Sei sulla pagina 1di 3

Numero de Barra flotante 1

Potencia Base 100MVA

DATOS DE LINEAS Y TRANSFORMADORES


RESISTENCIA
LINEA REACTANCIA (P.U.)
(P.U.)
1-6 0.123 0.518
1-4 0.08 0.37
2-3 0.0723 1.05
2-5 0.0282 0.66
3-4 0 0.133
4-6 0.097 0.407
5-6 0 0.3

DATOS DE TAPS
BARRA A BARRA B TAP EN A # DE BARRA
6 5 0.97561
4 3 0.90909

VOLTAJES Y ANGULOS DE BARRA (RESULTADOS)


BARRA VOLTAJE NGULO
1 1.05 0
2 1.1 -3.37
3 1.0003 -12.79
4 0.9294 -9.84
5 0.9188 -12.34
6 9187 -12.24
DATOS DE BARRAS

TIPO DE # DE GENERACIN CARGA


VOLTAJE (P.U.)
BARRA BARRA
MW MVAR MW MVAR
Slack 1 1.05
PV 2 1.1 50
PQ 3 55 13
PQ 4 0 0
PQ 5 30 10
PQ 6 50 5

DATOS DE LOS CAPACITOTES LIMITES DE GENERACION


# DE BARRA SUSCEPTANCIA (MVAR) #BARRA
4 2.9326 2
1 3.3898
6 3.5088
ITES DE GENERACION D LAS BARRAS PV
MAX (MVAR) MIN(MVAR)
25 0

Potrebbero piacerti anche