Design of Sump Wall:

Pump pedestals

Platform

Columns 12m

16.8 m

Short Wall: Platform

Length of the short wall = 12 m

Total height of the wall including free board = 3.3 m

Ratio of Length of the wall to height of the wall = 12/3.3 = 3.64 >3

Long Wall:

Length of the long wall = 16.8 m

Total height of the wall including free board = 3.3 m

Ratio of Length of the wall to height of the wall = 16.8/3.3 = 5.09 >3

Both walls are designed for cantilever action,

Same design procedure is followed for short and long walls

case (i): Tank full and No earth pressure outside

Height of liquid at hydrotest condition = 3.3 m

liquid pressure at base = p= wb =(10.5 x 3.3) = 34.65 kN/m2

Max. Vertical bending moment at base = pb/6 = 34.65 x 3.3/6 = 62.89 kNm

Max. Shear force at base = pb/2 = 34.65 x 3.3/2 = 57.17 kN

Thickness of wall required as uncracked section for vertical BM =

= My x 6/(bt x b) = [(62.89x 6 x 1000000)/(1.8 x 1000)] = 458 mm

Provide wall thickness at base = 475 mm


PROJECT: DOCUMENT NO. DATE

TITLE DESIGNED CHECKED PAGE

Provide wall thickness at top = 175 mm

Area of steel required for vertical BM on liquid face at base:

Dia of bar = 16 mm

Clear cover = 50 mm

Effective depth (d) = 475 - 50 - 16/2 = 417 mm

Ast reqd = My/(stxjxd) = = (62.89x10^6)/(150 x0.872x417) = 1153.02 mm2/m

Min. Area of steel required on each face (0.08%) = 380 mm2/m

Provide 16 mm dia tor steel at spacing = 150 mm c/c

Area of steel provided = 1339.73 mm2/m

Percentage of steel provided = 0.32 %

Safe

Check for shear at Base:

Ref pg Max SF acting at the base of wall (Fy) = 57.17 kN/m

Max shear stress at the base of wall = 57.17 x 1000 /(1000 x417) = 0.14 N/mm2

Percentage of steel provided at the base of the wall = 0.32 %

Permissible shear stress from IS:456-2000 = 0.25 N/mm2

Safe
PROJECT: DOCUMENT NO. DATE

TITLE DESIGNED CHECKED PAGE

case (ii): Tank Empty and soil outside upto FGL:

a) Active earth pressure:

Height of soil outside the sump = 3m

Active Earth pressure at base = p = Kab = [(1/3) x 18 x 3] = 18 kN/m2

Vertical bending moment at base = pb/6 = 18 x 3/6 = 27 kNm

Shear force at base = pb/2 = 18 x 3/2 = 27 kN

b) Surcharge load:

Surcharge Pressure considered q= 10 kN/m2

Surcharge Pressure acting at the base of the wall = = 10 x 1/3 = 3.33 kN/m2

Vertical bending moment at base = pb/2 = 3.33 x 3/2 = 14.99 kNm

Shear force at base = pb = 3.33 x 3 = 9.99 kN

BM due to Soil pressure + Surcharge Pressure:

Maximum Vertical BM acting at the base of the wall causing tension

on the Soil face = 27 + 14.99 = 41.99 kN-m

Maximum shear force acting at the base of wall = 27 + 9.99 = 36.99 kN-m

Thickness of wall required as uncracked section for vertical BM =

= My x 6/(bt x b) = [(41.99x 6 x 1000000)/(1000 x 1.8)] = 374 mm

Provide over all uniform thickness = 475 mm

Area of steel required for vertical BM on soil face at base:

Dia of bar = 12 mm

Clear cover = 30 mm

Effective depth (d) = 475 - 30 - 12/2 = 439 mm


PROJECT: DOCUMENT NO. DATE

TITLE DESIGNED CHECKED PAGE

Ast reqd = My/(stxjxd) = = (41.99x10^6)/(190 x0.89x439) = 565.64 mm2/m

Min. Area of steel required on each face (0.08%) = 380 mm2/m

Provide 12 mm dia tor steel at spacing = 175 mm c/c

Area of steel provided = 645.94 mm2/m

Percentage of steel provided = 0.15 %

Safe

Check for shear:

Ref pg Max SF acting at the base of wall (Fy) = 36.99 kN/m

Max shear stress at the base of wall = 36.99 x 1000 /(1000 x439) = 0.08 N/mm2

Percentage of steel provided at the base of the wall = 0.15 %

Permissible shear stress from IS:456-2000 = 0.19 N/mm2

Safe

Distribution Steel Required:

Minimum area of steel required on each face = 380 mm2/m

Diameter of bar provided = 10 mm

Spacing of bar provided = 200 mm c/c


PROJECT: DOCUMENT NO. DATE

TITLE DESIGNED CHECKED PAGE


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Design of Strip Footing for Sump wall:

case (i): Liquid at Hydrotest condition and No Soil outside

Thickness of footing assumed = 0.35 m

Clear Cover Liquid face = 50 mm

Soil face = 40 mm

Thickness of screed = 0m

Total height of wall including free board = #NAME? m

Height of liquid inside the tank at Hydrotest condition = 3.3 m

Height of soil outside the tank = 0m

Net Safe Bearing Capacity of soil = 120 kN/m2

Thickness of wall at base = 475 mm

Thickness of wall at top = 175 mm

Projection of footing on soil side = 1 m

Projection of footing on liquid side = 1.5 m

Total width of footing provided = 2.975 m

Footing not in contact with soil = 0m

No soil outside Liquid at hydrotest

condition

0.35

A 1 0.475 1.5

2.975

1 2

#NAME? #NAME?

1 2
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

#NAME? #NAME?

Load acting on the strip footing per m run

Self weight of footing = 0.35 x 2.975 x 25 = W1 = 26.03 kN

Self weight of screed = 0 x 1.5 x 24 = W2 = 0 kN

#NAME? W3 = #NAME? kN

#NAME? W4 = #NAME? kN

Weight of liquid inside the tank = 3.3 x 1.5 x 10.5 = W5 = 51.975 kN

Total load acting on the strip footing W = P = #NAME? kN

Lever arm from A Restoring Moment about A

Footing x1 = 1.4875 m M1 = 38.72 kNm

Screed x2 = 0 m M2 = 0 kNm

Wall(Tri) x3 = 1.2 m M3 = #NAME? kNm

Wall(Rect) x4 = 1.3875 m M4 = #NAME? kNm

liquid x5 = 2.225 m M5 = 115.64 kNm

Restoring MomentMR = #NAME? kNm

Ref pg. Overturning Moment Mo = 62.89 + (57.17 x 0.35) = 82.9 kNm

#NAME? #NAME? #NAME? #NAME?

Resultant force will act at a distance of x' from A,

x' = #NAME? = #NAME? m

e = (b/2) - x' = #NAME? m

emax = b/6 = 2.975/6 = 0.496 m

#NAME? #NAME?

Max. pressure at the base of wall = (P/A+6Pe/b2) = #NAME? kN/m2

Min. pressure at the base of wall = (P/A - 6Pe/b2) = #NAME? kN/m2

#NAME?
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Pressure acting at the face of the wall:

1) Pressure acting at section 1-1 =

#NAME? #NAME? kN/m2

2) Pressure acting at section 2-2 =

#NAME? #NAME? kN/m2

BM acting at the face of support:

BM at section 2-2:

1) Due to liquid load acting on the footing = 3.3 x 10.5 x 1.5/2 = 38.98 kN-m/m

2) Due to self weight of screed = 0 x 24 x 1.5/2 = 0 kN-m/m

3) Due to self weight of footing = 0.35 x 25 x 1.5/2 = 9.84 kN-m/m

Ref pg. 4) Due to base pressure acting at the base of footing

#NAME? #NAME? kN-m/m

Resultant bending moment acting at sec 2-2 (causes tension on top

face of the footing) = #NAME? #NAME? kN-m/m

Shear force acting at section 2-2 =

1) Force due to liquid = = 3.3 x 10.5 x 1.5 = 51.98 kN/m

2) Force due to screed = = 0 x 24 x 1.5 = 0 kN/m

3) Force due to selfweight of footing = 0.35 x 25 x 1.5 = 13.13 kN/m

Ref pg. 4) Force due to base pressure =

#NAME? #NAME? kN/m

Resultant shear force acting at sec 2-2 #NAME? #NAME? kN/m

BM at section 1-1:

1) Due to self weight of footing = 0.35 x 25 x 1/2 = 4.38 kN-m/m

Ref pg. 2) Due to base pressure acting at the base of footing,

Rectangular Portion of pressure diagram #NAME? #NAME? kN-m/m


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Triangular Portion of pressure diagram,

#NAME? #NAME? kN-m/m

Resultant bending moment acting at sec 1-1 (causes tension on the

bottom face of the footing) #NAME? #NAME? kN-m/m

Shear force acting at section 1-1:

1) Force due to self weight of footing = 0.35 x 25 x 1 = 8.75 kN/m

Ref pg. 2) Force due to pressure acting at the base of footing,

Rectangular portion of base pressure #NAME? #NAME? kN/m

Triangular portion of base pressure #NAME? #NAME? kN/m

Resultant shear force acting at sec 1-1 #NAME? #NAME? kN/m

BM at sec 2-2 causes tension on top face of the footing,

Thickness of footing required as uncracked section

Ref pg. #NAME? #NAME? mm

Thickness of footing assumed at sec 2-2 = 350 mm

Effective depth of footing at sec 2-2 = 350-50-12/2 = 294 mm

Dia of bar provided = 12 mm

Area of tension steel required at sec 2-2 =

fig 4, IS:456 #NAME? #NAME? mm2/m

Provide 12 dia tor steel as top steel at a spacing = 100 mm c/c

Area of steel provided as top steel near sec 2-2 = 1130.4 mm2/m

Percentage of steel provided = 0.38 %

Minimum area of steel required for each face as per IS:3370,

= (0.183/100) x 350 x 1000/2 = 320.25 mm2/m

#NAME?

BM at sec 1-1 causes tension on bottom face of the footing

Ref pg. Thickness of footing required as uncracked section


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

#NAME? #NAME? mm

Thickness of footing assumed at sec 1-1 = 350 mm

Effective depth of footing at sec 1-1 = 350-40-12/2 = 304 mm

Dia of bar provided = 12 mm

Area of tension steel required at sec 1-1

#NAME? #NAME? mm2/m

Provide 12 dia tor steel as bottom steel at a spacing = #NAME? mm c/c

Area of tension steel provided as bottom tension steel near sec 1-1 = #NAME? mm2/m

Percentage of steel provided = #NAME? %

Minimum area of steel required on each face =

= 0.183/100x350x1000/2 = 320.25 mm2/m

#NAME?

Check for shear at sec 2-2:

Ref pg. Maximum shear stress #NAME? #NAME? N/mm2

Ref Pg. Percentage of steel provided at Sec 2-2 = 0.38 %

Permissible shear stress as per IS:456 = 0.27 N/mm2

#NAME?

Check for shear at sec 1-1:

Ref pg. Maximum shear stress #NAME? #NAME? N/mm2

Ref Pg. Percentage of steel provided at Sec 1-1 = #NAME? %

Permissible shear stress as per IS:456 = #NAME? N/mm2

#NAME?

Distribution Steel Required:

Minimum area of steel required on each face = 320.25 mm2/m

Diameter of bar provided = 10 mm

Spacing of bar provided = 200 mm c/c


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Design of Strip Footing for Sump wall:

case (ii): Tank Empty with soil outside upto FGL

Thickness of footing assumed = 0.35 m

Clear Cover Liquid face = 50 mm

Soil face = 40 mm

Thickness of screed = 0m

Total height of wall including free board = #NAME? m

Height of liquid inside the tank = 0m

Height of soil outside the tank above footing = 3m

Net Safe Bearing Capacity of soil = 120 kN/m2

Overall thickness of wall at base = 475 mm

Thickness of wall at top = 175 mm

Projection of footing on soil side = 1 m

Projection of footing on liquid side = 1.5 m

Total width of footing provided = 2.975 m

Footing not in contact with soil = 0m

Soil outside upto FGL Tank Empty


e

0.35

1 0.475 1.5 B

2.975

1 2

#NAME? #NAME?

1 2
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

#NAME? #NAME?

Load acting on the strip footing per m run

Self weight of footing = 0.35 x 2.975 x 25 = W1 = 26.03 kN

Self weight of screed = 0 x 1.5 x 24 = W2 = 0 kN

#NAME? W3 = #NAME? kN

#NAME? W4 = #NAME? kN

Wt. of soil outside the tank,

Triangular Portion = x 3 x (0.475-0.175) x 18 = W5 = 8.1 kN

Rectangular Portion = 3 x 1 x 18 = W6 = 54 kN

Total load acting on the strip footing W = P = #NAME? kN

Lever arm from B Restoring Moment about B

Footing x1 = 1.4875 m M1 = 38.72 kNm

Screed x2 = 0 m M2 = 0 kNm

Wall(Tri) x3 = 1.775 m M3 = #NAME? kNm

Wall(Rect) x4 = 1.5875 m M4 = #NAME? kNm

Soil-(Tri) x5 = 1.875 m M5 = 15.19 kNm

Soil-(Rect) x6 = 2.475 m M6 = 133.65 kNm

Restoring MomentMR = #NAME? kNm

Ref Pg. Overturning Moment Mo = 27+(27 x 0.35) = 36.45 kNm

#NAME? #NAME? #NAME? #NAME?

Resultant force will act at a distance of x' from B,

x' = #NAME? = #NAME? m

e = (b/2) - x' = #NAME? m

emax = b/6 = 2.975/6 = 0.496 m

#NAME? #NAME?

Min. pressure at the base of wall = (P/A+6Pe/b2) = #NAME? kN/m2


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Max. pressure at the base of wall = (P/A-6Pe/b2) = #NAME? kN/m2

#NAME?

Pressure acting at the face of the wall:

1) Pressure acting at section 1-1

#NAME? #NAME? kN/m2

2) Pressure acting at section 2-2

#NAME? #NAME? kN/m2

BM acting at the face of support:

BM at section 2-2:

1) Due to liquid load acting on the footing = 0 x 10.5 x 1.5/2 = 0 kN-m/m

2) Due to self weight of screed = 0 x 24 x 1.5/2 = 0 kN-m/m

3) Due to self weight of footing = 0.35 x 25 x 1.5/2 = 9.84 kN-m/m

Ref pg. 4) Due to base pressure acting at the base of footing =

#NAME? #NAME? kN-m/m

Resultant bending moment acting at sec 2-2 (causes tension on

bottom face of the footing) #NAME? #NAME? kN-m/m

Shear force acting at section 2-2 =

1) Force due to liquid = 0 x 10.5 x 1.5 = 0 kN/m

2) Force due to screed = 0 x 24 x 1.5 = 0 kN/m

3) Force due to selfweight of footing = 0.35 x 25 x 1.5 = 13.13 kN/m

Ref pg. 4) Force due to base pressure =

#NAME? #NAME? kN/m

Shear force acting at sec 2-2 #NAME? #NAME? kN/m

BM at section 1-1:
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

1) Due to self weight of footing = 0.35 x 25 x 1/2= 4.38 kN-m/m

2) Due to soil load acting on the footing = 3 x 1 x 18 x 1/2 = 27 kN-m/m

Ref pg. 3) Due to base pressure acting at the base of footing =


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Rectangular Portion of pressure diagram #NAME? #NAME? kN-m/m

Triangular Portion of pressure diagram

#NAME? #NAME? kN-m/m

Resultant bending moment acting at sec 1-1 (causes tension on the

top face of the footing) #NAME? #NAME? kN-m/m

Shear force acting at section 1-1:

1) Force due to self weight of footing = 0.35 x 25 x 1 = 8.75 kN/m

2) Force due to soil acting on top of footing = 3 x 18 x 1 = 54 kN/m

Ref pg. 3) Force due to pressure acting at the base of footing:

Rectangular portion of base pressure #NAME? #NAME? kN/m

Triangular portion of base pressure #NAME? #NAME? kN/m

Resultant SF acting at sec 1-1 #NAME? #NAME? kN/m

BM at sec 2-2 causes tension on bottom face of the footing:

Thickness of footing required as uncracked section

Ref pg. #NAME? #NAME? mm

Thickness of footing assumed at sec 2-2 = 350 mm

Effective depth of footing at sec 2-2 = 350-40-12/2 = 304 mm

Dia of bar provided = 12 mm

Area of tension steel required at sec 2-2

fig 4, IS:456 Ast #NAME? #NAME? mm2/m

Provide 12 dia tor steel as bottom steel at a spacing = #NAME? mm c/c

Area of steel provided as bottom steel near sec 2-2 = #NAME? mm2/m

Percentage of steel provided = #NAME? %

Minimum area of steel required for each face as per IS:3370,

= (0.183/100) x 350 x 1000/2 = 320.25 mm2/m


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

#NAME?
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

BM at sec 1-1 causes tension on top face of the footing

Ref pg. Thickness of footing required as uncracked section

#NAME? #NAME? mm

Thickness of footing assumed at sec 1-1 = 350 mm

Effective depth of footing at sec 1-1 = 350-50-12/2 = 294 mm

Dia of bar provided = 12 mm

Area of tension steel required at sec 1-1

#NAME? #NAME? mm2/m

Provide 12 dia tor steel as top steel at a spacing = #NAME? mm c/c

Area of tension steel provided as top tension steel near sec 1-1 = #NAME? mm2/m

Percentage of steel provided = #NAME? %

Minimum area of steel required on each face =

= 0.183/100x350x1000/2 = 320.25 mm2/m

#NAME?

Check for shear at sec 2-2:

Ref pg. Maximum shear stress #NAME? #NAME? N/mm2

Ref Pg. Percentage of steel provided at Sec 2-2 = #NAME? %

Permissible shear stress as per IS:456 = #NAME? N/mm2

#NAME?

Check for shear at sec 1-1:

Ref pg. Maximum shear stress #NAME? #NAME? N/mm2

Ref Pg. Percentage of steel provided at Sec 1-1 = #NAME? %

Permissible shear stress as per IS:456 = #NAME? N/mm2

#NAME?

Distribution Steel Required:

Minimum area of steel required on each face = 320.25 mm2/m

Diameter of bar provided = 10 mm


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE:

Spacing of bar provided = 200 mm


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
Design of Strip Footing for Sump wall:

case (iii): Liquid upto TWL with soil outside upto FGL

Thickness of footing assumed = 0.35 m

Clear Cover Liquid face = 50 mm

Soil face = 40 mm

Thickness of screed = 0m

Total height of wall including free board = #NAME? m

Ht. of liquid inside the tank at working condition (TWL) = 1.8 m

Height of soil outside the tank above footing = 3m

Net Safe Bearing Capacity of soil = 120 kN/m2

Overall thickness of wall at base = 475 mm

Thickness of wall at top = 175 mm

Projection of footing on soil side = 1 m

Projection of footing on liquid side = 1.5 m

Total width of footing provided = 2.975 m

Footing not in contact with soil = 0m

Soil outside upto FGL Liquid at TWL


e

0.35

1 0.475 C
1.5

2.975

1 2

#NAME? #NAME?

1 2
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
#NAME? #NAME?
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
Load acting on the strip footing per m run

Self weight of footing = 0.35 x 2.975 x 25 = W1 = 26.03 kN

#NAME? W2 = #NAME? kN

#NAME? W3 = #NAME? kN

Wt. of soil outside the tank,

Triangular Portion = x (0.475-0.175) x 3 x 18 = W4 = 8.1 kN

Rectangular Portion = 1 x 3 x 18 = W5 = 54 kN

Wt. of liquid inside the tank = 1.5 x 1.8 x 10.5 = W6 = 28.35 kN

Self weight of screed = 0 x 1.5 x 24 = W7 = 0 kN

Total load acting on the strip footing W = P = #NAME? kN

Lever arm from C Restoring Moment about C

Footing x1 = 1.4875 m M1 = 38.72 kNm

Wall(Tri) x2 = 1.775 m M2 = #NAME? kNm

Wall(Rect) x3 = 1.5875 m M3 = #NAME? kNm

Soil-(Tri) x4 = 1.875 m M4 = 15.19 kNm

Soil-(Rect) x5 = 2.475 m M5 = 133.65 kNm

liquid x6 = 0.75 m M6 = 21.26 kNm

Screed x7 = 0 m M7 = 0 kNm

Restoring MomentMR = #NAME? kNm

liquid pressure at base at working condition p = wb =(10 x 1.8) = 18 kN/m2

Max. Vertical bending moment at base = pb/6 = 18 x 1.8/6 = 9.72 kNm

Max. Shear force at base = pb/2 = 18 x 1.8/2 = 16.2 kN

Ref Pg. Overturning Moment Mo = (27-9.72) + ((27-16.2) x 0.35) = 21.06 kNm

FOS against Overturning=MR/Mo #NAME? #NAME? #NAME?


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
Resultant force will act at a distance of x' from C,
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
x' = #NAME? = #NAME? m

e = (b/2) - x' = #NAME? m

emax = b/6 = 2.975/6 = 0.496 m

#NAME? #NAME?

Min. pressure at the base of wall = (P/A+6Pe/b2) = #NAME? kN/m2

Max. pressure at the base of wall = (P/A-6Pe/b2) = #NAME? kN/m2

#NAME?

Pressure acting at the face of the wall:

1) Pressure acting at section 1-1 =

#NAME? #NAME? kN/m2

2) Pressure acting at section 2-2 =

#NAME? #NAME? kN/m2

BM acting at the face of support:

BM at section 2-2:

1) Due to liquid load acting on the footing = 1.8 x 10.5 x 1.5/2 = 21.26 kN-m/m

2) Due to self weight of screed = 0 x 24 x 1.5/2 = 0 kN-m/m

3) Due to self weight of footing = 0.35 x 25 x 1.5/2 = 9.84 kN-m/m

Ref pg. 4) Due to base pressure acting at the base of footing

#NAME? #NAME? kN-m/m

Resultant bending moment acting at sec 2-2 (causes tension on

bottom face of the footing) = #NAME? #NAME? kN-m/m

Shear force acting at section 2-2 =

1) Force due to liquid = 1.8 x 10.5 x 1.5 = 28.35 kN/m

2) Force due to screed = 0 x 1.5 x 24 = 0 kN/m

3) Force due to selfweight of footing = 0.35 x 25 x 1.5 = 13.13 kN/m


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
Ref pg. 4) Force due to base pressure =

#NAME? #NAME? kN/m

Shear force acting at sec 2-2 #NAME? #NAME? kN/m

BM at section 1-1:

1) Due to self weight of footing = 0.35 x 25 x 1/2= 4.38 kN-m/m

2) Due to soil load acting on the footing = 3 x 18 x 1/2 = 27 kN-m/m

Ref pg. 3) Due to base pressure acting at the base of footing,

Rectangular Portion of pressure diagram #NAME? #NAME? kN-m/m

Triangular Portion of pressure diagram

#NAME? #NAME? kN-m/m

Resultant bending moment acting at sec 1-1 (causes tension on the

top face of the footing) #NAME? #NAME? kN-m/m

Shear force acting at section 1-1:

1) Force due to self weight of footing = 0.35 x 25 x 1 = 8.75 kN/m

2) Force due to soil acting on top of footing = 3 x 18 x 1 = 54 kN/m

Ref pg. 3) Force due to pressure acting at the base of footing,

Rectangular portion of base pressure #NAME? #NAME? kN/m

Triangular portion of base pressure #NAME? #NAME? kN/m

Resultant shear force acting at sec 1-1 #NAME? #NAME? kN/m

BM at sec 2-2 causes tension on bottom face of the footing

Thickness of footing required as uncracked section

Ref pg. #NAME? #NAME? mm

Thickness of footing assumed at sec 2-2 350 mm

Effective depth of footing at sec 2-2 = 350 - 40 - 12/2 = 304 mm


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
Dia of bar provided = 12 mm

Area of tension steel required at sec 2-2 =

fig 4, IS:456 #NAME? #NAME? mm2/m

Provide 12 dia tor steel as bottom steel at a spacing = #NAME? mm c/c

Area of steel provided as bottom steel near sec 2-2 = #NAME? mm2/m

Percentage of steel provided = #NAME? %

Minimum area of steel required for each face as per IS:3370,

= (0.183/100) x 350 x 1000/2 = 320.25 mm2/m

#NAME?

BM at sec 1-1 causes tension on top face of the footing

Ref pg. Thickness of footing required as uncracked section

#NAME? #NAME? mm

Thickness of footing assumed at sec 1-1 = 350 mm

Effective depth of footing at sec 1-1 = 350 - 50 - 12/2 = 294 mm

Dia of bar provided = 12 mm

Area of tension steel required at sec 1-1 =

#NAME? #NAME? mm2/m

Provide 12 dia tor steel as top steel at a spacing = #NAME? mm c/c

Area of tension steel provided as top tension steel near sec 1-1 = #NAME? mm2/m

Percentage of steel provided = #NAME? %

Min. area of steel reqd. on each face = 0.183/100 x 350 x 1000/2 = 320.25 mm2/m

#NAME?

Check for shear at sec 2-2:

Ref pg. Maximum shear stress #NAME? #NAME? N/mm2

Ref Pg. Percentage of steel provided at Sec 2-2 = #NAME? %

Permissible shear stress as per IS:456 = #NAME? N/mm2

#NAME?
PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
Check for shear at sec 1-1:

Ref pg. Maximum shear stress #NAME? #NAME? N/mm2

Ref Pg. Percentage of steel provided at Sec 1-1 = #NAME? %

Permissible shear stress as per IS:456 = #NAME? N/mm2

#NAME?

Distribution Steel Required:

Minimum area of steel required on each face = 320.25 mm2/m

Diameter of bar provided = 10 mm

Spacing of bar provided = 200 mm c/c


PROJECT: DOCUMENT NO. DATE
02-Mar-2017
DESIGNED CHECKED PAGE
STRUCTURE: NP
PROJECT: DOCUMENT NO. DATE
25-Jul-2005
TITLE DESIGNED CHECKED PAGE
NP
Design of Platform Slab:

2.469 2.469

Beam B3
B1 B4
3.688 m

1.234 Columns

Beam B2

Assuming thickness of slab = 150 mm

Long span 3.75+(0.175/2)-(0.3/2) = 3.688 m

Short span = 1.234 m

Floor Load:

Self wt. of slab = 0.15 x 25 = = 3.75 kN/m2

Live load = 5 kN/m2

Total Load = 8.75 kN/m2

8.75kN/m

1.234 1.234 1.234 1.234

Analysing as a continuous slab,

Ref IS: 456 Max. Bending Moment = (8.75 x 1.234/10) = 1.33 kNm

Thickness of slab required for Max. BM = M x 6/(bt x b)

= [(1.33x 6 x 1000000)/(1000 x 1.8)] = 67 mm

Provide overall slab thickness = 150 mm


PROJECT: DOCUMENT NO. DATE
25-Jul-2005
TITLE DESIGNED CHECKED PAGE
NP
Safe
PROJECT: DOCUMENT NO. DATE
25-Jul-2005
TITLE DESIGNED CHECKED PAGE
NP
Area of steel required:

Dia of bar = 8 mm

Clear cover = 50 mm

Effective depth (d) = 150 - 50 - 8/2 = 96 mm

Ast required = M/(st x j x d) = 1.33x10^6/(150x0.872x96) = 105.92 mm2/m

Min. Area of steel required (0.23%) = 345 mm2/m

Provide 8 mm dia tor steel at spacing = 125 mm c/c

Area of steel provided = 401.92 mm2/m

Percentage of steel provided = 0.42 %

Safe

Distribution Steel Required:

Minimum area of steel required = 345 mm2/m

Diameter of bar provided = 8 mm

Spacing of bar provided = 125 mm c/c

Provide Y8 @ 125 c/c bothways at top and bottom


PROJECT: DOCUMENT NO. DATE
25-Jul-2005
TITLE DESIGNED CHECKED PAGE
NP
PROJECT: DOCUMENT NO. DATE
25-Jul-2005
TITLE DESIGNED CHECKED PAGE
NP

Check for Tension in Grade Slab:

Assume thickness of Slab d= 150 mm

Clear cover Liquid face = 50 mm

Soil face = 30 mm

Ref Pg. Max. Tension in grade slab due to wall when tank is full T= 57.17 kN/m

Thickness of slab required for T = (57.17 x 1000)/(1.3 x 1000) = 44 mm

Safe

Area of steel required:

Ast required along walls due to T = T/2t = 190.57 mm2

Dia of bar = 8 mm

Effective depth (d) = 150-50-8/2 = 96 mm

Min. Area of steel required on each face (0.23%) = 172.5 mm2/m

Provide 8 mm dia tor steel at spacing = 200 mm c/c

Area of steel provided = 251.2 mm2/m

Percentage of steel provided = 0.26 %

Provide Y8 @ 200 mm c/c in both the directions at top and bottom