PSSSINCAL

Protection

Protection Simulation for Electrical Trans- Initially, all values are calculated for the first
mission and Distribution Networks zones, then for all the second zones, and finally
PSSSINCAL offers a wide range of procedures for all the third zones. Protection device set-
for the complex field of protecting or examining tings can be varied interactively on the screen
electrical transmission and distribution net- and customized with ease.
works. PSSSINCAL provides the results as grading

PSS SINCAL provides the following proce- diagrams drawn to scale and a table with set-
dures: tings for each protection device.

Distance Protection Setting Since there are different concepts or philoso-


phies for setting protection devices, you need to
Protection Simulation for DI and OC Protec- implement one of the following as the solution
tion Devices strategy for the simulation:
Protection Route Diagrams DISTAL strategy
Protection Documentation This strategy is based on DISTAL. The dis-
tance protection devices are set according to
Fault Location absolute selectivity.
Distance Protection Setting Line impedance strategy

PSS SINCALs Distance Protection method This strategy determines the impedance ar-
calculates impedance settings for the three eas of protection devices and their settings
zones and the overreach zones (auto-reclosure from the sum of the line impedances in the
and signal comparison) of distance protection protection zones.
devices in any type of meshed network.
Line impedance strategy connected

When PSS SINCAL calculates grading values, This strategy determines the settings for pro-
it gives priority to the setting that causes the tection devices with the help of the line im-
protection to respond selectively regardless of pedances in the network.
how the network is connected.
Medium voltage network strategy
This strategy determines the impedance ar-
eas of protection devices and their settings
from loop impedances in protection zones.
Protection simulation for DI and OC protec-
tion devices

The PSS SINCAL Protection Simulation mod-
ule simulates the time sequence for fault clear-
ance in networks, even in very complex,
meshed networks. The program considers all
the overcurrent time protection devices and
impedance protection devices that have been
installed in the network.
The locations of faults to be examined can be
Figure 1: Settings for a 7SA500 protection device
defined at nodes or anywhere on any power

Power Technologies International (Siemens PTI)


Software Solutions

Answers for infrastructure and cities.


lines or cables. Single-phase, two-phase Protection Route Diagrams The protection documentation is stored
or three-phase faults can be simulated, Large high and medium voltage net- directly as a view in the PSSSINCAL
arc impedances included. works are updated all the time. This network database. You can document as
means that a lot of time and effort is many protection zones as you want.
The program uses as many time steps
as necessary to simulate starting and involved in maintaining tripping plans. Network elements and protection de-
triggering protection devices. The oper- Calculating second and third selective vices displayed in the documentation
ating state of the protection devices can tripping levels in meshed networks is can be edited with the same user-
be visualized in the network diagram time consuming and yields calculations friendly functions as for normal network
with the help of a color code. The pro- that are at best approximate. This simu- diagrams. Input data, opening data-
gram finds any violations to grading lation procedure can calculate these output forms, switches, filters, etc. can
times and multiple tripped protection levels quickly and accurately. be modified with ease.
devices. Directional elements can be
PSS SINCAL generates various dia-
freely defined. Damage curves for ca- grams for the network and the built-in
bles, motor start behavior and trans- protection devices. These diagrams can
former loadings are also displayed be used to check the accuracy of the
graphically. The system generates grad- protection settings.
ing diagrams for I2t, RX, and Zt func-
tionality. PSS SINCAL has the following dia-
grams:
Opening behavior
Absolute radius
Impedance ratio
Impedance and tripping areas
Figure 5: Documentation for a selected protec-
tion zone

Fault Location
This procedure localizes a fault at a
protection device, determining the pre-
Figure 2: Grading diagram for RX functionality cise position of the fault within the supply
network.
Modern protection devices store the
impedance that caused the tripping when
Figure 4: Grading diagrams there is a fault. These values are then
used to calculate the exact position of
Protection Documentation the fault in the network.
PSSSINCAL protection documentation
is a practical tool creating enhanced
documentation for settings and results
for OC protection devices. In addition to
It diagrams for the protection devices,

PSS SINCAL can graphically display
complete protection zones with the ac-
companying settings. The diagram can
Figure 3: It Diagram for multiple OC devices with
be edited interactively.
current ranges

Published by and copyright 2012: Siemens Industry, Inc. For more information, please contact All rights reserved.
Siemens AG Siemens Power Technologies International our Customer Support Center. Trademarks mentioned in this document
Infrastructure & Cities Sector 400 State Street Phone: +49 180 524 84 37 are the property of Siemens AG, its affiliates,
Smart Grid Division, Services P.O. Box 1058 Fax: +49 180 524 24 71 or their respective owners.
IC SG SE PTI BD Schenectady, NY 12301-1058 USA (Charges depending on provider) Subject to change without prior notice.
Freyeslebenstr. 1 E-mail: support.ic@siemens.com The information in this document contains general
91058 Erlangen, Deutschland descriptions of the technical options available,
Smart Grid Division which may not apply in all cases.
Printed in Germany The required technical options should therefore be
www.siemens.com/power-technologies Printed on elementary chlorine-free specified in the contract.
bleached paper.

www.siemens.com/smartgrid

Potrebbero piacerti anche