Modern electrical switching plants ZIEHL SW-type voltage monitors are used to monitor
for power generation and distri- the mains voltage in DC, AC and 3-phase networks for
bution, for tooling and finishing under- and/or overvoltage. In the case of deviation of
machinery and a number of other the rated voltage the plant must be switched off or the
drives, are generally equipped operator should be warned by an optical or acoustic
with control devices. The use of signal.
such instruments, however, also
requires that the mains voltage Special applications where the SW device can be used
differs only slightly from its no- are in building machinery, hoisting plant, escalators and
minal value, as otherwise the re- travelling staircases, cranes , tooling machinery of all
quired accuracy of the measuring kinds, switching frequency motors and motors with high
2
results or control commands will starting and braking times, as well as emergency plant
not be achieved, or downstream and electronic devices.
devices may be destroyed by
overvoltage. The following table provides a summary of the different
models of the ZIEHL-voltage monitors.
Summary
Function
Monitoring of
- Undervoltage - X X X X X X
- Overvoltage X X - X X X -
Switching point adjustable Scale digital - digital digital digital -
Relay output 1 U 2 U 2 U 2 U 2 U 2 U 1U
Housing V 2 V 4 V 2 V 4 V 6 V 6 K
Other devices for monitoring of voltage AC/DC you can find at chapter MINIPAN Digital Panelmeters. The Limit-Value-Switch
TR210 monitors voltages of DC 0 - 10 V.
Function and Features When the mains voltage turns on, Single-phase instruments measure phase against N
the integrated relay closes if the (the single-phase measuring principle). 3-phase cur-
voltage values in the mains to be rent instruments monitor the voltage phase against
monitored do not fall short or are phase.
exceeded. The relay releases if
the set limit value falls short. The Upon request the instruments can also be equipped
instruments with overvoltage with measurement phase against N.
monitoring switch off if their up-
per limit is exceeded. According These instruments operate with high reliability - even
to the switching hysteresis, the in mains with high interference voltage superimposition
switchback points are closer to - by using integrated overvoltage protection against
the rated voltage than to switch voltage peaks.
off points (see electr. Data).
ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de 73
Voltage Monitoring Type SW
.com
12090-1201-00
Ie = 2 A
mA / 2-10 V Stromrelais 60 80
AC 15
0.1... 10 s doff
3 10 s
(2/4) (no)
Output relay 1 change-over 0,1
Technical Data Rated supply voltage Us AC/DC 24 - 240 V, 0/50/60 Hz, < 2W, < 3VA
(DC 20,4 - 297 V, AC 20 - 264 V)
Function Maximum
Measurement inputs DC 0/4 ... 20 mA, 20
DC 0...10 V, 63 k
Switch point/limit adjustable 0...100%
Hysteresis adjustable 5...30% of set value
Adjustment error < 10% of span
Repeatability < 0,2%
Temperature influence 0,05 %/K
On-delay don adjustable 0,1...10 sec.
Response-delay doff adjustable 0,1...10 sec.
74 ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de
Voltage Monitoring Type SW
SW31V Modern electrical switchgear for measurements or the actuating signal is not attained,
energy generation and distributi- or downstream units are destroyed by overvoltage.
on, for treatment and processing
machines and for a variety of SW series voltage monitors from ZIEHL are used to
other drives are usually equipped monitor the mains voltage in direct, alternating and
with measuring and control- three-phase current networks for undervoltage and/or
engineering devices. overvoltage. If the nominal voltage deviates by various
However, the use of such devices values which, depending on the consumer, are not
demands that the supplied mains allowed to be undercut, the involved system needs to
voltage deviates only slightly from be disconnected, or at least the operator needs to be
the nominal value as otherwise optically or acoustically warned.
the required accuracy of the
2
When the mains voltage is ap- Features:
plied, the integrated relay picks Monitoring three-phase current networks 3 AC 400 V
up if the voltage value preset with neutral conductor
for the network to be monitored Monitoring alternating current networks AC 230 V
is not undercut. If the set limit is (connect inputs L1/2/3)
undercut, the relay releases. Monitoring own power supply
Type SW voltage monitors com- Switching point fixed 80 %
ply with Class III acc. VDE 0435 Output relay 2 change-over contacts
Part 303, Para. 4.8.2, for static Panel mounted housing, 35 mm wide
measuring relays (SMR).
Order-number: S222281
Undervoltage monitors () for
three-phase current networks K11
L1
with N and alternating voltage K12
L2
networks. The switching point lies K13
L3
at approx. 80% UNom. Hysteresis K14
is approx. 5%. The voltages of the N
3 phases are measured against L1 N L2 L3
ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition May 2012 75
Voltage Monitoring Type SW
SW 32 V The voltage-relay SW32V is a The digital display shows the measured value as well
high-grade voltage monitor with as it helps setting the limits, switching-delays and
a wide measuring-range for mo- switching functions.
nitoring DC-, AC- and 3-phase
voltages for over- and/or under- Application:
voltage. As voltage monitor in equipment for generation or
In 3-phase power networks phase- ditribution of electric energy, especially in photovoltaic
symmetry and phase-sequence plants and block heating stations,
can also be monitored. Monitoring of voltage in machines and plants to protect
The limits are set in Volts. Thus them from damage caused by failure or deviation of
the device can be used at different voltage.
nominal voltages.
settings SW32V
codelock against manipulation Spannungs- U
Up /
of settings relais
Err8 = limit error, high < low
Err9 = parameter error Max
locked
Reset
70 mm wide, height 55 mm N(-) NC L1(+) NC L2 NC L3
2s
Display: L1
3 digit display for measured L2
values and settings
MIN/MAX-values of measured
L3
voltages N
4 LEDs for alarm
4 LEDs for displayed inputs L1
2 LEDs for states or relays N
resolution <100V: 0,1V
76 ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition May 2012
Voltage Monitoring Type SW
Power Supply Rated supply voltage Us AC/DC 24-270 V, 0/45...100 Hz, <5VA
DC: 20,4...297 V, AC: 20,4...297 V
Measuring time DC
40...100 Hz
DC average over 50 ms
2
Measuring time AC < 50 ms
Measuring accuracy DC >100V: 0,5% of value 1 Digit
<100V: 0,5% of value 5 Digit (res. 0,1V)
Measuring accuracy AC with N >100V: 0,8% of value 1Digit
<100V: 0,8% of value 5Digit (res. 0,1V)
without N >100V: 1,0% of value 1Digit
<100V: 1,0% of value 5Digit (res. 0,1V)
Test Conditions
Rated impulse voltage EN 50178 / EN 60 664-1
Overvoltage catagory 6000 V
Rated Insulation voltage III
Contamination level AC 690 V
On-period 2
Rated ambient temp. range 100 %
Interference resistance -20 C...+55 C EN 60 068-2-1 dry heat
Interference transmission EN 61 000-6-2
EN 61 000-6-4
Housing
Design V4
Dimensions (h x w x d) 90 x 70 x 58 mm, mounting height 55 mm
Protection housing IP 30
Protection terminals IP20
Attachment DIN-rail 35 mm or screws M4
Weight app. 200 g
ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition Aug 2011 77
Voltage Monitoring Type SW
UFR1001 The voltage- and frequency-relay Monitoring of over- and undervoltage 40520 V
UFR1001 monitors voltage and monitoring of over- and underfrequency 4565 Hz
frequency in two- or three-phase monitoring of quality of voltage (10-minutes-average)
networks with or without neutral monitoring of vector-shift 220 , 1 or 3-phase
and switches off rapidly when Switching-delay adjustable <0,0560,0 s
required. Switching-back-delay adjustable 01000 s
The device can be easily adapted Alarm-counter for up to 100 alarms (with measured
to the requirements of the carrier value and reason)
of the power network. Added time of alarm up to 999 hours. Displays the
With the integrated vector-step time, alarms have been active (while supply voltage
relay it can also monitor networks applied only)
at synchronous generators. LEDs for alarms, allocation of values and states of
After selecting a basic program, relays
for each relay limits can be 2 output-relays, each for monitoring frequency and/
programmed for over-/undervol- or voltage
tage and over-/underfrequency. function of relays (nc- or no -operating mode) pro-
In programs with vector-step- grammable
monitoring, K2 is used for vector- interlocked switching or autoreset
step only. input for Enable / Reset
Applications are monitoring easy programming by help of basic programs
power-networks at great solar- Sealing of settings is possible
plants, in block power heating code-lock against manipulation of settings
stations, also with synchronous universal power-supply AC/DC 24-240 V
generators (vector shift) or ge- housing for DIN-rail-mount, 70 mm wide, mounting
nerally monitoring the quality in height 66 mm
power networks at machines or
power-supplies.
Order-number: S222295
78 ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition May 2012
Voltage Monitoring Type SW
Power supply Rated supply voltage Us AC/DC 24-270 V, 0/45...65 Hz, <5VA
DC: 20,4...297 V, AC: 20,4...297 V
Housing Design V4
Dimensions (h x w x d) 90 x 70 x 58 mm, mounting height 66 mm
Protection housing IP 30
Protection terminals IP20
Attachment DIN-rail 35 mm or screws M4
Weight app. 200 g
ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition May 2012 79
Voltage Monitoring Type SW
UFR1001E The UFR1001E monitors voltage Monitoring of under- and overvoltage 15-520 V
and frequency in plants for own Measuring phase-neutral or phase-phase
generation of electricity. It fulfills Monitoring of under- and overfrequency 45-65 Hz
the requirements of VDE-AR-N Monitoring of quality of voltage (10-minutes-
4105 for generators connected average)
to the low-voltage and the direc- Monitoring of vector shift 220
tive bdew 2008 for the medium- Monitoring of rate of change of frequency (ROCOF,
voltage distribution network. df/dt)
Monitoring of feedback contacts One-fault-proof with monitoring of connected swit-
can be suppressed during shutoff ches (defeatable), 2 automatic restarts at error
and syncronisation. Passive detection of insular grid acc. to ch. 6.5.3
The UFR1001E is a dual-channel and app. D2
device and thus one-fault-proof. Support of synchronisation of generators
Input-circuit, A/D-converter, pro- Selftest
Certificate Grid- and Plant
cessor and output-relay are Switching delay adjustable 0,05 130 s
Protection acc. to doubly present. The processors Switching-back-delay adjustable 0 999 s
VDE-AR-N 4105 control each other. The function Switching-back-delay at alarms <3 s: 5 s
of the output-relays and of the Preset values acc. to VDE-AR-N 4105 and bdew-
Certificate medium volta- connected switches can be mo- directive
ge acc. to bdew-directive nitored with feed-back contacts. Alarm-counter for 100 alarms with value, reason
At an alarm the device switches and elapsed time
off and the reason is displayed Recording of added time of alarms
with LEDs and signaled with Input for standby with counter and recording of
transistor-outputs. time
The limits are pre-set according Test-button and simulation with measuring of
to VDE-AR-N 4105. They can switching-times
be changed if required and be LEDs for alarms. Allocation of values and states
protected with a code and/or a of relays
seal. Sealing. All values can be read-out when sealed
An alarm-counter stores the Easy installation and programming with 6 pre-set
last 100 alarms with reason and programs
elapsed time. In addition the time Outputs for reporting of alarms to superior control
the UFR1001E has interrupted Supply-voltage AC/DC 24-270 V
the plant is recorded. All values Housing for DIN-rail-mount, 105 mm wide, mounting
can be read-out with the inte- height 66 mm
grated display and give the ope-
rator valuable information about Medium voltage:
the availability of the plant.
Kurzbezeichnung: Bezeichnung: 2 x 2 alarms for voltage and frequency (U>>, U>,
UFR1001E Spannungs- und Frequenzrelais
With a test-button the function
bearbeitet: 18.06.12 Ba/Fz
of U<, U<<, F>>, F>, F<, F<<) Mastab: - Ers. fr: 12420-0900-07 Zeichnung
DC27V/20mA
6) 2)
Enable /
Standby
4) 5)
6A 1)
L1
L2
PV
L3
N
3)
80 ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition Sept. 2013
Voltage Monitoring Type SW
Power supply Rated supply voltage Us AC/DC 24-270 V, 0/45...65 Hz, <5VA
DC: 20,4...297 V, AC: 20,4...297 V
EN 60255
Test Conditions Rated impulse voltage 4000 V
Overvoltage category III
Rated Insulation voltage 2
Contamination level 300 V
Isolation material group II
ON-period 100 %
Rated ambient temp. range -20 C...+55 C EN 60 068-2-2 dry heat
Interference resistance EN 61 000-6-2
Interference transmission EN 61 000-6-4
Housing Design V6
Dimensions (h x w x d) 90 x 105 x 69 mm, mounting height 66 mm
Protection housing IP30
Protection terminals IP20
Attachment DIN-rail 35 mm according to EN 60 715 or screws M4
Weight ca. 250 g
ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de Edition Sept. 2013 81
Voltage Monitoring Type SW
SPI1021 The SPI1021 monitors voltage When the device has been installed, a self-test starts
and frequency in plants for own automatically. The self-test can be repeated when
generation of electricity. It fulfills required. All values of the test are stored and can be
the requirements of CEI 0-21. read out at the display.
3 selectable programs allow Monitoring of under- and overvoltage 15-520 V
measuring 3 phases to neutral Measuring of 3 phase with or without neutral or
(4-wire mode), 3 phases phase- single phase
phase (3-wire mode) and single Monitoring of over- and underfrequency 45-65 Hz
phase to neutral (2-wire). Monitoring of quality of voltage (10-minutes-
The SPI1021 can monitor all de- average)
centralized power, photovoltaic, Monitoring of vector-shift (connectible)
wind or thermal plants, that feed Input IN2 for selection of frequency window
in the low voltage and medium Input In3 for selection of mode transitory or defi-
voltage grid. In applications with nitive
Dichiarazione die confomit
possible asymmetry >6 kVA, Input Y0/Y1 for monitoring function of connected
alle prescrizioni alla Norma power balance has to be moni- switch (automatic detection of nc/no)
CEI 0-21. Accreditamento a tored extra. Relay K2 picks up (on time <500 ms) only at failure
DAkkS, D-ZE-12024-01-01, at switch connected to K1
Rif. DIN EN 45011
All limits are preset according to 2 restarts at switch-on error of connected switch
CEI 0-21. They can be changed Selftest with storing of values
if required and be protected with Switching delays adjustable 0,05130 s
a code and/or a seal. Switching-back-delays adjustable 0999 s
A counter for alarms and standbys Different switching time according to type of alarm
stores the last 100 events with and selected mode
reason and elapsed time. In ad- Switch-on delay 300 s (adjustable)
dition the time the SPI1021 has All parameters preset according to CEI 0-21
interrupted the plant is recorded. Alarm counter for 100 alarms with value. Reason
All values can be displayed at and elapsed time
the device and give the operator Recording of added time of alarms
valuable information about the Input for standby (off time <50ms) with counter and
availability of the plant. recording of time
The standby input allows a remote Simulation for testing
shutoff e.g. with a RCR. It can also Sealing, all parameters can be read out while
be used to switch to an energy sealed
saving mode by a timer or a twi- Easy installation and programming with 3 preset
light switch. Number of standbys programs
and added time are stored and Supply-voltage AC/DC 24-270 V
can be read in the display. Housing for DIN-rail-mount, 105 mm wide, mounting
height 70 mm
Order-Number: S222300
82 ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de
Voltage Monitoring Type SW
Power supply Rated supply voltage Us AC/DC 24-270 V, 0/40...70 Hz, <5VA
DC: 20,4...297 V, AC: 20,4...297 V
Hysteresis
Measurement accuracy (with
adjustable1,0...99,9 V
0,6% of measured value
2
neutral)
Measurement accuracy (without 0,8% of measured value
neutral)
Accuracy of display >100V: 1 digit (resolution 1 V)
<100V: 1 digit (resolution 0,1 V)
Measurement functions 3-phase with / without neutral, single phase
Switching-delay (dAL) adjustable 0,05 ( 15ms)...130,0 s
Switching-back-delay (doF) adjustable 0 (= 40ms)...999 s
Housing Design V6
Dimensions (h x w x d) 90 x 105 x 69 mm, mounting height 70 mm
Wiring connection single strand 1 x 4 mm2
Finely stranded with wire end 1 x 2,5 mm2
ferule
Protection housing IP30
Protection terminals IP20
Attachment DIN-rail 35 mm according to EN 60 715 or screws M4
Weight ca. 250 g
ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de 83
Voltage Monitoring Type SW
Application:
Monitoring of three-phase net-
works on loss of a phase
monitoring of fuses
84 ZIEHL industrie-elektronik, D-74523 Schwbisch Hall, Tel. +49 791 504-0, info@ziehl.de, www.ziehl.de