Spacial SF Seismic application

Main characteristics

General overview
Around the world can be found different zones with a specific seismic risk.
These zones have been classified according to the Uniform Building Code (UBC).

zone 4
zone 3
zone 2
zone 1
zone 0
PB501884

Spacial SF seismic solutions


Schneider Electric offers a range of LV earthquake resistant floor-standing
switchboards. The Spacial range is among these, with an answer to each type of
project for different seismic risk zones.

From weak to strong earthquakes:


Automation & Control switchboards.
The standard Spacial SF with dimensions 2000 H 3 800 W 3 600 D has been
tested to guarantee the right performance on seismic risk up to UBC zone 3.
Industrial 19" Electronic applications.
Standard Spacial SF with dimensions 2000 H 3 600 W 3 800 D and with a 19"
fixed rack configuration suitable for seismic risk up to UBC zone 3.
LV power distribution up to 3200A.
Standard Spacial SFP is tested to perform up to UBC zone 3.

For very strong earthquakes:


Automation & Control and 19" rack applications.
Spacial SF 5G performs up to UBC zone 4 thanks to its reinforced structure,
special panel fixation and locking system.
LV power distribution up to 3200 A.
Spacial SFP 5G performs up to UBC zone 4, also thanks to its reinforce structure,
special panel fixation and locking system.

All tests have been performed according to the following technical regulations:
EDF CRT 91 C 112 00, Nuclear. EDF (French Electricity Board) technical
specification.
IEC 61587-2, 60917 & 60297-2.
Weak to Strong Very Strong

Spacial SF Spacial SF 19" IEC 60068-3-3 Seismic characteristics


Spacial Spacial Spacial
(2000 3 800 (2000 3 800 Ground aceleration General Richter scale UBC MSK
SFP SF 5G SFP 5G g m/s
3 600) 3 600) reference description magnitude Zone Intensity**
Intensity from weak 0
AG2 2 > 5.5 > VIII
to average 1
OK OK OK
OK OK Intensity from
AG3 3 5.5 to 7.0 2-3 VIII to IX
average to strong
Intensity from strong
AG5 5 > 7.0 4 > IX
to very strong
* Aproximate value of the Uniform Building Code Zone.
** MSK (Medvedev-Sponheuer-Kamik corresponding to the intensity scale Mercalli modified).

2 version: 2.0 SFM084.indd


Spacial SF Seismic application
Standard Spacial SF

Standard Spacial SF
Two configuration of the standard Spacial SF have been tested:
Automation & Control configuration.
150 kg dummy load installed on mounting plate and homogeneously distributed,
according to IEC 61587-2.
19" fixed rack configuration.
150 kg dummy load installed on a 19" fixed rack, homogeneously distributed,
according to IEC 61587-2.

Nominal dimensions Additional Plain door Plinth 100 (mm)


Side Mounting
dummy load With mounting Without 19" Rack
Height Width Depth tested (kg) panels Front panel Side panel plate
plate mounting plate
A&C
2000 800 600 150 NSYSF20860P NSYSF20860 NSY2SP206 NSYSPF8100 NSYSPS6100 NSYMP208 -
Configuration
19"
2000 600 800 150 - NSYSF20680 NSY2SP208 NSYSPF6100 NSYSPS8100 - NSYRCK42
Configuration

Compliance with local standards


Standard Level and specifications of the standard
Standard EDF
60% of the ensemble response spectrum: 3 g peak and 0.6 g ZPA*
CRT91C11200
AS1170 Australia Soil Type: Ee / Floor zero
Soil Type: D (delta)
Seismic importance factor: gi = 0.85
Ground acceleration factor: a = 0.12
EAK 2000 Greece
Foundation factor: q = 1
Quality factor = 1.35
Spectral amplification factor: b0 = 2.5
Seismic Category A
ENDESA 1986 5% damping
Ground acceleration = 0.5 g
Soil type: S4
5% damping
RPA 99 2003
Ground acceleration factor A = 0.15
Algeria
Behaviour factor = 2
Quality factor z = 1.35
5% damping
Gore GR 63
Zone 3
Site Class: Z4
Turkish Seismic 5% damping
Code 2009 Importance factor = 1.5
Ground acceleration factor: A0 = 0.4
GOST 17516.1-90 Civil market standardl
Russia MSK (Mercalli) intensity 9, level 2: envelope epectra CRT91C11200
* ZPA - Zero Period Acceleration.

SFM084.indd version: 2.0 3


Spacial SF Seismic application
Standard Spacial SFP

Standard Spacial SFP


Two configuration of standard Spacial SFP have been tested. Functional systems
have been installed on the switchboard and checked at the end of the test to verify
that there was no damage. The 2 tested configurations are:
1600 A configuration.
3200 A configuration.

Nominal dimensions Additional dummy


Plain door Side panels
Height Width Depth load (kg)

Spacial SFP 2000 700 500 350 NSYSFP20750 NSY2SP205


1600 A configuration
Busbar duct 2000 300 500 350 NSYSF20350 NSY2SP205
Spacial SFP 2000 700 800 450 NSYSF20780 NSY2SP208
3200 A configuration
Busbar duct 2000 300 800 450 NSYSF20380 NSY2SP208

Compliance with local standards


Standard Level and specifications of the standard
Standard EDF
71% of the ensemble response spectrum: 3.5 g peak and 0.71 g ZPA*
CRT91C11200
AS1170 Australia Soil Type: Ee / Floor zero
Soil Type: D (delta)
Seismic importance factor: gi = 0.85
Ground acceleration factor: a = 0.12
EAK 2000 Greece
Foundation factor: q = 1
Quality factor = 1.35
Spectral amplification factor: b0 = 2.5
Seismic Category A
ENDESA 1986 5% damping
Ground acceleration = 0.5 g
Soil type: S4
5% damping
RPA 99 2003
Ground acceleration factor A = 0.15
Algeria
Behaviour factor = 2
Quality factor Q = 1.35
5% damping
Gore GR 63
Zone 3
Site Class: Z4
Turkish Seismic 5% damping
Code 2009 Importance factor = 1.5
Ground acceleration factor: A0 = 0.4
GOST 17516.1-90 Civil market standardl
Russia MSK (Mercalli) intensity 9, level 2: envelope epectra CRT91C11200
* ZPA - Zero Period Acceleration.

4 version: 2.0 SFM084.indd


Spacial SF Seismic application
Spacial SF 5G

Spacial SF 5G & Spacial SFP 5G


Spacial SF 5G and Spacial SFP 5G have been designed to withstand earthquakes
up to UBC zone 4. The two tested configurations, automation & control and LV
power distribution, enable it to be certified for nuclear applications.

This new design is based on the following principles:

Reinforced cross
PB501885

Two reinforced crosses guarantee the mechanical withstand of the structure.

Panel fixations
PB501886

Fixation systems that avoid loosening of screws.

Security locking system


PB501887

PB501888

EDF-certified seismic locking system.


Specific bars and handle to avoid accidental door opening under severe vibration
conditions.

Reinforced plinths
PB501889

New monoblock reinforced plinths.

SFM084.indd version: 2.0 5


Spacial SF Seismic application
Spacial SF 5G

Spacial SF 5G
Same characteristics as the Spacial SF but with the upgrades already mentioned.

Nominal dimensions Additional Plain door


Mounting
dummy load With mounting With out Side panels Plinth 100 (mm) 19" Rack
Height Width Depth plate
tested (kg) plate mounting plate
A&C
2000 800 600 150 - NSYSF5G20860 NSY5G2SP206 NSYS5GPC86 NSYMP208 -
Configuration
19"
2000 600 800 150 - NSYSF5G20680 NSY5G2SP208 NSYS5GPC68 - NSYRCK42
Configuration

Spacial SFP 5G
Same characteristics as the Spacial SFP but with the upgrades already mentioned.

Nominal dimensions Additional


dummy load Plain door Side panels Plinth 100 (mm)
Height Width Depth (kg)
1600 A Spacial SFP 2000 700 500 350 NSYSFP5G20750 NSY5G2SP205 NSYS5GPC75
configuration Busbar duct 2000 300 500 350 NSYSF5G20350 NSY5G2SP205 NSYS5GPC35
3200 A Spacial SFP 2000 700 800 450 NSYSF5G20780 NSY5G2SP208 NSYS5GPC78
configuration Busbar duct 2000 300 800 450 NSYSF5G20380 NSY5G2SP208 NSYS5GPC38
Important: Spacial SFP 5G 300 mm width for busbar duct purpose is not compatible with Spacial SF 5G.

Compliance with local standards


Standard Level and specifications of the standard
General response spectrum:
Standard EDF
- ZPA = 1 g in horizontal & maximum aceleration = 5 g.
CRT91C11200
- ZPA = 0.8 g in vertical & maximum aceleration = 4 g.
AS1170 Australie All type of soil class / Floor zero
All type of soil class (delta)
Seismic importance factor: gi = 1.3
Ground acceleration factor: a = 0.36
EAK 2000 Greece
Foundation factor: q = 1
Quality factor = 1.35
Spectral amplification factor: b0 = 2.5
All seismic category
ENDESA 1986
Ground acceleration = 0.5 g
All type of soil class
RPA 99 2003 Ground acceleration factor A = 0.36
Algeria Behaviour factor R = 2
Quality factor Q = 1.35
Zone 4 with a factor 0.8 for the vertical severity relating to the
Gore GR 63
horizontal severity
All type of site class
Turkish Seismic
Importance factor = 1.5
Code 2009
Ground acceleration factor: A0 = 0.4
Civil market:
MSK (Mercalli) intensity 9, level 2
GOST 17516.1-90
Russia Nuclear market:
- MSK (Mercalli) intensity 9, level 0.
- MSK (Mercalli) intensity 8, level 2.
IEEE 693 High Level

6 version: 2.0 SFM084.indd


Spacial SF Seismic application
Spacial SF 5G

Reinforcement kits for Spacial SF 5G


In case the following mounting components are used inside the SF 5G:
Plain mounting plates
19" fixed rack
then it is mandatory to mount the corresponding reinforcement kits, in order to
guarantee safety and maximum performance of the enclosure and of the equipment
installed inside.

Plain mounting plate reinforcement kit


PB502031

Kit for reinforcement of fixation between the plain mounting plate and structure.

Depth Reference
600 NSY5GSPK6
800 NSY5GSPK8

Supply:
2 90 mm universal cross rails.
2 brackets for central fixation.
2 heavy cross rails & fixing elements.

19" fixed rack reinforcement kit


PB502030

Kit for reinforcement of fixation between 19" fixed rack and structure.
The purpose of this kit is to reinforce the 19" fixed rack.

Depth Reference
600 NSY5GRCK42

Supply:
2 90 mm universal cross rails.
4 brackets for upright support.
1 set of standard 42 units 19" fixed rack.
Fixing elements.

SFM084.indd version: 2.0 7