Intelligent Solutions for Stormwater Management

AquaCell Systems:
Product and Installation Guide

Solutions for Essentials


The AquaCell
Range

Email: technical.design@wavin.co.uk www.wavin.co.uk 3


Introduction to Wavin

Wavin Stormwater Transportation Systems


Wavin is the leading European manufacturer of industrial plastic Solid Wall Pipe Systems plastic and clay
products, and one of the largest producers of plastic pipe and Structured Wall Pipe Systems plastic
fittings in the world. Land Drainage Systems plastic

Wavin is credited with inventing and pioneering the use of plastic Inspection Cambers and Silt Traps
pipe for water distribution in the mid 1950s. Constant research Anti-Flood, Non-return Valve
and development has enabled Wavin to maintain its position at
the forefront of plastics technology.
Vortex Flow Control Valves
Fluidic-Amp
Environmental responsibility Fluidic-Cone

Wavin has BS EN ISO 9001: 2000 BSI status and was the first
Infiltration and Attenuation Systems
plastic pipe manufacturer to be accredited to BS EN ISO 1401
AquaCell Modular Storage Units.
Environmental Management Systems.
AquaCell Eco
Wavin is committed to its environmental responsibility, and is
AquaCell Prime
a leading pioneer of systems to conserve and control water. In
production the Company recycles the majority of waste material it AquaCell Core
produces and sets annual targets for energy efficiency, audited by AquaCell Plus
independent certificating bodies.

Oil Separation Systems


Passion and resourcefulness Full Retention
All Wavin personnel are committed to providing a comprehensive By-pass
and responsive customer service and are passionate about
To request details with regards to any of the above components
delivering Customer Satisfaction.
and/or for any technical enquires please contact:
Wavin maintains an industry-wide dialogue and rigorous
Literature Requests
assessment of all procedures to ensure that Wavin product
Tel: 01249 766333
development and product support accurately addresses the
Email: literature@wavin.co.uk
needs of all Customers today and into the future.
Technical Design
Quality assured products Tel: 0844 8565161
Email: technical.design@wavin.co.uk
Wavin systems are the benchmark for excellence and product
innovation: precision manufactured in the UK using the most Wavin Online
advanced injection moulding and extrusion machines. All products
The complete Wavin product catalogue, together with design and
comply with our exceed relevant British and European Standards
installation guidance, is also available online at:
to ensure reliability and long-lasting service.
www.wavin.co.uk
Stormwater management solutions All Wavin literature can be downloaded via the searchable PDF
Wavins unique expertise in stormwater management combines library at:
focused stormwater systems with proven project management
www.wavinpdfs.co.uk
skills to offer sustainable, customised, end-to-end solutions that
deliver guaranteed performance and optimum customer value. Wavin images can be downloaded at different resolutions from:

The Wavin Stormwater Management Systems include: www.wavinimages.co.uk

Surface Catchment Systems


Plastic Channel Systems
Polymer Concrete Channel Systems
Plastic Pervious Paving Systems
Plastic Road and Yard Gullies

4 Orders: 0844 8565152 Technical Advice: 0844 8565161


Contents

Introduction to Wavin 4
Contents 5
Overview 6-8
Overview of AquaCell Systems 6-7
Principal Components 8
Ancillary Components 8
Applications 9-14
AquaCell Unit Selector 9
AquaCell Eco 10
AquaCell Prime 11
AquaCell Core 12
AquaCell Plus 13-14
Design and Installation 15-21
Design and Installation Guidance 15-18
Typical Soakaway Installation Method 19
Typical Storage Tank Installation Method 20
Silt Trap 21
Air Vent Design 21
Typical Connections 22-24
Typical Air Vent Connections 22
Typical Connections to AquaCell Units 23
Typical Connection Configurations 24
Typical Details 25-33
Soakaway Non-Traffic Loading 25
Soakaway Traffic Loading 26
On-Line Storage Box Feed 27
On-Line Storage Manifold Feed 28
On-Line Storage Central Pipe Feed 29
Off-Line Storage Box Feed 30
Off-Line Storage Manifold Feed 31
Off-Line Storage Central Pipe Feed 32
Soakaway or Storage Tank With Silt Trap 33
Wavin Stormwater Management 34

Wavin operates a programme of continual product development, and therefore reserves the
right to modify or amend the specification of their products without notice. All information in this
publication is given in good faith, and believed to be correct at the time of going to press. However,
no responsibility can be accepted for any errors, omissions or incorrect assumptions. Users should
satisfy themselves that products are suitable for the purpose and application intended.

Email: technical.design@wavin.co.uk www.wavin.co.uk 5


Overview of AquaCell Systems

AquaCell units are a fully tried and tested modular technique For impervious ground (e.g. clay) or where infiltration
for managing excessive rainfall. Units are assembled to create is not desirable, the geomembrane holds stormwater
an underground structure as either a temporary storage tank or in temporary storage until local drainage flows can
soakaway. accept it for normal disposal.

Continuing urban development, a changing climate and the


consequences of intensified rainfall: all are increasingly prominent
Benefiting community and environment
issues on the political and environmental agenda. AquaCell units contribute the following benefits:

In combination, they represent a complex need for the most l Significantly reduced flooding risk
intelligent, effective Stormwater Management solutions possible.  Controlled,
l reduced-volume release of stormwater
There are 4 types of unit: into existing sewer systems or watercourses

l Recharging of local groundwater


AquaCell Eco (if infiltration/soakaway application)
AquaCell Eco is manufactured from specially reformulated,
l Aerobic purification to improve water run-off quality
recycled material and has been designed for shallow,
non-trafficked, landscaped applications (see page 10). l Sustainable, cost effective management
of the water environment
AquaCell Prime
AquaCell Prime is manufactured from specially reformulated,
Helping SUDS and planning approval
recycled material. It is ideal for use in both shallow and deep The proven qualities and performance of AquaCell systems
applications, subject to either regular traffic loading such as car not only support the achievement of SUDS, they can also
parks (for vehicles up to 12 tonnes) or for landscaped areas help reinforce and enhance planning applications, and enable
(see page 11). development to proceed.

AquaCell Core
AquaCell Core has been designed for use in deep applications,
subject to both regular and heavy traffic loadings, such as cars
and HGVs (for vehicles up to 44 tonnes) (see page 12).

AquaCell Plus
AquaCell Plus has been designed primarily for use in applications
where inspectability is required, and is suitable for use in all
applications from landscaped areas to heavily trafficked areas (for
vehicles up to 44 tonnes) (see page 13).

For quick, versatile assembly


The lightweight polypropylene, high void units are securely
linked together using special clips and shear connectors.

They can be assembled quickly on site into whatever


configuration suits each specific location.

AquaCell geocellular systems also allow brick-bonding,


which can give extra stability, without the need for additional
connector pieces. See Installation Guidance page 16.

Wrapped for infiltration or storage


The complete assembly is wrapped in either geotextile
sheet or a geomembrane:

For pervious soils, the geotextile option allows infiltration


of stormwater into the surrounding ground.

6 Orders: 0844 8565152 Technical Advice: 0844 8565161


Overview of AquaCell Systems

Types of Connections Acceptance British Board of Agrment


There are a number of ways to provide a controlled feed into the The AquaCell Infiltration and Attenuation units; Eco, Prime,
AquaCell units to suit the required flow capacity. Core and Plus have all been awarded British Board of Agrment
These being: approval under all Certificate No. 03/4018.

1. Manifold Configuration this configuration utilizes standard The certificate covers the design data, technical specification,
pipe and fittings (see page 24) installation and maintenance aspects for each unit as follows:
2. Box Configuration this configuration utilizes the AquaCell
units (see page 24)
3. Central Pipe Configuration this configuration utilizes standard
perforated TwinWall pipe and fittings (see page 24)

Box systems select with care AquaCell Eco


Rising rainfall levels, and increased focus on SUDS compliance,
Approved under BBA Agrment
have led to a sharp increase in the use of modular units to create
Certificate No.03/4018, Product Sheet 4
underground structures for infiltration or, temporary storage of
stormwater. AquaCell Prime
However, not all currently available systems have the proven Approved under BBA Agrment
performance characteristics necessary for the wide range of Certificate No 03/4018, Product Sheet 5
complex underground geocellular applications.
AquaCell Core
The Wavin range of AquaCell units however provide peace of mind
since, all strength and hydraulic capabilities have been verified by Approved under BBA Agrment
independent testing. Certificate No.03/4018, Product Sheet 1

AquaCell Plus
Approved under BBA Agrment
Certificate No.03/4018, Product Sheet 3

AquaCell Features
The following AquaCell features are applicable to all units

Suitable for use when constructing either a soakaway and/or


storage tank

Modular, lightweight and versatile

95% vold: holds 190 litres of water per unit

Safer option then open or above ground storage structures

Easy to handle and install

Proven clip and peg system to secure units

Allows brickbonding assembly for extra stability

Full range of ancillaries including, silt traps and adaptors.

AquaCell units can be mixed and matched together (see


pages 15-18 for details)

Email: technical.design@wavin.co.uk www.wavin.co.uk 7


AquaCell Systems Principal Components

Principal Components

AquaCell Eco Unit AquaCell Prime Unit AquaCell Core Unit AquaCell Plus Unit
6LB025 6LB075 6LB100 6LB200
NOTE: All AquaCell units (Eco, Prime, Core and Plus) have identical dimensions: 1m (L) x 0.4m (H) x 0.5 (W)

Ancillary Components
6LB105
Clip
(Used to hold units
together horizontally)
6UR141 6TW141 6D099 6LB102
UltraRib S/S Adaptor TwinWall S/S Adaptor OsmaDrain S/S Reducer Shear Connector
(Fits into pre-formed socket to (Fits into pre-formed socket to 160mm x 110mm (fits into (Used to hold units
connect to 150mm UltraRib) connect to 150mm TwinWall) pre-formed socket to connect together vertically)
to 110mm OsmaDrain)

6D916 6D129
160mm OsmaDrain OsmaDrain S/S Adaptor
P/E Adaptor Thinwall Clay Spigot
(Fits into pre-formed socket as (For use with 6D916 when
an extension connection piece) connecting to a BS EN 295
Thinwall Clay Spigot)

SA15/2 TA/2
150mm SuperSleve Adaptor 150mm SuperSleve Adaptor
(Fits into pre-formed socket to (For use with 6LB104
connect to 150mm SuperSleve) Flange Adaptor)

TA/4 6LB300 6LB600


225mm SuperSleve Adaptor Domestic Silt Trap Silt Trap
(For use with 6LB106 (Bucket and extension piece available) (Use extension kit if required)
Flange Adaptor)

All ancillary components can be used with any AquaCell unit,


except the 225mm Flange Adaptor (6LB106) which must only
6LB104*
be used with AquaCell Core or AquaCell Plus.
150mm Flange Adaptor
(Adaptor to be used at points The 150mm Flange Adaptor (6LB104) should only be used
6SC205
other than pre-formed socket when constructing an air vent on the top surface of an
Extension Kit
to connect to 150mm UltraRib) AquaCell Eco unit. The adaptor should not be used to connect
*6LB104 Can only be used when
constructing an air vent, on the top inlet pipes to the side of the AquaCell Eco unit.
6LB106** surface of the unit, when installed with
225mm Flange Adaptor AquaCell Eco (6LB025).
NOTE: All components on this page are not shown to scale
**6LB106 Not suitable for use with
(To connect to 225mm UltraRib) AquaCell Eco (6LB025). Image not shown

8 Orders: 0844 8565152 Technical Advice: 0844 8565161


AquaCell Unit Selector

The following selector will help you to determine which


AquaCell unit, or combination of units, is the correct
choice for a particular project.

Will the site be subject to traffic loading?

NO YES

Does the site have a high water table?

NO YES

Will both tank length and width be


more than 12m?

NO YES

Will the tank be more than 1.5m deep?

NO YES
Will the base of the tank need to be
installed extra deep (ie deeper than
Will the tank be more than 3.82m deep? 3.55m in ideal soil conditions)?

NO YES NO YES

Use: Use: Use a combination of: Use: Use a combination of:


Eco to 1.5m deep Prime to 3.82m deep Eco to 1.5m deep Prime to 3.45m deep Prime to 3.45m deep and
OR a combination of: Prime to 3.7m deep and Core to 4.1m deep and
Eco to 1.5m deep and Core to 4.25 and Plus to 4.78m deep
Prime to 3.7m deep Plus to 5.08m deep

Eco AquaCell Eco (6LB025) See page 10 Notes:


Prime AquaCell Prime (6LB075) See page 11 AquaCell Eco cannot be used directly with AquaCell Plus.
Core AquaCell Core (6LB100) See page 12
If the tanks need to be inspectable, contact Wavin Technical Design
Plus AquaCell Plus (6LB200) See page 13 on 0844 856 5161.

Maximum height of tank = 2m (5 units). Any height greater than 2m,


please contact Wavin Technical Design on 0844 856 5161.

Allowable maximum depth to base of units is dependent on soil type,


angle of shearing resistance, loading and groundwater level.

The above depths are based on 38 angle of s hearing resistance


and no groundwater. F
 or tanks in high water tables, please contact
Wavin Technical Design.

For typical specification of geomembrane, see table on page 17.

Email: technical.design@wavin.co.uk www.wavin.co.uk 9


AquaCell Eco

Application: Features and Benefits:


AquaCell Eco is manufactured from specially reformulated, Manufactured from specially reformulated, recycled material
recycled material and has been specifically designed for shallow, Suitable for both soakaway and attenuation applications
non-trafficked, landscaped applications. AquaCell Eco is NOT Proven vertical loading capacity of: 17.5 tonnes/m
suitable for locations subject to high water tables. Proven lateral loading capacity of: 4.0 tonnes/m
AquaCell Eco is typically suitable for installations to a maximum Integral hand holds for ease of carrying/handling
depth of 1.5 metres, to the base of the units from ground Black in colour, for ease of identification from other
level, with a minimum cover depth of 0.3 metres, (Wavin AquaCell units
recommendation, is to allow a cover depth of 0.5 metres) BBA approved Certificate No 03/4018

Any installation using AquaCell Eco must NOT be subjected to


additional loading at any time. Trafficking by construction plant on
site, including mechanical equipment, must be avoided.

If trafficking of the buried tank by construction plant or, other


vehicles is unavoidable, the installation should be constructed
using AquaCell Core units (see page 12)

The width of an Aquacell Eco installation should not exceed 12


metres to allow for mechanical backfilling without loading. There is
no limit to the length of the installation.

Maximum installation depths (to base units) and minimum cover depths (1)
Typical soil type Typical angle of shearing Maximum depth of Minimum cover depth (m)
installation (m)
Stiff over-consolidated clay (e.g. London clay) 24 0.95 0.30
Normally consolidated silty, sandy clay (e.g. 26 1.05 0.30
alluvium, made ground)
Loose sand and gravel 29 1.2 0.30
Medium dense sand and gravel 33 1.5 0.30
Dense sand and gravel 38 1.9 0.30

(1) These values relate to installations where the groundwater is a minimum of one metre below the base of the excavation. AquaCell Eco units should not be
used where groundwater is present.

Source: BBA

10 Orders: 0844 8565152 Technical Advice: 0844 8565161


AquaCell Prime

Application: Features and Benefits:


AquaCell Prime is manufactured from specially reformulated, Manufactured from specially reformulated, recycled material
recycled material. It is ideal for use in both shallow and deep Suitable for both soakaway and attenuation applications
applications, subject to either regular traffic loading such as car Suitable for use in areas subject to regular traffic
parks (for vehicles up to 12 tonnes) or for landscape areas. loading, i.e. car parks
Proven vertical loading capacity of: 45.6 tonnes/m in line with
Typically AquaCell Prime is suitable for installations to a maximum
the recommendation of CIRIA C962 (due to supersede CIRIA
depth of 3.70m (landscaped) and 3.45m (trafficked), to the base of
C680 by June 2014)
the units from ground level, in best soil conditions.
Proven lateral loading capacity of: 7 tonnes/m in line with the
recommendation of CIRIA C962 (due to supersede CIRIA C680
by June 2014)
Grey in colour, for ease of identification from other
AquaCell units
BBA approved Certificate No 03/4018
Ideal for all types of projects including major attenuation and
infiltration schemes

Maximum installation depths (to base units)


Typical soil type Typical Maximum depth of installation to base of units (m)
angle of With groundwater at 1m below ground level Without groundwater below base
shearing and units wrapped in geomembrane of units (normal case)
resistance
Trafficked areas Non-trafficked areas Trafficked areas Non-trafficked areas
(1) (2)
( )
(cars only) (3) (cars only) (3)
Stiff over-consolidated clay 24 1.60 1.78 1.73 1.98
(e.g. London clay)
Normally consolidated silty, 26 1.75 1.78 2.01 2.27
sandy clay (e.g. alluvium,
made ground)
Loose sand and gravel 30 1.95 2.08 2.58 2.86
Medium dense sand and 34 2.04 2.16 2.98 3.24
gravel
Dense sand and gravel 38 2.04 2.24 3.45 3.70

(1) Loosening of dense sand or softening of clay by water can occur during installation. The designer should allow for any such likely effects when choosing an
appropriate value of .
(2) The design is very sensitive to small changes in the assumed value of , therefore, it should be confirmed by a chartered geotechnical engineer. In clay
soils, it may be possible to utilise cohesion in some cases.
(3) Applicable for car parks or other areas trafficked only by cars or occasional refuse collection trucks or similar vehicles (typically one per week).
Assumptions made are:
ground surface is horizontal
shear planes or other weaknesses are not present within the structure of the soil

Source: BBA

Email: technical.design@wavin.co.uk www.wavin.co.uk 11


AquaCell Core

Application: Features and Benefits:


AquaCell Core has been designed for use in deep applications, Suitable for regular and heavy traffic loadings
subject to both regular and heavy traffic loadings, such as cars Proven vertical loading capacity of: 56 tonnes/m
and HGVs (for vehicles up to 44 tonnes). In addition AquaCell Proven lateral loading capacity of: 7.7 tonnes/m
Core can also be used for deep soakaways and landscaped Dark blue in colour, for ease of identification from
applications. other AquaCell units

Typically for use down to depths of 4.25m (landscaped), 4.1m BBA approved Certificate No 03/4018
(trafficked by cars) and 4m (trafficked by HGVs), to the base of Ideal for all types of shallow and deep projects
the units from ground level, in best soil conditions. including major attenuation and infiltration schemes.

Trafficking by heavy construction plant on site, including


mechanical equipment, must be avoided until the minimum cover
depth of 0.9 metres is in place.

Maximum installation depths (to base units)


Typical soil type Typical Maximum depth of installation to base of units (m)
angle of With groundwater at 1m below ground level Without groundwater below base
shearing and units wrapped in geomembrane of units (normal case)
resistance
Trafficked areas Non-trafficked areas Trafficked areas Non-trafficked areas
(1) (2)
( )
(cars only) (3) (cars only) (3)
Stiff over-consolidated clay 24 1.65 1.75 2.35 2.50
(e.g. London clay)
Normally consolidated silty, 26 1.70 1.80 2.50 2.65
sandy clay (e.g. alluvium,
made ground)
Loose sand and gravel 29 1.80 1.90 2.85 2.95
Medium dense sand and 33 1.90 2.00 3.30 3.45
gravel
Dense sand and gravel 38 2.05 2.15 4.10 4.25

(1) Loosening of dense sand or softening of clay by water can occur during installation. The designer should allow for any such likely effects when choosing an
appropriate value of .
(2) The design is very sensitive to small changes in the assumed value of , therefore, it should be confirmed by a chartered geotechnical engineer. In clay
soils, it may be possible to utilise cohesion in some cases.
(3) Applicable for car parks or other areas trafficked only by cars or occasional refuse collection trucks or similar vehicles (typically one per week).
Assumptions made are:
ground surface is horizontal
shear planes or other weaknesses are not present within the structure of the soil

Source: BBA

12 Orders: 0844 8565152 Technical Advice: 0844 8565161


AquaCell Plus

Application: Features and Benefits:


AquaCell Plus has been designed primarily for use in applications Suitable for extra deep installations
where inspectability is required, and is suitable for use in all Inspectable (supplied with end cap for use when an
applications from landscaped areas to heavily trafficked areas inspection channel is not required
(for vehicles up to 44 tonnes) The units can be used in Proven vertical loading capacity of: 65 tonnes/m
combination with AquaCell Prime and Core (and with Eco if there Proven lateral loading capacity of: 8.5 tonnes/m
is at least one layer of AquaCell Prime or Core in between the Plus Light blue in colour, for ease of identification from
and Eco layer). other AquaCell units

Extra lateral loading capacity allows installation at greater depths. BBA approved Certificate No 03/4018

Integral inspection channels in each unit combine to create


viewing channels for the full length of the installed structure.

Typically for use down to depths of 5.08m (landscaped),


4.78m (trafficked by cars) and 4.48m (trafficked by HGVs), to the
base of the units from ground level, in best soil conditions.

Trafficking by heavy construction plant on site, including


mechanical equipment, must be avoided until the minimum cover
depth of 0.9 metres is in place.

Maximum installation depths (to base units)


Typical angle of Maximum depth of installation to base of units (m)
shearing resistance Non-trafficked areas Trafficked areas
(1) (2)
( )
Cars (3) HGV
24 2.96 2.65 2.35
26 3.18 2.88 2.57
28 3.42 3.12 2.82
30 3.69 3.39 3.08
32 3.98 3.68 3.38
34 4.31 4.01 3.71
36 4.68 4.38 4.07
38 5.08 4.78 4.48

(1) Loosening of dense sand or softening of clay by water can occur during installation. The designer should allow for any such likely effects when choosing an
appropriate value of .
(2) The design is very sensitive to small changes in the assumed value of , therefore, it should be confirmed by a chartered geotechnical engineer. In clay
soils, it may be possible to utilise cohesion in some cases.
(3) Applicable for car parks or other areas trafficked only by slow moving vehicles.
Assumptions made are:
ground surface is horizontal
shear planes or other weaknesses are not present within the structure of the soil

Source: BBA

Email: technical.design@wavin.co.uk www.wavin.co.uk 13


AquaCell Plus for Inspectability

AquaCell Plus: for inspectability Inspectability scenarios


By aligning AquaCell Plus units end-to-end, full length viewing
channels can be created allowing for CCTV inspection if
required. These are created in the bottom layer of an AquaCell
tank installation.

The units can be used in combination with AquaCell Prime and


Core (and with Eco if there is at least one layer of AquaCell Prime
or Core in between the Plus and Eco layer).

NOTE: For any AquaCell Plus units on the perimeter of a structure


that are NOT required for inspection access, the open ends of
the integral inspection tunnels should be fitted with the end caps
provided.

Inspection chambers
An inspection chamber should precede the inlet pipework
for the AquaCell structure: AquaCell Core and AquaCell Plus

A silt trap or hydro-dynamic separator prior to the inspection


chamber is also recommended.

For on-line installations the following Wavin Chambers are


recommended:
(down to 3m) Wavin Non-Entry Inspection Chambers
(down to 5m) Wavin 600 Non-Entry Inspection Chamber or,
a traditional manhole*

*where inlet pipework is replaced by AquaCell units acting as


flow conduit.

For off-line installations:


Manhole with in-built flow control

Recommendation: If installing any Wavin Non-Entry Inspection


Chamber, deeper than 1.2 metres, ensure that the cover and
Trafficked tank installation with inspection channels
frame includes a 350mm restrictor to prevent man entry.

Inspection and maintenance


CCTV inspection at every inspection point is recommended:

after every major storm


at regular intervals according to the specific maintenance
plan for the site

Silt traps prior to inlet pipework


should be routinely
inspected and cleaned out
to minimise debris reaching
the tank. It is important to
prevent construction silt
from entering the AquaCell
structure.
AquaCell Plus 6LB200

End cap for when an inspection


channel is not required

14 Orders: 0844 8565152 Technical Advice: 0844 8565161


Design and Installation Guidance

Hydraulic and
Minimum cover depth
Structural Design
AquaCell AquaCell AquaCell AquaCell
All AquaCell units have
Location type Eco Prime Core Plus
identical dimensions: 1m x
0.4m x 0.5m, with a nominal Landscaped/non-trafficked areas 0.3mb 0.3mb 0.3mb 0.3mb
void ratio of 95%. Hydraulic
C
 ar parks, vehicle up to 12000 kga
calculations are accordingly
gross mass n/a 0.71 0.75m 0.75m
the same for AquaCell Eco,
Prime, Core and Plus. HA/HGV loading (a) n/a
n/a 1.2m 1.1m

Structural design however, Maximum depth to base of unit


requires careful consideration (Landscaped) 1.5m 3.7m 4.25mc 5.08m
of loading factors specific to Maximum depth to base of unit
each location see CIRIA C680 (Trafficked) n/a 3.45m 4.1m 4.78m
(to be superceded by CIRIA
a For specific advice on cover depths for heavier loadings/HGV applications, contact Wavin
C962 June 2014). Technical Design on 0844 856 5161.
b 0.3 is minimum depth for AquaCell Eco, although 0.5m cover is recommended to prevent accidental damage.
If construction plant is to be used on site, extra protection may be needed.
c Allowable maximum depth to base of bottom layer of units is dependent on soil type, angle of shearing resistance,
loadings, and groundwater level. The above depths are based on 38 angle of shearing resistance and no
groundwater.

Installation and AquaCell Systems: trafficking by cars/HGVs. l 


Deep-running drainage
In each case, the cover depths network
Cover Depths Installation Depths
shown in the diagram include
After deciding which AquaCell Each AquaCell unit has been l 
Other buried services running
both absolute minimum and
unit is correct for the project designed to have specific above tank location
recommended minimum cover
location (using the System loading capacities (see l 
Installation into banked/
depths.
Selector on page 9), see pages 10-13) that define the sloping ground
Table for the recommended maximum depth parameters for However, in some situations,
installations may have to be l 
Upper layer of clay
maximum installation depths which they are suitable.
located with greater cover preventing infiltration
and minimum cover depths.
Minimum depth of cover varies
depths. Reasons may include:
The diagram also shows the according to whether or not the
depth parameters for each installation will be subject to
unit, and so gives guidance on
combining two or more of the
AquaCell units. Landscaped installation Trafficked installation

0.3-0.5m
minimum 0.71-0.75m
cover depth minimum
cover depth
Max. depth
to 1.5m
Maximum Maximum
height from Max. depth
Max. depth to 3.45m height from
base of tank to 3.7m base of tank
2m Max. depth
Max. depth to 4.1m 2m
to 4.25m
Max. depth Max. depth
to 5.08m to 4.78m

Eco Prime Core Plus

Mixing AquaCell units together

Email: technical.design@wavin.co.uk www.wavin.co.uk 15


Design and Installation Guidance

Geocellular Structures Brick-bonding unit assembly


Important design considerations Recommended for extra stability
To guarantee the structural integrity of an engineered drainage When assembling a geocellular structure that comprises two or
system, any underground structure must be strong enough more layers, it is recommended that AquaCell units are placed
to support the loads to which it will be subjected without any in a brick-bonded configuration.
unacceptable deflection.

The correct choice of geocellular unit must have appropriate


proven top (vertical) and side (lateral) load bearing capacity and
deflection characteristics to suit site conditions.

The five key site considerations to be noted when designing


a geocellular structure are:

1 Depth of cover (See page 15)


2 Soil type
3 Surface finishing
4 Presence of groundwater
5 Type of traffic/loading

Non-trafficked Trafficked
This helps minimise
continuous vertical joints
5 in the assembly, and gives
the structure extra stability.
3 3
No extra connectors required with AquaCell
A significant advantage of AquaCell unit design is that
brick-bonding placement does not require extra connectors.
1 1
All four AquaCell units may be placed in this way, unless
inspection channels and cleaning access are required using
2 2
Suitable box Suitable box AquaCell Plus.
system = ? system = ? AquaCell Plus units incorporate integral inspection channels.
4 4
These are designed for combined alignment to create viewing
tunnels at the base of an assembled structure (see page 14).

The combination of these 5 factors effectively means that the


required characteristics of a geocellular structure to be installed
under a trafficked location (for example) will be very different
from that under a landscaped/low-loaded location. Two typical
examples are given below.

EXAMPLE A: Landscaped/ EXAMPLE B: Car park with


non-trafficked location occasional light delivery
and 0.3m cover depth. traffic and between
Typically requires minimum 0.71 - 0.75m cover depth.
vertical strength of Typically requires minimum
17.5 tonnes/m 2
vertical strength of
40 tonnes/m2

These factors have already been taken into consideration


within the System Selector on page 9 for the four AquaCell units,
and in the cover depth and installation depth guidance on
page 15.

16 Orders: 0844 8565152 Technical Advice: 0844 8565161


Design and Installation Guidance

Soakaway or tank? However, if the site is subject to groundwater or a high water


table, it is important to ensure that the tank is not vulnerable to
Checking site suitability
flotation. Sufficient weight from soil, or other covering placed over
Infiltration criteria the AquaCell units, must be sufficient to counter any buoyancy
A site is suitable for infiltration (soakaway) provided that BOTH uplift force from the rising groundwater level.
of the following are confirmed:
Site assessment
l The underlying soil surrounding the proposed installation
Ground conditions may be established as part of a geotechnical
is sufficiently permeable
assessment. This may include tests for infiltration and ground
 The
l seasonally high water table is a minimum of 1 metre water level.
below the base of the proposed installation
If there is no confirmation that such assessments have been
If either of these criteria is not the case, or cannot be confirmed conducted, or resulting conclusions are unavailable, a trial pit
for any reason, a soakaway system may not be suitable for the will be required in accordance with BRE 365.
application.
For information and guidance, please contact the Wavin
Storage tank Technical Design Team.
If infiltration is not possible, the system may be wrapped in an
impermeable geomembrane to create a storage tank which would
discharge at a fixed flow rate via a flow restriction device to a
permissible outflow point.

This may be designed to be online or offline (see pages 27-32


for typical details).

Typical specification for a polypropylene geomembrane


Property Value Test method
Thickness +/- (mm) 1.0 ASTM D 751
Density (minimum) (g.cm-3) 0.9 ASTM D 792
Tensile stress at break (minimum) (N.mm-2) 18 ASTM D 638
Elongation break (%) > 700 ASTM D 638
Puncture resistance (minimum) (N) 150 FTMS 101C, Method 2065
Tear resistance (minimum) (N) 60 ASTM D 1004
Dimensional stability (maximum) (% change) +/- 2.0 ASTM D 1204, 1h at 100C
Stress crack resistance (%) 100 ASTM D 5397
Volatile loss, 5% loss (maximum) 0.2 ASTM D 1203
Ozone resistance No cracks ASTM D 1149
Carbon black content (%) 2 to 3 ASTM D 1603
Moisture vapour (g m-2 day-1) < 0.1 ASTM E 96
Friction angle (non-woven geotextile) 21 Shear box
Methane permeability (g m day atm )
-2 -1 -1
0.11 European Standard
Methane transmission rate (m m s atm )
3 -2 -1 -1
0.8 x 10 -9
BRE
Permeability coefficient 1.8 x 10-12
Application temperature (C) >4

Source: BBA

Email: technical.design@wavin.co.uk www.wavin.co.uk 17


Design and Installation Guidance

AquaCell Prime, Core and Plus: AquaCell Eco:


Construction Loads Construction Loads
Construction plant such as excavators can impose significant As AquaCell Eco is designed for landscaped and non-loaded
loads on any AquaCell unit. The following guidelines should be applications, certain precautions are recommended on site to
observed: prevent damage to the units through excess loading.

l Tracked excavators (not exceeding 21 tonnes weight) should be Manual assembly


used to place fill over the AquaCell units when the geotextile or Whilst assembling the tank, it may be necessary to walk on top of
geomembrane wrapping has been completed previously laid AquaCell units. Therefore care should be taken not

l 
At least 300mm of fill should be placed before the excavators to damage the edges of the units.

or trucks delivering the backfill are allowed to traffic over the Backfilling
installed units When backfilling AquaCell Eco installations:
l 
Compaction plant used over the AquaCell units should not l 
Machines placing the material must be located OFF the units
exceed 2300kg/metre width. This will allow the compaction of
l 
Only light compaction should be applied to the material
Type 1 sub-base in 150mm layers over the units in accordance
with the Specification for Highways Works l 
Backfill with suitable, stone-free, as-dug material

l 
All other construction plant should be prevented from trafficking l 
First layer should be 300mm thick before using any compaction
over the system once it is installed and surfacing completed, plant
unless a site specific assessment demonstrates that it is
l 
NO vibratory mechanism should be used for compacting
acceptable
this first layer
l 
In particular cranes should not be used over, or place their
l 
Compaction plant must not exceed 2300kg per metre width
outriggers over the system
Construction traffic on site
If construction plant (e.g. excavators or loaders) are likely to run
over the installation:

l 
MINIMUM protective cover should be 500mm well-compacted
granular material

l 
Only tracked excavators can be used and MUST NOT weigh
more than 14 tonnes.

l 
HGVs MUST NOT run over installed AquaCell Eco units

Ancillaries and Adaptors


All ancillaries and adaptors (see page 8) can be used with
either the AquaCell Eco, Prime, Core or Plus units, except the
225mm Flange Adaptor (6LB106) which must only be used
with AquaCell Prime, Core or Plus.

The 150mm Flange Adaptor (6LB104) should only be used when


constructing an air vent on the top surface of an AquaCell Eco
unit. The adaptor should not be used to connect inlet pipes to the
side of an Eco unit.

18 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Soakaway Installation Method

AquaCell Units

100mm

Permeable geotextile*

Pre-formed socket

100mm

Coarse sand or non angular granular material base and surround


100mm

Example shows the use of


AquaCell Eco. However, a Typical Installation Procedure
soakaway can also be installed 1. Excavate the trench to the required depth ensuring that the plan area is slightly greater than
as shown using either of the that of the AquaCell units.
other versions of AquaCell 2. Lay 100mm bed of coarse sand or non angular granular material, level and compact.
units (Prime, Core or Plus)
3. Lay the geotextile* over the base and up the sides of the trench.
as appropriate.
4. Lay the AquaCell units parallel with each other. In multiple layer applications, wherever
* The geotextile should be selected
according to specific site conditions. possible, continuous vertical joints should be avoided. AquaCell units can be laid in
Typically, however, a 300g a brick bonded formation (i.e. to overlap the joints below) see page 16. For single layer
non-woven material will be suitable.
Specialist advice should be sought applications use the AquaCell Clips and for multi layers use the AquaCell Clips and the
if surrounding soil characteristics AquaCell Shear Connectors (vertical rods).
exhibit a high degree of fines/low
infiltration capacity and/or there is 5. Fix the Adaptors to the AquaCell units as required and connect pipework.
a high risk of damage from ground
contaminants. 6. In order to prevent silt from entering the tank, clogging inlet pipework and reducing storage
capacity, it is recommended that the Domestic Silt Trap (6LB300) or the standard Silt Trap
(6LB600) is installed prior to the inlet pipework see page 21 for installation guidelines.
7. Wrap and overlap the geotextile covering the entire AquaCell structure.
8. Lay 100mm of coarse sand or non angular granular material between the trench walls and
the AquaCell structure and compact.
9. Lay 100mm of coarse sand or non angular granular material over the geotextile and
compact.
10. Backfill with suitable material.
11. Rainwater from roof areas may discharge directly into the soakaway but rainwater from
carparks must discharge through a catchpit manhole and/or a petrol interceptor.

Email: technical.design@wavin.co.uk www.wavin.co.uk 19


Typical Storage Tank Installation Method

AquaCell Units

100mm

Suitable impermeable
geomembrane

Suitable protective
geotextile layer

Pre-formed socket

100mm

Coarse sand or non angular granular material base and surround


100mm

Example shows the use of


AquaCell Prime. However, Typical Installation Procedure
a storage tank can also be 1. Excavate the trench to the required depth ensuring that the plan area is slightly greater
installed as shown using any than that of the AquaCell units.
of the other versions of
2. Lay 100mm bed of coarse sand, level and compact.
AquaCell units (Eco, Core or
3. Lay the geotextile over the base and up the sides of the trench.
Plus) as appropriate.
* For large scale, deep installations 4. Lay the geomembrane on top of the geotextile over the base and up the sides of the trench.
a 1mm thick geomembrane is
recommended and joints should be 5. Lay the AquaCell units parallel with each other. In multiple layer applications, wherever
sealed using proprietary welding possible, continuous vertical joints should be avoided. AquaCell units can be laid in
techniques. For further details
contact Wavin Technical Design. a brick bonded formation (i.e. to overlap the joints below) see page 16. For single layer
applications use the AquaCell Clips and for multi layers use the AquaCell Clips and the
AquaCell Shear Connectors (vertical rods).

6. Wrap the geomembrane around the AquaCell structure and seal to manufacturers
recommendations.*

7. If side connections into the AquaCell units is required, (other than the preformed socket),
use the appropriate Flange Adaptor (6LB104 or 6LB106). Fix the flange adaptor to the unit
using self-tapping screws. Drill a hole through the Flange Adaptor and connect the
pipework. (6LB106 should not be used with AquaCell Eco).

8. In order to prevent silt from entering the tank, clogging inlet pipework and reducing storage
capacity, it is recommended that the Domestic Silt Trap (6LB300) or the standard Silt Trap
(6LB600) is installed prior to the inlet pipework see page 21 for installation guidelines.

9. Wrap and overlap the geotextile covering the entire AquaCell structure, to protect the
geomembrane.

10. Lay 100mm of coarse sand between the trench walls and the AquaCell units and compact.

11. Lay 100mm bed of coarse sand over the geotextile and compact. Backfill with suitable
material.

NB: A storage tank must be vented, and it is recommended that one vent pipe, 110mm in
diameter is provided per 7,500 square metres of impermeable catchment area on a site,
see page 21 for design.

20 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Installation: Silt Trap and Air Vent Termination

Silt Trap

Cover and frame (4D920)


Typical Installation
Procedure
150mm side
fill of suitable 1. Place the Silt Trap (6LB600) on a
as dug material
minimum of 100mm bed as per pipe
with no particle sizes
larger than 40mm bedding specification. Ensure that the
Shaft 500mm trap is as close to the AquaCell unit as
1250mm possible and in a suitable position to
allow pipework connection.
110/100mm
OsmaDrain or
2. Connect the relevant pipework in
SuperSleve pipe +
adaptor accordance with standard pipe
450mm installation guidelines.

3. Surround the sides of the Silt Trap


with 150mm of as dug material, with
no particle sizes larger than 40mm.

4. Fit relevant cover and frame.


100mm bed as
Silt Trap per pipe bedding NOTE: When surrounded by a concrete plinth
(6LB600) specification (150mm x 150mm) the 4D920 Cover and Frame
can be used in situations with a loading of up to
50kN (5 tonne).

Typical Air Vent Design


Open grating Balloon grating

150mm concrete
plinth Ventilation box

110mm OsmaDrain pipe

Flange
Connector 150mm x 110mm Reducer
(6LB104) (6UR099)
Geomembrane sealed to
Flange

AquaCell Units

NOTE: It is recommended that all connections and air NOTE: It is recommended that one vent pipe,
vent installations in storage applications (using 110mm in diameter, is provided per 7,500
geomembrane) are made using a Flange Adaptor. square meters of impermeable catchment area
Adhesive or double sided tape should be used on a site. Please contact Wavin Technical Design
between the geomembrane and the flange plate to for further details.
ensure a watertight seal.

Email: technical.design@wavin.co.uk www.wavin.co.uk 21


Typical Air Vent Connections

Top Connection for Air Vent


Typical Installation
Connect into the top of the AquaCell unit,
Procedure
using Flange Adaptor.
1. Fix Flange Adaptor to the AquaCell tank
with self-tapping screws.
Connect suitable pipework to form air vent
2. Cut through geomembrane.
Flange Adaptor (6LB104) 3. Insert pipework into Flange Adaptor to

Geomembrane wrap
form air vent.

AquaCell Units

Coarse sand or non angular


granular material base and
surround

Protective
geotextile layer

Side Connection for Air Vent


Connect into the side of the AquaCell tank unit using
standard Reducer.
Jubilee clip Suitable bend and
pipework to form air vent

Geomembrane wrap

AquaCell Units

Coarse sand or non angular


granular material base and
surround

OsmaDrain S/S reducer (6D099)

Protective
geotextile layer
Typical Installation
Procedure
1. Fix OsmaDrain Reducer to the
AquaCell tank.
2. Cut through geomembrane.
3. Insert pipework into OsmaDrain Reducer
to form air vent.

22 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Connections to AquaCell Units

Connection for soakaway application using either


the pre-formed socket (as shown below) or standard
adaptors into pre-formed socket*

Permeable
Geotextile Wrap Jubilee clip

*NOTE: For pipework other than 160mm


OsmaDrain, these adaptors can be used to
connect to the following:

l 
6TW141: TwinWall S/S Adaptor connects
AquaCell Units to 150mm TwinWall

l 
6D099: OsmaDrain Adaptor connects
to 110mm OsmaDrain
150mm
pipework to suit
l 
4D916: OsmaDrain PE Adaptor connects
to 160mm OsmaDrain

l 
6UR141: UltraRib S/S Adaptor connects
Coarse Sand or Non-Angular Granular
Material Base and Surround to 150mm UltraRib

l 
6D129: OsmaDrain S/S Adaptor connects
to 150mm SuperSleve clay. (Use an
appropriate reducer, as required, e.g.
6D099)
Connection for storage application using Flange
Adaptor at points other than pre-formed socket,
(for AquaCell Prime, Core or Plus).

Geomembrane Wrap

Protective
geotextile layer Installation Procedure
Flange Adaptor
(6LB104/6LB16) 1. Fix Flange Adaptor to the AquaCell unit
with self tapping screws.

AquaCell Prime, 2. Cut through the geomembrane.


Core or Plus
3. Insert pipework into Flange Adaptor.

Coarse Sand or Non-Angular Granular 150mm *NOTE: AquaCell Eco is not suitable for side
Material Base and Surround pipework to suit
connection using a Flange Adaptor.

Email: technical.design@wavin.co.uk www.wavin.co.uk 23


Typical Connection Configurations

Introduction
The connections shown here in schematic form, are the typical options used to connect
AquaCell unit
AquaCell units to control chambers. They provide a controlled feed assembly
into and out of the AquaCell units, and are used for either infiltration
or attenuation schemes.
Cover and frame

Manifold Connection
Using standard pipes and fittings
150mm/225mm UltraRib/
SuperSleve

Pipe
Sump

Precast concrete chamber


sections and cover slab

150mm concrete surround

NOTE: The configuration of pipes in a manifold arrangement will vary to suit site conditions and aniticipated stormwater intensity.
See pages 28 and 31 for this option in context.

Cover and frame AquaCell unit assembly


Box Connection
Using AquaCell units
for fast water transfer

Pipe
Sump

Precast concrete chamber


sections and cover slab

150mm concrete surround

NOTE: See pages 27 and 30 for this option in context.

14mm - 20mm single AquaCell unit assembly


size granular bedding /
backfill material
Cover and frame
Central Pipe Connection
Using standard perforated
Wavin TwinWall pipe and fittings

Pipe
Sump

Precast concrete chamber


sections and cover slab

150mm concrete surround Perforated


Wavin
TwinWall pipe
NOTE: See pages 29 and 32 for this option in context.

AquaCell unit assembly

24 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Details: Soakaway Non-Traffic Loading

T S

Key
S = AquaCell units soakaway

(See note 2)
S T
T = 250mm Dia Silt Trap

Soakaway
Non-traffic load area Ground level
Notes
1. Soakaways should
be sited at least 5m
Min depth* away from the building
(Ref BS EN 752-4)

2. The exact size


and shape of the
soakaways are to
be determined once
all the necessary
calculations have
Installation
depth* been produced.
110/100mm Domestic
OsmaDrain or Silt Trap * For information
SuperSleve pipe + (6LB300) regarding cover depths
adaptor
and installation depths,
AquaCell Units see page 15.

Trench Soakaway AquaCell Units


Non-traffic load area Ground level

Min depth*

Installation
depth*

Email: technical.design@wavin.co.uk www.wavin.co.uk 25


Typical Details: Soakaway Traffic Loading

Ground level

For minimum depth of


cover contact Wavin
160/150mm
OsmaDrain or
SuperSleve pipe +
adaptor

Silt Trap 160/150mm


(6LB600) OsmaDrain or
SuperSleve pipe +
adaptor

AquaCell Eco, Prime or Core


(depending on application and site)

26 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Details: On-Line Storage Box Feed

Typical vent detail

Cover and frame Open grating Cover and frame

Ventilation box

Precast
150mm concrete surround
Precast concrete
concrete chamber
chamber sections and
sections and A cover slab
cover slab

Flow control
Water Water
flow flow

Sump Sump
A

AquaCell unit assembly Coarse sand or non angular


granular material base and
Long Section surround 150mm concrete surround

Upstream control chamber AquaCell unit assembly Downstream control chamber

Water Water
flow flow

Sump

Plan Cover and frame Flow control

Geomembrane wrap with outer


protective geotextile wrap AquaCell Core units

What happens to the water?


1. The water level in the upstream control chamber rises.

Cross Section A-A AquaCell Plus units 2. T


 hen, during a storm event, the AquaCell storage assembly
used as the lower
quickly fills with water via the AquaCell feed connection.
layer
3. A
 fter storm event, water flows back out of the AquaCell
storage assembly, finding its own level, and into the
downstream control chamber.
4. The water then flows through the vortex flow control valve.

Email: technical.design@wavin.co.uk www.wavin.co.uk 27


Typical Details: On-Line Storage Manifold Feed

Typical vent detail

Cover and frame Open grating Cover and frame

Ventilation box

Precast
150mm concrete surround
Precast concrete
concrete chamber
chamber sections and
sections and A cover slab
cover slab

Flow control
Water Water
flow flow

* *

Sump Sump
A

AquaCell unit assembly Coarse sand or non angular


granular material base and
Long Section *Alternative pipe configuration surround 150mm concrete surround

AquaCell unit assembly

Upstream control chamber Downstream control chamber

Water Water
flow flow

Sump

Plan
Cover and frame Flow control
3-pipe manifold

Geomembrane wrap with outer


protective geotextile wrap AquaCell Core units

What happens to the water?


1. The water level in the upstream control chamber rises.
Cross Section A-A AquaCell Plus units used
2. During a storm event, the AquaCell storage assembly fills as inspection access
with water via the manifold feed connection.
3. After storm event, water flows back out of the AquaCell
storage assembly, finding its own level, and into the
downstream control chamber.
4. The water then flows through the vortex flow control valve.

28 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Details: On-Line Storage Central Pipe Feed

Typical vent detail

Cover and frame Open grating Cover and frame

Ventilation box

Precast
150mm concrete surround
Precast concrete
concrete chamber
chamber A sections and
sections and cover slab
cover slab

Flow control
Water Water
flow flow

Sump A Sump

AquaCell unit assembly Wavin TwinWall half-perforated pipe

Long Section 150mm concrete surround


AquaCell unit assembly

Upstream control chamber Downstream control chamber

Water Water
flow flow

Sump

Plan Cover and frame Flow control


Water flow during storm event Water flow after storm event

Coarse sand or non angular granular 14mm - 20mm single size granular
material base and surround bedding/backfill material

Wrap the entire


AquaCell unit
assemblies
with a geotextile
wrapping as
appropriate

Cross Section A-A


Geomembrane to perimeter of constructon

What happens to the water?


1. The water level in the upstream control chamber rises.
2. AquaCell storage assemblies fill with water via the central pipe connection and percolates
through the granular bedding material.
3. After storm event, water flows back out of the AquaCell storage assemblies, finding its own
level, and into the downstream control chamber.
4. The water then flows through the vortex flow control valve.

Email: technical.design@wavin.co.uk www.wavin.co.uk 29


Typical Details: Off-Line Storage Box Feed

Typical vent detail

Open grating Cover and frame

Ventilation box

Precast
Coarse sand or non angular granular 150mm concrete surround concrete
material base and surround chamber
sections and
A cover slab
Weir
wall
Flow
control Water
flow

Sump
A
Long Section
AquaCell unit assembly Geomembrane wrap with outer
protective geotextile wrap
Non-return flap valve

AquaCell unit assembly Cover and frame


Flow control

Water
flow

Weir
wall

Plan
Precast concrete 150mm concrete
chamber sections surround
Water
Geomembrane wrap with outer flow
protective geotextile wrap

What happens to the water?


1. Control chamber fills with water, up to the top of the
weir wall.
2. The water overflows the weir wall and enters the AquaCell
Cross Section A-A storage assembly via the AquaCell connection.
3. The AquaCell storage assembly fills with water.
4. After storm event, water flows back out of the AquaCell
storage assembly, finding its own level, and through the
non-return flap valve at the bottom of the
weir wall.
5. The water then flows through the vortex flow control valve.

30 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Details: Off-Line Storage Manifold Feed

Typical vent detail

Open grating Cover and frame

Ventilation box

Precast
Coarse sand or non angular granular 150mm concrete surround concrete
material base and surround chamber
sections and
cover slab
A
Weir
wall
Flow
control Water
flow

Sump
A
Long Section
AquaCell unit assembly Geomembrane wrap with outer
protective geotextile wrap
Non-return flap valve

AquaCell unit assembly Cover and frame


Flow control

Water
flow

Weir
wall

Plan Precast concrete 150mm concrete


chamber sections surround

Water
flow

Geomembrane wrap with outer


protective geotextile wrap

What happens to the water?


1. Control chamber fills with water, up to the top of the
weir wall.
2. The water overflows the weir wall and enters the AquaCell
storage assembly via the manifold connection.
Cross Section A-A
3. The AquaCell storage assembly fills with water.
4. After storm event, water flows back out of the AquaCell
storage assembly, finding its own level, and through the
non-return flap valve at the bottom of the
weir wall.
5. The water then flows through the vortex flow control valve.

Email: technical.design@wavin.co.uk www.wavin.co.uk 31


Typical Details: Off-Line Storage Central Pipe Feed

Typical vent detail

Open grating Cover and frame

Ventilation box

Precast
Coarse sand or non angular granular
150mm concrete surround concrete
material base and surround
chamber
sections and
A cover slab

Weir
wall
Flow
control Water
flow

Long Section
A Sump
Wavin TwinWall half-perforated pipe
AquaCell unit assembly

Wavin TwinWall half-perforated pipe 14mm - 20mm single size granular Non-return flap valve
bedding/backfill material
Flow control

Water
flow

Water
Water flow during storm event Water flow after storm event flow
Plan
14mm - 20mm single size granular bedding/backfill material

Wrap the entire


AquaCell unit
assemblies
with a geotextile
wrapping as
appropriate

Cross Section A-A


Geomembrane to perimeter of constructon

What happens to the water?


1. Control chamber fills with water, up to the top of the weir wall.
2. The water overflows the weir wall and enters the AquaCell storage assemblies via the central
pipe connection and percolates through the granular bedding material.
3. The AquaCell storage assembly fills with water.
4. After storm event, water flows back out of the AquaCell storage assemblies, finding its own
level, and through the non-return flap valve at the bottom of the weir wall.
5. The water then flows through the vortex flow control valve

32 Orders: 0844 8565152 Technical Advice: 0844 8565161


Typical Details: Soakaway or Storage Tank With Silt Trap

Ground level

110/100mm OsmaDrain
or SuperSleve pipe +
For minimum depth of
adaptor
cover contact Wavin

110/100mm Domestic 110/100mm


OsmaDrain or Silt Trap OsmaDrain or
SuperSleve pipe (6LB300) SuperSleve
+ adaptor pipe +
adaptor

AquaCell Eco
AquaCell Prime
AquaCell Core
AquaCell Plus

(Choice depends on application and site conditions)

Notes
For bedding specification information refer to page 21.

The silt trap can be used in conjunction with a soakaway (as


shown) or a storage tank.

Email: technical.design@wavin.co.uk www.wavin.co.uk 33


Wavin Stormwater Management System

To achieve optimum Below Ground Water Transportation


Wavin Stormwater installations can draw from an extensive choice
stormwater management of plastic and clay water conveyance systems, including:

l OsmaDrain solid wall PVC-U pipe system


The Wavin Stormwater Management System represents a
l Structured wall plastic UltraRib and TwinWall pipe systems
combination of specialist expertise and technology from Wavin.
l SuperSleve and HepSeal clay pipe systems
This is specifically focused on achieving the optimum solution
for each project requiring effective and sustainable management Other options include perforated pipe for land drainage:
of stormwater. WavinCoil plastic and HepLine clay and a full range of
Such a solution may be entirely based on a tailored combination Wavin Non-Entry Inspection Chambers.
of our engineered systems.
Rainwater Re-use
In other cases, Wavin Stormwater Systems can be integrated
with soft SUDS techniques, such as ponds and swales, to help The Wavin Stormwater Water Range can also exploit stored

achieve the optimal solution. rainwater. These reduce the use of potable mains water for non-
potable purposes.

Other Wavin Stormwater Systems Below ground domestic rainwater re-use systems are available.

Oil Separators
A comprehensive range of NS Oil Separators, tested to The Wavin Stormwater
service
EN 858 Class 1 standard and complying with PPG-3 legislation
for England and Wales.

Channel Drainage Precision and Performance


Environmentally-friendly polyester concrete systems to cover all The Wavin Stormwater team are ready to contribute to any

EN 1433 load classes. With outstanding chemical resistance and stormwater management project.

low water absorption: This may be at the very earliest stage or when initial plans have
already been developed. There are no pre-conditions with regards
l PolyChannel SK range: general purpose channel
to you requesting Wavin to become involved.
for applications up to E600
We are ready to:
l PolyChannel SKS range: heavy duty channel
for applications up to F900 l Originate project design

l Comment on an existing design


Plastic Pervious Paving
l Help validate a specification or, where we see an opportunity
High performance, plastic pervious paving system, for use in all
to do so, to suggest how it may be enhanced
types of Sustainable Drainage systems (SUDS)
l Check, clarify and confirm maximum cost-efficiency,
l AquaGrid 50 for use in landscape projects
performance capability and regulatory compliance
l AquaGrid 75 for use in car parking areas
This involvement is a core part of the Wavin principle. It extends
beyond the systems and components.
Flow Control Valves
The Vortex Valve range that can be custom-built to suit site To discuss your stormwater management project, call
conditions:
0844 856 5161
l Fluidic-Amp and Fluidic Cone stainless steel units with no
or email technical.design@wavin.co.uk
moving parts or power needs

Anti-Flood Valves
l Anti-Flood Valves that comply with EN 13546-1, and Part H1-
Sections 2.8-2.12 of Building Regulations

34 Orders: 0844 8565152 Technical Advice: 0844 8565161


Intelligent Solutions for Stormwater Management

Wavin working to ensure


optimum stormwater management

The combination of urban development and intensified rainfall from climate


change can create serious problems. Stormwater situations are challenges
that may be unavoidable, but they can be very effectively overcome
when the right expertise is applied.

Wavins stormwater range offers a specialist focus for the most efficient
capture, transportation, cleansing, infiltration, attenuation and re-use of
stormwater at source.

The Wavin Team has the essential experience and design insight
to help engineer the best possible solution, in its widest sense,
every time.

Our well-proven system technology is intelligently applied to


the individual needs of each location and situation. We make
thorough checks to ensure efficient performance and full
adherence to the latest statutory regulations.

By making Wavin part of your project approach, the


outcome is assured: the optimum balance of cost,
function and compliance.

Wavin operates a programme of continuous product development, and therefore reserves the right to modify or
amend the specification of their products without notice. All information in this publication is given in good faith, and
believed to be correct at the time of going to press. However, no responsibility can be accepted for any errors,
omissions or incorrect assumptions. Users should satisfy themselves that products are suitable for the purpose and
application intended.