Scotland
Part S
Northern Ireland
Part H
CONTENTS ENGLAND SCOTLAND NORTHERN FIRE IMPACT THERMAL CALCULATION
& WALES IRELAND SAFETY SAFETY PROGRAMS
Foreword
For new buildings and for buildings subject to major refurbishment,
the requirements for glazing when incorporated in the designs of
stairs, ramps and barriers can be found in three Building Regulation
Documents.
England and Wales
The Building Regulations 1991 Part K Stairs, Ramps and Guards.
Approved Document K Stairs, Ramps and Guards 1992 Edition
gives general guidance on the interpretation of the requirements.
Scotland
The Building Standards (Scotland) Regulations 1990 Part S Stairs,
Ramps and Protective Barriers.
The 1990 Technical Standards document provides guidance on the
interpretation of the requirements.
Requirements
The type of building and its intended use must be given careful
consideration when the type of barrier is being determined.
Generally when there is a change in adjacent levels (600mm in
dwellings, 380mm in other buildings) a barrier is needed to restrict
the movement of people or vehicles. (Glass is not a suitable
material to use when protection for or from vehicles is required).
CONTENTS ENGLAND SCOTLAND
Building NORTHERN FIRE IMPACT THERMAL CALCULATION
& WALES Regulations IRELAND SAFETY SAFETY PROGRAMS
The design of the barrier should minimise and 1995, even though the minimum
the risk of people falling, sliding, rolling permissible height of the barrier may be
or slipping through gaps in the barrier. less. Apart from Scotland, Building
Regulations suggest that the load should
Where children under 5 years are likely to be applied at the actual barrier height
be involved, the barrier should be which is quoted for the particular
designed so that the widest gap will situation where guarding is required. The
prevent a sphere of 100mm passing Building Standards (Scotland)
through it. This is to prevent young Regulations 1990 Part S simply refer to
children falling through. BS 6180: 1982.
Where multiple use of an area in or around (The notional design height of 1.1m is
a building is anticipated, barriers should chosen as being representative of the
be designed to meet the particular height of the centre of gravity of a human
situations. being above the datum level).
Barriers must be designed to minimum Glass Free standing glass protective barrier
permissible heights and to withstand
Guidance for the choice of appropriate
various forms of design load which are
glass specifications for given loadings
stipulated in each Building Regulation and
and support configurations is given in the
in BS 6180: 1982.
Pilkington Technical Bulletin Glass and
Mechanical Strength.
The Horizontal UDL (uniformly
distributed load) should be applied at a
notional height of 1.1m above finished
floor level, according to BS 6180: 1982
CONTENTS ENGLAND SCOTLAND NORTHERN FIRE IMPACT THERMAL CALCULATION
& WALES IRELAND SAFETY SAFETY PROGRAMS
Free Standing Glass Protective Barrier Free Standing Glass Protective Barrier
requires four design loadings to be taken into account:
Line load (Horizontal UDL) kN/m2
UDL (Infill UDL) kN/m2
Concentrated load kN
Impact Force BS 6206 Class A or C
The design loadings which need to be taken into account will vary with the type of barrier.
CONTENTS ENGLAND SCOTLAND NORTHERN FIRE IMPACT THERMAL CALCULATION
& WALES IRELAND SAFETY SAFETY PROGRAMS
900 mm
900mm for flights H
Retail all locations 1.5kN/m
otherwise 1100mm
All buildings
at glazing to to provide
below 800mm
changes of level containment H
Figure 2. Requirement for vision panels in doors on main
traffic routes and swing doors
Note. H is the height at which the applied load (horizontal design load) is located, it is not necessarily the height of the barrier itself.
CONTENTS ENGLAND SCOTLAND NORTHERN FIRE IMPACT THERMAL CALCULATION
& WALES IRELAND SAFETY SAFETY PROGRAMS
Infill Panels
Where infill panels are provided they must be designed and
constructed in accordance with the relevant parts of BS 6180: 1982
Code of practice for protective barriers in and around buildings.
Where the building or part of a building is likely to be used
by children under 5 years old, the guarding must be constructed so that
a sphere of 100mm in diameter cannot pass through any opening in it, CILL BARRIER
other than a triangular opening formed by a tread, a rise and the
bottom edge of the guarding if that bottom edge is not more than 800mm 800mm
50mm above the pitch line. It must not be easy for a child to climb up
it.
800mm
More
than
2000mm