Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
91.40.3041.3100
DS-125.0-1107
The information and recommendations contained herein are based on the experience of the author
and LATICRETE International, Inc. While we believe the information presented in these documents to
be correct, LATICRETE International, Inc. and its employees assume no responsibility for its accuracy
or for the opinions expressed herein. The information contained in this publication should not be
used or relied upon for any specific application or project without competent examination by qualified
professionals and verification of its accuracy, suitability, and applicability. Users of information from this
publication assume all liability arising from such use.
1
2
Table of Contents
Preface..................................................................................................................................................5
Section 1: Introduction
1.1 Steam Room Facts......................................................................................................................9
1.2 Tile Installations in Steam Rooms Materials and Methods....................................................9
1.3 Summary . ................................................................................................................................13
Section 6: Appendix.............................................................................................................................
6.1 Steam Room Frequently Asked Questions............................................................................. 78
6.2 Resource Guide Trade Organizations and Technical Resources......................................... 80
6.3 Glossary................................................................................................................................... 82
3
4
Preface
LATICRETE International, Inc., a world leader in the manufacturing of ceramic tile and stone
installation systems, has long recognized the need for a technical design manual to provide
guidelines and recommendations for the design, specification and installation of tile and
stone in steam room/steam shower applications. Improved technology in steam room
construction and equipment has made steam rooms and steam showers readily available
to anyone. In keeping with our position as an industry leader, LATICRETE International
is publishing this Tiled Steam Room and Steam Shower Technical Design Manual to
provide information and guidelines to architects, design professionals, construction
professionals, tile installation professionals, and the tile and stone distribution industry.
It is the goal of this manual to provide the necessary information to help ensure a proper
and long-lasting tile installation in a steam room or steam shower environment.
5
6
Section 1: Introduction
7
8
Section 1: Introduction
1.1 Steam Room Facts Membrane. Tile is the perfect finish for a steam
Who wouldnt like to have a steam bath or room application and choosing the right tile is
steam shower in their own home? Steam important. For best results, the tile should be
provides an invigorating way to maintain or impervious (i.e. porcelain) or have a glazed
restore physical and mental health. Sitting in surface to help limit the amount of moisture
a steam room environment can help the body and moisture vapor that makes its way into the
to burn calories, improve circulation, relax system.
muscles, flush toxins from the body, cleanse An acceptable vapor barrier can be a vital
pores, relieve stress, and help induce more component of any steam room and, when
relaxing sleep. All of this in just twenty minutes properly installed, can prevent moisture from
a day! getting into wall and ceiling cavities. When hot,
The fact is; steam rooms and steam showers moist air comes in contact with cooler surfaces
are becoming more and more common in home (at or below dew point) it condenses and turns
environments. They are no longer just for back into water. If the dew point temperature
health clubs or the very wealthy; now anybody is within the wall cavity then the moisture will
can own their own steam room. Steam room either build up within the wall or show up in
and steam showers are fairly often included in areas where water is not supposed to be found.
new home construction, rather than a standard This can lead to structural damage, mold,
shower. While there are many benefits to water problems, poor indoor air quality, and
owning and using a steam room or steam more. In order to function properly it is critical
shower there are also some basic principles that this vapor barrier laps into the shower pan
that must be kept in mind when designing, (another critical component of a steam room
installing and using these units: installation).
1. Prevent steam from escaping. 1.2 Tile Installations in Steam Room
2. Collect any condensed water and allow it and Shower Applications Materials and
to drain properly. Methods
3. Keep water from dripping on the steam Lets look at two typical steam room
room occupants. constructs:
Steam generation units create a great deal of 1. The first design incorporates steel or wood
moisture; this moisture initially takes the form framing and a concrete, slab-on-grade
of water vapor (steam). This water vapor is sub-floor. The ceiling should be sloped
highly penetrative and any room not properly at least 2" minimum per foot (50 mm per
prepared may be exposed to damage caused 300 mm) to prevent water from dripping
by excessive moisture. Proper measures must on steam room occupants (per Tile Council
be taken to prevent moisture transgression of North America recommendations). The
into or through walls, ceiling and floor. floor should be pre-pitched (prior to the
installation of the shower pan liner) at the
These preventive measures include a properly
rate of 1/4" per foot (6 mm per 300 mm)
placed, suitable vapor barrier and/or an
to make sure that water flows toward the
acceptable waterproofing membrane.
drain. Keep in mind that a shower pan is
LATICRETE International, Inc. always
required in all steam room/steam shower
recommends using both a vapor barrier, placed
installations!
on the framing or on the concrete/concrete
masonry units prior to further construction,
and LATICRETE 9235 Waterproofing
9
Heading1:Here
Section Introduction
The installation begins with the proper choice so that it laps into the shower pan liner! This
and placement of a two-part clamping-ring- way any moisture that comes in contact with
style drain with weepers as per ASME A112.6.3. the vapor barrier will drain into the shower pan
Place tile spacers or gravel around weep holes, and through the weep holes of the drain.
as detailed by the design professional, to Next, install a 2" (50 mm) thick (minimum)
prevent mortar from clogging the weep holes wire-reinforced, mortar bed comprised of
and should be installed by a qualified plumber LATICRETE 226 Thick Bed Mortar gauged with
in accord with International Residential Code LATICRETE 3701 Mortar Admix onto the shower
(IRC) P2709.4. The pipes and drain should floor. The wire-reinforcement should be
be properly supported to prevent problems 2" x 2" (50 mm x 50 mm), 16 gauge,
in the future. A suitable primary shower pan galvanized, welded wire mesh and should be
liner, complying with ASTM D 4068, D 4551 placed at half the depth of the mortar bed.
or other approved material, would then be Make sure that the mortar bed maintains the
installed to tie into the bottom flange of the 1/4" per foot (6 mm per 300 mm) slope to
drain (without blocking the weep holes). The drain which was established by the pre-pitch in
liner must be turned up the walls to a point at the sub-floor. After the mortar bed has cured,
least 3" (75 mm) above the top of the curb or the installation of the cement backer board on
6" (150 mm) above the floor in steam rooms the walls and ceiling can begin.
or steam showers without curbs. The shower
The addition of a suitable insulation material
pan must be properly formed and fastened to
between the wall and ceiling framing should be
prevent problems. Check with local building
done before installation of the cement backer
code to help determine what shower pan liner
board. Insulation will help keep the heat in
is acceptable in your area. This pan will act as
the steam room, cool air out, and helps to
your vapor barrier on the floor. Curbs must be
control the dew point (the temperature where
sloped to drain back into the steam room for
condensation takes place) within the wall. The
condensation runoff. Perform a flood test to
cement backer board used must be acceptable
determine integrity of the pan liner and make
for steam room use and installed per the
repairs as necessary before proceeding.
board manufacturers written installation
After the shower pan liner is in place, install instructions; this includes taping of all board
the vapor barrier directly onto the side of the joints. Use LATICRETE 254 Platinum and 2" (50
wall and ceiling framing that will be exposed to mm) wide, alkali-resistant fiberglass mesh tape
the steam room. The vapor barrier should be to treat the board joints. Be sure to allow space
4 6 mil thick polyethylene (cross laminated at the ceiling/wall transition for the insertion
virgin polyethylene is excellent) and, if possible, of a slip joint to allow for proper expansion/
should be one piece that can fit into the entire contraction to take place.
area. Fasten the vapor barrier to the studs
Pipes and penetrations through board should
with corrosion-resistant fasteners. A spot of
be accounted for and space between board
LATICRETE Latasil (100% silicone sealant)
and penetration should be kept to a minimum.
onto the fasteners will help prevent moisture
Allow the mortar used to tape the board
penetration through the fastener holes. Make
joints to harden and then commence with
sure that the vapor barrier is properly formed
waterproofing the entire inside area of the
and is tight to the studs of the walls and ceiling.
steam room with LATICRETE 9235
Yes the vapor barrier must be installed onto
Waterproofing Membrane. The entire steam
the ceiling as well as the walls because steam
room should be waterproofed, including
can certainly escape through the ceiling. It is
the ceiling, walls, floor, seat, and any other
imperative that this vapor barrier be placed
exposed area; this will help improve the
10
Section 1: Introduction
functionality of the vapor barrier and inhibit flows toward the drain. Also, a shower pan is
the passage of most of the moisture through required in ALL steam room/steam shower
the system. Loop the LATICRETE 9235 installations!
Waterproofing Membrane into the slip joints The installation begins with the proper
to allow for movement in these areas. Any choice and placement of a two-part clamping
vapor transpiring through the LATICRETE 9235 ring style drains with weepers as per ASME
Waterproofing Membrane should easily be A112.6.3. Place tile spacers or gravel around
handled by the vapor barrier. Make sure weep holes, as detailed by the design
that ANY and ALL penetrations are properly professional, to prevent mortar from clogging
waterproofed and sealed tightly with the weep holes, they should be installed by a
LATICRETE Latasil! qualified plumber in accord with IRC P2709.4.
Tile can be installed directly onto the The pipes and drain should be properly
LATICRETE 9235 Waterproofing Membrane as supported to prevent problems in the future.
soon as it is dry to the touch. LATICRETE 254 For this type of steam room construction,
Platinum is the thin-set of choice for steam LATICRETE 9235 Waterproofing Membrane
room/steam shower installations. Check with can be used as the primary shower pan liner.
the manufacturer of the tile to make sure that it A suitable primary shower pan liner material,
is compatible in steam room applications. complying with ASTM D4068, D4551 or other
Once the tiles have set firm, grout the code approved material may also be used as
installation with LATICRETE SpectraLOCK the primary shower pan liner. No matter which
PRO Grout for best performance. Alternative of the approved materials is used as the shower
grouting choices would be either LATICRETE pan liner, it must be tied into the bottom
1500 Sanded Grout or LATICRETE 1600 flange of the drain properly. The liner is
Unsanded Grout gauged with LATICRETE 1776 applied directly onto the concrete or masonry
Grout Enhancer. Use LATICRETE Latasil, with walls and concrete floor. The liner must be
LATICRETE 9118 Primer, in slip joints, steam turned up the walls to a point at least 3"
jets, movement joints, around the drain, to seal (75 mm) above the top of the curb or 6"
lighting fixtures, access panels (if present), (150 mm) above the floor in steam rooms or
or at any change of plane. The use of steam showers without curbs. The shower
LATICRETE SpectraLOCK PRO Grout will add
to the performance of the tile installation
because it has an absorption rate of <.5%. It
will be necessary to wait for 14 days for the
cementitious grout, and 10 days for LATICRETE
SpectraLOCK PRO Grout to cure at 70F (21C)
before turning on the steam generation unit.
2. The second design involves installation
over all other substrates including concrete
or masonry walls. Again, the ceiling should be
sloped at least 2" minimum per foot (50 mm
per 300 mm) to prevent water from dripping
on steam room occupants (per Tile Council of
North America recommendations). The floor
should be pre-pitched (prior to the installation
of the shower pan) at the rate of 1/4" per foot
(6 mm per 300 mm) to make sure that water
11
Section 1: Introduction
pan must be properly formed and fastened to according to the current revision of ANSI A108.1
prevent problems. Check with local building (1.1 and 1.2). Make sure that no fasteners
code to help determine what shower pan liner penetrate the shower pan liner. Pencil rods and
is acceptable in your area. This pan will act as tie wires may also be used to secure the metal
your vapor barrier on the floor. Curbs must be lath in place.
sloped to drain back into the steam room for Apply a mortar bed consisting of LATICRETE 226
condensation runoff. Perform a flood test to Thick Bed Mortar gauged with LATICRETE 3701
determine integrity of the pan liner and make Mortar Admix as scratch and leveling coats,
repairs as necessary before proceeding. Allow in compliance with ANSI A108.1A (1.3 and 1.4)
a 7 day cure at 70F (21C) prior to flood testing over the wire lath on the walls and ceiling. The
LATICRETE 9235 Waterproofing Membrane. scratch and float coats can be installed in lifts
After the shower pan liner is in place, install up to 5/8" (13 mm) thick and should be floated
the vapor barrier directly onto the concrete/ to be plumb and true.
masonry walls making sure that the vapor Next, install a 2" (50 mm) thick (minimum) wire-
barrier laps into the shower pan liner. The vapor reinforced, mortar bed comprised of LATICRETE
barrier should be 4 6 mil polyethylene (cross 226 Thick Bed Mortar gauged with LATICRETE
laminated virgin polyethylene is excellent) 3701 Mortar Admix onto the shower floor. The
and, if possible, should be one piece that can wire-reinforcement should be 2" x 2" (50 mm
fit into the entire area. Fasten the vapor barrier x 50 mm), 16 gauge, galvanized, welded wire
to the wall with corrosion resistant fasteners. mesh and should be placed at half the depth
A spot of LATICRETE Latasil (100% silicone) of the mortar bed. Make sure that the mortar
onto the fasteners will help prevent moisture bed maintains the 1/4" per foot (6 mm per
penetration through the fastener holes. Make 300 mm) slope to drain which was established
sure that the vapor barrier is properly formed by the pre-pitch in the sub-floor.
and is tight to the walls and ceiling. Yes
Allow the floor mortar bed to set until firm and
the vapor barrier must be installed onto the
then commence with waterproofing the inside
ceiling as well as the walls because steam
area of the steam room with LATICRETE 9235
can certainly escape through the ceiling. It is
Waterproofing Membrane. The entire steam
imperative that this vapor barrier be placed
room should be waterproofed, including the
so that it laps into the shower pan liner! This
ceiling, walls, floor, seat, and any other exposed
way any moisture that comes in contact with
area; this will help improve the functionality
the vapor barrier will drain into the shower pan
of the vapor barrier and inhibit the passage
and through the weep holes of the drain.
of most of the moisture through the system.
Once the vapor barrier has been properly Any vapor transpiring through the LATICRETE
installed, application of the insulation panels 9235 Waterproofing Membrane should easily
can commence. These panels are typically be handled by the vapor barrier. Make sure
fastened mechanically through to the substrate that any and all penetrations and fixtures are
through the vapor barrier; check with the properly waterproofed and sealed tightly with
insulation manufacturer for proper installation LATICRETE Latasil.
instructions for their product in this
Tile can now be installed directly onto the
application. A dab of LATICRETE Latasil can
LATICRETE 9235 Waterproofing Membrane
help prevent moisture from getting through
once it has sufficiently cured. LATICRETE 254
the fastener holes. Install galvanized diamond
Platinum is the thin-set of choice for steam
metal lath, complying with ASTM C847,
room/steam shower installations. Check with
12
Section 1: Introduction
13
14
Section 2: Specification for Steam Room
Full Mortar Bed
15
Section 2: Detail ES SR 613
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
* United States Patent No.: 6881768 (and other Patents).
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
16 Offices, Marca Registrada. All other trademarks are property of their respective companies.
Section 2: Part 1 General Information
17
Section 2: Part 1 General Information
B. American National Standards Institute M. American Society For Testing And Materials
(ANSI) A137.1 (ASTM) C150
American National Standard Specifications For Standard Specification for Portland Cement
Ceramic Tile N. American Society For Testing And Materials
(ASTM) C171
C. American National Standards Institute
(ANSI) A108.01 A108.17 Standard Specification for Sheet Materials for
American National Standard Specifications For Curing Concrete
The Installation Of Ceramic Tile O. American Society For Testing And Materials
(ASTM) C241
D. American National Standards Institute
(ANSI) A118.1 A118.12 Standard Test Method for Abrasion Resistance
American National Standard Specifications For of Stone Subjected to Foot Traffic
The Installation Of Ceramic Tile P. American Society For Testing And Materials
(ASTM) C267
E. American National Standards Institute
(ANSI) A136.1 Standard Test Method for Chemical Resistance
American National Standard Specifications For of Mortars, Grouts, and Monolithic Surfacings
The Installation Of Ceramic Tile Q. American Society For Testing And Materials
(ASTM) C482
F. American Plywood Association (APA) Y510T
Standard Test Method for Bond Strength of
Plywood Design Specifications
Ceramic Tile to Portland Cement
G. American Society For Testing And Materials
(ASTM) A82 R. American Society For Testing And Materials
(ASTM) C503
Standard Specification for Steel Wire, Plain, for
Standard Specification for Marble Dimension
Concrete Reinforcement
Stone (Exterior)
H. American Society For Testing And Materials
(ASTM) A185 S. American Society For Testing And Materials
(ASTM) C531
Standard Specification for Steel Welded Wire
Standard Test Method for Linear Shrinkage
Fabric, Plain, for Concrete Reinforcement
and Coefficient of Thermal Expansion of
I. American Society For Testing And Materials Chemical-Resistant Mortars, Grouts,
(ASTM) C33 Monolithic Surfacings and Polymer Concretes
Standard Specification for Concrete Aggregate
T. American Society For Testing And Materials
J. American Society For Testing And Materials (ASTM) C627
(ASTM) C36 Standard Test Method for Evaluating Ceramic
Standard Specification for Gypsum Wallboard Floor Tile Installation Systems Using the
K. American Society For Testing And Materials Robinson-Type Floor Tester
(ASTM) C109
U. American Society For Testing And Materials
Standard Test Method for Compressive (ASTM) C794
Strength of Hydraulic Cement Mortars (Using Standard Test Method for Adhesion-in-Peel of
2" [or 50 mm] Cube Specimens) Elastomeric Joint Sealants
V. American Society For Testing And Materials
(ASTM) C847
Standard Specification for Metal Lath
18
Section 2: Part 1 General Information
W. American Society For Testing And Materials GG. American Society For Testing And
(ASTM) C905 Materials (ASTM) D4397
Standard Test Method for Apparent Density Standard Specification for Polyethylene
of Chemical-Resistant Mortars, Grouts, and Sheeting for Construction, Industrial and
Monolithic Surfacings Agricultural Applications
X. American Society For Testing And Materials HH. American Society For Testing And
(ASTM) C920 Materials (ASTM) D4716
Standard Specification for Elastomeric Joint Standard Test Method for Determining the (In
Sealants Plane) Flow Rate Per Unit Width and Hydraulic
Y. American Society For Testing And Materials Transmissivity of a Geo-synthetic Using a
(ASTM) C955 Constant Head
Standard Specification for Load Bearing II. American Society For Testing And Materials
(Transverse and Axial) Steel Studs, Runners (ASTM) E84
(Tracks), and Bracing or Bridging for Screw Standard Test Method for Surface Burning
Application of Gypsum Board and Metal Plaster Characteristics of Building Materials
Bases JJ. American Society For Testing And Materials
Z. American Society For Testing And Materials (ASTM)
(ASTM) D226 E90 Standard Test Method for Laboratory
Standard Specification for Asphalt- Measurement of Airborne Sound Transmission
Saturated Organic Felt Used in Roofing And Loss of Building Partitions
Waterproofing KK. American Society For Testing And
AA. American Society For Testing And Materials (ASTM) E96
Materials (ASTM) D227 Standard Test Methods for Water Vapor
Standard Specification for Coal-Tar Transmission of Materials
Saturated Organic Felt Used in Roofing and LL. American Society For Testing And Materials
Waterproofing (ASTM) E413
BB. American Society For Testing And Standard Classification for Rating Sound
Materials (ASTM) D751 Insulation
Standard Test Method for Coated Fabrics MM. American Society For Testing And
CC. American Society For Testing And Materials Materials (ASTM)
(ASTM) D751 E492 Standard Test Method for Laboratory
Standard Test Method for Rubber Property Measurement of Impact Sound Transmission
Durometer Hardness Through Floor-Ceiling Assemblies Using the
DD. American Society For Testing And Tapping Machine
Materials (ASTM) D1248 NN. American Society For Testing And
Standard Test Method for Staining of Porous Materials (ASTM) E989
Substances by Joint Sealants Standard Classification for Determination of
EE. American Society For Testing And Materials Impact Insulation Class (IIC)
(ASTM) D2240 OO. American Society of Mechanical Engineers
Standard Test Method for Coated Fabrics (ASME) ASME A112.6.3
FF. American Society For Testing And Materials Floor and Trench Drains
(ASTM) D4263 PP. Canadian Sheet Steel Building Institute
Standard Test Method for Indicating Moisture (CSSBI)
in Concrete by The Plastic Sheet Method Lightweight Steel Framing Binder (Publication
52M)
19
Section 2: Part 1 General Information
20
Section 2: Part 1 General Information
3. LEED NC v2.2 Credit MR 5.2 (20% Extracted, B. Installation System Manufacturer (single
Processed and Manufactured Regionally): source responsibility)
Product data indicating location of material Company specializing in adhesives, mortars,
manufacturer for regionally manufactured grouts and other installation materials with ten
materials. (10) years minimum experience and ISO 9001
certification. Obtain installation materials
Include statement indicating cost and
from a single source manufacturer to insure
distance from manufacturer to Project for
consistent quality and full compatibility.
each regionally manufactured product.
C. Submit shop drawings and manufacturers C. Submit laboratory confirmation of
adhesives, mortars, grouts and other
product data under provisions of Section installation materials
(01300) (01340). 1. Identify proper usage of specified materials
D. Submit samples of each type/style/finish/ using positive analytical method.
size/color of ceramic tile, mosaic, paver, trim 2. Identify compatibility of specified materials
unit or threshold under provisions of Section using positive analytical method.
(01300) (01340).
3. Identify proper color matching of specified
E. Submit manufacturers installation materials using a positive analytical
instructions under provisions of Section method.
(01300) (01340).
D. Installer Qualifications
F. Submit manufacturers certification under
Company specializing in installation of ceramic
provisions of Section (01405) that the materials
tile, mosaics, pavers, trim units and thresholds
supplied conform to ANSI A137.1.
with five (5) years documented experience
G. Submit proof of warranty. with installations of similar scope, materials
H. Submit sample of installation system and design.
demonstrating compatibility/functional 1.13 Mock-Ups
relationships between adhesives, mortars, A. Provide mock-up of each type/style/finish/
grouts and other components under provision size/color of ceramic tile, mosaics, pavers,
of Section (01300) (01340). trim unit and threshold, along with respective
I. Submit list from manufacturer of installation installation adhesives, mortars, grouts and
system/adhesive/mortar/grout identifying a other installation materials, under provisions
minimum of three (3) similar projects, each with of Section (01400) (01405).
a minimum of ten (10) years service.
1.14 Pre-Installation Conference
J. For alternate materials, at least thirty (30) Pre-installation conference: At least three
days before bid date submit independent weeks prior to commencing the work attend a
laboratory test results confirming compliance meeting at the job site to discuss conformance
with specifications listed in Part 2 Products. with requirements of specification and job
1.12 Quality Assurance site conditions. Representatives of owner,
A. Tile Manufacturer (single source architect, general contractor, tile subcontractor,
responsibility) Tile Manufacturer, Installation System
Company specializing in ceramic tile, mosaics, Manufacturer and any other parties who are
pavers, trim units and/or thresholds with three involved in the scope of this installation must
(3) years minimum experience. Obtain tile attend the meeting.
from a single source with resources to provide
products of consistent quality in appearance
and physical properties.
21
Section 2: Part 1 General Information
22
Section 2: Part 1 General Information
23
Section 2: Part 2 Products
24
Section 2: Part 2 Products
25
Section 2: Part 2 Products
A. Waterproofing Membrane
LATICRETE 9235 Waterproofing Membrane** as
manufactured by LATICRETE International, Inc.
B. Crack Suppression Membrane
LATICRETE Blue 92 Anti-Fracture
Membrane** as manufactured by LATICRETE
International, Inc.
NOTE TO SPECIFIER: Edit applicable tile installation
accessories.
26
Section 2: Part 3 Execution Statement
27
Section 2: Part 3 Execution Statement
installation, follow method ESB414. For more B. Lath and Plaster Method
information on the wall and ceiling installation; Install prior to installing the waterproofing
follow method ES-W221(I). membrane: Install cleavage membrane
Structure to receive the installation assembly complying with current revision of ANSI A108.02
must be sound, solid, well bonded, stripped (3.8 Membrane or cleavage membrane). Install
clean and free from dust, wax, grease, sealer metal lath complying with the current revision of
and all other contamination which may reduce ANSI A108.1 (3.3 Requirements for lathing and
or prevent adhesion to comply with ANSI portland cement plastering, ANSI A108.02 (3.6
A108.02 (4.0). Metal lath) and A108.1A (1.0 1.2, 1.4, and 5.1).
Apply latex portland cement mortar as scratch/
B. Bonded Thick Bed Pitch Layer Over Floor
leveling coat over wire lath, concrete or masonry
Substrate
in compliance with current revision of ANSI
To provide pitch over a concrete deck, prepare
A108.01 (3.3.5.1) and A108.1A (1.4). Float surface
a LATICRETE latex leveling bed mix (see 3.4D
of scratch/leveling coat plumb, true and allow
thick bed mortar material below applied over
mortar to set until firm. For installation of tile,
a slurry bond coat consisting of LATICRETE
brick or stone, follow Thin Bed Method ( 3.4 E.).
254 Platinum). Apply mortar over dampened
substrate. Pitch layer 1/4" per 1' (6 mm per Use the following LATICRETE System Materials
300 mm) per ANSI A108.1A (2.3.4). LATICRETE 3701 Mortar Admix
C. List other Substrates as required and means LATICRETE 226 Thick Bed Mortar
of preparation as required LATICRETE 254 Platinum
(Insert any Special Means of Preparation
References
In addition to the surface preparation
LATICRETE Data Sheets: 231.9, 239.1, 677.0
requirements listed above.)
LATICRETE MSDS: 3701, 226, 254
NOTE TO SPECIFIER: The above are example surface
categories; edit for project specific surfaces and conditions. LATICRETE Technical Data Sheets: 106, 114,
122, 199, 204
3.3 Installation Accessories
(edit as required) C. Waterproofing Membrane
Waterproofing Membrane installed over pre-
3.4 Installation Tile, Brick and Stone sloped floor substrate under the mortar bed
A. General and over vertical lath and plaster portland
Install in accordance with current versions of cement scratch and brown coat walls and
American National Standards Institute, Inc. ceilings. Membrane must be used on all areas
(ANSI) A108 American National Standard in the steam room. Loop membrane into all slip
Specifications for Installation of Ceramic joints to allow for movement in these areas.
Tile and TCNA Handbook for Ceramic Tile
NOTE TO SPECIFIER: Adhesives/mastics, mortars and grouts
Installation. Cut and fit ceramic tile, brick for ceramic tile, mosaics, pavers, brick and stone are not
or stone neatly around corners, fittings, and replacements for waterproofing membranes and will not
obstructions. Perimeter pieces to be minimum prevent water penetration into occupied or storage spaces
below. Drains must be a two-part clamping ring style drains
half tile, brick or stone. Chipped, cracked, split with weepers and as per ASME A112.6.3. Place tile spacers
pieces and edges are not acceptable. Make or gravel around weep holes to prevent mortar from clogging
joints even, straight, plumb and of uniform the weep holes.
width to tolerance +/- 1/16" over 8' (1.5 mm Install the waterproofing membrane in
in 2.4 m). Install divider strips at junction of compliance with current revisions of ANSI
flooring and dissimilar materials. A108.01 (2.7 Waterproofing) and ANSI
A108.13. Review the installation and plan
the application sequence. Pre-cut LATICRETE
28
Section 2: Part 3 Execution Statement
9235 Waterproofing Membrane Reinforcing wide reinforcing fabric into liquid. Cover
Fabric, allowing 2" (50 mm) for overlap at ends with a second layer of liquid. When dry, seal
and sides to fit the areas as required. Roll up flashing with a waterproof sealant. Refer to
the pieces for easy handling and placement. Drawing WP300 for information on completing
Shake or stir LATICRETE 9235 Waterproofing penetrations treatment.
Membrane Liquid before using. Main Membrane Application
Pre-Treat Coves, Corners and Joints Allow pre-treated areas to dry to the touch. Apply
Apply a liberal coat of liquid at coves, corners, a liberal coat of LATICRETE 9235 Waterproofing
seams, joints and changes in substrate plane. Membrane Liquid with brush or roller over
Fold 6" (150 mm) wide reinforcing fabric in half substrate including pre-treated areas. Before the
and imbed it into the liquid, flashing fabric 3" coat dries, unroll LATICRETE 9235 Waterproofing
(75 mm) up walls. Apply second liberal coat of Membrane Reinforcing Fabric, smooth out any
liquid to seal reinforcing fabric. Refer to TDS wrinkles and press with brush or roller until
188 for corner and cove treatment. LATICRETE 9235 Waterproofing Membrane
Wet coat thickness is 20 30 mils, 0.02 0.03", Liquid bleeds through to surface. Apply another
0.5 0.8 mm; use wet film gauge to check liberal coat of LATICRETE 9235 Waterproofing
thickness; consumption/coat is approximately Membrane Liquid and allow it to dry to the
0.01 gal/ft l (0.4 l/m2); coverage/coat is touch, ~1 3 hours at 70F (21C) and 50% RH.
approximately 100 ft2/gal. (2.5 m2/l ); Apply a third liberal coat of LATICRETE 9235
Waterproofing Membrane Liquid to seal
Pre-Treat Drains
membrane. When last coat has dried to the
Cut a square of reinforcing fabric approximately
touch, inspect final surface for pinholes, voids
38" x 38" (965 mm x 965 mm). In the center
or thin spots. Use additional LATICRETE 9235
of the reinforcing fabric square, cut a hole
Waterproofing Membrane Liquid to seal such
that matches the diameter of the drain throat
defects. Allow LATICRETE 9235 Waterproofing
as closely as possible. Apply a liberal coat of
Membrane to cure for at least 7 days at 70F
liquid around and over the bottom half of the
(21C) and 50% RH before running water
drain-clamping ring. Center the circular cutout
penetration tests.
over the drain throat and imbed the reinforcing
fabric square into the liquid. If 38" (965 mm) Protection
wide reinforcing fabric is not available, imbed Provide protection for newly installed
pieces of 6" (150 mm) wide fabric into the membrane, even if covered with a thin bed
liquid, encircling the drain throat as closely as ceramic tile, stone or brick installation, against
possible. Cover with a second layer of liquid. exposure to rain or other water for a minimum
When dry, apply a sealant bead (e.g. LATICRETE of 5 days at 70F (21C) and 50% RH.
Latasil) where the reinforcing square cutout Flood Testing
meets the drain throat. Install top half of Allow membrane to cure fully before flood
drain clamping ring. Refer to Drawing WP301, testing, typically 7 days at 70F (21C) and
WP302, WP303 for information on completing 50% RH. Cold and/or wet conditions will
drain treatment. require a longer curing time.
Pre-Treat Penetrations Tile/Stone Installation Notes
Pack any gaps around pipes, lights or other Once membrane has dried to the touch,
penetrations with a compressible backer rod ceramic tile, stone or brick maybe installed
and suitable sealant (e.g. LATICRETE Latasil). by the thin bed method with a LATICRETE
Apply a liberal coat of liquid around penetration latex thin-set mortar. Allow membrane to
opening. Imbed pieces of 6" (150 mm)
29
Section 2: Part 3 Execution Statement
1. Chemical Resistant, Water Cleanable Tile- sponge diagonally over the scrubbed surfaces
Grouting Epoxy (ANSI A118.3) to remove froth. Rinse sponge frequently and
Follow manufacturers recommendations change cleaning solution at least every 50 ft2
for minimum cure time prior to grouting. (4.7 m2). Discard sponges as they become
Store liquid components of LATICRETE gummy with residue. Within one (1) hour
SpectraLOCK PRO Grout for 24 hours at of finishing first cleaning, clean the same
70 80F (21 27C) prior to use to facilitate area again following the same procedure but
mixing and application. Substrate temperature utilizing a clean white scrub pad and fresh
must be 40 95F (4 35C). Verify joints are cleaning solution. Rinse scrub pad frequently.
free of dirt, debris or grout spacers. Sponge or Drag a clean sponge diagonally over the
wipe dust/dirt off tile faces and remove water scrubbed surfaces to remove froth. Use each
standing in joints. Apply grout release to face side of sponge only once before rinsing and
of absorptive, abrasive, non-slip or rough change cleaning solution at least every 50
textured ceramic tile, pavers, bricks, stone ft2 (4.7 m2). Allow cleaned areas to dry and
or trim units that are not hot paraffin coated inspect tile/stone surface. For persistent grout
to facilitate cleaning. Cut open pouch and film/haze (within 24 hours), repeat scrubbing
pour LATICRETE SpectraLOCK PRO Grout Part procedure with undiluted white vinegar and
A Liquid into a clean mixing pail. Then open clean pad. Rinse with clean water and allow
pouch and pour LATICRETE SpectraLOCK PRO surface to dry. Inspect grout joint for pinholes/
Grout Part B Liquid into the mixing pail. Mix by voids and repair them with freshly mixed
hand or with a slow speed (<300 rpm) mixer LATICRETE SpectraLOCK PRO Grout.
until the two liquids are well blended. Then,
Cautions: Do not use undiluted white vinegar on polished
while mixing, add LATICRETE SpectraLOCK marble or limestone unless a test spot in an inconspicuous
PRO Grout Part C Powder and blend until area indicates no change in finish appearance; Do not use
acid cleaners on epoxy grout less than 7 days old.
uniform. Install LATICRETE SpectraLOCK PRO
Grout in compliance with current revisions of Use the following LATICRETE System Materials
ANSI A108.02 (3.13) and ANSI A108.6 (3.0 LATICRETE SpectraLOCK PRO Grout
4.0). Spread using a sharp edged, hard rubber
References
float and work grout into joints. Using strokes
LATICRETE Data Sheets: 685.0, 685.5
diagonal (at 45 angle) to the grout lines, pack
joints full and free of voids/pits. Then hold LATICRETE MSDS: PRO Part A, PRO Part B,
float face at a 90 angle to grouted surface Part C Powder, Cleaning Additive
and use float edge to squeegee off excess LATICRETE Technical Data Sheets: 111, 198,
grout, stroking diagonally to avoid pulling 212, 400
grout out of filled joints. Once excess grout is 2. Polymer Modified Cement Grout (ANSI
removed, a thin film/haze will be left. Initial A118.7)
cleaning of the remaining film/haze can begin Allow ceramic tile, mosaics, pavers, brick or
approximately 20 30 minutes after grouting stone installation to cure a minimum of 24
(wait longer at colder temperatures). Begin by hours at 70F (21C). Verify grout joints are
mixing cleaning additive packet with 2 gallons free of dirt, debris or tile spacers. Sponge or
(7.6 l) of clean water in a clean bucket to make wipe dust/dirt off veneer face and remove any
cleaning solution. Dip a clean sponge into the water standing in joints. Apply grout release
bucket and then wring out cleaning solution to face of absorptive, abrasive, non-slip or
until sponge is damp. Using a circular motion, rough textured ceramic tile, pavers, bricks, or
lightly scrub grouted surfaces with the damp trim units that are not hot paraffin coated to
sponge to dissolve grout film/haze. Then drag facilitate cleaning. Surface temperature must
31
Section 2: Part 3 Execution Statement
be between 40 90F (4 32C). Thoroughly NOTE TO SPECIFIER: select one of following and specify color
for each type/color of ceramic tile, mosaic, paver, trim unit.
shake or stir LATICRETE 1776 Grout Enhancer
and pour into a clean mixing container. Add 1. Latex portland cement sanded floor grout
LATICRETE 1500 Sanded Grout or LATICRETE for joint widths 1/16" (1.5 mm) and 1/2"
1600 Unsanded Grout powder, in approximately (12 mm).
the proportions indicated in the chart below, 2. Latex portland cement unsanded grout for
to the container while mixing. Mix by hand soft glazed tiles and soft/polished stone
or with a slow speed mixer to a smooth, stiff with joints widths 1/8" (3 mm).
consistency.
Use the following LATICRETE System Materials
LATICRETE 1776 LATICRETE 1500 LATICRETE 1600 LATICRETE 1500 Sanded Grout
Grout Enhancer Sanded Grout Unsanded Grout
26 fl oz (0.8 l) bottle 10 lbs (4.5 kg) bag LATICRETE 1600 Unsanded Grout
47 fl oz (1.4 l) bottle 8 lbs (3.6 kg) bag LATICRETE 1776 Grout Enhancer
64 fl oz (1.9 l) bottle 25 lbs (11.3 kg) bag
References
Install polymer modified cement grout in LATICRETE Data Sheets: 256.0, 258.0, 265.0
compliance with current revisions of ANSI
LATICRETE MSDS: 1500, 1600, 1776
A108.1A (7.0 Grouting of tile) and ANSI
A108..02 (4.5 Cleaning tile) and ANSI A108.10. LATICRETE Technical Data Sheets: 201m 400
Dampen dry surfaces with clean water. Spread G. Expansion and Control Joints
using a sharp edged, hard rubber float and Provide control or expansion joints as located
work grout into joints. Using diagonal (at 45 in contract drawings and in full conformity,
angle to direction of grout line) strokes, pack especially in width and depth, with architectural
joints full and free of voids/pits. Hold float face details.
at a 90 angle to grouted surface and use float 1. Substrate joints must carry through, full
edge to squeegee off excess grout, stroking width, to surface of tile, brick or stone.
diagonally to reduce pulling grout out of filled
2. Install expansion joints in tile, brick or
joints. Initial cleaning can begin as soon as
stone work over construction/cold joints
grout has become firm, typically 20 30 minutes
or control joints in substrates.
after grouting depending on temperature. Drag
a clean towel dampened with water, or wipe a 3. Install expansion joints where tile, brick or
clean, dampened sponge, diagonally over the stone abut restraining surfaces (such as
veneer face to remove any grout haze left after perimeter walls, curbs, columns), changes
squeegeeing. Rinse towel/sponge frequently in plane and corners.
and change rinse water at least every 200 ft2 4. Joint width and spacing depends on
(19 m2). Repeat this cleaning sequence again application follow TCNA Handbook
if grout haze is still present. Allow grout joints for Ceramic Tile Installation Detail
to become firm. Buff surface of grout with EJ-171 Expansion Joints or consult sealant
clean coarse cloth. Inspect joint for pinholes/ manufacturer for recommendation based
voids and repair them with freshly mixed grout. on project parameters.
Within 24 hours, check for remaining haze and 5. Joint width: 1/8" (3 mm) and 1" (25 mm).
remove it with warm soapy water and a nylon
6. Joint width: depth ~2:1 but joint depth
scrubbing pad, using a circular motion, to
must be 1/8" (3 mm) and 1/2" (12 mm).
lightly scrub surfaces and dissolve haze/film.
Do not use acid cleaners on latex portland 7. Layout (field defined by joints): 1:1 length:
cement grout less than 10 days old. width is optimum but must be 2:1.
32
Section 2: Part 3 Execution Statement
33
Section 2: Part 4 Health and Safety
34
Section 3: Specifications for Steam Room
Thin Bed Method
35
Section 3: Detail ES-SR614
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
* United States Patent No.: 6881768 (and other Patents).
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
36 Offices, Marca Registrada. All other trademarks are property of their respective companies.
Section 3: Part 1 General Information
37
Section 3: Part 1 General Information
B. American National Standards Institute M. American Society For Testing And Materials
(ANSI) A137.1 (ASTM) C150
American National Standard Specifications For Standard Specification for Portland Cement
Ceramic Tile N. American Society For Testing And Materials
(ASTM) C171
C. American National Standards Institute
(ANSI) A108.01 A108.17 Standard Specification for Sheet Materials for
American National Standard Specifications For Curing Concrete
The Installation Of Ceramic Tile O. American Society For Testing And Materials
(ASTM) C241
D. American National Standards Institute
(ANSI) A118.1 A118.12 Standard Test Method for Abrasion Resistance
American National Standard Specifications For of Stone Subjected to Foot Traffic
The Installation Of Ceramic Tile P. American Society For Testing And Materials
(ASTM) C267
E. American National Standards Institute
(ANSI) A136.1 Standard Test Method for Chemical Resistance
American National Standard Specifications For of Mortars, Grouts, and Monolithic Surfacings
The Installation Of Ceramic Tile Q. American Society For Testing And Materials
(ASTM) C482
F. American Plywood Association (APA) Y510T
Standard Test Method for Bond Strength of
Plywood Design Specifications
Ceramic Tile to Portland Cement
G. American Society For Testing And Materials
(ASTM) A82 R. American Society For Testing And Materials
(ASTM) C503
Standard Specification for Steel Wire, Plain, for
Standard Specification for Marble Dimension
Concrete Reinforcement
Stone (Exterior)
H. American Society For Testing And Materials
(ASTM) A185 S. American Society For Testing And Materials
(ASTM) C531
Standard Specification for Steel Welded Wire
Standard Test Method for Linear Shrinkage and
Fabric, Plain, for Concrete Reinforcement
Coefficient of Thermal Expansion of Chemical-
I. American Society For Testing And Materials Resistant Mortars, Grouts, Monolithic
(ASTM) C33 Surfacings and Polymer Concretes
Standard Specification for Concrete Aggregate
T. American Society For Testing And Materials
J. American Society For Testing And Materials (ASTM) C627
(ASTM) C36 Standard Test Method for Evaluating Ceramic
Standard Specification for Gypsum Wallboard Floor Tile Installation Systems Using the
K. American Society For Testing And Materials Robinson-Type Floor Tester
(ASTM) C109
U. American Society For Testing And Materials
Standard Test Method for Compressive (ASTM) C794
Strength of Hydraulic Cement Mortars (Using Standard Test Method for Adhesion-in-Peel of
2" or [50 mm] Cube Specimens) Elastomeric Joint Sealants
V. American Society For Testing And Materials
(ASTM) C847
Standard Specification for Metal Lath
38
Section 3: Part 1 General Information
W. American Society For Testing And Materials GG. American Society For Testing And
(ASTM) C905 Materials (ASTM) D4397
Standard Test Method for Apparent Density Standard Specification for Polyethylene
of Chemical-Resistant Mortars, Grouts, and Sheeting for Construction, Industrial and
Monolithic Surfacings Agricultural Applications
X. American Society For Testing And Materials HH. American Society For Testing And
(ASTM) C920 Materials (ASTM) D4716
Standard Specification for Elastomeric Joint Standard Test Method for Determining the (In
Sealants Plane) Flow Rate Per Unit Width and Hydraulic
Y. American Society For Testing And Materials Transmissivity of a Geo-synthetic Using a
(ASTM) C955 Constant Head
Standard Specification for Load Bearing II. American Society For Testing And Materials
(Transverse and Axial) Steel Studs, Runners (ASTM) E84
(Tracks), and Bracing or Bridging for Screw Standard Test Method for Surface Burning
Application of Gypsum Board and Metal Plaster Characteristics of Building Materials
Bases JJ. American Society For Testing And Materials
Z. American Society For Testing And Materials (ASTM)
(ASTM) D226 E90 Standard Test Method for Laboratory
Standard Specification for Asphalt- Measurement of Airborne Sound Transmission
Saturated Organic Felt Used in Roofing And Loss of Building Partitions
Waterproofing KK. American Society For Testing And
AA. American Society For Testing And Materials (ASTM) E96
Materials (ASTM) D227 Standard Test Methods for Water Vapor
Standard Specification for Coal-Tar Transmission of Materials
Saturated Organic Felt Used in Roofing and LL. American Society For Testing And Materials
Waterproofing (ASTM) E413
BB. American Society For Testing And Standard Classification for Rating Sound
Materials (ASTM) D751 Insulation
Standard Test Method for Coated Fabrics MM. American Society For Testing And
CC. American Society For Testing And Materials Materials (ASTM)
(ASTM) D751 E492 Standard Test Method for Laboratory
Standard Test Method for Rubber Property Measurement of Impact Sound Transmission
Durometer Hardness Through Floor-Ceiling Assemblies Using the
DD. American Society For Testing And Tapping Machine
Materials (ASTM) D1248 NN. American Society For Testing And
Standard Test Method for Staining of Porous Materials (ASTM) E989
Substances by Joint Sealants Standard Classification for Determination of
EE. American Society For Testing And Materials Impact Insulation Class (IIC)
(ASTM) D2240 OO. American Society of Mechanical Engineers
Standard Test Method for Coated Fabrics (ASME) ASME A112.6.3
FF. American Society For Testing And Materials Floor and Trench Drains
(ASTM) D4263 PP. Canadian Sheet Steel Building Institute
Standard Test Method for Indicating Moisture (CSSBI)
in Concrete by The Plastic Sheet Method Lightweight Steel Framing Binder (Publication
52M)
39
Section 3: Part 1 General Information
40
Section 3: Part 1 General Information
3. LEED NC v2.2 Credit MR 5.2 (20% Extracted, B. Installation System Manufacturer (single
Processed and Manufactured Regionally): source responsibility)
Product data indicating location of material Company specializing in adhesives, mortars,
manufacturer for regionally manufactured grouts and other installation materials with ten
materials. (10) years minimum experience and ISO 9001
certification. Obtain installation materials from
a. Include statement indicating cost and
single source manufacturer to insure consistent
distance from manufacturer to Project for
quality and full compatibility.
each regionally manufactured product.
C. Submit shop drawings and manufacturers C. Submit laboratory confirmation of
adhesives, mortars, grouts and other
product data under provisions of Section installation materials
(01300) (01340). 1. Identify proper usage of specified materials
D. Submit samples of each type/style/finish/ using positive analytical method.
size/color of ceramic tile, mosaic, paver, trim 2. Identify compatibility of specified materials
unit or threshold under provisions of Section using positive analytical method.
(01300) (01340).
3. Identify proper color matching of specified
E. Submit manufacturers installation materials using a positive analytical
instructions under provisions of Section method.
(01300) (01340).
D. Installer Qualifications
F. Submit manufacturers certification under
Company specializing in installation of ceramic
provisions of Section (01405) that the materials
tile, mosaics, pavers, trim units and thresholds
supplied conform to ANSI A137.1.
with five (5) years documented experience
G. Submit proof of warranty. with installations of similar scope, materials
H. Submit sample of installation system and design.
demonstrating compatibility/functional 1.13 Mock-Ups
relationships between adhesives, mortars, A. Provide mockup of each type/style/finish/
grouts and other components under provision size/color of ceramic tile, mosaics, pavers,
of Section (01300) (01340). trim unit and threshold, along with respective
I. Submit list from manufacturer of installation installation adhesives, mortars, grouts and
system/adhesive/mortar/grout identifying a other installation materials, under provisions
minimum of three (3) similar projects, each with of Section (01400) (01405).
a minimum of ten (10) years service.
1.14 Pre-Installation Conference
J. For alternate materials, at least thirty (30) Pre-installation conference: At least three
days before bid date submit independent weeks prior to commencing the work attend a
laboratory test results confirming compliance meeting at the job site to discuss conformance
with specifications listed in Part 2 Products. with requirements of specification and job
1.12 Quality Assurance site conditions. Representatives of owner,
A. Tile Manufacturer (single source architect, general contractor, tile subcontractor,
responsibility) Tile Manufacturer, Installation System
Company specializing in ceramic tile, mosaics, Manufacturer and any other parties who are
pavers, trim units and/or thresholds with three involved in the scope of this installation must
(3) years minimum experience. Obtain tile attend the meeting.
from a single source with resources to provide
products of consistent quality in appearance
and physical properties.
41
Section 3: Part 1 General Information
1.15 Delivery, Storage and Handling until cured to prevent premature evaporation
A. Acceptance at Site: deliver and store of moisture. Epoxy mortars and grouts require
packaged materials in original containers with surface temperatures between 60F (16C)
seals unbroken and labels, including grade and 90F (32C) at time of installation. It is the
seal, intact until time of use, in accordance General Contractors responsibility to maintain
with manufacturers instructions. temperature control.
B. Store ceramic tile and installation system 1.17 Sequencing and Scheduling
materials in a dry location; handle in a A. Scheduling
manner to prevent chipping, breakage, and Coordinate installation of tile work with related
contamination. work.
C. Protect latex additives, organic adhesives, B. Site Preparation
epoxy adhesives and sealants from freezing or Proceed with tile work only after curbs, vents,
overheating in accordance with manufacturers drains, piping, and other projections through
instructions; store at room temperature when substrate have been installed and when
possible. substrate construction and framing of openings
D. Store portland cement mortars and grouts have been completed.
in a dry location. NOTES FOR SPECIFIER: Edit for project specific sequence
and scheduling.
1.16 Project/Site Conditions
A. Ventilation 1.18 Warranty
Provide ventilation and protection The Contractor warrants the work of this
of environment as recommended by Section to be in accordance with the Contract
manufacturer. Documents and free from faults and defects
B. Space Heating in materials and workmanship for a period
Prevent carbon dioxide damage to ceramic of 10 years. The manufacturer of adhesives,
tile, mosaics, pavers, trim, thresholds, as mortars, grouts and other installation materials
well as adhesives, mortars, grouts and other shall provide a written ten (10) year warranty,
installation materials, by venting temporary which covers materials and labor reference
heaters to the exterior. LATICRETE Warranty Data Sheet 230.12 for
complete details and requirements.
C. Working Temperature
Maintain ambient temperatures not less than 1.19 Maintenance
50F (10C) or more than 100F (38C) during Submit maintenance data under provisions
installation and for a minimum of seven (7) of Section 01730. Include cleaning methods,
days after completion. Setting of portland cleaning solutions recommended, stain
cement is retarded by low temperatures. removal methods, as well as polishes and
Protect work for extended period of time and waxes recommended.
from damage by other trades. Installation 1.20 Extra Materials Stock
with latex portland cement mortars requires Upon completion of the work of this Section,
substrate, ambient and material temperatures deliver to the Owner 2% minimum additional
at least 37F (3C). There should be no ice tile and trim shape of each type, color, pattern
in slab. Freezing after installation will not and size used in the Work, as well as extra
damage latex portland cement mortars. stock of adhesives, mortars, grouts and other
Protect portland cement based mortars and installation materials for the Owners use in
grouts from direct sunlight, radiant heat, replacement and maintenance. Extra stock is
forced ventilation (heat and cold. and drafts to be from same production run or batch as
42
original tile and installation materials.
Section 3: Part 2 Products
44
Section 3: Part 2 Products
45
Section 3: Part 3 Execution Statement
46
Section 3: Part 3 Execution Statement
Structure to receive the installation assembly NOTE TO SPECIFIER: Adhesives/mastics, mortars and grouts
for ceramic tile, mosaics, pavers, brick and stone are not
must be sound, solid, well bonded, stripped replacements for waterproofing membranes and will not
clean and free from dust, wax, grease, sealer prevent water penetration into occupied or storage spaces
and all other contamination which may reduce below. Drains must be a two-part clamping ring style drains
with weepers and as per ASME A112.6.3. Place tile spacers
or prevent adhesion. or gravel around weep holes to prevent mortar from clogging
B. Bonded Thick Bed the weep holes.
Pitch Layer Over Floor Substrate To provide Install the waterproofing membrane in
pitch over a concrete deck, prepare a compliance with current revisions of ANSI
LATICRETE latex leveling bed mix (see 3.4 C A108.01 (2.7 Waterproofing) and ANSI
thick bed mortar material below applied over A108.13. Review the installation and plan the
a slurry bond coat consisting of LATICRETE application sequence. Pre-cut LATICRETE 9235
254 Platinum). Apply mortar over dampened Waterproofing Membrane Reinforcing Fabric,
substrate. Pitch layer 1/4" per 1' (6 mm per allowing 2" (50 mm) for overlap at ends and
0.3 m) per ANSI A108.1A (2.3.4). sides to fit the areas as required. Roll up the
C. (List other Substrates as required and pieces for easy handling and placement.
means of preparation as required) Shake or stir LATICRETE 9235 Waterproofing
(Insert any Special Means of Preparation In Membrane Liquid before using.
addition to the surface preparation requirements Pre-Treat Coves, Corners and Joints
listed above; ) Apply a liberal coat of liquid at coves, corners,
NOTE TO SPECIFIER: The above are example surface seams, joints and changes in substrate plane.
categories; edit for project specific surfaces and conditions.
Fold 6" (150 mm) wide reinforcing fabric in half
3.3 Installation Accessories and imbed it into the liquid, flashing fabric 3"
(edit as required) (75 mm) up walls. Apply second liberal coat of
liquid to seal reinforcing fabric. Refer to TDS
3.4 Installation Tile, Brick and Stone 188 for corner and cove treatment.
A. General
Wet coat thickness is 20 30 mils, 0.02 0.03",
Install in accordance with current versions of
0.5 0.8 mm; use wet film gauge to check
American National Standards Institute, Inc.
thickness; consumption/coat is approximately
(ANSI) A108 American National Standard
0.01 gal/ft2 (0.4 l/m2); coverage/coat is
Specifications for Installation of Ceramic
approximately 100 ft2/gal. (2.5 m2/l).
Tile and TCNA Handbook for Ceramic Tile
Installation. Cut and fit ceramic tile, brick Pre-Treat Drains
or stone neatly around corners, fittings, and Cut a square of reinforcing fabric approximately
obstructions. Perimeter pieces to be minimum 38" x 38" (965 mm x 965 mm). In the center
half tile, brick or stone. Chipped, cracked, split of the reinforcing fabric square, cut a hole
pieces and edges are not acceptable. Make that matches the diameter of the drain throat
joints even, straight, plumb and of uniform as closely as possible. Apply a liberal coat of
width to tolerance +/- 1/16" over 8' (1.5 mm liquid around and over the bottom half of the
in 2.4 m). Install divider strips at junction of drain-clamping ring. Center the circular cutout
flooring and dissimilar materials. over the drain throat and imbed the reinforcing
fabric square into the liquid. If 38" (965 mm)
B. Waterproofing Membrane
wide reinforcing fabric is not available, imbed
Waterproofing Membrane installed over
pieces of 6" (150 mm) wide fabric into the
pre-sloped floor substrate and all walls and
liquid, encircling the drain throat as closely
ceilings. Membrane must be used on all areas
as possible. Cover with a second layer of
in the steam room. Loop membrane into all slip
joints to allow for movement in these areas.
47
Section 3: Part 3 Execution Statement
48
Section 3: Part 3 Execution Statement
49
Section 3: Part 3 Execution Statement
good contact with the substrate and comb with pour LATICRETE SpectraLOCK PRO Grout Part
notched side of trowel. Spread only as much A Liquid into a clean mixing pail. Then open
latex portland cement mortar as can be covered pouch and pour LATICRETE SpectraLOCK PRO
while the mortar surface is still wet and tacky. Grout Part B Liquid into the mixing pail. Mix by
When installing large format (>8" x 8"/200 hand or with a slow speed (<300 rpm) mixer
mm x 200 mm) tile/stone, rib/button/lug until the two liquids are well blended. Then,
back tiles, pavers or sheet mounted ceramics/ while mixing, add LATICRETE SpectraLOCK
mosaics, spread latex portland cement mortar PRO Grout Part C Powder and blend until
onto the back of (i.e. back-butter) each piece/ uniform. Install LATICRETE SpectraLOCK PRO
sheet in addition to trowelling latex portland Grout in compliance with current revisions of
cement mortar over the substrate. Beat each ANSI A108.02 (3.13) and ANSI A108.6 (3.0
piece/sheet into the latex portland cement 4.0). Spread using a sharp edged, hard rubber
mortar with a beating block or rubber mallet float and work grout into joints. Using strokes
to insure full bedding and flatness. Allow diagonal (at 45 angle) to the grout lines, pack
installation to set until firm. Clean excess latex joints full and free of voids/pits. Then hold
portland cement mortar from tile or stone face float face at a 90 angle to grouted surface
and joints between pieces. and use float edge to squeegee off excess
Use the following LATICRETE System Materials grout, stroking diagonally to avoid pulling
LATICRETE 254 Platinum grout out of filled joints. Once excess grout is
removed, a thin film/haze will be left. Initial
Reference cleaning of the remaining film/haze can begin
LATICRETE Data Sheet: 677.0 approximately 20 30 minutes after grouting
LATICRETE MSDS: 254 (wait longer at colder temperatures). Begin by
LATICRETE Technical Data Sheets: 105, 118, mixing cleaning additive packet with 2 gallons
126, 129, 199, 209 (7.6 l) of clean water in a clean bucket to make
cleaning solution. Dip a clean sponge into the
F. Grouting or Pointing
bucket and then wring out cleaning solution
NOTE TO SPECIFIER: Select one of following and specify
color for each type/color of ceramic tile, mosaic, paver, trim until sponge is damp. Using a circular motion,
unit. lightly scrub grouted surfaces with the damp
1. Chemical Resistant, Water Cleanable sponge to dissolve grout film/haze. Then drag
Tile-Grouting Epoxy (ANSI A118.3). Follow sponge diagonally over the scrubbed surfaces
manufacturers recommendations for minimum to remove froth. Rinse sponge frequently and
cure time prior to grouting. Store liquid change cleaning solution at least every 50 ft2
components of LATICRETE SpectraLOCK (4.7 m2). Discard sponges as they become
Pro Grout for 24 hours at 70 80F (21 gummy with residue. Within one (1) hour
27C) prior to use to facilitate mixing and of finishing first cleaning, clean the same
application. Substrate temperature must be area again following the same procedure but
40 95F (4 35C). Verify joints are free of utilizing a clean white scrub pad and fresh
dirt, debris or grout spacers. Sponge or wipe cleaning solution. Rinse scrub pad frequently.
dust/dirt off tile faces and remove water Drag a clean sponge diagonally over the
standing in joints. Apply grout release to face scrubbed surfaces to remove froth. Use each
of absorptive, abrasive, non-slip or rough side of sponge only once before rinsing and
textured ceramic tile, pavers, bricks, stone change cleaning solution at least every 50
or trim units that are not hot paraffin coated ft2 (4.7 m2). Allow cleaned areas to dry and
to facilitate cleaning. Cut open pouch and inspect tile/stone surface. For persistent grout
50
Section 3: Part 3 Execution Statement
film/haze (within 24 hours), repeat scrubbing Install polymer modified cement grout in
procedure with undiluted white vinegar and compliance with current revisions of ANSI
clean pad. Rinse with clean water and allow A108.1A (7.0 Grouting of tile), ANSI A108.02
surface to dry. Inspect grout joint for pinholes/ (4.5 Cleaning tile) and ANSI A108.10. Dampen
voids and repair them with freshly mixed dry surfaces with clean water. Spread using
LATICRETE SpectraLOCK PRO Grout. a sharp edged, hard rubber float and work
Cautions: Do not use undiluted white vinegar on polished grout into joints. Using diagonal (at 45 angle
marble or limestone unless a test spot in an inconspicuous to direction of grout line) strokes, pack joints
area indicates no change in finish appearance; Do not use full and free of voids/pits. Hold float face at
acid cleaners on epoxy grout less than 7 days old.
a 90 angle to grouted surface and use float
Use the following LATICRETE System Materials edge to squeegee off excess grout, stroking
LATICRETE SpectraLOCK PRO Grout diagonally to reduce pulling grout out of filled
References joints. Initial cleaning can begin as soon as
LATICRETE Data Sheets: 685.0, 685.5 grout has become firm, typically 20 30 minutes
after grouting depending on temperature. Drag
LATICRETE MSDS: PRO Part A, PRO Part B,
a clean towel dampened with water, or wipe a
Part C Powder, Cleaning Additive
clean, dampened sponge, diagonally over the
LATICRETE Technical Data Sheets: 111, 198, veneer face to remove any grout haze left after
212, 400 squeegeeing. Rinse towel/sponge frequently
2. Polymer Modified Cement Grout (ANSI and change rinse water at least every 200 ft2
A118.7). Allow ceramic tile, mosaics, pavers, (19 m2). Repeat this cleaning sequence again
brick or stone installation to cure a minimum if grout haze is still present. Allow grout joints
of 24 hours at 70F (21C). Verify grout to become firm. Buff surface of grout with
joints are free of dirt, debris or tile spacers. clean coarse cloth. Inspect joint for pinholes/
Sponge or wipe dust/dirt off veneer face voids and repair them with freshly mixed grout.
and remove any water standing in joints. Within 24 hours, check for remaining haze and
Apply grout release to face of absorptive, remove it with warm soapy water and a nylon
abrasive, non-slip or rough textured ceramic scrubbing pad, using a circular motion, to
tile, pavers, bricks, or trim units that are not lightly scrub surfaces and dissolve haze/film.
hot paraffin coated to facilitate cleaning. Do not use acid cleaners on latex portland
Surface temperature must be between 40 cement mortar grout less than 7 days old.
90F (4 32C). Thoroughly shake or stir NOTE TO SPECIFIER: Select one of following and specify
LATICRETE 1776 Grout Enhancer and pour color for each type/color of ceramic tile, mosaic, paver, trim
into a clean mixing container. Add LATICRETE unit.
1500 Sanded Grout or LATICRETE 1600 1. Latex portland cement sanded floor grout
Unsanded Grout powder, in approximately for joint widths 1/16"( 1.5 mm ) and 1/2"
the proportions indicated in the chart below, (12 mm).
to the container while mixing. Mix by hand
2. Latex portland cement unsanded grout for
or with a slow speed mixer to a smooth, stiff
soft glazed tiles and soft/polished stone
consistency.
with joints widths 1/8" (3 mm).
LATICRETE 1776 LATICRETE 1500 LATICRETE 1600
Grout Enhancer Sanded Grout Unsanded Grout
26 fl oz (0.8 l) bottle 10 lbs (4.5 kg) bag
47 fl oz (1.4 l) bottle 8 lbs (3.6 kg) bag
64 fl oz (1.9 l) bottle 25 lbs (11.3 kg) bag
51
Section 3: Part 3 Execution Statement
Use the following LATICRETE System Materials on expansion joint design and as specified in
LATICRETE 1500 Sanded Grout 07920. Apply masking tape to face of tile,
LATICRETE 1600 Unsanded Grout brick or stone veneer. Use caulking gun, or
other applicator, to completely fill joints with
LATICRETE 1776 Grout Enhancer
sealant. Within 5 10 minutes of filling joint,
References tool sealant surface to a smooth finish.
LATICRETE Data Sheets: 256.0, 258.0, 265.0 Remove masking tape immediately after
LATICRETE MSDS: 1500, 1600, 1776 tooling joint. Wipe smears or excess sealant off
LATICRETE Technical Data Sheets: 201, 400 the face of non-glazed tile, brick, stone or other
absorptive surfaces immediately.
G. Expansion and Control Joints
Provide control or expansion joints as located Use the following LATICRETE System Materials
in contract drawings and in full conformity, LATICRETE Latasil
especially in width and depth, with architectural LATICRETE Latasil 9118 Primer
details. References
1. Substrate joints must carry through, full LATICRETE Detail Drawings: WP300, WP301,
width, to surface of tile, brick or stone. WP302, WP303, EJ-01, EJ-02, EJ-03, EJ-04,
2. Install expansion joints in tile, brick or EJ-05, EJ-06, EJ-07, EJ-08, EJ-09, EJ-10, EJ-11,
stone work over construction/cold joints EJ-12, EJ-13, EJ-14, EJ-15, P605 (Sealant
or control joints in substrates. treatments only)
3. Install expansion joints where tile, brick or LATICRETE Data Sheets: 6200.1, 6524.1, 6526.1
stone abut restraining surfaces (such as LATICRETE MSDS: Latasil, Stone Primer, Pool
perimeter walls, curbs, columns), changes Primer
in plane and corners. LATICRETE Technical Data Sheets: 211, 252
4. Joint width and spacing depends on H. Adjusting
application follow TCNA Handbook Correction of defective work for a period of
for Ceramic Tile Installation Detail one (1) year following substantial completion,
EJ-171 Expansion Joints or consult sealant return to job and correct all defective work.
manufacturer for recommendation based Defective work includes, without limitation,
on project parameters. tiles broken in normal abuse due to deficiencies
5. Joint width: 1/8" (3 mm) and 1" (25 mm). in setting bed, loose tiles or grout, and all other
6. Joint width: depth ~2:1 but joint depth defects which may develop as a result of poor
must be 1/8" (3 mm) and 1/2" (12 mm). workmanship.
7. Layout (field defined by joints): 1:1 length: 3.5 Cleaning
width is optimum but must be 2:1. Clean excess mortar/epoxy from veneer
Remove all contaminants and foreign material surfaces with water before they harden and
from joint spaces/surfaces, such as dirt, dust, as work progresses. Do not contaminate open
oil, water, frost, setting/grouting materials, grout/caulk joints while cleaning. Sponge and
sealers and old sealant/backer. Use LATICRETE wash veneers diagonally across joints. Do not
Latasil 9118 Primer for underwater or use acids for cleaning. Polish with clean dry
permanent wet area applications, or for cloth. Remove surplus materials and leave
porous stone (e.g. limestone, sandstone, premises broom clean.
etc) installations. Install appropriate Backing
Material (e.g. closed cell backer rod) based
52
Section 3: Part 3 Execution Statement
3.6 Protection
A. Time to Traffic
Protect finished installation under provisions
of 01500 and 01535. Close areas to other
trades and traffic until tile being installed has
set firmly. Keep traffic off horizontal portland
cement thick bed mortar installations for at
least 72 hours at 70F (21C).
B. Curing
Keep floors installed with epoxy adhesive
closed to foot traffic for 24 hours at 70F (21C),
and to heavy traffic for 48 hours at 70F (21C)
unless instructed differently by manufacturer.
Use kneeling boards, or equivalent, to walk/
work on newly tiled floors. Cure tile work
in swimming pools, fountains and other
continuous immersion applications for 10 days
at 70F (21C) for epoxy based grout and 14 days
at 70F (21C) for latex portland cement based
grout before flood testing or filling installation
with water. Extend period of protection of tile
work at lower temperatures, below 60F (15C),
and at high relative humidity (>70% RH) due
to retarded set times of mortar/adhesives.
Replace or restore work of other trades
damaged or soiled by work under this section.
53
Section 3: Part 4 Health and Safety
54
Section 4: Steam Room Detail Drawings
55
Section 4: ES-SR613
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
* United States Patent No.: 6881768 (and other Patents).
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
56 Offices, Marca Registrada. All other trademarks are property of their respective companies.
Section 4: ESSR614
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
* United States Patent No.: 6881768 (and other Patents).
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies. 57
Section 4: ES-SR614B
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
* United States Patent No.: 6881768 (and other Patents).
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
58 Offices, Marca Registrada. All other trademarks are property of their respective companies.
Section 4: ES-P605
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
* United States Patent No.: 6881768 (and other Patents).
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
Offices, Marca Registrada. All other trademarks are property of their respective companies. 59
Section 4: ES-WP302
NOTE: For complete application information and As a professional courtesy, LATICRETE offers
limitations consult related Product Data Sheets technical services free of charge. The user maintains
and Execution Statements related to this detail and all responsibility for verifying the applicability and
applicable industry standards. suitability of the technical service or information
provided.
2007 LATICRETE INTERNATIONAL, INC. All rights reserved. The right to utilize LATICRETE details for commercial purposes is granted exclusively to contractors, architects, quantity
surveyors, engineers, and specifications writers. LATICRETE, LATAPOXY, SPECTRALOCK are registered trademarks of LATICRETE International, Inc. U.S. and Foreign Patent and Trademark
60 Offices, Marca Registrada. All other trademarks are property of their respective companies.
Section 5: Maintenance and Protection
61
Section 5: Quality Assurance
as each component, and its installation, of the monitoring (spreading, thickness, open
system. So choosing the proper products and time, tackiness, beat-in, coverage)
installing them correctly is critical to the long- Clean-up and protection
n
Owner
n Define scope of work
n Organizational requirements
n Quality objectives
62
Section 5: Preventative and Corrective Maintenance
63
Section 5: Protection and Sealing
64
Section 5: Case Study Full Mortar BedHeading
Steam Room
Here
3.2# expandable diamond metal lath fastened to rigid foam insolation board which has been
installed over a vapor barrier.
Bench/wall transition and proper placement of 3.2# expandable diamond metal lath.
65
Section 5: Case Study Full Mortar Bed Steam Room
Transition of walls to ceiling prior to installation of LATICRETE 226 Thick Bed Mortar and LATICRETE
3701 Mortar Admix scratch coat.
Proper tie-in of 3.2# expandable diamond metal lath to steam room light fixture.
66
Section 5: Case Study Full Mortar Bed Steam Room
Ceiling (with sprinkler head) showing Tile Council of North America (TCNA) recommended pitch of
2" per foot (50 mm per 300 mm).
Pipe penetration for steam generation unit and proper tie-in of 3.2# expandable diamond metal
lath.
67
Section 5: Case Study Full Mortar Bed Steam Room
Installation of 3.2# expandable diamond metal lath to stainless steel door frame and flashing.
Wall partially finished with scratch coat of LATICRETE 226 Thick Bed Mortar and LATICRETE 3701
Mortar Admix.
68
Section 5: Case Study Full Mortar Bed Steam Room
Finishing the application of the LATICRETE 226 Thick Bed Mortar and LATICRETE 3701 Mortar Admix
scratch coat.
Scratching the LATICRETE 226 Thick Bed Mortar and LATICRETE 3701 Mortar Admix with a piece of
metal lath.
69
Section 5: Case Study Full Mortar Bed Steam Room
A finished, scratch coat wall which is now ready for the float coat.
The steam room seats after the installation of the LATICRETE 3701 Mortar Admix and LATICRETE
226 Thick Bed Mortar.
70
Section 5: Case Study Full Mortar Bed Steam Room
Pre-treatment of ceiling joint with 6" (150 mm) wide, treatment of LATICRETE 9235 Waterproofing
Membrane.
Lighting fixture waterproofing membrane pre-treatment. The vapor retarder, insulation board, mud
bed, and LATICRETE 9235 Waterproofing Membrane are all clearly visible.
71
Section 5: Case Study Full Mortar Bed Steam Room
Waterproofing treatment of corner and floor with LATICRETE 9235 Waterproofing Membrane.
Completed installation of LATICRETE 9235 Waterproofing Membrane over all seat, wall, ceiling and
floor surfaces.
72
Section 5: Case Study Full Mortar Bed Steam Room
Installation of tile onto LATICRETE 9235 Waterproofing Membrane using LATICRETE 254 Platinum.
Continuing installation of tile onto all surfaces using LATICRETE 254 Platinum.
73
Section 5: Case Study Full Mortar Bed Steam Room
Finished installation of 2" x 2" (5 cm x 5 cm) vitreous tile using LATICRETE 254 Platinum. Notice the
cut-out for the emergency call switch.
Installation of LATICRETE 1500 Sanded Grout mixed with LATICRETE 1776 Grout Enhancer on ceiling,
walls and seat.
74
Section 5: Case Study Full Mortar Bed Steam Room
Finished floor installation of tile. Floor and seats are sloped 1/4" per foot (6 mm per 300 mm) to
the drain.
75
Section 5: Case Study Full Mortar Bed Steam Room
Finished wall showing door, light and emergency call switch installations.
Tile provided and installation done by: Coastal Tile and Marble, Branford, CT.
76
Section 6: Appendix
77
Section 6: Steam Room Frequently Asked Questions
Q: Do I need a shower pan for my steam room/ Q: Should the vapor barrier drape into the
steam shower? shower pan liner?
Yes. A shower pan is an extremely important Yes. As water vapor permeates through the tile
component of any steam room, steam shower or installation and the waterproofing membrane,
regular shower and may be required per building the moisture will hit the impermeable vapor
code. A vinyl liner (or other vapor impermeable barrier. The moisture will eventually condense
material which can be used as a shower pan into water form and, by gravity, work its way
membrane) is perfectly suited for this type of down into the shower pan. A moisture barrier
application and must be properly installed to that has been improperly placed means that
protect against damage caused by water. the water will end up on the outside of the
shower pan. This can lead to structural damage
Q: Does the floor of the steam room require a and mold/health problems.
pitch to drain?
Yes. In fact, the pitch must exist in the sub-floor Q: Where should a vapor barrier be placed in a
so water that accumulates in the shower pan steam room installation?
flows towards the drain weep holes. If the sub- According to ES-SR613 the vapor barrier
floor is properly pitched then the depth of the would be placed directly onto the concrete
mortar bed can remain a consistent depth. The or masonry. In ES-SR614 the vapor barrier
pitch to drain for steam room/steam shower is placed directly onto the face of the studs
floor installations is recommended at 1/4" per (steel or wood), directly underneath (in contact
foot (6 mm per 300 mm). with) the cement backer board and fastened
with corrosion resistant fasteners. A spot of
Q: Should I conduct a flood test in my steam LATICRETE Latasil should then be placed
room prior to setting tile? onto each fastener to help prevent moisture
Yes. It is important to verify that the shower penetration through the fastener hole. Please
pan does not leak prior to setting tile. refer to the appropriate execution statement
located in this design manual or at www.
Q: Why do I need a vapor barrier in my laticrete.com/ag for more information.
steam room/steam shower if I have a
waterproofing membrane? Q: If there is no water in a steam room then
LATICRETE 9235 Waterproofing Membrane, why do I need a waterproofing membrane?
like most waterproofing membranes, prevents In actuality, there is water in a steam room; a
water from penetrating past the membrane. significant amount of water. Water enters the
However, like most waterproofing membranes, room as a vapor, meaning it must be heated to a
LATICRETE 9235 Waterproofing Membrane is temperature greater than 212F (100C). As the
vapor permeable. Moisture vapor will be able steam enters the room it will condense when
to permeate through the membrane, water it hits dew point and the resulting water must
itself will not. In a steam room environment the have an escape route. Directly or indirectly the
moisture that enters the room is in vapor form condensed water in the steam room will end
and is also under some pressure. The vapor up going through the drain.
barrier is designed and placed to keep the
moisture vapor from entering into areas where Q: Do I require a waterproofing membrane on
the vapor will condense and possibly cause the walls and ceiling?
structural and mold/health problems. Yes. The waterproofing membrane is required
throughout the steam room/steam shower
installation to help limit the amount of moisture
vapor that reaches the vapor barrier. The low
perm rating of LATICRETE 9235 Waterproofing
Membrane means that a very low amount of
water will come in contact with the vapor barrier.
78
Section 6: Steam Room Frequently Asked Questions
Q: Does a steam room/steam shower ceiling Q: What LATICRETE grout should I use for my
require a pitch? steam room/steam shower?
Yes. The ceiling requires a pitch to prevent The ideal grout would be LATICRETE
water droplets from falling onto steam room SpectraLOCK PRO Grout. LATICRETE
occupants. It also prevents water from staying SpectraLOCK PRO Grout provides an extremely
on the ceiling surface for extended periods of low absorption rate, antimicrobial protection,
time. The recommended pitch for a ceiling in a a significant reduction in efflorescence
steam room is 2" per foot (50 mm per 300 mm) problems, and ease of installation making
minimum. it the ideal choice for a steam room/steam
shower environment.
Q: Do I need a vapor barrier on the ceiling?
Yes. Water vapor in a steam room will Q: Does LATICRETE Latasil require
definitely come in contact with the ceiling. the LATICRETE 9118 Primer prior to
The vapor barrier must be placed within the application?
entire confines of the steam room structure so Yes. Due to the amount of moisture in a steam
that no moisture vapor can transpire into the room/steam shower, it is a good idea to treat
surrounding building structure or spaces. this type of installation the same way that you
would treat a swimming pool LATICRETE Latasil
Q: Is insulation required in my steam room/ application.
steam shower?
This is a question that should be answered by Q: If I use a cement based grout will
the project design professional. Applications efflorescence be a concern?
and project conditions may vary and will have a Yes. Efflorescence can be a concern when
direct impact on the use of insulation. The use a portland cement based grout is used in a
of a suitable insulation should dramatically steam room installation. The high amount of
improve the performance of the steam room/ moisture and the fact that the moisture will
steam shower and help to conserve energy. work its way back out through the grout can,
very possibly lead to efflorescence problems.
Q: How do I waterproof the penetrations An easy way to reduce efflorescence problems
(e.g. steam jets, pipes, drains, lights, etc) is to use LATICRETE SpectraLOCK PRO Grout.
in my steam room/steam shower?
For steam jets and pipes you can refer to Detail Q: What regular maintenance is needed for a
ES-P605 (located in Section 4.4) for direction. steam room?
For drains you can refer to the appropriate detail Outside of maintaining the steam generation
for your application (located in Section 4.5). unit (contact steam generation unit
manufacturer for more information) a steam
Q: What LATICRETE Thin-Set should I use for room requires some regular maintenance.
my steam room installation? Establish a suitable and consistent cleaning
LATICRETE 254 Platinum, a premium regimen for long term, safe and healthy steam
multipurpose thin-set mortar is ideal for room enjoyment.
installing most types of tile or stone in a
steam room/steam shower environment. For
installation of resin backed stone, moisture
sensitive tile or stone, mesh backed mosaics,
or dot mounted mosaics it is recommended
that LATAPOXY 300 Adhesive be used. For
more information please contact LATICRETE
Technical Services at support@laticrete.com
79
Section 6: Resource Guide
80
Section 6: Resource Guide
81
Section 6: Glossary
ABSORPTION the relationship of the weight BOND STRENGTH a bond coats ability to resist
of water absorbed to the weight of the dry separating from the tile and underlayment,
specimen, expressed in percentages measured in pounds per square inch (psi)
AGGLOMERATE TILE a man-made stone BROWN COAT the second coat in a three-coat
product generally consisting of either crushed render or mortar application
marble, granite or quartz chips with a matrix of
resins and mineral pigments. Usually available BULLNOSE a trim tile with a convex radius on
in assorted sizes as well as large slabs. one edge
APA American Plywood Association CEILING SLOPE steam rooms require ceilings
to be pitched 2" per foot (150mm per m) to
ASME American Society of Mechanical prevent condensation from dripping on steam
Engineers room occupants
ASTM American Society for Testing and CEMENT binding component of mortars and
Materials concrete (usually portland cement)
BACK-BUTTER the spreading of a bond coat CEMENT BACKER BOARD a backer board,
to the back of ceramic tile and stone just before usually composed of cement, fillers and
the tile is placed fiberglass mesh, designed for use with ceramic
tile in wet areas
BACK MOUNTED MOSAIC TILE mosaic tile
which may have perforated paper, fiber mesh, CEMENT GROUT a cementitious mixture of
resin or other suitable material bonded to the portland cement, sand or other ingredients,
back of each tile which becomes an integral pigments and water, to produce a water
part of the tile installation resistant, uniformly colored material used to
fill the joints between tile units
BICOTTURA method for producing tile by
firing it twice (first fire is for body, second is CEMENTITIOUS having the properties of
to fuse glazes or patterns in glaze onto the cement
body).
CERAMIC TILE a surfacing unit, usually
BISQUE the refined mixture of clay, water and relatively thin in relation to facial area, made
additives that has been shaped into the body from clay or a mixture of clay and other
of a tile materials called the body of the tile, and having
either a glazed or unglazed face
BODY the structural portion of a ceramic tile
CHEMICAL RESISTANCE the resistance
BOND COAT a material used between the offered by products to physical or chemical
back of a tile and the substrate. Suitable bond reactions as a result of contact with or
coats for a steam room application include latex immersion in various solvents, acids, alkalis,
portland cement mortar and epoxy adhesive. salts, etc
82
Section 6: Glossary
CRAZING the cracking that occurs in fired GLAZED TILE tile with a fused impervious
glazes or other ceramic coatings due to critical facial finish composed of ceramic materials
tensile stresses fused to the body of the tile
CURING maintenance of humidity and GROUT a material used for filling the joints
temperature of freshly placed mortar or grout between tile
to assure satisfactory hydration of cement and
proper hardening of mortar or grout GROUTING the process of filling tile joints
with grout
CUSHIONED EDGED TILE tile on which the
facial edges have a distinct curvature that IAPMO International Association of Plumbing
results in a slightly recessed grout joint and Mechanical Officers
EFFLORESCENCE the residue deposited on MARBLE TILE marble cut into tiles and
the surface of a material (usually cement grout) available in various finishes
by crystallization of soluble salts
83
Section 6: Glossary
MEDIUM BED tile setting material that has a PLUMB perpendicular to a true level
finished thickness between 3/8" (9 mm)
PORCELAIN TILE a ceramic tile that is dense,
METAL LATH expandable diamond metal impervious and has an absorption rate of
lath material which is mechanically fastened <0.5%
to a surface and onto which a mortar bed is
applied POT LIFE the period of time during which a
material maintains its workable properties
MONOCOTTURA method of producing tile by after it has been mixed
a single firing
SCRATCH COAT a mortar bed, applied as the
MORTAR BED the final coat of mortar on a first coat of a mortar on a wall or ceiling, whose
wall, floor or ceiling before the installation of surface is scratched or roughened so that
tile subsequent mortar coats will bond properly
MOSAIC TILE any tile (ceramic, porcelain SEALANT an elastomeric material used to fill
or stone) with a facial dimension of less than and seal expansion and control joints, prevents
6 in2 which usually comes in sheets (paper face the passage of moisture and does not allow
mounted, dot mounted, back mounted, etc) horizontal and lateral movement to affect the
tile installation
MUD see mortar bed
SELF-SPACING TILE tile with lugs, spacers or
NON-VITREOUS TILE tile with an absorption protuberances on the sides which automatically
rate greater than 7.0% space the tile for the grout joint
NOTCHED TROWEL a trowel with a serrated SEMI-VITREOUS TILE tile with an absorption
or notched edge which is used to gauge the rate between 3.0 7.0%
amount of mortar or adhesive to a specific
thickness when setting tile SHELF LIFE the maximum period of time that
an item can be stored before it is used
OPEN TIME the period of time that a bond
coat retains its ability to adhere to the tile and SHOWER PAN a waterproof shower floor
bond the tile to the substrate membrane which is specifically recognized
for use in this application required for steam
PENCIL ROD reinforcing rod with a diameter rooms as well as showers per local building
no greater than 1/4" (6 mm) code
PINHOLES imperfections in the surface of tile SLAKE the process of mixing a cementitious
or grout mortar or grout, allowing it to stand for 5 10
minutes and then remixing. This process makes
PLASTER a cementitious material and
sure that the moisture in the mix penetrates
aggregate that, when mixed with a gauging
lumps in the dry components, making it easier
liquid, forms a plastic mass or paste which
to complete the mixing procedure.
when applied to a surface, adheres to it and
subsequently hardens, preserving in a rigid
state the form or texture imposed during
installation
84
Section 6: Glossary
SLURRY COAT a coat of thin-set used to bond WET AREA surfaces that are either soaked,
a mortar bed to a cementitious substrate saturated, or regularly and frequently subjected
to moisture or liquids (usually water), such as
SPACERS plastic or rubber units used to saunas, steam rooms, showers, swimming
separate and provide consistent spacing pools, and more
between tiles
85
Notes
86
Notes
87
Notes
88
Notes
89
Notes
90
Notes
91
Notes
92
Notes
93
Notes
94
Notes
95
Notes
96
2007 LATICRETE International, Inc. All rights reserved. No part of this publication (except for previously
published articles and industry references) may be reproduced or transmitted in any form or by any
means, electronic or mechanical, without the written permission of LATICRETE International, Inc.
The information and recommendations contained herein are based on the experience of the author
and LATICRETE International, Inc. While we believe the information presented in these documents to
be correct, LATICRETE International, Inc. and its employees assume no responsibility for its accuracy
or for the opinions expressed herein. The information contained in this publication should not be
used or relied upon for any specific application or project without competent examination by qualified
professionals and verification of its accuracy, suitability, and applicability. Users of information from this
publication assume all liability arising from such use.
91.40.3041.3100
DS-125.0-1107