moment calculations
C+D-short ft 5.53
C+D-long ft 13.53
b0-effective perimeter inch 457.50
ratio of length to width of footing 1.33
vc/d 85.20
minimum two way shear capacity required 560.16
required depth inch 6.57
total two way shear capacity provided kip 1,565.52
depth of footing is
remarks for two way shear
okay for 2way shear
compression steel criteria for deth of footing
compression steel criteria inch 13.69
depth of footing is
remarks for compression steel embedment
okay
cantilever moments
cantilever distance ft 2.50
cantilever moments kip-ft 271.38
moment due to base seismic shear kip-ft 376.92