zdata= [0 1 0 1.25; 0 3 0 1.25; 1 4 0 .25; 1 2 0 .25; 2 4 0 .125; 2 3 0 .4; 3 4 0 .

2;]

zdata =

0 1.0000 0 1.2500
0 3.0000 0 1.2500
1.0000 4.0000 0 0.2500
1.0000 2.0000 0 0.2500
2.0000 4.0000 0 0.1250
2.0000 3.0000 0 0.4000
3.0000 4.0000 0 0.2000

>> ybus= ybus(zdata)

ybus =

0.0000 - 8.8000i 0.0000 + 4.0000i 0.0000 + 0.0000i 0.0000 + 4.0000i


0.0000 + 4.0000i 0.0000 -14.5000i 0.0000 + 2.5000i 0.0000 + 8.0000i
0.0000 + 0.0000i 0.0000 + 2.5000i 0.0000 - 8.3000i 0.0000 + 5.0000i
0.0000 + 4.0000i 0.0000 + 8.0000i 0.0000 + 5.0000i 0.0000 -17.0000i

>> zbus= zbuild(zdata)

zbus =

0.0000 + 0.6840i 0.0000 + 0.6307i 0.0000 + 0.5660i 0.0000 + 0.6242i


0.0000 + 0.6307i 0.0000 + 0.7187i 0.0000 + 0.6193i 0.0000 + 0.6688i
0.0000 + 0.5660i 0.0000 + 0.6193i 0.0000 + 0.6840i 0.0000 + 0.6258i
0.0000 + 0.6242i 0.0000 + 0.6688i 0.0000 + 0.6258i 0.0000 + 0.7045i
>> symfault(zdata,zbus)
Warning: Control Character '\T' is not valid. See 'doc sprintf' for control
characters valid in the format string.
> In symfault (line 34)
Enter Faulted Bus No. -> 1

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0).
Zf = j*.18

Balanced three-phase fault at bus No. 1


Total fault current = 1.1574 per unit

Bus Voltages during fault in per unit

Bus Voltage Angle


No. Magnitude degrees
1 0.2083 0.0000
2 0.2701 0.0000
3 0.3450 0.0000
4 0.2776 0.0000

Line currents for fault at bus No. 1

From To Current Angle


Bus Bus Magnitude degrees
G 1 0.6333 -90.0000
1 F 1.1574 -90.0000
2 1 0.2470 -90.0000
G 3 0.5240 -90.0000
3 2 0.1872 -90.0000
3 4 0.3369 -90.0000
4 1 0.2770 -90.0000
4 2 0.0599 -90.0000
Another fault location? Enter 'y' or 'n' within single quote -> 'y'
Enter Faulted Bus No. -> 2

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0).
Zf = j*.18

Balanced three-phase fault at bus No. 2


Total fault current = 1.1127 per unit

Bus Voltages during fault in per unit

Bus Voltage Angle


No. Magnitude degrees
1 0.2982 0.0000
2 0.2003 0.0000
3 0.3108 0.0000
4 0.2559 0.0000

Line currents for fault at bus No. 2

From To Current Angle


Bus Bus Magnitude degrees
G 1 0.5614 -90.0000
1 4 0.1696 -90.0000
1 2 0.3918 -90.0000
2 F 1.1127 -90.0000
G 3 0.5513 -90.0000
3 2 0.2764 -90.0000
3 4 0.2749 -90.0000
4 2 0.4445 -90.0000
Another fault location? Enter 'y' or 'n' within single quote -> 'y'
Enter Faulted Bus No. -> 3

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0).
Zf = j*.18

Balanced three-phase fault at bus No. 3


Total fault current = 1.1574 per unit

Bus Voltages during fault in per unit

Bus Voltage Angle


No. Magnitude degrees
1 0.3450 0.0000
2 0.2832 0.0000
3 0.2083 0.0000
4 0.2757 0.0000

Line currents for fault at bus No. 3

From To Current Angle


Bus Bus Magnitude degrees
G 1 0.5240 -90.0000
1 4 0.2770 -90.0000
1 2 0.2470 -90.0000
2 4 0.0599 -90.0000
2 3 0.1872 -90.0000
G 3 0.6333 -90.0000
3 F 1.1574 -90.0000
4 3 0.3369 -90.0000
Another fault location? Enter 'y' or 'n' within single quote -> 'y'
Enter Faulted Bus No. -> 4

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0).
Zf = j*.18

Balanced three-phase fault at bus No. 4


Total fault current = 1.1306 per unit

Bus Voltages during fault in per unit

Bus Voltage Angle


No. Magnitude degrees
1 0.2943 0.0000
2 0.2439 0.0000
3 0.2924 0.0000
4 0.2035 0.0000

Line currents for fault at bus No. 4

From To Current Angle


Bus Bus Magnitude degrees
G 1 0.5646 -90.0000
1 4 0.3630 -90.0000
1 2 0.2016 -90.0000
2 4 0.3230 -90.0000
G 3 0.5660 -90.0000
3 2 0.1214 -90.0000
3 4 0.4446 -90.0000
4 F 1.1306 -90.0000