAN SHALL BE B. RED HEAD TRUBOLT + WEDGE ANCHORS (ICC-ES ESR2427)
SUPPLEMENTS. A. FOOTINGS (WALL & MAT) 4000 3/4" 0.45 3-5 DESIGNED FOR A MINIMUM SHEAR, IN COMPRESSION, OF 15 PERCENT OF THE END C. SIMPSON STRONG-TIE STRONG-BOLT (STB) (ICC-ES ESR1771)(FL8668)
B. FOUNDATION WALLS 4000 4/4" 0.45 3-5 10. MASONRY BOND BEAMS AND CONCRETE TIE BEAMS CAST ON MASONRY WALLS SHALL BE REACTION. THIS MINIMUM DESIGN LOAD SHALL BE TO ACCOUNT FOR THE POSSIBILITY OF 2. USE THE FOLLOWING ONLY WHERE SPECIFICALLY CALLED OUT ON THE
3. STRUCTURAL STEEL CODES: C. SLAB-ON-GRADE 3000 3/4" 0.50 3-5 CONSTRUCTED SO AS TO KEY AND BOND INTO BLOCK CELLS. THE USE OF BUILDING PAPER SHEAR REVERSAL DUE TO UNBALANCED LOADING. DOCUMENTS:
A. SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, MARCH 9,2005 D. ELEVATED FLOORS & BEAMS 4000 3/4" 0.45 3-5 OR SHEET PLASTIC TO CLOSE VOIDS BELOW BEAMS IS NOT ALLOWED DUE TO BREAKAGE OF A. HILTI HDA (ICC-ES ESR1546)
(AISC 360-05). MORTAR BOND. 12. JOIST SEATS SHALL HAVE THE CAPACITY TO RESIST A LATERAL LOAD APPLIED TO THE TOP B. HILTI HSL-3 ANCHOR (ICC-ES ESR1545)
B. CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, ADOPTED 3. CONCRETE SLUMP IS TAKEN AT POINT OF PLACEMENT INTO STRUCTURE. CHORD, PERPENDICULAR TO THE SPAN (ROLLOVER). PROVIDE A MINIMUM ROLLOVER FORCE C. SIMPSON STRONG-TIE TITEN HD (THD) (ICC-ES ESR2713)(FL2304) Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

EFFECTIVE MARCH 18, 2005 (AISC 303-05). 11. SEE ARCHITECT'S DRAWINGS FOR THE EXTENT AND EXACT LOCATION OF MASONRY WALLS. OF 2,000 POUNDS FOR SEATS UP TO 3 1/2 INCHES DEEP AND 1,200 POUNDS FOR SEAT B. MECHANICAL ANCHORS INTO MASONRY LINTELS OR GROUT FILLED CELLS:
4. WATER REDUCING AND AIR ENTRAINING AGENTS SHALL BE INCLUDED IN DESIGN MIXES. OVER 3 1/2 INCHES DEEP. 1. USE THE FOLLOWING (UNO):
5. OPEN WEB STEEL JOISTS: SUPERPLASTICIZERS MAY BE USED AT THE CONTRACTOR'S OPTION. 12. WALL CONTROL JOINTS (WCJ): A. HILTI KWIK BOLT 3 MASONRY ANCHORS (ICC-ES ESR1385)
A. STANDARD SPECIFICATION FOR OPEN WEB STEEL JOISTS, K-SERIES (K-1.1-05). A. WALL CONTROL JOINTS SHALL BE PROVIDED IN ALL CONCRETE MASONRY STEEL ROOF DECK: B. SIMPSON STRONG-TIE WEDGE-ALL ANCHOR(WA)
B. CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST GIRDERS, EFFECTIVE 5. A CONCRETE MIX DESIGN FOR EACH UNIQUE COMBINATION OF STRENGTH, COARSE AGGREGATE CONSTRUCTION AT LOCATIONS INDICATED ON THE STRUCTURAL OR ARCHITECTURAL 1. ROOF DECK SHALL BE 1-1/2" DEEP. SEE ROOF PLAN FOR GAGE AND PROFILE (ICBO-ES ER-3631) (FL5415)
MAY 03, 2005. GRADATION AND WATER CEMENT RATIO SPECIFIED SHALL BE PREPARED BY THE SUPPLIER OR DRAWINGS BUT UNLESS NOTED OTHERWISE AT A SPACING NOT GREATER THAN 24' DESIGNATION. 2. USE THE FOLLOWING ONLY WHERE SPECIFICALLY CALLED OUT ON THE
C. STANDARD SPECIFICATIONS, LOAD TABLES AND WEIGHT TABLES FOR STEEL JOISTS AN INDEPENDENT TESTING LABORATORY AND BE SUBMITTED FOR REVIEW PRIOR TO CASTING O.C. DOCUMENTS:
AND JOIST GIRDERS (SJI-02). ANY CONCRETE. MIXES THAT WILL BE TRANSPORTED AT THE PROJECT SITE BY PUMPING B. HORIZONTAL JOINT REINFORCING SHALL BE INTERRUPTED EACH SIDE OF WALL 2. ROOF DECK SHALL BE PLACED SO AS TO COVER AT LEAST TWO SPANS. NO SINGLE SPAN A. HILTI HUS-H SCREW ANCHOR (ICC-ES ESR2369)
D. STANDARD SPECIFICATIONS FOR LONGSPAN STEEL JOISTS, LH SERIES AND DEEP
LONGSPAN JOISTS, DLH SERIES (LH/DLH-1.1-05).
SHALL BE SPECIFICALLY DESIGNED FOR PUMPING.
C.
CONTROL JOINTS.
WALL CONTROL JOINTS SHALL NOT BE PLACED OVER OPENINGS OR WITHIN AN
CONDITIONS SHALL BE USED.
C.
B. SIMPSON STRONG-TIE TITEN HD (THD) (ICC-ES ESR1056)(FL2304)
ADHESIVE ANCHORS INTO CONCRETE:
Proton Therapy
E. STANDARD SPECIFICATION FOR JOIST GIRDERS (JG-1.1-05). 6. SLABS ON GRADE: UNLESS NOTED OTHERWISE, CONCRETE SLABS ON GRADE SHALL BE A
MINIMUM OF 4" THICK, REINFORCED WITH 6x6 W1.4Xw1.4 WWF PLACED 1-1/2" CLEAR
OPENING JAMB WIDTH. SEE PLANS AND/OR JAMB REINFORCING SCHEDULE FOR
MINIMUM JAMB WIDTHS.
3. DECK SHALL BE FABRICATED SO THAT DECK RUNS CONTINUOUSLY OVER OPENINGS. THE
OPENINGS IN THE DECK SHALL NOT BE CUT UNTIL THE OPENING IS NEEDED (PER OSHA).
1. USE THE FOLLOWING (UNO):
A. HILTI HIT-RE 500-SD ADHESIVE (ICC-ES ESR2322) LINAC Addition
6. MASONRY CONSTRUCTION: FROM THE TOP OF THE SLAB. SLABS SHALL BE PLACED OVER PROPERLY COMPACTED EARTH. D. SEE ARCHITECTURAL DRAWINGS FOR SEALANT REQUIREMENTS AT WALL CONTROL B. RED HEAD EPCON G5 ADHESIVE (ICC-ES ESR1137)(FL6582)
A. BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES JOINTS. 4. STEEL DECK SHALL CONFORM TO ASTM A653 SQ GRADE 33 (Fy = 33,000 PSI). C. SIMPSON STRONG-TIE SET-XP EPOXY-TIE ADHESIVE (SETXP) Shands Jacksonville Campus
(ACI 530-05/ASCE 5-05/TMS 402-05). 7. CONCRETE TIE BEAMS: UNLESS NOTED OTHERWISE, CONCRETE TIE BEAMS SHALL BE A E. SEE THESE DRAWINGS FOR ADDITIONAL REQUIREMENTS. (ICC-ES ESR2508)
B. SPECIFICATIONS FOR MASONRY STRUCTURES
(ACI 530.1-05/ASCE 6-05/TMS 602-05).
MINIMUM OF 16" DEEP BY THE SUPPORTING WALL WIDTH, REINFORCED WITH 2 #5
CONTINUOUS TOP AND BOTTOM AND #3 TIES AT 24" O.C. 13. MASONRY WALLS SHALL BE BRACED EITHER BY OTHER INTERSECTING WALLS OR BY
5. STEEL DECK SHALL BE GALVANIZED WITH A PROTECTIVE ZINC COATING CONFORMING TO
ASTM A924, WITH COATING DESIGNATION G90.
2. USE THE FOLLOWING ONLY WHERE SPECIFICALLY CALLED OUT ON THE
DOCUMENTS:
UF LM-4985
ANCHORAGE OR BRACING TO THE STRUCTURE ABOVE, OR TO ADJACENT WALLS, AS DETAILED A. HILTI HIT HY 150 MAX ADHESIVE (ICC-ES ESR2262)
7. STEEL DECK: REINFORCING STEEL: ON THE STRUCTURAL DRAWINGS. 6. SEE ROOF PLAN AND DETAILS FOR ROOF DECK ATTACHMENT AND FORCES IMPOSED DUE TO D. ADHESIVE ANCHORS INTO MASONRY LINTELS OR GROUT FILLED CELLS: Project Phase
A. NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL 1. REINFORCING STEEL: ASTM A 615, GRADE 60. UPLIFT AND DIAPHRAGM SHEAR UNDER WIND LOADING. SEE SPECIFICATIONS FOR 1. USE THE FOLLOWING (UNO): 100% Construction Documents
STRUCTURAL MEMBERS, INCLUDING 2004 SUPPLEMENT (NAS-01). 14. BLOCK LINTELS SHALL BE SPECIALLY FORMED U-SHAPED LINTEL OR LOW WEB LINTEL UNITS INSPECTION AND REPORTING REQUIRED ON ROOF DECK ATTACHMENT. A. HILTI HIT HY-150 MAX ADHESIVE (ICC-ES ESR1967)
B. SDI DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS AND ROOF DECKS. 2. WELDED WIRE FABRIC: ASTM A 185 (FLAT SHEETS), MINIMUM YIELD STRENGTH OF 70,000 WITH REINFORCING BARS, OR PRECAST UNITS DESIGNED FOR THE WEIGHT OF MASONRY B. SIMPSON STRONG-TIE SET EPOXY-TIE ADHESIVE (SET)
Sheet Title
PSI. ABOVE AND OTHER APPLIED LOADS. 7. PROVIDE A MINIMUM END BEARING OF 2" OVER SUPPORTS. END LAPS OF SHEETS SHALL BE (ICC-ES ESR1772)(FL5550)
8. COLD FORMED METAL FRAMING: A MINIMUM OF TWO INCHES AND SHALL OCCUR OVER SUPPORTS.
A. NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL
STRUCTURAL MEMBERS, INCLUDING 2004 SUPPLEMENT (NAS-01).
3. MINIMUM REINFORCING STEEL CLEAR COVER (U.N.O.):
A.
B.
CONCRETE CAST DIRECTLY AGAINST EARTH .. 3"
INTERIOR SLABS ........................ 1"
15. ALL MASONRY WALLS SHOWN ON THE STRUCTURAL DRAWINGS HAVE BEEN DESIGNED TO RESIST
THE REQUIRED CODE VERTICAL AND LATERAL FORCES IN THE FINAL CONSTRUCTED
CONFIGURATION ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ADEQUATELY
8. THE CONTRACTOR SHALL COORDINATE ALL TRADE REQUIREMENTS AND CONFIRM THE SIZE AND
LOCATION OF ALL OPENINGS. OPENINGS LARGER THAN 12", AND AS DETAILED, SHALL HAVE
STRUCTURAL DRAWING INDEX GENERAL NOTES
DESIGN LOADS: C. INTERIOR BEAMS ........................ 1-1/2" TO TIES BRACE THE WALLS FOR VERTICAL AND LATERAL LOADS THAT COULD POSSIBLY BE APPLIED STEEL FRAMING SUPPORTING ALL EDGES. SEE TYPICAL ANGLE FRAMING DETAILS. AND DRAWING
1. ROOF LIVE LOADS: D. SLABS ON GRADE ........................ 1-1/2" FROM TOP PRIOR TO COMPLETION OF LATERAL SUPPORT BY CONNECTIONS AT FLOORS OR ROOF FRAMING
A. UNIFORMLY DISTRIBUTED LIVE LOAD ON HORIZONTAL
4. WHERE REINFORCING BARS ARE NOTED AS CONTINUOUS, THE FOLLOWING SHALL BE COMPLIED
LEVELS. 9. STEEL MEMBERS SUPPORTING STEEL DECK AT THE PERIMETER OF THE BUILDING SHALL BE
CONTINUOUS, BUTT WELD PIECES WHERE SPLICES OCCUR.
Sheet No. Sheet Title/Drawing Description
INDEX
PROJECTION....................................... 20 PSF
B. SEE ROOF FRAMING PLAN FOR OTHER CONCENTRATED EQUIPMENT LOADS. WITH: 16. QUALITY ASSURANCE: ALL REINFORCED MASONRY SHALL BE TESTED/INSPECTED IN S001 GENERAL NOTES AND DRAWING INDEX
A. THE TERMINATION OF ALL CONTINUOUS REINFORCING BAR RUNS SHALL BE A CONFORMANCE WITH THE REFERENCED ACI 530/ASCE 5/TMS 402 CODES AND THE PROJECT
STANDARD HOOK UNLESS NOTED OTHERWISE. SPECIFICATIONS. QUALITY ASSURANCES SHALL MEET THE REQUIREMENTS OF SECTION 1.6, COLD FORMED METAL FRAMING:
S002 ABBREVIATIONS, SYMBOLS & WIND LOADS Scale Drawn By
2. FLOOR LIVE LOADS:
A. UNIFORMLY DISTRIBUTED LIVE LOADS: B. SPLICES IN CONTINUOUS TOP BARS, IF REQUIRED, SHALL OCCUR OVER PARALLEL TABLE 4 LEVEL B, UNLESS MORE RESTRICTIVE REQUIREMENTS ARE SPECIFIED ELSEWHERE 1. SEE NOTES ON PRIMARY CODES AND SPECIFICATIONS. S101 MACHINE PIT PLAN
TREATMENT ROOM FLOOR............................ 150 PSF CMU WALLS OR AT THE CENTER OF THE OPENING SPAN. IN THESE DOCUMENTS S102 LEVEL 1 SLAB PLAN CSH
B. CONCENTRATED FLOOR LIVE LOADS: C. SPLICES IN CONTINUOUS BOTTOM BARS, IF REQUIRED, SHALL OCCUR OVER CMU 2. ALL EXTERIOR WALLS, LINTELS, BEAMS, TRUSSES, ETC. AS WELL AS ALL INTERIOR
S103 PARTIAL STRUCTURAL CEILING PLAN
GANTRY VERTICAL LOAD........................ 24,500 LBS. WALLS OR CENTERED OVER COLUMNS. 17. TYPICAL SCHEDULED VERTICAL WALL REINFORCING SIZE AND SPACING SHALL ALSO BE BEARING WALLS, LINTELS, BEAMS, ETC. SHALL BE DESIGNED, SIGNED AND SEALED BY THE
GANTRY HORIZONTAL LOAD AT 710 CONTINUED ABOVE AND BELOW ALL OPENINGS. SUPPLIER'S DELEGATED ENGINEER REGISTERED IN THE STATE OF FLORIDA. S104 PARTIAL ROOF FRAMING PLAN
ABOVE TOP OF FOUNDATION...................... 7,300 LBS. 5. WHERE SPLICE LENGTHS ARE NOT SPECIFIED, USE 48 BAR DIAMETERS IN MASONRY AND S201 PARTIAL BUILDING SECTIONS Date Checked By
40 BAR DIAMETERS IN CAST CONCRETE.
S301 MASONRY SECTIONS AND DETAILS
3. SUPERIMPOSED DEAD LOADS: 09 DEC 2011 RWG
6. REINFORCING STEEL SHALL NOT BE TACK WELDED FOR ANY REASON. WELDED REINFORCING S302 FOUNDATION SECTIONS AND DETAILS
A. TYPICAL FLOORS................................... 25 PSF
STEEL SPLICES ARE NOT PERMITTED S303 CONCRETE SECTIONS AND DETAILS
S401 FRAMING SECTIONS AND DETAILS
11069

AEI Project No.

11662-00
12/8/2011 4:08:06 PM

Sheet No.

S001
Affiliated
ABBREVIATIONS Engineers

Affiliated Engineers, Inc.


3007 SW Williston Rd.
A/C - AIR CONDITIONING CM - CONSTRUCTION MANAGER EW - EACH WAY ICF - INSULATED CONCRETE FORM MTL - METAL, MATERIAL RD - ROOF DRAIN T&B - TOP & BOTTOM Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
A/E - ARCHITECT AND/OR ENGINEER CMU - CONCRETE MASONRY UNIT EXIST - EXISTING ID - INSIDE DIAMETER MULL - MULLION REF - REFERENCE T&G - TONGUE & GROOVE www.aeieng.com
AB - ANCHOR BOLT CO - CUT OFF EXP - EXPANSION IF - INSIDE FACE N - NORTH REINF - REINFORCED, REINFORCING, REINFORCEMENT TB - TIE BEAM FL Cert of Auth - 0005140
ACI - AMERICAN CONCRETE INSTITUTE COL - COLUMN EXP JT - EXPANSION JOINT IN - INCHES NGVD - NATIONAL GEODETIC VERTICAL DATUM REM - REMAINDER TEMP - TEMPORARY, TEMPERATURE
AFF - ABOVE FINISHED FLOOR COMP - COMPOSITE, COMPRESSOR, COMPRESSIVE EXT - EXTERIOR INFO - INFORMATION NIC - NOT IN CONTRACT REQD - REQURIED THK - THICK
AHU - AIR HANDLING UNIT CONC - CONCRETE F - FAHRENHEIT INSUL - INSULATION No. - NUMBER REV - REVISION THRD - THREADED
AISC - AMERICAN INSTITUTE OF STEEL CONSTRUCTION CONN - CONNECTION, CONNECT f`c - MINIMUM 28-DAY CONCRETE STRENGTH INT - INTERIOR NOM - NOMINAL RFG - ROOFING TOC - TOP OF CONCRETE
AISI - AMERICAN IRON AND STEEL INSTITUTE CONSTR - CONSTRUCTION f`m - SPECIFIED MASONRY STRENGTH JST - JOIST NS - NEAR SIDE RM - ROOM TOF - TOP OF FOOTING
AITC - AMERICAN INSTITUTE FOR TIMBER CONSTRUCTION CONT - CONTINUOUS FB - FLAT BAR JT - JOINT NTS - NOT TO SCALE RO - ROUGH OPENING TOGB - TOP OF GRADE BEAM
ALT - ALTERNATE CONTR - CONTRACTOR FBC - FLORIDA BUILDING CODE K - KIPS (1000 LBS.) OA - OVERALL RTN - RETURN TOJ - TOP OF JOIST
ALUM - ALUMINUM CRSI - CONCRETE REINFORCING STEEL INSTITUTE FD - FLOOR DRAIN KB - KNEE BRACE OC - ON CENTER RTU - ROOF TOP UNIT TOM - TOP OF MASONRY
AMT - AMOUNT CSK - COUNTERSINK FDN - FOUNDATION KD - KILN DRIED OD - OUTSIDE DIAMETER S - SOUTH, STANDARD BEAM TOPC - TOP OF PILE CAP
ANCH - ANCHOR, ANCHORAGE CTR - CENTER FF - FINISHED FLOOR KO - KNOCK OUT OF - OUTSIDE FACE SBC - STANDARD BUILDING CODE TOPG - TOPPING
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE CTRD - CENTERED FIN - FINISH, FINISHED KSF - KIPS PER SQUARE FOOT OPNG - OPENING SC - SLIP CRITICAL TOPL - TO OF PLATE
APPROX - APPROXIMATE CW - CURTAIN WALL, CURTAINWALL FLR - FLOOR KSI - KIPS PER SQUARE INCH OPP - OPPOSITE SCHED - SCHEDULE TOS - TOP OF STEEL
AR - ANCHOR ROD CY - CUBIC YARD FOS - FACE OF STUD L - STEEL ANGLE, LENGTH OPPH - OPPH SDI - STEEL DECK INSTITUTE TOSL - TOP OF SLAB
ARCH - ARCHITECT, ARCHITECTURAL DBA - DEFORMED BAR ANCHOR FRPF - FIREPROOF LAM - LAMINATED OSHA - OCCUPATIONAL SAFETY AND HEALTH SE - STRUCTURAL ENGINEER TOW - TOP OF WALL
ASCE - AMERICAN SOCIETY OF CIVIL ENGINEERS DBL - DOUBLE FRT - FIRE RETARDANT LBS - POUNDS ADMINISTRATION SECT - SECTION TPL - TRIPLE
ASD - ALLOWABLE STRESS DESIGN DEG - DEGREES FS - FAR SIDE LF - LINEAL FEET OVS - OVERSIZED SF - SQUARE FEET TYP - TYPICAL
Architecture
ASTM - AMERICAN SOCIETY OF TESTING & MATERIALS DEMO - DEMOLITION FT - FOOT, FEET LL - LIVE LOAD OZ - OUNCE SGL - SINGLE UNO - UNLESS NOTED OTHERWISE Walker Architects, Inc.
AVG - AVERAGE DEPT - DEPARTMENT FTG - FOOTING LLBB - LONG LEG BACK TO BACK P - STEEL PIPE SHT - SHEET VERT - VERTICAL 4055 NW 43rd St, #28
Gainesville, Florida 32606
AWS - AMERICAN WELDING SOCIETY DET - DETAIL Fy - YIELD STRENGTH OF STEEL LLH - LONG LEG HORIZONTAL PAF - POWDER ACTUATED FASTENER SIM - SIMILAR VOL - VOLUME Tel 352.672.6448 Fax 352.672.6468
BB - BOND BEAM DIA - DIAMETER GA - GAUGE LLO - LONG LEG OUTSTANDING PC - PRECAST, PILE CAP, PIECE SJ - SAWED CONTROL JOINT W - STEEL WIDE FLANGE SHAPE, WEST www.walker-arch.com
AA26002009
BLDG - BUILDING DIAG - DIAGONAL GALV - GALVANIZED LLV - LONG LEG VERTICAL PCF - POUNDS PER CUBIC FOOT SJI - STEEL JOIST INSTITUTE W/ - WITH
BLK - BLOCK DIAPH - DIAPHRAGM GC - GENERAL CONTRACTOR LRFD - LOAD AND RESISTANCE FACTOR DESIGN PCI - PRESTRESSED CONCRETE INSTITUTE SLBB - SHORT LEG BACK TO BACK W/O - WITHOUT
PE - PROFESSIONAL ENGINEER Structural
BLKG - BLOCKING DIM - DIMENSION GCL - GRANULAR CAPILLARY LAYER LSH - LONG SIDE HORIZONTAL SLO - SHORT LEG OUTSTANDING WCJ - WALL CONTROL JOINT Structural Engineers Group, Inc.
BM - BEAM DL - DEAD LOAD GEN - GENERAL LSL - LONG SLOTTED PED - PEDESTAL SLOT - SLOTTED WD - WOOD 4114 Sunbeam Rd, Bldg 200
PEMB - PRE-ENGINEERED METAL BUILDING Jacksonville, Florida 32257
BOS - BOTTOM OF STEEL DN - DOWN GLB - GLULAM BEAM LSV - LONG SIDE VERTICAL SLP - SLOPE WEJ - WALL EXPANSION JOINT
Tel 904.262.4000 Fax 904.262.4100
PERP - PERPENDICULAR
BOTT - BOTTOM DO - DITTO GR - GRADE LT - LIGHT
PL - PLATE
SLV - SHORT LEG VERTICAL WF - WALL FOOTING www.segonline.com
Cert of Auth - 6523
S EG
BRDG - BRIDGE, BRIDGING DT - DOUBLE TEES GRND - GROUND LW - LIGHTWEIGHT, LONG WAY SOG - SLAB ON GRADE WGT - WEIGHT
BRG - BEARING DWG - DRAWING GWB - GYPSUM WALLBOARD M - STEEL SHAPE PLF - POUNDS PER LINEAL FOOT SPA - SPACED, SPACING, SPACES WL - WIND LOAD
BS - BOTH SIDES DWL - DOWEL GYP - GYPSUM MACH - MACHINE PNL - PANEL SPEC - SPECIFICATION WP - WORKING POINT, WATERPROOF
BTWN - BETWEEN E - EAST HC - HOLLOW CORE MAS - MASONRY PP - PANEL POINT SQ - SQUARE WPFG - WATERPROOFING ENGINEER OF RECORD
PREFAB - PREFABRICATED ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961
BUR - BUILT-UP ROOF EA - EACH HCA - HEADED CONCRETE ANCHOR MATL - MATERIAL SS - STAINLESS STEEL WS - WATERSTOP
C - STEEL CHANNEL SHAPE EE - EACH END HD - HEAVY DUTY, HEAD MAX - MAXIMUM PRELIM - PRELIMINARY SSL - SHORT SLOTTED WT - WIDE FLANGE STRUCTURAL TEE, WATER TABLE,
CAD - CADMIUM EF - EACH FACE HDG - HOT DIPPED GALVANIZED MB - MACHINE BOLT, MASONRY BEAM PREP - PREPARATION SSPC - STEEL STRUCTURES PAINTING COUNCIL WALL TYPE
CANT - CANTILEVER EJ - EXPANSION JOINT HDR - HEADER MBM - METAL BUILDING MANUFACTURER PSC - PRESTRESSED CONCRETE ST - STANDARD FLANGE, STRUCTURAL TEE WWF - WELDED WIRE FABRIC
CAP - CAPACITY EL - ELEVATION HEX - HEXAGONAL MBR - MEMBER PSF - POUNDS PER SQUARE FOOT STD - STANDARD XS - EXTRA STRONG
CB - CORNER BAR ELEC - ELECTRICAL HGR - HANGER MC - MISCELLANEOUS STEEL CHANNEL, MOMENT PSI - POUNDS PER SQUARE INCH STIFF - STIFFENER XXS - DOUBLE EXTRA STRONG
CC - CENTER TO CENTER ELEV - ELEVATOR HGT - HEIGHT CONNECTION PT - PRESSURE TREATED STIR - STIRRUP YD - YARD
CF - CUBIC FEET, COLUMN FOOTING ENCL - ENCLOSURE HJR - HORIZONTAL JOINT REINFORCING MECH - MECHANICAL PTC - POST TENSIONED CONCRETE STL - STEEL
CFMF - COLD FORMED METAL FRAMING ENGR - ENGINEER HK - HOOK MED - MEDIUM PTD - PAINTED STRUCT - STRUCTURAL
CHKD - CHECKERED EOD - EDGE OF DECK HORIZ - HORIZONTAL MEMB - MEMBRANE PVMT - PAVEMENT SUSP - SUSPENDED
CI - CAST IRON EOS - EDGE OF SLAB HP - STEEL BEARING PILE MEZZ - MEZZANINE QA - QUALITY ASSURANCE SW - SHORT WAY, SHEAR WALL
CIP - CAST-IN-PLACE EQ - EQUAL HS - HIGH STRENGTH MFR - MANUFACTURER QC - QUALITY CONTROL SY - SQUARE YARD
CJ - CONSTRUCTION JOINT EQPT - EQUIPMENT HSS - SQUARE, RECTANGULAR OR ROUND HOLLOW MID - MIDDLE QTR - QUARTER SYM - SYMMETRICAL
CL - CENTERLINE ES - EACH SIDE STRUCTURAL SECTION MIN - MINIMUM QTY - QUANTITY SYP - SOUTHERN YELLOW PINE
CLG - CEILING EST - ESTIMATED HWH - HEX WASHER HEAD MISC - MISCELLANEOUS R - RISER, REACTION, RADIUS SYS - SYSTEM
CLR - CLEARANCE, CLEAR ETC - AND OTHERS IBC - INTERNATIONAL BUILDING CODE MO - MASONRY OPENING R/W - RIGHT OF WAY T - TREAD

Revisions

WIND LOAD INFORMATION SYMBOL LEGEND

COMPONENTS & CLADDING JOIST NET UPLIFT SCHEDULE


WIND LOAD DESIGN PRESSURE SCHEDULE # DETAIL NUMBER
CAST-IN-PLACE CONCRETE WOOD OR TIMBER
DESIGN PRESSURE (PSF) DESIGN S# SHEET WHERE DRAWN IN SECTION
COMPONENT ZONE EFFECTIVE WIND ZONE EFFECTIVE WIND
AREA (SF) POSITIVE NEGATIVE AREA (SF) PRESSURE (PSF)
10 12 -30 PARAPETS 10 -21 PRECAST CONCRETE OR
20 11 -29 20 -20 PRECAST PRESTRESSED
1 5P 1 # SECTION NUMBER
CONCRETE
50 10 -28 50 -19 LAMINATED WOOD
A S# SHEET WHERE DRAWN MEMBER
>100 10 -27 >100 -18
10 12 -50 5P 10 -41 NON-SHRINK GROUT
4P ELEVATION
20 11 -45 4P 20 -36
ROOF ELEMENTS 2 2 PLYWOOD
50 10 -38 50 -29 SPAN DIRECTION
3 2 3
A

>100 10 -32 >100 -23 (SLAB, DECK, ETC.)


10 12 -75 10 -66 GROUT FILL REVISION NUMBER -
5P
SLAB DEPRESSION # CLOUD INDICATES
20 11 -62 20 -53 LIMIT OF REVISION
3 3
50 10 -45 50 -36
>100 10 -32 >100 -23 BRICK #
# KEYED PLAN NOTE P#
10 27 -30 4 MARKS FOR SCHEDULED
NOTES: X
26 -28 5 ELEMENTS SUCH AS SLABS
20 1. JOISTS SHALL BE CLASSIFIED AS COMPONENTS
2 1 2 OR FOOTINGS OR MARKS FOR
4 50 24 -27 4 AND SHALL BE DESIGNED USING THE NET WT# DS
PRESSURES LISTED IN THE TABLE. A COLUMN LINE STRUCTURAL DETAILED ELEMENTS
100 23 -26 STEEL SUCH AS TILT-UP PANELS
2. REFER TO THE WIND PRESSURE DIAGRAM FOR Project
22 -23 S# C#
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

>500 5 ZONE LOCATIONS AND EXTENTS.


10 72 -- 3. NEGATIVE PRESSURES ACT AWAY FROM EACH
EXISTING COLUMN
20 65 -- COMPONENT SURFACE. 1 LINE
A 4. LINEAR INTERPOLATION BETWEEN EFFECTIVE EARTH
4P 50 56 -- # COMBINED SCHEDULE OF
EXTERIOR WALL WIND AREAS MAY BE USED TO OBTAIN THE
ELEMENTS, 100 46 -- 3 2 3 REQUIRED COMPONENT DESIGN NET UPLIFT X DETAILED INFORMATION

A
WINDOWS, -- 5 PRESSURE. S FOOTING STEP
>500 46
DOORS AND
CURTAIN WALLS
10 27 -36 A CONCRETE
MASONRY UNIT Proton Therapy
20 26 -34 A MOMENT CONNECTION
5 50 24 -31
A A SHEAR CONNECTION
LINAC Addition
100 23 -28 A = 12'-0"
>500 22 -23 Shands Jacksonville Campus
WALLS ROOF
10 98 -- UF LM-4985
20 83 --
5P 50 64 --
WIND PRESSURE DIAGRAMS
Project Phase
REFER TO 'COMPONENTS & CLADDING WIND
100 48 -- LOAD DESIGN PRESSURE SCHEDULE' ON THIS SHEET 100% Construction Documents
>500 46 --
Sheet Title
NOTES:
1. DESIGN WIND PRESSURES SHALL BE USED IN THE DESIGN OF ALL
COMPONENTS AND CLADDING ELEMENTS COMPRISING THE
BUILDING ENVELOPE. ABBREVIATIONS,
2. REFER TO THE WIND PRESSURE DIAGRAM FOR ZONE LOCATIONS
AND EXTENTS. SYMBOLS & WIND
3. POSITIVE PRESSURES ACT TOWARD COMPONENT SURFACES AND
NEGATIVE PRESSURES ACT AWAY FROM EACH COMPONENT LOADS
SURFACE.
4. LINEAR INTERPOLATION BETWEEN EFFECTIVE WIND AREAS MAY
BE USED TO OBTAIN THE REQUIRED COMPONENT AND CLADDING Scale Drawn By
DESIGN WIND PRESSURE.
5. VALUES FOR OVERHANGS INCLUDE PRESSURE CONTRIBUTIONS 12" = 1'-0" CSH
FROM BOTH UPPER AND LOWER SURFACES.
6. DIMENSION A = 12' - 0"

Date Checked By

09 DEC 2011 RWG


11069

AEI Project No.

11662-00
12/8/2011 4:08:07 PM

Sheet No.

S002
Affiliated

Affiliated Engineers, Inc.


Engineers
3007 SW Williston Rd.
Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
www.aeieng.com
FL Cert of Auth - 0005140

PLAN NOTES
PLAN NOTES ARE TYPICAL FOR THIS DRAWING UNLESS SPECIFICALLY
DESIGNATED OTHERWISE.
REFER TO DRAWING S001 FOR STRUCTURAL DRAWING INDEX.
1

18" FOUNDATION MAT / SLAB OVER VAPOR RETARDER AND


2
COMPACTED EARTH; REINFORCE W/ #7 @ 12" OC EACH WAY TOP AND
BOTTOM. ELEVATION TOP OF SLAB= -4'-3 1/4".
Architecture
VERO TO SUPPLY AND INSTALL ALL BASE PLATES AND ANCHOR BOLTS. Walker Architects, Inc.
3 4055 NW 43rd St, #28
Gainesville, Florida 32606
REFER TO ARCHITECTURAL DRAWINGS FOR REQUIRED DEMOLITION (TYP). Tel 352.672.6448 Fax 352.672.6468
4 www.walker-arch.com
AA26002009
4
ADD 2-#6x4'-0" T&B AT ALL RE-ENTRANT CORNERS. PLACE IN INNER SLAB
5
REINFORCING LAYER, 2" CLEAR FROM CORNER.
Structural
Structural Engineers Group, Inc.
4114 Sunbeam Rd, Bldg 200
Jacksonville, Florida 32257
Tel 904.262.4000 Fax 904.262.4100
www.segonline.com
Cert of Auth - 6523
S EG

ENGINEER OF RECORD
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

1'-1 1/2"
5
TYP
S303

1'-0"
4

13'-7 1/2"
COUCH BASE PL Revisions
AND ANCHOR BOLTS

11'-6"
DRIVING UNIT
BASE PL AND
OUTLINE OF WALLS
ANCHOR BOLTS
ABOVE (TYP)

1
S201

21'-6"
ISOCENTER

3'-0" GANTRY BASE PL


AND ANCHOR BOLTS 2

8'-0"
5

11'-5"
TOSL -4'-3 1/4"
Project
TOSL -6'-3 1/4"
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

3'-0"

8
S302
1'-0"

Proton Therapy
2'-0" 10" 1'-0" 10'-6" 8'-0" 1'-0" 3'-4" 2'-0"
LINAC Addition
2'-5"

20'-6" Shands Jacksonville Campus


UF LM-4985
12'-4" 12'-4"
Project Phase
SIM
8 100% Construction Documents
S302
2 Sheet Title

S201
MACHINE PIT
PLAN

Scale Drawn By

As indicated CSH

Date Checked By

09 DEC 2011 RWG


11069

AEI Project No.

11662-00
MACHINE PIT PLAN
12/8/2011 4:08:07 PM

N
Sheet No.
SCALE: 3/8" = 1'-0"

S101
Affiliated

Affiliated Engineers, Inc.


Engineers
PLAN NOTES 3007 SW Williston Rd.
Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
14'-8" www.aeieng.com
FL Cert of Auth - 0005140
PLAN NOTES ARE TYPICAL FOR THIS DRAWING UNLESS SPECIFICALLY
DESIGNATED OTHERWISE.
REFER TO DRAWING S001 FOR STRUCTURAL DRAWING INDEX.
1
1
S302 6" CONCRETE SLAB OVER VAPOR RETARDER AND COMPACTED EARTH;
2
REINFORCE W/ 6x6-W2.9xW2.9 WWF, 1 1/2" CLEAR FROM TOP OF SLAB.
WF2.0
5 OPP HAND
S302 SIM 18" CONCRETE SLAB OVER VAPOR RETARDER AND COMPACTED EARTH;
3
REINFORCE W/ #6 @ 12" EW, T&B. ELEVATION TO TOP OF SLAB = 0'-0" (DATUM)
MATCH EXISTING CONCRETE.

4 REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS, DETAILS AND LOCATIONS


OF INTERIOR PARTITIONS, DOORS AND WINDOWS, AND TO VERIFY DEPTH AND
EXTENT OF SLAB DEPRESSIONS.
8
ADD 2 #4x4'-0" @ 3" OC AT AT ALL RE-ENTRANT CORNERS (TYP), PLACE ON
5
INNER LAYER 1 1/2" CLR FROM CORNER. Architecture
Walker Architects, Inc.
WALL FOOTINGS ARE DESIGNATED BY "WF'' . 4055 NW 43rd St, #28
6 Gainesville, Florida 32606
Tel 352.672.6448 Fax 352.672.6468
www.walker-arch.com
TOSL -1'-0"

11'-8 1/2"
REFERENCE ELEVATION TOP OF FOOTINGS (TOF) -2-0" UNO. AA26002009
1 7
S302 7 NOTE:
Structural
TEMPORARY SHORING OF CONCRETE SLAB ALL EXTERIOR 8" CMU WALLS SHALL BE WT1, UNO.
S302 8 Structural Engineers Group, Inc.
REQUIRED WHENEVER VERO MACHINE IS 4114 Sunbeam Rd, Bldg 200
TRANSPORTED ACROSS THE FLOOR. Jacksonville, Florida 32257
2

EJ
INFILL OPENING CUT IN EXISTING WALL W/ SOLID HEAVY WEIGHT CMU BLOCK. Tel 904.262.4000 Fax 904.262.4100
9 www.segonline.com
Cert of Auth - 6523
S EG
8" CONCRETE SLAB; REINFORCE W/ #6 @ 6" OC EACH WAY TOP AND
10
BOTTOM. ELEVATION TOP OF SLAB= 0'-0" (DATUM) MATCH EXISTING
2 CONCRETE. ENGINEER OF RECORD
4'-0" 3'-4" ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961
S302 CONTRACTOR SHALL COORDINATE EDGE OF STRUCTURE WITH ARCHITECTURAL
11
DRAWINGS TO SUIT EACH TYPE OF ARCHITECTURAL FINISH.

SJ REFER TO DRAWING S101 FOR DIMENSIONS NOT SHOWN ON THIS PLAN.

1'-1 1/2"
12

REFER TO ARCHITECTURAL DRAWINGS FOR REQUIRED DEMOLITION (TYP).


26'-8"

13

9 6" DIAMETER PVC CONDUIT PIPE CAST IN MID SLAB DEPTH SPACED AT 18" OC.
1

4"
14
S302 13
3 14

1'-0"
8'-0"

SIM
11

3'-0"
S302
WF2.0

TOSL 0'-0"
TOSL 0'-0" 1'-2" 1'-2"
2
S302 3
3'-0" Revisions
S303

13'-7 1/2"
10
SJ

12'-2"
1'-9 3/8" 7 EQUAL SPACES @ 18" ON CENTER 1'-9"

14

8'-4 1/2"
TOSL -1'-0"
EJ

2
SJ

1
S201

21'-6"
ISOCENTER

5
S302 "
1/2
'- 3
8 R =5
6 3
S301 S302 11
1 10
S302 S302
3'-0"

8'-8"
Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

11'-5"
3'-0"

10
22'-5"

8
15'-5 1/2"

S302

Proton Therapy
1'-0"

4"
LINAC Addition
Shands Jacksonville Campus
2'-5"

10" 4" 11'-2" 8'-8" 4" 3'-4"

UF LM-4985
19'-10"
Project Phase
SIM 100% Construction Documents
8
S302 Sheet Title

LEVEL 1 SLAB
PLAN

2'-0" 12'-4" 12'-4" 2'-0"


Scale Drawn By
24'-8"
As indicated CSH

2
S201
Date Checked By

09 DEC 2011 RWG


11069

AEI Project No.

LEVEL 1 SLAB PLAN N


11662-00
12/8/2011 4:08:08 PM

SCALE: 3/8" = 1'-0" Sheet No.

S102
Affiliated

Affiliated Engineers, Inc.


Engineers
3007 SW Williston Rd.
Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
www.aeieng.com
FL Cert of Auth - 0005140

11
S301
SIM
PLAN NOTES
PLAN NOTES ARE TYPICAL FOR THIS DRAWING UNLESS SPECIFICALLY
DESIGNATED OTHERWISE.
REFER TO DRAWING S001 FOR STRUCTURAL DRAWING INDEX.
1

REFERENCE ELEVATION TO TOP OF STEEL BEAMS (TOS) IS 11'-5"


2

Architecture
3 REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS, DETAILS AND LOCATIONS OF Walker Architects, Inc.
INTERIOR PARTITIONS, DOORS AND WINDOWS, AND TO VERIFY DEPTH AND EXTENT OF 4055 NW 43rd St, #28
SLAB DEPRESSIONS. Gainesville, Florida 32606
Tel 352.672.6448 Fax 352.672.6468
www.walker-arch.com
4 LIFT CAPACITY = 11,000# (MINIMUM). AA26002009

Structural
Structural Engineers Group, Inc.
4114 Sunbeam Rd, Bldg 200
Jacksonville, Florida 32257
Tel 904.262.4000 Fax 904.262.4100
www.segonline.com
Cert of Auth - 6523
S EG

ENGINEER OF RECORD
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

TOS EXACTRAC SUPPORT


VERIFY LOCATION.
11'-5" (TYP) REFER TO DETAIL
3/S201.
4
S401

MAINTENANCE OP'G
BELOW
4

W8x31
W8x31

W8x31

13'-7 1/2"
Revisions

1
S201

ISOCENTER

11
S301

4
S401

11'-5"
Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

5'-8 7/8" 5'-8 7/8"

12'-4" 12'-4"

MAINTENANCE OP'G
BELOW
Proton Therapy
LINAC Addition
Shands Jacksonville Campus
UF LM-4985
Project Phase
100% Construction Documents
Sheet Title

PARTIAL
STRUCTURAL
CEILING PLAN
2
S201 Scale Drawn By

As indicated CSH

Date Checked By

09 DEC 2011 RWG


11069

PARTIAL STRUCTURAL AEI Project No.

11662-00
CEILING PLAN N
12/8/2011 4:08:08 PM

NO SCALE Sheet No.

S103
Affiliated

Affiliated Engineers, Inc.


Engineers
3007 SW Williston Rd.
Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
14'-8" www.aeieng.com
FL Cert of Auth - 0005140

6
S301
PLAN NOTES
PLAN NOTES ARE TYPICAL FOR THIS DRAWING UNLESS SPECIFICALLY
DESIGNATED OTHERWISE.
6
REFER TO DRAWING S001 FOR STRUCTURAL DRAWING INDEX.
S401 1
5'-10"

REFERENCE ELEVATION TO TOP OF STEEL JOISTS IS 16'-2 1/2". FOR TOP OF JOISTS OR
2
BEAMS AT OTHER ELEVATIONS, TOP OF STEEL IS NOTED THUS (-2 1/2") IN RELATION TO THE
REFERENCE ELEVATION.
Architecture
Walker Architects, Inc.
ROOF DECK SHALL BE GALVANIZED 1.5B20 STEEL ROOF DECK OR APPROVED EQUAL A
3 4055 NW 43rd St, #28
CONFORMING TO SDI SPECIFICATIONS. REFER TO ROOF DECK DETAILS FOR Gainesville, Florida 32606
12K3 ATTACHMENT PATTERN: 2 Tel 352.672.6448 Fax 352.672.6468
www.walker-arch.com
AA26002009
USE STANDARD SJI CONTINUOUS TOP AND BOTTOM CHORD BRIDGING AT BRIDGING LINES
4 INDICATED. FOR ROOF JOISTS, PROVIDE AN ADDITIONAL SINGLE LINE OF BOTTOM CHORD
BRIDGING NEAR THE FIRST BOTTOM CHORD PANEL POINT AT EACH END OF ALL JOISTS. Structural
Structural Engineers Group, Inc.
ADD CONTINUOUS BOLTED `X' BRIDGING WHERE INDICATED AND AS OTHERWISE REQUIRED
4 4114 Sunbeam Rd, Bldg 200
TO COMPLY WITH SJI. Jacksonville, Florida 32257
12 Tel 904.262.4000 Fax 904.262.4100
S401
5
CONTRACTOR SHALL VERIFY MECHANICAL OPENING DIMENSIONS WITH EQUIPMENT
SUPPLIED. NOTIFY ENGINEER AND ARCHITECT IF DIMENSIONS VARY MORE THAN 1'-0".
www.segonline.com
Cert of Auth - 6523
S EG

EXTERIOR MASONRY WALLS SHALL BE WT1, UNO. MASONRY WALL TYPES CONTINUE FROM
6
12K3 FLOOR PLAN BELOW UNLESS NOTED OTHERWISE ON THE PLANS. IF NOT MARKED OR ENGINEER OF RECORD
CONTINUED FROM THE LOWER FLOOR, WALLS SHALL BE WT1. ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

3 PROVIDE PRE-CAST 'U' LINTELS OVER ALL OPENINGS IN MASONRY WALLS.


7
3 SPA @ 5'-0" = 15'-0"

COORDINATE EXACT SIZE, LOCATION AND ELEVATION WITH ARCHITECTURAL AND


5 MECHANICAL DRAWINGS. SEE MASONRY SCHEDULES AND DETAILS.
S401
26'-8"

12K3
7
S401

8
S401
Revisions
TYP
12K3
5'-10"

1
S201

11
S301
6
S401

Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

Proton Therapy
LINAC Addition
Shands Jacksonville Campus
UF LM-4985
Project Phase
100% Construction Documents
Sheet Title

PARTIAL ROOF
FRAMING PLAN

Scale Drawn By

As indicated CSH

Date Checked By

09 DEC 2011 RWG


11069

PARTIAL AEI Project No.

ROOF FRAMING PLAN N


11662-00
12/8/2011 4:08:09 PM

SCALE: 3/8" = 1'-0" Sheet No.

S104
Affiliated
1 Engineers

S201 Affiliated Engineers, Inc.


3007 SW Williston Rd.
2 Gainesville, Florida 32608
ISOCENTER LINE ISOCENTER LINE
S201 Tel 352.376.5500 Fax 352.375.3479
5 7 www.aeieng.com
LIFT CAPACITY = 11,000# (MINIMUM)
S401 FL Cert of Auth - 0005140
S401

TOW 18'-0"

2 3
S401 S201
TOW TOW
14'-10" 14'-10"

3'-4"
3'-4"
1
W8x31 W8x31 W8x31 2'-3" 2'-0" 5'-0" 2'-0"
S401 3
4'-3" S401
5'-8 7/8" 5'-8 7/8" Architecture
Walker Architects, Inc.
4055 NW 43rd St, #28
Gainesville, Florida 32606

11'-6"
Tel 352.672.6448 Fax 352.672.6468
11'-6"

www.walker-arch.com
5'-0" 7'-0" AA26002009
1
12'-4" 12'-4" 6'-5" 12'-0" 6'-7 1/2"
S302 Structural
7 Structural Engineers Group, Inc.
4'-0" 25'-0 1/2" VARIES
S302 4114 Sunbeam Rd, Bldg 200
(4'-6" MAX) Jacksonville, Florida 32257
Tel 904.262.4000 Fax 904.262.4100
= 10'-7"
.
LEVEL 1 -
www.segonline.com
Cert of Auth - 6523
S EG
LEVEL 1 -
TOSL

8"
TOSL
0'-0"

1'-6"
0'-0"
1'-6"

ENGINEER OF RECORD
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

2'-9 1/4"
2'-9 1/4"

MACHINE MACHINE
PIT FLOOR PIT FLOOR
-4'-3 1/4"

1'-6"
-4'-3 1/4"
1'-6"

SIM
9
1'-0" 19'-6" 1'-0"
9 S302
S302 1'-0" 21'-6"

1 SECTION 2 SECTION
Revisions

S201 NO SCALE S201 NO SCALE

PL 3/4x21x1'-9"

12" STD PIPE


10 1/2"
3/4"

14'-10"

"
/16
1'-9"

PL 3/4x18x1'-6" W/ 4 HILTI HDA-PF 1


9 EN
37 M20x250/100 ANCHORS OP
SPACED AT 14" OC EACH WAY
10 1/2"

1/4 12" STD PIPE NOTE:


1'-10 1/2"

PROVIDE HOLES TO
MATCH PROVIDED
EXACTRAC CEILING Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

1/4 PLATE. VERIFY PRIOR


TO ANY FABRICATION
4
PL 3/4x21x1'-9",
S201
SEE SECTION 10 1/2" 10 1/2"

12'-10" 1'-9"
Proton Therapy
LINAC Addition
3/4"

EXACTRAC CEILING PLATE N


Shands Jacksonville Campus
UF LM-4985
3 DETAIL 4 DETAIL Project Phase
100% Construction Documents
S201 NO SCALE S201 NO SCALE Sheet Title

PARTIAL BUILDING
SECTIONS

Scale Drawn By

As indicated CSH

Date Checked By

09 DEC 2011 RWG


11069

AEI Project No.

11662-00
12/8/2011 4:08:10 PM

Sheet No.

S201
Affiliated
VERTICAL REINFORCING:
SEE CMU WALL REINFORCING SCHEDULE
USE OPEN BOTTOM LOW WEB Engineers
BOND BEAM BLOCK WHERE Affiliated Engineers, Inc.
FOR REQUIRED SPLICE LENGTHS. INDICATED ON DRAWINGS OR 3007 SW Williston Rd.
HOLD IN POSITION AT INTERVALS OF Gainesville, Florida 32608
VERTICAL NOTES: AS REQUIRED. Tel 352.376.5500 Fax 352.375.3479
REINFORCING APPROXIMATELY 4'-8". www.aeieng.com
1. SEE PLAN & SCHEDULE FOR FILLED CELL LOCATIONS,
FL Cert of Auth - 0005140
REINFORCING SIZE, AND SPACING.
2. BED WEBS AS WELL AS FACE SHELLS ADJACENT TO PLACE METAL LATH UNDER BOND BEAM
CELLS TO BE FILLED TO PREVENT GROUT LEAKAGE TO TOP OF FOOTING, FLOOR VERTICAL REINFORCING TO CONFINE GROUT OVER OPEN CORES CORES CONTAINING REINFORCING
COVER UNITS WITH ADJACENT CELLS UNLESS ADJACENT CELLS ARE ALSO OR PREVIOUSLY OR OTHERWISE PLUG CORES IN SUCH A ARE FILLED SOLIDLY WITH GROUT;
ABSORPTIVE PAPER TO BE FILLED. GROUTED WALL MANNER THAT GROUT WILL KEY INTO VERTICAL CORES SHALL PROVIDE A
3. SEE SPECIFICATIONS AND GENERAL NOTES FOR GROUT CELL BELOW APPROXIMATELY 1". USE CONTINUOUS CAVITY FREE OF
REQUIREMENTS. OF BUILDING PAPER IS NOT ALLOWED. MORTAR DROPPINGS. TOP OF
SAW CUT 4" WIDE x 3" HIGH
4. ALL REINFORCING SHALL BE TIED OR SUPPORTED SLOT AT CELLS TO BE FILLED PREVIOUS LIFT SHALL ALSO BE
SECURELY IN POSITION. INSPECT REINFORCING AND OR USE PREFORMED BLOCK. REINFORCING IN BOND CLEAN. CLEAN-OUTS ARE NOT
GROUT TEST PRISM 3 CELL CONTINUITY PRIOR TO CLOSING CLEAN-OUTS. REQUIRED FOR LOW LIFT GROUTING.
BEAMS SHALL BE SET IN
1/2 x 3 1/2 x 7 5. GROUTING SHALL NOT COMMENCE UNTIL 48 HOURS HAS PLACE (ON CHAIRS) AS
ELAPSED SINCE THE SECTION OF THE WALL TO BE WALL IS LAID UP.
GROUTED HAS BEEN COMPLETED TO ITS FULL HEIGHT.
6. A GROUT PUMP SHALL BE USED TO PLACE GROUT FOR
THE HIGH LIFT METHOD.
7. PLACE THE FIRST LIFT OF GROUT FOR A SECTION OF
WALL TO MAXIMUM HEIGHT OF 5 FEET, VIBRATING THE FOOTING, FLOOR PLACE GROUT IN LIFTS NOT TO EXCEED 4'-8",
GROUT IN EACH FILLED CELL WITHIN 10 MINUTES OF OR PREVIOUSLY PUDDLE AND VIBRATE IN PLACE. HOLD DOWN
TAPE GROUTED WALL 1 1/2" BETWEEN LIFTS.
PLACEMENT.
8. PLACE THE NEXT SUCCESSIVE LIFT NOT LESS THAN 30
FRONT BLOCK NOT MINUTES NOR MORE THAN 60 MINUTES LATER AND NOTES:
Architecture
3 1/2 x 3 1/2 x 5/8 PLACE MORTAR ON CROSS WEB ADJACENT TO CORES Walker Architects, Inc.
SHOWN FOR CLARITY VIBRATE 12 INCHES INTO THE PREVIOUSLY PLACED LIFT. 1. CLEAN OUT MORTAR DROPPINGS AT MIDDAY AND AT THE END
WOOD PALLET THAT WILL BE GROUTED TO PREVENT LEAKAGE OF 4055 NW 43rd St, #28
(NON-ABSORPTIVE) USE SPACERS OR WIRE TIES 9. CONTINUE PLACING SUCCESSIVE LIFTS UNTIL OF EACH WORKING DAY. PLACE AND POSITION CELL GROUT INTO ADJACENT CELLS. Gainesville, Florida 32606
NOTES:
TO HOLD REINFORCING IN GROUTING OF SECTION OF WALL IS COMPLETED TO REINFORCING AFTER FINAL CLEANOUT. Tel 352.672.6448 Fax 352.672.6468
PROPER POSITION. SPACE AT THE TOP. 2. PLACE REINFORCING IN CELLS AFTER LAYING MASONRY. 1. CONSTRUCT WALL IN LIFTS, GROUTING CELLS AND HORIZONTAL BOND BEAMS
www.walker-arch.com
NOTES: 10. SEE CMU WALL REINFORCING SCHEDULE FOR AA26002009
INTERVALS NOT EXCEEDING 3. SEE GENERAL NOTES AND SPECIFICATIONS FOR INSPECTION PRIOR TO LAYING BLOCK ABOVE.
1. TEST PER ASTM C1019.
192 BAR DIAMETERS OR 10'-0". REQUIRED SPLICE LENGTHS. & ADDITIONAL REQUIREMENTS.
2. SEE SPECIFICATIONS FOR FREQUENCY REQUIREMENTS.
2. BOND BEAMS MAY NOT OCCUR IN ALL LIFTS. REFER TO PLANS AND Structural
METHOD OF CASTING GROUT TESTING PRISMS WALL SECTIONS FOR BOND BEAM LOCATIONS. Structural Engineers Group, Inc.
METHOD OF HIGH LIFT GROUTING CLEAN-OUT OPENINGS AT FILLED CELLS 4114 Sunbeam Rd, Bldg 200
Jacksonville, Florida 32257
REQUIRED WHERE HIGH LIFT GROUTING IS USED METHOD OF LOW LIFT GROUTING Tel 904.262.4000 Fax 904.262.4100
(4'-8" MAXIMUM LIFT) www.segonline.com
Cert of Auth - 6523
S EG

ENGINEER OF RECORD

1 2 3 4
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

DETAIL DETAIL DETAIL DETAIL


S301 NO SCALE S301 NO SCALE S301 NO SCALE S301 NO SCALE

PREMOLDED DUR-O-WAL REINFORCE 3 CELLS @ REINFORCE 2 CELLS @


REINFORCED CELL EACH RAPID CONTROL JOINT EACH CORNER W/ EACH INTERSECTION W/
SIDE OF CONTROL JOINT, WITH WIDE FLANGE SCHEDULED WALL SCHEDULED WALL
FILL WITH GROUT REINFORCING REINFORCING
MATCH REINFORCING
APPLY SEALANT ON BOTH SIDES FROM BELOW OPENING

CLR
4"
JAMB CONCRETE OR
REINFORCING CMU ROOF BEAM
STANDARD SASH BLOCK,

SCHEDULED
EACH SIDE OF CONTROL JOINT PREFABRICATED

SPLICE
PREMOLDED DUR-O-WAL RAPID PREFABRICATED TEE
PLAN DETAIL

SCHEDULED
CONTROL JOINT WITH WIDE CORNER JOINT JOINT REINFORCING

SPLICE
FLANGE, OR APPROVED EQUAL REINFORCING
SEE PLAN FOR CMU LINTEL Revisions
WALLS & REINFORCING REINFORCING DOWEL W/ STANDARD
HOOK OR TERMINATE
VERTICAL WITH A
STANDARD HOOK
REINFORCED CELL EACH
SIDE OF CONTROL JOINT, WALL REINFORCING AT CORNERS / INTERSECTIONS

CLR
FILL WITH GROUT

2"
1'-4" CMU WALL CMU WALL
ADD CORNER BARS TO ALL HORIZONTAL WALL REINFORCING
REINFORCING, LAP 48 BAR DIAMETERS (HOOKS NOT SHOWN), 5 TYP
SEE PLAN S401
7 SCHEDULED
S301 REINFORCING
48 BAR DIAMETER

CONTROL JOINT -
24'-0" OC, MAX ON EXTERIOR WALLS
LAP, TYP

SEE SECTIONS, DETAILS

CLR
28'-0" OC, MAX ON INTERIOR WALLS

2"
OR SCHEDULES FOR BEAM SLAB ON GRADE
DO NOT PLACE OVER OPENINGS OR

SCHEDULED
CONTINUE THROUGH CAST IN PLACE REINFORCING

SPLICE
BEAMS, UNO

SCHEDULED
APPLY SEALANT ON BOTH SIDES CONCRETE OR FOOTING
MASONRY BEAMS

SPLICE
NOTES:
1. SEE PLAN FOR LOCATIONS. SILL
2. INTERRUPT HORIZONTAL JOINT REINFORCING & CMU BOND REINFORCING
BEAM REINFORCING AT CONTROL JOINTS.
DOWEL WITH
METHOD OF WALL CONTROL JOINT (WCJ) CONSTRUCTION BEAM REINFORCING AT CORNERS / INTERSECTIONS

CLR
REINFORCING SIZE AND STANDARD HOOK

3"
SPACING SAME AS WALL

5 DETAIL 6 DETAIL
ADJACENT TO OPENING
(UNO)
NOTES:
1. REFER TO PLANS AND SCHEDULES FOR SIZE, NUMBER AND LOCATION OF
VERTICAL REINFORCING.
2. CLEAN-OUTS AND HJR NOT SHOWN BUT ARE REQUIRED, SEE SPECIFICATIONS. Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

NO SCALE NO SCALE NOTES: 3. SPLICE LOCATIONS ARE DIAGRAMMATIC. SPLICE AS REQUIRED.


S301 S301
1. REFER TO PLANS AND SCHEDULES FOR SIZE, NUMBER AND LOCATION OF
VERTICAL REINFORCING. AT SINGLE STORY WALL
2. CLEAN-OUTS AND HJR NOT SHOWN BUT ARE REQUIRED, ,SEE SPECIFICATIONS.
3. SPLICE LOCATIONS ARE DIAGRAMMATIC. SPLICE AS REQUIRED. DIAGRAMMATIC ELEVATION
TYPICAL CMU WALL VERTICAL REINFORCING
CLR
1/2"

EQ

1 PER CELL,
DIAGRAMMATIC ELEVATION
SEE SCHEDULE
WINDOW OPENING IN CMU (DOOR SIMILAR)
Proton Therapy
LINAC Addition
t

t
CLR

Shands Jacksonville Campus


1/2"

JAMB MASONRY JAMB


2 PER CELL, 1 PER CELL,
OPENING WIDTH
SEE SCHEDULE SEE SCHEDULE

MASONRY WALL REINFORCING SCHEDULE


9 ELEVATION 10 ELEVATION
UF LM-4985
Project Phase

WALL THICKNESS VERTICAL MAXIMUM SPLICE NO SCALE NO SCALE 100% Construction Documents
S301 S301
WALL TYPE "t" REINF. SPACING LENGTH HJR SPACING REMARKS
Sheet Title
WT1 7 5/8" 1-#6 16" 42" 16"
2 PER CELL,
SEE SCHEDULE
NEW EXIST
MASONRY
MASONRY WALL JAMB REINFORCING SCHEDULE CONSTRUCTION SECTIONS AND
EXPANSION JOINT
WALL MASONRY NUMBER OF REINFORCED CELLS PER JAMB METAL WALL ANCHORS FASTENED MATERIAL DETAILS
TYPE OPENING OPENING IN OPENING IN SPLICE LENGTH TO EXIST COLUMN W/ 1/4" TAPCON
WIDTH EXTERIOR WALL INTERIOR WALL ANCHORS. SPACE TO MATCH WALL
*SEE SEPARATE DETAIL/SCHEDULE FOR JAMB REINFORCING. HORIZ JOINT REINFORCING, TYP EXIST WALL CONCRETE WALL, Scale Drawn By
UP TO 3'-4" 1-#6 PER CELL 1-#6 PER CELL 42"
IN 2 CELLS IN 1 CELL NOTES: SEE PLAN WALL,
WT1 SEE PLAN As indicated CSH
1. VERTICAL REINFORCING SHALL RUN FROM FOOTING TO 4" CLEAR FROM TOP OF UPPERMOST
UP TO 6'-8" 2-#6 PER CELL 1-#6 PER CELL 42" SUPPORTED BEAM (ROOF BEAM OR OPENING LINTEL). VERTICALS MAY BE LAP SPLICED AS
IN 2 CELLS IN 2 CELLS
REQUIRED FOR EASE OF BLOCK INSTALLATION. PROVIDE HOOKED DOWEL FROM FOOTING OR
SUPPORT BEAM AT EACH FILLED BLOCK CELL. PROVIDE HOOK AT TOP OF VERTICAL. EACH POUR OF
Date Checked By
GROUT SHALL BE STOPPED AT LEAST 1 1/2" BELOW THE TOP OF THE LAST COURSE OF BLOCK LAID
(EXCEPT AT PRECAST LINTELS).
2. SEE TYPICAL DETAILS AND CODE REQUIREMENTS FOR CLEAN-OUTS. 09 DEC 2011 RWG
WALL,
SEE PLAN
TYPICAL FILLED CELLS WITH 1 BAR OR 2 BARS PER CELL
11069

AEI Project No.


2 REINF CELLS,
SEE SCHEDULE
11662-00
12/8/2011 4:08:11 PM

7 DETAIL & SCHEDULE 8 DETAIL & SCHEDULE 11 DETAIL 12 DETAIL


Sheet No.

S301 NO SCALE S301 NO SCALE S301 NO SCALE S301 NO SCALE


S301
TIE TYPES (SEE SCHEDULE)
Affiliated
ADD CORNER BARS,
TOP & BOTTOM
48 BAR DIAMETER
LAP, TYP
TYPE A
Affiliated Engineers, Inc.
Engineers
TYPE B 3007 SW Williston Rd.
Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
TYPE C www.aeieng.com
FL Cert of Auth - 0005140
CENTERED SEE PLAN FOR
ON FOOTING WALL & REINFORCING
UNO
WALL, SEE PLAN

2" CLR
3/8" EXPANSION JOINT FOOTING & TOF
MATERIAL & SEALANT REINFORCING,

SCHEDULED
SEE PLAN SEE PLAN

DEPTH
EXTERIOR SLAB OCCURS AT SLAB, SEE PLAN EMBEDED PVC 3" CLR
SOME LOCATIONS, CONDUIT, SEE PLAN TYP, UNO
SEE ARCHITECTURAL/CIVIL
TOSL SJ, SEE PLAN
2" SLAB, SEE PLAN CONTINUOUS FOOTING CORNER BARS
SEE PLAN SLAB, CLR SCHEDULED

CLR
REINFORCING

2"
SEE PLAN MINIMUM LAP SPECIFIED SCHEDULED
TOSL
IF CONSTRUCTION JOINT OCCURS AT WIDTH
0'-0" SPLICE IN CONT BARS
VAPOR RETARDER
CLR

NOTES:

1'-0"

1'-0"
2"

TOP & BOTTOM BARS 1. WALL IS CENTERED ON FOOTING, UNO. Architecture


TOF 2. DOWELS SHALL BE TIED IN THE PROPER LOCATION PRIOR TO Walker Architects, Inc.
SEE PLAN CONTINUE THROUGH JOINT 4055 NW 43rd St, #28
TOSL CJ CONCRETE PLACEMENT.
Gainesville, Florida 32606
-1'-0" ROUGHENED 3. EXTEND WALL FOOTING REINFORCING THROUGH COLUMN Tel 352.672.6448 Fax 352.672.6468
COMPACTED EARTH

6"
FOOTING OR 40 BAR DIAMETERS (2'-0" MIN) INTO COLUMN www.walker-arch.com

h
FOOTING. AA26002009
FILL ALL CELLS W/ GROUT 4. LAP ALL CONTINUOUS REINFORCING 40 BAR DIAMETERS (2'-0" MIN).

CLR
5. REFER TO CONCRETE SUPPORT BLOCK DETAIL FOR ADDITIONAL

3"
3" TO FINISHED FLOOR OR CONTINUOUS KEY TIES Structural
TOP OF GRADE, INFORMATION.
CLR

CLR EXTEND WWF 8" INTO VAPOR RETARDER NOTE: Structural Engineers Group, Inc.
3"

WHICHEVER IS HIGHER. 6. ALL FOOTING MARKS MAY NOT BE USED ON THIS PROJECT. 4114 Sunbeam Rd, Bldg 200
THICK SLAB a. USE ONE 2x4 KEY FOR 'h' 18"
Jacksonville, Florida 32257
COMPACTED EARTH b. USE ONE 2x6 KEY FOR 18" < 'h' 30" Tel 904.262.4000 Fax 904.262.4100
FOOTING, SEE PLAN c. USE TWO 2x6 KEYS FOR 'h' > 30" www.segonline.com S EG
SLAB STEP WALL FOOTING SCHEDULE Cert of Auth - 6523
WALL FOOTING CONSTRUCTION JOINT TOP BOTT. TIES
MARK WIDTH DEPTH BARS BARS TYPE SIZE SPACING REMARKS
WF2.0 2'-0" 1'-0" 3-#4 3-#4 B #3 12" ENGINEER OF RECORD

1 2 3
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

SECTION DETAIL DETAIL


4
S302 NO SCALE S302 NO SCALE S302 NO SCALE

WALL JOINT SCHEDULE & DETAIL


S302 NO SCALE

EXISTING
WALL & SLAB EXISTING
3
4-#5 CONT W/ #3 3'-0" S303
11 SAWCUT SLAB AS SOON AS CUT CAN BE 3/8" EXPANSION JOINT STIRRUPS @ 12" OC SLAB,
MADE WITHOUT DAMAGING EDGES OF MATERIAL + SEALANT SEE PLAN

1/4 SLAB DEPTH


S301 SEE PLAN FOR SLAB &
CUT (24 HOURS MAX). PROVIDE TOOLED
REINFORCING, CUT EVERY
JOINT AT ENDS OF SAWED JOINT Level 01 -

(1" MIN)
OTHER WIRE AT JOINT
AGAINST WALLS, COLUMNS, ETC. AS TOSL
REQUIRED TO COMPLETE SLAB JOINT. 0'-0"
FILL W/ SEALANT.
Revisions
TOSL
LEVEL 1 CONCRETE SLAB,
SEE PLAN SEE PLAN
0'-0"

#6 @ 12"
1'-6"

TOSL 1'-6"
TOSL

3'-1"
-1'-0"
-1'-0" 4-#6 @ 12" OC
3/8" EXPANSION
COMPACTED EARTH VAPOR RETARDER
1'-0"

JOINT MATERIAL
+ SEALANT 1'-6"

TOF VAPOR RETARDER


TYPICAL SAWED CONTROL JOINT (SJ) 3'-0" 1'-0"
-2'-0"
(x3'-0")
1'-0"

COMPACTED EARTH SLAB,


8 SEE PLAN
GRATING, S303
SEE ARCH
MACHINE
FOOTING, SEE PLAN PIT FLOOR
-4'-3 1/4"
COMPACTED EARTH SEE 9/S302 SUMP PIT
WALL REINF
AND #6 @ 12"

2'-0"
5 SECTION 6 DETAIL 7 SECTION
ADDITIONAL
INFORMATION
EW T&B

CLR
2"
S302 NO SCALE S302 NO SCALE S302 NO SCALE SUMP PIT
-6'-3 1/4"
CONT 2x4
KEY W/
3/8" EJ MATERIAL + SEALANT WATERSTOP

1'-6"
Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

SAWCUT EXISTING SLAB


STRAIGHT AND SQUARE
4" 8" #5 CONT
EXISTING GROUND
2" CLR

FLOOR SLAB
CLR

CLR
3" CLR
1"

3"
(NTS)
2x4 CONT Level 01 -
TOSL
1"

KEYWAY
0'-0" COMPACTED EARTH Proton Therapy
8"

5'-0" LINAC Addition


1'-6"

NEW EXIST
8 Shands Jacksonville Campus
CLR

DETAIL
1"

CONSTRUCTION SLAB & WALL CONSTRUCTION


UF LM-4985
#6 CONT @ 6" OC
HEAVY WEIGHT S302 NO SCALE
Project Phase
SOLID CMU
WATERSTOP BLOCK INFILL 100% Construction Documents
WALL BEYOND, CONT, 2x4 KEYWAY
#6x4'-0" + HK SEE PLAN CUT INTO EXIST
@ 12" OC SLAB EDGE Sheet Title
2'-9 1/4"

2'-6" LAP

#5 CONT @ 12" OC (MAX), EA FACE


3"
CLR
1 1/2"
CLR SLAB, SEE PLAN SLAB, SEE PLAN FOUNDATION
#6x3'-9" + STD HK @ 12" OC
CJ, ROUGHENED SECTIONS AND
#7 + HK EE @ 12" OC
TOSL TOSL TOSL DETAILS
CLR
2"

MACHINE EXIST
-1'-0"
PIT FLOOR
6"

10"
1'-0"

-4'-3 1/4"
2-#4 x (OPNG - 4") Scale Drawn By

TOF As indicated CSH


WATERPROOFING &
1'-6"

VAPOR BARRIER, SEE PLAN


6"

SEE ARCH DWG'S


VAPOR RETARDER
6" Date Checked By
CONT 2x4 KEY COMPACTED EARTH
EXIST SLAB
CLR

W/ WATERSTOP 09 DEC 2011 RWG


3"

VAPOR RETARDER #5x1'-8" DWLS


#4 + HK @ 12" OC @ DRILLED AND SET IN
COMPACTED EARTH COMPACTED EARTH
DOORWAY OPENING APPROVED EPOXY ANCHORING
11069

SYSTEM @ 12" OC AEI Project No.


FOOTING, SEE PLAN
11662-00
12/8/2011 4:08:12 PM

9 DETAIL 10 SECTION 11 SECTION Sheet No.

S302 NO SCALE S302 NO SCALE S302 NO SCALE


S302
3" 3"
SLAB & REINFORCING, TYP
TYP
SEE PLAN Affiliated

Affiliated Engineers, Inc.


Engineers

2" P
3007 SW Williston Rd.

TY
14 GAGE WIRE TIE

2" P
Gainesville, Florida 32608

TY
Tel 352.376.5500 Fax 352.375.3479
SEE MECHANICAL FOR SIZE AND LOCATION OF PAD www.aeieng.com
3000 PSI CONCRETE SUPPORT BLOCK - FL Cert of Auth - 0005140
USE 2 @ 4'-0" OC IN CONTINUOUS WALL
4" EQUIPMENT SIZE
FOOTINGS, 1 PER 16 SQUARE FEET (4 MIN)
2-#5 x 4'-0" DIAGONAL BARS,
IN COLUMN FOOTINGS, AND @ 3'-0" OC,
1 TOP & BOTTOM INNER 2-#5 x 4'-0" DIAGONAL
EACH WAY IN SLABS, TYPICAL 1'-0" ROUGHEN TOP OF STRUCTURAL SLAB REINFORCING LAYERS, BARS, 1 EACH FACE,
MIN (FLOAT FINISH OR HEAVY BROOM) TYPICAL EACH CORNER TYP EACH CORNER WALL &
REINFORCING,
SEE MECHANICAL SEE PLAN
FOR EQUIPMENT
APPLY APPROVED
ANCHORAGE
3/4" CHAMFER BONDING AGENT
ALL SIDES
1-#4 CONTINUOUS 6x6 W2.1xW2.1

TYP
ALL SIDES

3"
CENTERED

TYP
3"
3 1/2"
UNO
4" TOSL
SEE PLAN PROVIDE 180 HOOKS ON
ALL INTERRUPTED BARS Architecture
3 1/2" 3'-0" OPENING Walker Architects, Inc.
NOTE: OPENING
NOTES: MAX 4055 NW 43rd St, #28
AS AN ALTERNATE, 3" CASTLE CHAIR 3'-0" MAX Gainesville, Florida 32606
BY AZTEC CONCRETE ACCESSORIES NOTES:
Tel 352.672.6448 Fax 352.672.6468
MAY BE USED 1. ADD HALF OF THE PARALLEL INTERRUPTED BARS ON EACH SIDE OF THE 1. ADD HALF OF THE PARALLEL INTERRUPTED BARS ON EACH SIDE OF THE www.walker-arch.com
SLAB, SEE PLAN OPENING & ENSURE THAT MINIMUM REINFORCING REQUIREMENTS ARE OPENING & ENSURE THAT MINIMUM REINFORCING REQUIREMENTS ARE MET. AA26002009
MET. ADDED REINFORCING SHALL BE NOT LESS THAN THE FOLLOWING: ADDED REINFORCING SHALL BE NOT LESS THAN THE FOLLOWING.
a. 2-#5 MIN @ SLABS 10" THICK, (1 TOP & BOTTOM, EACH WAY) a. 2-#5 MIN @ WALLS 12" THICK, (1 EACH FACE, EACH WAY)
CONTRACTOR FABRICATED CONCRETE SUPPORT BLOCK
TYPICAL EQUIPMENT PAD b. 2-#7 MIN @ SLABS > 10" THICK, (1 TOP & BOTTOM, EACH WAY) b. 2-#7 MIN @ WALLS > 12" THICK, (1 EACH FACE, EACH WAY) Structural
Structural Engineers Group, Inc.
4114 Sunbeam Rd, Bldg 200
2. EXTEND REINFORCING 48 BAR DIAMETERS BEYOND THE OPENING OR 2. EXTEND REINFORCING 48 BAR DIAMETERS BEYOND THE OPENING OR Jacksonville, Florida 32257
PROVIDE A STANDARD HOOK AT THE SLAB EDGES AROUND THE OPENING. PROVIDE A STANDARD HOOK AT THE WALL EDGES AROUND THE OPENING. Tel 904.262.4000 Fax 904.262.4100
www.segonline.com
Cert of Auth - 6523
S EG
TYPICAL SMALL SLAB OPENING TYPICAL SMALL WALL OPENING ELEVATION

ENGINEER OF RECORD

1 2 3 4
ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

DETAIL DETAIL PLAN DETAIL DETAIL


S303 NO SCALE S303 NO SCALE S303 NO SCALE S303 NO SCALE

1'-4"
0" TYP

"U" BARS & DIAGONALS, 1'-1 5/8"


SAME SIZE & SPACING AS
TYP
HORIZONTAL REINFORCING S S
SEE PLAN FOR NUMBER

2" CLR
HALF OF TYPICAL OF REQUIRED STEPS Revisions
VERTICAL SPACING SEE PLAN FOR WALL ALUMINUM GRATING,
& REINFORCING TOF SEE ARCHITECTURAL
48 BAR DIAMETER

TYP
SEE PLAN

0",

UNO
SLAB, SEE PLAN

8"
LAP, TYP

ADDITIONAL BARS

UNO
8"
AS REQUIRED TOSL
TOF
SEE PLAN

3 1/2"
MIN
SEE PLAN
SEE PLAN FOR WALL 48 BAR DIAMETER
& REINFORCING CONTINUOUS KEY STEP BARS TO

3"
h
(2x4, MIN) LAP, TYP MATCH NUMBER &

CL
SIZE OF FOOTING CONTINUOUS STAINLESS

R
REINFORCING STEEL L4x3x3/8 (LLV),
TWO LAYERS OF REINFORCING
TWO LAYERS OF REINFORCING MITER AT CORNERS AND
h TIES TO MATCH FOOTING TIES WELD JOINTS. CONNECT
TYPICAL WALL CORNER TYPICAL WALL CONSTRUCTION JOINTS W/ 3/4" SS HILTI KWIK
LAP 40 BAR , MIN BOLT 3 @ 8" FROM
CORNERS W/ REMAINDER
@ 24" OC
NOTE: TYPICAL WALL FOOTING STEP
SEE SECTIONS, DETAILS, ETC FOR REINFORCING LAYERING REQUIREMENTS, TYPICAL
NOTED THUS "$" ON PLAN

5 PLAN DETAIL 6 PLAN DETAIL 7 DETAIL 8 DETAIL


Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

S303 NO SCALE S303 NO SCALE S303 NO SCALE S303 NO SCALE

Proton Therapy
LINAC Addition
Shands Jacksonville Campus
UF LM-4985
Project Phase
100% Construction Documents
Sheet Title

CONCRETE
SECTIONS AND
DETAILS
Scale Drawn By

As indicated CSH

Date Checked By

09 DEC 2011 RWG


11069

AEI Project No.

11662-00
12/8/2011 4:08:13 PM

Sheet No.

S303
Affiliated

Affiliated Engineers, Inc.


Engineers
1'-4" EXISTING CONCRETE WALL 3007 SW Williston Rd.
Gainesville, Florida 32608
Tel 352.376.5500 Fax 352.375.3479
2" 1'-0" 2" www.aeieng.com
FL Cert of Auth - 0005140
2 EXISTING 2L 8x6x5/8 W/ 2 - 3/4" A325X IN SSL CONNECTION TO W8.
CONCRETE CONNECT EACH ANGLE TO CONCRETE WALL W/2 HILTI
S401 BEAM HDA-PF 37 M20x250/100 ANCHORS SPACED @ 12" OC CENTERLINE OF
VERTICALLY AND 12" OC HORIZONTALLY MAINTENANCE OPENING
AND HOIST SUPPORT (TBD)

EXISTING CONCRETE SLAB


EXISTING REINFORCING -
EMBED

2"
CONTRACTOR TO HAVE
10"

TESTING AGENCY
ACCURATELY LOCATE

8"
REINFORCING IN RELATION TO 10"

2 1/2"
BEAM ANCHOR PLATE AND

EMBED
BOC BOC

7 1/2"
HDA ANCHORS. REINFORCING TOS

1'-0"

1'-4"
11'-6" IS NOT TO BE CUT. 11'-6"
(VERIFY) (VERIFY) 11'-5"
SEE 1/S401 BOC 14'-10"
1/4

3"
1/4
Architecture
1/4 1/4 EXISTING REINFORCING - Walker Architects, Inc.

2"
CONTRACTOR TO HAVE PL 3/4x6x1'-0" W/ 4055 NW 43rd St, #28
TESTING AGENCY ACCURATELY 2 HILTI HDA-PF 30M16x190/40 Gainesville, Florida 32606
1 1/2" 4 1/2" 4 1/2" 1 1/2"

2 1/2"
3" Tel 352.672.6448 Fax 352.672.6468
LOCATE REINFORCING IN CENTER PLATE OVER www.walker-arch.com
2" 1'-0" 2" RELATION TO BEAM ANCHOR MAINTENANCE OPENINGS
W8x31, SEE PLAN AA26002009
W8x31 6" PLATE AND HDA ANCHORS. 1'-0" ON LINAC FLOOR
1'-4" REINFORCING IS NOT TO BE
W8x31, SEE PLAN CUT. Structural
MAINTENANCE HOIST Structural Engineers Group, Inc.
CONNECTOR AS REQUIRED. 4114 Sunbeam Rd, Bldg 200
Jacksonville, Florida 32257
PL 1x16x1'-4" W/ 4-HILTI HDA-PF 37 Tel 904.262.4000 Fax 904.262.4100
M20x250/100 ANCHORS
SPACED AT 12" OC EACH WAY
www.segonline.com
Cert of Auth - 6523
S EG

ENGINEER OF RECORD

1 DETAIL 2 DETAIL 3 DETAIL 4 DETAIL


ROBERT W. GIVENS, P.E. FL. P.E. NO. 31961

S401 NO SCALE S401 NO SCALE S401 NO SCALE S401 NO SCALE


CONTINUOUS L4x4x1/4 W/ 3/4"
INSERTS @ 32" OC, EMBED 4" BOND BEAM W/
#5 CONTINUOUS

BOND BEAM W/ CONNECT OVERLAPPED SIDE LAPS WITH #10 HEX HEAD

SEE PLAN
#5 CONTINUOUS SELF-DRILLING SCREWS. SEE ROOF PLAN FOR NUMBER
TOW CONTINUOUS L4x4x1/4 W/ REQUIRED IN EACH SPAN BETWEEN SUPPORTS.
3/16 2
TYP 18'-0" 3/4" INSERTS @ 32" OC, INTERLOCKED STANDING SIDE LAPS NOT ACCEPTABLE.
EXISTING CONCRETE
3/16 2 EMBED 4"
TOW WALL, SEE PLAN

1'-4"
18'-0"

@ EACH JOIST ROOF DECK, SEE PLAN SEE 5/S401 6"


3/16 TOW
2'-0"

16'-8"
ROOF DECK, SEE PLAN TOJ PROVIDE @ 6" OC AT
SECTION STRUCTURAL
DISCONTINUED EDGES AND SUPPORT AT

1'-4"
SEE PLAN
2 1/2"
MIN

TOJ OVER PARALLEL END OF SHEET


TOJ SEE PLAN STRUCTURAL SUPPORTS Revisions
5/8" PUDDLE WELD, TYP
TOC SEE PLAN JOIST, SEE PLAN
16'-0"

4"
REINF
1'-4"

2-#5 CONTINUOUS
TOP & BOTTOM,
#3 TIES @ 16" OC

END LAP
JOIST, SEE PLAN JOIST, SEE PLAN

MIN

2"
EXTEND WALL
L5x3x3/8x0'-10" (LLH) W/ 2- 1/2" x 6" REINFORCING
HCA, PROVIDE 1/4" VENT HOLE @ TO PARAPET L6x4x1/2x1'-0" (LLV) W/ 2-3/4"
7 5/8"x16" CONCRETE BEAM CENTER OF ANGLE INSERTS @ 8" OC, EMBED 6" MIN
BRIDGING, SEE PLAN JOIST TOP CHORD
W/ 2-#5 TOP & BOTTOM,
PLAN SHOWN,
#3 TIES @ 16" OC
BEAM SIMILAR
WALL, SEE PLAN TYPICAL BRIDGING ANGLE L3x3x1/4 x JOIST
7 5/8"
DEPTH W/ 2-3/4" EXPANSION ANCHORS NOTES: SECTION
W/ 5" EMBEDMENT, MIN CONNECT DECK TO ALL SUPPORTS BY WELDING AT SIDE LAPS AND AT
INTERMEDIATE RIBS AT THE FOLLOWING SPACINGS:
WALL, SEE PLAN
PATTERN 'A' AT 6" ON CENTER (EVERY RIB)
PATTERN 'B' AT 12" ON CENTER (EVERY OTHER RIB)
1'-4".

A
SEE ROOF PLAN FOR LOCATIONS OF WELDING PATTERN - SHOWN THUS
PRECAST LINTEL BLOCK & THE NUMBER OF SIDE LAP SCREWS BETWEEN SUPPORTS - SHOWN THUS
1'-4".

REINFORCING W/ 2-#5 T&B #


T. OPNG
AT SOUTH WALL
SEE ARCH TYPICAL ROOF DECK DIAPHRAGM ATTACHMENT
PRECAST LINTEL BLOCK T. OPNG
REINFORCING W/ 2-#5 T&B
SEE ARCH
AT SOUTH WALL

5 SECTION 6 SECTION 7 SECTION 8 DETAIL


Project
C:\Users\phi.segonline\Documents\Revit Structure 2012 Local\UF_PROTON_11069 - STRT_phi.rvt

S401 NO SCALE S401 NO SCALE S401 NO SCALE S401 NO SCALE


SEE ARCHITECTURAL OR
MECHANICAL DRAWINGS
FOR SIZE AND LOCATION OF
VARIES OPENING VARIES

SEE ARCHITECTURAL OR
MECHANICAL DRAWINGS
FOR SIZE AND LOCATION OF
SEE PLAN FOR ROOF DECK.
WELD WITH 5/8" PUDDLE
Proton Therapy
LINAC Addition
DIRECTION OF

VARIES OPENING VARIES WELDS @ 6" OC AROUND


L1 1/2x1 1/2x3/16 (MIN) TO
DECK SPAN

FRAME PERIMETER. 2" MIN


TOP CHORD PANEL POINT
TYP TYP
ROUND OR SQUARE HOLES FROM
3" TO 12" MAX DIMENSION FOR
SELF-FLASHING 3/16 TYP
(ALTERNATE SIDES) WELD
FOR 3k (MIN) EACH SIDE
Shands Jacksonville Campus
PREFABRICATED 1/8
OPENING OVER 12" PROVIDE METAL CURB UF LM-4985
3" MIN

ANGLE FRAME, SEE DETAILS TOJ TOJ


2" MIN SEE PLAN SEE PLAN
20 GAGE GALVANIZED TYP Project Phase
REINFORCING PLATE TYP 3/16 1"
WITH #12 SCREWS @ 3" TYP 100% Construction Documents
OC MAX (4 SCREWS MIN L2 1/2x2 1/2x1/4
TOJ Sheet Title
PER CORRUGATION) FRAME
SEE PLAN JOIST, SEE PLAN
1"
TYP
FRAMING
L4x4x1/4
FRAME DOUBLE NUT W/ 1/4" THICK
SECTIONS AND
JOIST, SEE PLAN
TOP OF CORRUGATION
PLATE WASHER NOTES: DETAILS
TYP 3/16 C4x5.4 EACH SIDE WHERE
3/16 1. DECK OPENINGS ARE TO BE FABRICATED SO THAT DECKING RUNS
HANGER RODS OCCUR CONTINUOUSLY OVER OPENINGS. THE OPENINGS IN THE DECK ARE Scale Drawn By
FOR SUPPORTS LOCATED AT BC BETWEEN JOISTS NOT TO BE CUT UNTIL OPENING IS NEEDED (PER OSHA)
NOTES: PANEL POINTS WELD L4x3x5/16 LLV As indicated CSH
BETWEEN JOISTS 2. WELD DECK TO FRAME W/ 5/8" PUDDLE WELDS @ 6" OC. DECK NOT
1. PROVIDE JOIST TOP CHORD SUPPORT FOR LOADS BETWEEN JOIST PANEL SHOWN FOR CLARITY.
NOTE: POINTS. SEE DETAILS. TYP
DECK OPENINGS ARE TO BE FABRICATED SO THAT DECKING RUNS 5/8" THREADED ROD TO EQUIPMENT 1/8
OR SUSPENDED LOAD, LOCATE 3. ANCHOR ROOF DRAIN TO FRAME. Date Checked By
CONTINUOUSLY OVER OPENING. THE OPENINGS IN THE DECK ARE NOT TO 2. DECK OPENINGS ARE TO BE FABRICATED SO THAT DECKING RUNS
BE CUT UNTIL OPENING IS NEEDED (PER OSHA) AND REINFORCING PLATE BETWEEN JOIST CHORD L's IF
CONTINUOUSLY OVER OPENINGS.THE OPENINGS IN THE DECK ARE NOT TO BE HANGER RODS LOCATED ON JOIST CL
HAS BEEN INSTALLED. CUT UNTIL OPENING IS NEEDED (PER OSHA). 09 DEC 2011 RWG
TYPICAL ROOF DRAIN OPENING FRAME
TYPICAL ROOF OPENING FRAME NOTE:
11069

TYPICAL REINFORCEMENT USE THIS DETAIL WHEN SUPPORTING MISCELLANEOUS MINOR AEI Project No.
CONCENTRATED LOADS, OR FOR LOADS SHOWN ON FRAMING PLANS,
AT SMALL OPENINGS IN ROOF DECK FROM JOIST BOTTOM CHORDS.
11662-00
12/8/2011 4:08:14 PM

9 DETAIL 10 DETAIL 11 DETAIL 12 DETAIL


Sheet No.

S401 NO SCALE S401 NO SCALE S401 NO SCALE S401 NO SCALE


S401