CALCULATION SHEET

FIRE WATER DEMAND

JOB NO. : INL/SPJ/02/2016


FIRE ZONE : Fire Zone 12 (FZ-12)
PREP'D : ADT
PROJECT : PROYEK PEMBANGUNAN PABRIK MINYAK GORENG KAPASITAS 600.000 Ton CPO/Tahun CHK'D : ABI
APP'D : IS
CLIENT : PT. INDUSTRI NABATI LESTARI REV : 1
DATE : 22-Feb-17

1. TPS LIMBAH B3
Sprinkler Quantity per Area
Floor Area : 144 m2
Sprinkler spacing (maximum) : 4.6 m
Sprinkler spacing (minimum) : 1.83 m
Protection Area : 20.9 m2
Sprinkler quantity (minimum) : 7
Sprinkler quantity / branch line : 4
Distance from Sprinkler to wall (Maximum) : 2.3 meter
Distance from Sprinkler to wall (Minimum) : 0.1 meter

2.3 m

2.5 m
2.3 m 4m

2.3 m
2.3 m

Minimum Flow & Pressure per Sprinkler


Sprinkler distance along the wall (maximum) (S) : 2.5 m
Sprinkler distance across the room (maximum) (L) : 4 m
Protection area of coverage per sprinkler (As) : 40 m2
Density / Application Rate : 4.10 L/min/m2
Minimum Flow per Sprinkler (Q) : 164.00 L/min
K-Factor : 80.6 L/min/bar1/2
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 4.1 bar
Sprinkler Quantity : 8
Total Flow : 1312 L/min
2. BOILER ROOM
Sprinkler Quantity per Area
A. Part A (Boiler)
2
Floor Area : 26 m
Sprinkler spacing (maximum) : 4.6 m
Sprinkler spacing (minimum) : 1.83 m
Protection Area : 20.9 m2
Sprinkler quantity (minimum) : 2
Sprinkler quantity / branch line : 2
Distance from Sprinkler to wall (Maximum) : 2.3 meter
Distance from Sprinkler to wall (Minimum) : 0.1 meter

B. Part B (Boiler)

4.6 m 4.6 m

4.6 m 4.6 m
Minimum Flow & Pressure per Sprinkler
A. Part A (Boiler)
Sprinkler distance along the wall (maximum) (S) : 4.6 m
Sprinkler distance across the room (maximum) (L) : 1.75 m
Protection area of coverage per sprinkler (As) : 32.2 m2
Density / Application Rate : 4.10 L/min/m2
Minimum Flow per Sprinkler (Q) : 132.02 L/min
1/2
K-Factor : 80.6 L/min/bar
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 2.7 bar
Sprinkler Quantity : 2
Total Flow : 264 L/min

Assumed pipe length from pipe rack to boiler : 8m


Sprinkler spacing (maximum) : 4.6 m
Sprinkler Quantity Required : 2

Total Sprinkler Required : 4

B. Part B (Boiler)
Sprinkler distance along the wall (maximum) (S) : 4.6 m
Sprinkler distance across the room (maximum) (L) : 1.75 m
2
Protection area of coverage per sprinkler (As) : 32.2 m
Density / Application Rate : 4.10 L/min/m2
Minimum Flow per Sprinkler (Q) : 132.02 L/min
K-Factor : 80.6 L/min/bar1/2
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 2.7 bar
Sprinkler Quantity : 2
Total Flow : 264 L/min

Assumed pipe length from pipe rack to boiler : 8m


Sprinkler spacing (maximum) : 4.6 m
Sprinkler Quantity Required : 2

Total Sprinkler Required : 4

3. HYDRANT / MONITOR / HYDRANT BOX


Available hydrant, hydrant box or monitor:
Tag Equipment
HB-08 Hydrant Box : 378.5 L/min/hose NFPA 14 Section 7.10.1.1.1
WH-08 Pillar Hydrant (Outside of the building) : 946.4 L/min/hose NFPA 14 Section 7.10.1.1.1
WH-07 Pillar Hydrant (Outside of the building) : 946.4 L/min/hose NFPA 14 Section 7.10.1.1.1

4. SUMMARY
Scenario 1: TPS Limbah B3 on fire
Sprinkler system : 1312 L/min
Hydrant Box HB-08 : 379 L/min
Total Fire Water Requirement 1691 L/min

Scenario 2: TPS Limbah B3 fire escalate


Pillar Hydrant WH-07 : 946 L/min
Pillar Hydrant WH-08 : 946 L/min
Total Fire Water Requirement 1893 L/min

Sprinkler Nozzle Head Quantity


TPS Limbah : 8