Solution Parameters Results WAHX Options

Select Rate Selection Savings Face Velocity Dimensions

Fin Height mm
Rows 6 FPI 10
6 10 1.8 6.2 Fin Length mm
FPI Range
Rows Fins/Inch Tons Cooling kW Reheat Face Velocity 2.5 m/s
8 10 12 14

Air Flow 0.5 m3/s Effectiveness 47.3 % Total Pressure Drop 189.83 Pa

Incoming Air Passive Cool Active Cool Supply Air

Dry Bulb (C) 33.5 27.8 11.4 21.8

Wet Bulb (C) 30.0 27.8 11.3 15.5

RH (%) 77.6 100.0 99.4 51.1

Humidity Ratio (kg/kg) 0.026 0.024 0.008 0.008

Enthalpy (kJ/kg) 99.5 88.5 32.5 43.2

Dew Point (C) 29.0 27.8 11.3 11.3

Pre Cool Coil Active Cooling Coil Re Heat Coil

WAHX w/o WAHX


Total Energy -6.2 kW Total Energy 6.2 kW
Total Energy -32.8 -38.9 kW
Sensible Energy -3.5 kW Sensible Energy 6.2 kW

Latent Energy -2.8 kW Difference 1.8 Tons Latent Energy 0.0 kW

Moisture Difference 4.0 kg/hr Moisture Difference 0.0 kg/hr


Sensible Energy -10.6 -14.1 kW
SHR 0.559 SHR 1.000
Latent Energy -22.2 -24.9 kW

Moisture Difference 32.5 36.5 kg/hr

SHR 0.323 0.361