TECHNICAL PARTICULARS AND GUARANTEE

GARDU INDUK 150 kV JENEPONTO


20 kV SWITCHGEAR WITH PANELS

No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

A 20 kV SWITCHGEAR
1 Manufacturer to be mentioned
2 Type Indoor metal clad
3 Highest system voltage kV 24
4 Rated basis insulation level kV 125
5 Rated one minute power frequency withstand voltage kV 50
6 Rated frequency Hz 50
7 Rated normal current A 630, 1250
8 Degree of protection IP 41
9 Materials of busbars Copper
10 Number of phase busbar 3
11 Number of neutral busbar : No
- for switchgear type A (general) 1
- for switchgear type B
12 Cross section of phase busbar sqmm
13 Cross section of neutral busbar sqmm
14 Rated continuous current of phase busbar A 2500
15 Rated cont. current of neutral busbar A 1000 (minimum)
16 Rated of short circuit kA, 1 sec 16
17 Insulation material for main busbar
18 Has the insulation material been flammability tested to IEC
60466 or other standard?

Page 1 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

19 Minimum clearance in air ;


(A) between phase mm
(B) phase to earth mm
20 iInsulation medium-busbars
21 Insulation medium-arc control
heat shrinkable, or slip-on type metalic
22 Type of cable termination
& earthed
23 Partitions of metalclad switchgear & controlgear
24 Construction data : Single busbar
- thickness of steel sheet
- front panel mm 2.5
- other section mm 2
25 Dimension of switchgear cubicle :
- width (max ) mm 1000
- depth (max) mm 2900
- height (max) mm 2900
26 Test certificate report: to be submitted
- Issued by
- Reference No.
- Date of test report
27 Weight (exclude C.B Switchgear) kg

B 20 kV INDOOR CIRCUIT BREAKER


1 Manufacturer to be mentioned
2 Type withdrawable, truck-mounted
3 Operation duty O - 1 min - CO - 3 min - CO
4 Highest system voltage kV 24

Page 2 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

5 Rated nominal current for ;


- Incoming A 1250
- Outgoing feeder A 630
- Bus section A -
6 Basic Insulation Level on 1.2x50 wave kV 125
7 Breaking capacity at 24 kV for:
- Incoming kA, 1 sec 25
- Outgoing feeder kA, 1 sec 25
- Bus section kA, 1 sec 25
- Outgoing for shunt Capacitor (N.A) kA, 1 sec 25
8 Making capacity
- Incoming kA, 1 sec 63
- Outgoing feeder kA, 1 sec 63
- Bus section kA, 1 sec 63
- Outgoing for shunt Capacitor kA, 1 sec 63
9 Frequency Hz 50
Interrupting medium SF6 or vacuum
Mechanism type motorized spring-charged
Is CB trip free Yes
Rated transient recovery voltage at 100% rated short
circuit breaker current kVp
Weight of CB kg
Test certificate report to be submitted
- Issued by
- Reference No.
- Date of test report

Page 3 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

C 20 kV CURRENT TRANSFORMER
i) 20 kV CURRENT TRANSFORMER
FOR INCOMING FEEDER
1 Manufacturer to be mentioned
2 Type indoor
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio, class, rated output:
a). For differential protection and for REF protection :
- ratio A 600-1200/5
- class 5P20
- output VA 30
b). For O/C and E/F protection :
- ratio A 600-1200/5
- class - 5P20
- output VA 30
c). For Instrument and metering :
- ratio A 600-1200/5
- class - 0.5
- output VA 40
6 Rated short time current kA, 1 sec 25
7 Knee point voltage V
8 Rated continuous thermal current A 2000
9 Weight kg

ii) 20 kV CURRENT TRANSFORMER


FOR OUTGOING FEEDER
1 Manufacturer to be mentioned

Page 4 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

2 Type indoor
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio, class, rated ouput ;
a). For O/C and E/F protection :
- ratio A 300-600/5
- class - 5P20
- output VA 30
b). For instrument and metering :
- ratio A 300-600/5
- class - 0.5
- output VA 40
6 Rated short time current kA,1 sec 25
7 Knee point voltage V
8 Rated continuous thermal current A 2000
9 Weight kg

iii) 20 kV CURRENT TRANSFORMER


OF ZERO-PHASE-SEQUENCE (N.A.)
1 Manufacturer to be mentioned
indoor, three phase, molded, cable
2 Type
through, separate core type
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio output :
a). Rated zero-phase-sequence primary current A 30
b). Rated zero-phase-sequence secondary current A 1
c). Rated output Ohm 10

Page 5 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

6 Class - 5P10
7 Weight kg

iv) 20 kV CURRENT TRANSFORMER FOR NEUTRAL OF


POWER TRANSFORMER (for REF Protection)
1 Manufacturer to be mentioned
2 Type Outdoor
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio, class, rated output :
a). For transformer E/F protection ;
- ratio A 300-600/5
- class 5P20
- output VA 15
6 Rated short time current kA, 1 sec. 12.5
7 Knee point voltage VA
8 Rated continuous thermal current A 2000
9 Weight kg

D 20 kV POTENTIAL TRANSFORMER
1 Manufacturer to be mentioned
2 Type
3 Highest system voltage kV 24
4 Frequency Hz 50
5 Ratio, class, output : V/V 20000:V3/100:V3/100:V3
for busbar and tap changer control, under-voltage relay : - 0.2
- ratio - 3P
- class of accuracy of secondary VA 100
- output of secondary VA 30

Page 6 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

6 Weight kg
7 Drawing No.

E PROTECTION
i) OVERCURRENT RELAY
1 Manufacturer to be mentioned
2 Type of overcurrent relay
3 Range of current settings
- Phase element % of CT rating
- Earth fault element % of CT rating
4 Range of timing settings at 10 x CT rating sec.
5 Burden of relay at 10 x CT rating sec.
6 Percentage of current setting at which relay will reset %

ii) DIRECTIONAL OVERCURRENT RELAY


1 Manufacturer to be mentioned
2A Type of overcurrent relay
2B Type of directional element
3 Range of current settings
- Phase element % of CT rating
- Earth fault element % of CT rating
4 Range of timing settings at 10 x CT rating sec.
5 Burden of relay at 10 x CT rating sec.
6 Percentage of current setting at which relay will reset %
iii) UNDER FREQUENCY RELAY
1 Manufacturer to be mentioned
2 Type of relay
3 Number of stage

Page 7 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

4 Frequency range Hz
5 Frequency adjusment step Hz 0.1
6 Time delay range sec. 0.15-1.5
iv) AUTORECLOSE RELAY
1 Manufacturer to be mentioned
2 Type of relay
3 Number of reclosing shot
v) OVERVOLTAGE RELAY
1 Manufacturer to be mentioned
2 Type of relay
3 Number of stage
4 Voltage range V
5 Voltage adjustment step V
6 Time delay range sec.
vi) UNDERVOLTAGE RELAY
1 Manufacturer to be mentioned
2 Type of relay
3 Number of stage
4 Voltage range V
5 Voltage adjustment step V
6 Time delay range sec.
vii 20 kV LOAD BREAK SWITCH
1 Manufacturer to be mentioned
2 Type Indoor
3 Nominal voltage kV 20
4 Highest system voltage kV 24
5 Rated current A 400

Page 8 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

6 Current withstand capacity A 25


7 Manual operated - Yes

viii 20 kV FUSES
1 Manufacturer to be mentioned
2 Type
3 Nominal voltage kV 20
4 Highest system voltage kV 24
5 Rated current A 20
6 Current characteristic - Required
7 Weight kg

F ALARM ANNUNCIATOR / FAULT


INDICATION PANEL WITH
ILLUMINATED INSCRIPTIONS
1 Manufacturer - to be mentioned
2 Type -
3 Design - indoor
4 Protection degree - IP42
5 Number of indication acc. To drawing - Yes
6 Type of indication - Lamp
7 Fast flicker - Yes
8 Slow flicker - Yes
9 Steady light - Yes
10 Voltage Vdc 110
11 Mounting position - Flush
12 Respective push buttons :
- horn off - Yes
- accept - Yes

Page 9 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

- reset - Yes
- lamp test - Yes
13 To be installed into control cubicle as specified - Yes

G AC AMMETER
1 Manufacturer to be mentioned
2 Type
3 Quantity to be measured : A
- AC ( 3 phase, 1 Phase) 1 phase
4 Class of accuracy - 0.2
5 Range of indication A 0-1200; 0-2400
0-300 ; 0-600
6 Effective range
7 Rated operating conditions :
- rated current A 1
- rated voltage
- rated internal resistance
- rated resistivity of separate
resistance
- rated transformation ratio of CT A/A
- rated power consumption VA
8 Minimum creepage distance between live
conductor and earthed case
9 Protection degree IP54
10 Size mm 96x96
11 Type of instrument mechanism
12 Scale characteristics :
- scale length

Page 10 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

- scale pattern : - linear


- non-linear
- scale with overload range
- max. scale value A 0-1200;0-2400
0-300 ; 0-600
13 Vibration strength N
14 Mounting position - Flush
15 Circuit of rectifier :
- full wave bridge current
- full wave shunt current
- center-tapped circuit with current transformer
16 Design of case (round/square/rectangular) - Square
17 Color of case
18 Error of indication (absolute error)
19 Relative error in %
20 Limit of temperature rise ref. ambient temperature - 40 0C at 100% humidity
21 Weight per instrument kg
22 Catalog, drawing or other references - to be submitted
23 Type test certificate - to be submitted
24 Sample test report - to be submitted
H AC VOLTMETER
1. Manufacturer to be mentioned
2. Type
3. Quantity to be measured : V
- AC (3 phase, 1 phase) - 1 phase
4. Class of accuracy - 0.2
5. Range of indication kV 0 - 25
6. Effective range

Page 11 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

7. Rated operating conditions :


- rated current
- rated voltage V 110
- rated internal resistance
- rated resistivity of separate resistance
- rated transformation ratio of VT kV/kV 20:3/0.100:3
- rated power consumption VA
Minimum creepage distance between live conductor and earthed
8.
cased
9. Protection degree IP54
10. Size mm 96 x 96
11. Type of instrument mechanism - Moving iron
12. Scale characteristics :
- scale length
- scale pattern : - linear
- non-linear
- scale with overload range
- max. scale value kV 30
13. Vibration strength N
14. Mounting position - Flush
15. Design of case (round/square/rectangular)
16. Color of case
17. Error of indication (absolute error)
18. Relative error in %
19. Limit of temperature rise ref. ambient temperature - 40 0C at 100% humidity
20 Weight per instrument kg
21 Catalog, drawing or other references - to be submitted
22 Type test certificate - to be submitted

Page 12 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

23 Sample test report - to be submitted

I WATTMETER
1. Manufacturer to be mentioned
2. Type
3. Quantity to be measured MW
- AC (3 phase, 1 phase) - 3 phase
- balanced Yes
- unbalanced Yes
- DC -
4. Class of accuracy 0.2
5. Range of indication MW As required
6. Effective range
7. Rating operating conditions :
- rated current A 1
- rated voltage V 110
- rated power consumption VAMax
- rated transformation ratio of : kV/kV 20:3/0.100:3
- voltage transformer A/A
- current transformer
- ohmic resistance of:
- current path
- voltage path
- inductance of current path
8. Minimum creepage distance
9. Protection degree IP54
10. Size mm 96 x 96
11' Type of instrument mechanism Electrodynamic
(number of watt/meter elements)

Page 13 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

12. Scale characteristics : Multi scale


- scale length
- scale pattern linear, 0 point at central position Yes
- scale with overage range
- max.scale value MW
13. Vibration strength N
14. Mounting position - Flush
15. Design of case (round/square/rectangular) - Square
16. Color of case
17. Error of indication (absolute error)
18. Relative error in %
19. Limit of temperature rise.ref. ambient temperature - 40 C at 100 % humidity
20. Weight per instrument kg
21. Catalog, drawing, or other references - to be submitted
22. Type test certificate - to be submitted
23. Sample test report to be submitted

J. VARMETER
1. Manufacturer to be mentioned
2. Type
3. Quantity to be measured MVAR
- AC (3 phase, 1 phase) - 3 phase
- balanced Yes
- unbalanced Yes
- DC -
4. Class of accuracy 0.2
5. Range of indication MVAR
6. Effective range

Page 14 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

7. Rating operating conditions :


- rated current A 1
- rated voltage V 110
- rated power consumption VAMax Yes
- rated transformation ratio of : kV/kV 20:3/0.100:3
- voltage transformer A/A
- current transformer
- ohmic resistance of:
- current path
- voltage path
- inductance of current path
8. Minimum creepage distance
9. Protection degree IP54
10. Size mm 96 x 96
11' Type of instrument mechanism
(number of watt/meter elements)
12. Scale characteristics : Multi scale
- scale length
- scale pattern linear, 0 point at central position Yes
- scale with overage range
- max.scale value MVAR
13. Vibration strength N
14. Mounting position - Flush
15. Design of case (round/square/rectangular) - Square
16. Color of case
17. Error of indication (absolute error)
18. Relative error in %
19. Limit of temperature rise.ref. ambient temperature - 40 C at 100 % humidity
20. Weight per instrument kg
21. Catalog, drawing, or other references - to be submitted

Page 15 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

22. Type test certificate - to be submitted


23. Sample test report to be submitted

K. SINGLE RATE KILOWATT-HOUR METER


1. Manufactured to be mentioned
2. Type
3. Class of accuracy and counter registration - 0.2
4. Rated Voltage V 110
5. Rated max.current A 1
6. Rated frequency Hz 50
7. Rated load : kW
- balanced
- unbalanced
8. Continous load rating kW
9. Max. permissible continous load %
10. Starting power W
11. Meter or ( testing ) constant -
12. Peak asym, short circuit current kA
13. Rated transformation ratio kV/kV A/A 20:3/0.100:3
14. Protection degree IP54
15. Kind of installation
16. Basic meter design (register) kWh
17. Type of register construction Digits 6+1
18. Mounting position - Flush
19. vibration Strength N
20. Calibration error in % at 100 % balance load cos phi = 1 %
21. Max. permissible ambient temperature rise
22. Design of case(round/square/rectangular) - Rectangular
23. Color of case

Page 16 of 17
No. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

24. Weight per instrument kg


25. Catalog, drawing, or other references Required
26. Type test certificate - Required
27. Sample test report - Required
28. Official meter calibration certificate - Required

Page 17 of 17