Sei sulla pagina 1di 116

HC Centrifugal fans for industry

Technical data 2010


Contents Page 3

Components included in delivery 4

General description 5-7

Direct-driven fans
HCBB 9
Ordering key - Fan 10
Ordering key - Accessories 11 - 12
Description - Accessories, inlet and outlet 13
Charts - Air flow - Pressure rise 14 - 15
Design data 16
Moment of inertia - Sound data 17 - 18
Dimensions and weights - Fan 19 - 22
Tables, dimensions and weights - Accessories 23 - 24

HCBT 25
Ordering key - Fan 26
Ordering key - Accessories 27 - 28
Description - Accessories, inlet and outlet 29
Charts - Air flow - Pressure rise 30 - 31
Design data 32
Moment of inertia - Sound data 33 - 34
Dimensions and weights - Fan 35 - 37
Tables, dimensions and weights - Accessories 38 - 39

Belt-driven fans with impellers 1000 mm 40


Ordering key - Fan 41
Ordering key - Accessories 42 - 43
Description - Accessories, inlet and outlet 44
Sound data 45 - 46
Dimensions and weights - Fan 47 - 52
Tables, dimensions and weights - Accessories 53 - 54
Choice of belt drive 55 - 57

Charts - belt-driven fans 58 - 83

Belt-driven fans with impellers > 1000 mm 84


Ordering key - Fan 85 - 86
Ordering key - Accessories 87 - 88
Description - Accessories, inlet and outlet 89
Sound data 90 - 91
Dimensions and weights - Fan 92 - 94
Dimensions and weights - Steel base frame 95 - 96
Location of fan and motor 97
Slide rails 98
Tables, dimensions and weights - Accessories 99 - 100

Motors 101 - 104

Dampers
DMEG 105
HXEG 106 - 111

Fan theory, vibration and insulation of structure borne sound 112 - 114

The right to alter details and specifications without notice is reserved.


Components included in delivery Page 4

Direct-driven fans HCBB and HCBT


The following components are included as standard:
- Stand and housing mounted on steel base frame
- Anti-vibration mountings
- Inspection cover
- Boss equipped draining
- Brass ring shaft packing (approx. 0.3 mm clearance)

Belt-driven fans with impellers 1000 mm


The following components are included as standard:
- Stand and housing mounted on steel base frame
- Anti-vibration mountings
- Inspection cover
- Boss equipped draining
- Brass ring shaft packing (approx. 0.3 mm clearance)
- SKF Pop Release bearing
- Belts that do not require tensioning after installation

Belt-driven fans with impellers > 1000 mm


The following components are included as standard:
- Inspection cover
- Boss equipped draining
- Brass ring shaft packing (approx. 0.3 mm clearance)
- Bearing housings with spherical roller bearings
The fan can be ordered with or without a steel base frame which can always be supplied with anti-vibration mountings if
required. Please refer to the ordering key for other possibilities.

The quality assurance system at Flkt Woods AB,


is ISO 9001 certificated.
The company also has ISO/DIS 14001 and EMAS
environment certification.
General description Page 5

General

Design
- Robust design for use in industry.
- Direct-driven or belt-driven.
- Range of impeller types, (B, P and T impellers).
- Right-hand and left-hand versions (clockwise/counter clockwise rotation). For direction of discharge alternatives,
please refer to the catalogue section on each fan.

Material
- Carbon steel as standard.
- Stainless or acid-proof steel.
- Other materials possible on request.

Standards
Capacity and sound measurements can be carried out to the following standards:
- Capacity AMCA 210, ISO/DIS 5801
- Sound AMCA 300, ISO 3744, ISO 9614

The following standards apply for series-produced fans:


- Balancing ISO 1940 Class Q 6.3
- Hot-dip galvanizing SS 3583 (Class A)
- Flanges ISO 13351

Surface treatment
- Please refer to the individual ordering keys.
- All guards (belt guards, shaft guards and cooling disc guards) are epoxy painted in a yellow warning colour, (80 ).

Packing
- Fans are delivered on wooden laths suited for handling by fork-lift truck.

Instructions
- Installation and maintenance instructions are supplied with every fan.
General description Page 6

HCBB/HCBT Direct-driven centrifugal fans


Description
- The fans are supplied with B or T type impellers.
- A range of 9 sizes.
- Each fan size has from 8 to 13 different possibilities as regards impeller diameter.
- Impellers are equipped with a hole/groove for an extractor.
- Max. operating temperature without heat shielding, 100C. With heat shielding, 200C. Refer to accessories.
- Max. ambient temperature as regards motor cooling, 40C.

Characteristics
- Compact.
- Low capital investment cost.
- Operational reliability.
- Low operating costs.
- High efficiency, up to 88% with a type B impeller.

Impeller types
Type B impellers:
- Have backward-curved blades which, depending on size, give an overall efficiency of up to 88%.
- Enable the selection of a fan with an at least 80% efficiency within the greater part of the flow-pressure range.
- Are primarily for clean gas applications.
Type T impellers:
- Have straight radial blades for handling dust-laden gases. Not having a wheel inlet ring, this impeller is open and is
thus also suitable for fibrous dusts.
- Is supplied as standard in a strengthened, wear-resistant design.

Dust
Dust quantity and impeller choice.
- B impeller 0 - 30 mg/m3 NB! The stated values apply to dry dust and are for guidance only. Dust composition
and air speed greatly affect particle impact and wear. For further information,
- T impeller 150 - 1000 mg/m 3
please contact ABB Ventilation Products AB, Division Flkt Industri.

Key charts

HCBB HCBT
10 000 10 000
Total pressure risel, Pa
Total pressure rise, Pa

5000 5000

2000 2000

1000 1000

500 500
400 400
0.05 0.1 0.2 0.5 1 2 5 10 20 0.05 0.1 0.2 0.5 1 2 5 10
Gas flow m3/s Gas flow m3/s
General description Page 7

Belt-driven centrifugal fans


Description
- High efficiency, belt-driven.
- Impellers are equipped with a hole/groove for an extractor.
- Max. operating temperature, 350C.
- Supplied with any of the following impellers:

HCGB HCLP HCLT


HCMB B impeller HCMP P impeller HCMT T impeller *
HCHB HCHP HCHT

Characteristics
- Compact.
* T impellers are available for fans
- Low capital investment cost. with an impeller diameter of up to
- Operational reliability. 1000 mm.

- Low operating costs.


- High efficiency, up to 88% with a type B impeller.

Impeller types
Type B impellers:
- Have backward-curved blades which, depending on size, give an overall efficiency of up to 88%.
- Enable the selection of a fan with an at least 80% efficiency within the greater part of the flow-pressure range.
- Are primarily for clean gas applications.
Type P impellers:
- Have flat, backward-inclined blades.
- Are for handling clean gases and gases with a low dust content (e.g. flue gases).
Type T impellers:
- Have straight radial blades for handling dust-laden gases. Not having a wheel inlet ring, this impeller is open and is
thus also suitable for fibrous dusts.
- Is supplied as standard in a strengthened, wear-resistant design.

Dust
Dust quantity and impeller choice.
- B impeller 0 - 30 mg/m3
NB! The stated values apply to dry dust and are for guidance only. Dust composition
- P impeller 30 - 300 mg/m3 and air speed greatly affect particle impact and wear. For further information,
- T impeller 150 - 1000 mg/m3 please contact ABB Ventilation Products AB, Division Flkt Industri.

Key charts

HCGB, HCLP, HCM(B,P), HCH(B,P) HCLT, HCMT, HCHT


Total pressure rise, Pa

10 000
Total pressure rise, Pa

HCH(B,P) 10 000

5000 HCM(B,P) HCHT


5000
HCLP
HCMT
2000
2000
HCGB
HCLT
1000
800 1000
0.3 0.5 1 2 3 45 10 20 50 80 800
0.06 0.1 0.2 0.5 1 2 5 10
Gas flow m3/s Gas flow m3/s
Jotter Page 8
HCBB Page 9
Ordering Key - HCBB - Direct-driven Page 10

HCBB-aaa-bb-cc-dd-ee-fff

Size 1) (aaa)
010, 012, 016, 020, 025, 031, 040, 050 and 063.

Impeller diameter, cm, 1) (bb)

Motor size - IEC (cc)


Motor size (cc) is as per the "design data" table on page 16.
NB! Motors must always be ordered separately and in accordance with the ordering key on page 16.

Designations for rotation and discharge (dd)

11 0o 12 45o 13 90o 14 135o 17 270o 18 315o


Right
(RD)

61 0o 62 45o 63 90o 64 135o 67 270o 68 315o


Left
(LG)

NB! The above diagrams show the drive side.

Fan version (ee)


01 = standard version.
02 = sparkproof version, (brass ring at the inlet and brass washers at the shaft inlet).

Material, finish (fff)


001 = Standard material, GA80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Not fully welded Max. temperature 150oC. 2)
032 = Standard material, GA80TD80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Not fully welded
300 = SS 2333 throughout. Not fully welded
400 = SS 2343 throughout. Not fully welded

1)
For variants in a size, impeller diameter, number of poles combination, please refer first to page 16, Design data.
2)
GP40-01 primer can be used where temperatures exceed 120C. This primer tolerates temperatures up to 150C
and vaporises at higher temperatures without emitting any toxic substances.
Ordering key - HCBB - Accessories Page 11

Heat shield for temperatures up to 200oC HCEZ-07-b-cc


Size: Refer to "Heat shield selection" table, page 23
Variants: Refer to "Heat shield selection" table, page 23

Cleanout cover HCEZ-09-bb-c-ddd


Cover size: Refer to table on page 23
Location
With discharge directions 11 and 61 c = 1
For other discharge directions c=2
Material and finish: Refer to the fff code in the main fan ordering key

Inlet taper piece without connecting flange 1) HCEZ-20-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key
1)
For direct connection to fans without inlet flange.

Inlet taper piece with connecting flange 2) HCEZ-21-bbb-ccc


Size (= 040 - 063)
Material and finish: Refer to the fff code in the main fan ordering key
2)
For connection to fans with inlet flange or to inlet vane assemblies or regulating dampers.

Counterflange, inlet, (not fitted) HCEZ-25-bbb-ccc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Inlet flange, (fitted) HCEZ-27-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Inlet connecting flange 3) HCEZ-29-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key
3)
NB! When connecting to size 031 inlet vane assemblies, size 040 inlet connecting flange must be used.

Fabric duct, inlet, without connecting flanges 4) HCEZ-aa-bbb


Temp. class
40 = max. 70oC.
41 = max. 200oC.
Size (= fan size)
4)
For connection to fans without inlet flange.

Fabric duct, inlet, with connecting flanges 5) HCEZ-aa-bbb-ccc


Temp. class
45 = max. 70oC.
46 = max. 200oC.
Size (= 040 - 063)
For material and finish (flanges), refer to the fff code in the main fan ordering key
5)
For connection to fans with inlet flange or to inlet vane assemblies.
NB! When connecting to size 031 inlet vane assemblies, size 040 must be used.
Ordering key - HCBB - Accessories, cont. Page 12

Protective screen, outlet HCEZ-30-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Counterflange, outlet, (not fitted) HCEZ-35-bbb-cc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Fabric duct, outlet, with connecting flanges HCEZ-aa-bbb-ccc


Temp. class
50 = max. 70oC.
51 = max. 200oC.
Size (= fan size)
Material and finish (flanges), refer to the fff code in the main fan ordering key
HCBB - Description - Accessories, inlet and outlet Page 13

12 2
Duct
11
3 4

10 3
5, 6
4
3
5, 6
7
8

3
5, 6
9
2

2
9
5, 6

8
NB! Flanges comply with ISO 13351

Inlet
1 HCEZ-20 Inlet taper piece with protective screen and fixing lugs for connection to inlet without
connecting flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HCEZ-40, 41 Fabric duct, inlet without connecting flanges. 2)
3 HCEZ-27 Inlet flange, (fitted).
4 HCEZ-21 Inlet taper piece with protective screen and connecting flange for installation to inlet with
connecting flange.(Pressure loss across the accessory, 0.35 x dyn. press. pd).
5 HXEG Inlet vane control assembly, see pages 106 - 111. 1)
6 DMEG Regulating damper, see page 105. 1)
7 HCEZ-45, 46 Fabric duct, inlet with connecting flange. 2)
8 HCEZ-25 Counterflange, inlet, (not fitted).
9 HCEZ-29 Inlet connecting flange, for fitting ducts without connecting flange.

Outlet
10 HCEZ-30 Protective screen, outlet.
11 HCEZ-50, 51 Fibre duct, outlet, with connecting flanges. 2)
12 HCEZ-35 Counterflange, outlet, (not fitted).
1)
NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that the anti-vibration mountings can
cope with the increased component load on the fan.
2)
For size and temperature limits, please refer to the appropriate ordering keys.
HCBB - Air flow and dynamic pressure rise charts Page 14

The charts are valid for gas at a density of 1.2 kg/m2.


Gas flow, m3/h
300 400 500 1000 2000 3000 4000 5000 10 000 20 000 30 000 50 000
10 000
9000 Impeller diameter 80 040 063
8000 71 75
2-pole motor 8
7000 71
71 85 7
6000 71 4-pole motor 025 82
6-pole motor 67 80
63
5000 63
60 75
4000 016 56
60 71
56 67
50
53 63
3000 47 53
Size 010 45 50 99
50
40 47 95
37 42
2000 45 90
35 40 80
42
33 37 75 85
31 35 40 71 80
33 37 67
30 99
35 63
1000 28 95
33 60
900 26
Total pressure rise, Pa

31 56
800 53 90
700 53 85
50
600 50 80
47
500 45
42
400

300
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s

1500

1000

500
400
300
Dynamic pressure, Pa

Size 010 016 025 040 063


200

100

50
40
30
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s

Example: Flow 3.0 m3/s, total pressure rise 2100 Pa. Pressure losses across accessories:
HCEZ-20 and 21 inlet taper piece:
Select an HCBB-040 with a 50 cm diameter impeller and 0.35 x dynamic pressure Pd.
a 2-pole motor, or an HCBB-050 with an 80 cm diameter
impeller and a 4-pole motor, see chart on next page.

Dynamic pressure: 330 and 130 Pa respectively.

Moment of inertia (J) See page 17. Sound data See pages 17-18.
HCBB - Air flow and dynamic pressure rise charts Page 15

The charts are valid for gas at a density of 1.2 kg/m2.


Gas flow, m3/h
300 400 500 1000 2000 3000 4000 5000 10 000 20 000 30 000 50 000
10 000
9000 Impeller diameter 031 050
8000 71 80
2-pole motor 71
7000 71 75
71 4-pole motor 67
6000
6-pole motor 71
5000
020 63
67
56 60
4000
53
Size 012
50 99
3000 45 50
47 95
42 47
45 90
40 45
2000 42 85
37 42 80
35 40
40 75
37
33
35 71
31
33 67
30
1000 31
900 63
Total pressure rise, Pa

30
800
80
700 75
600 50
25 47 71
500 45

400

300
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s

1500

1000

500
400
300
Dynamic pressure, Pa

Size 012 020 031 050


200

100

50
40
30
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 5 6 7 8 9 10 16
Gas flow, m3/s

Moment of inertia (J) See page 17. Sound data See pages 17-18.
HCBB - Design data Page 16

Fan Motor * Fan Motor *


Max. Max.
Im- Motor Rated power Im- Motor Rated power
Fan peller Motor- size out- Ordering demand Fan peller Motor- size out- Ordering demand
size dia. size as per R P M put, key of fan, size dia. size as per R P M put, key of fan,
aaa bb cc IEC kW APAL- kW aaa bb cc IEC kW APAL- kW
26 01 63 2820 0.25 2-00025-c-0 0.13 40 06 100L 2900 3.0 2-00300-c-0 2.6
28 01 63 2820 0.25 2-00025-c-0 0.17 42 07 112M 2850 4.0 2-00400-c-0 3.3
30 02 71 2840 0.37 2-00037-c-0 0.22 08 132S 2855 5.5 2-00550-c-0 4.2
45
31 02 71 2840 0.37 2-00037-c-0 0.28 03 80 1420 0.55 4-00055-c-0 0.48
010
33 02 71 2850 0.55 2-00055-c-0 0.35 08 132S 2855 5.5 2-00550-c-0 5.2
47
35 02 71 2850 0.55 2-00055-c-0 0.45 03 80 1420 0.75 4-00075-c-0 0.59
031
37 03 80 2860 0.75 2-00075-c-0 0.54 08 132S 2855 7.5 2-00750-c-0 6.4
40 03 80 2860 0.75 2-00075-c-0 0.65 50
04 90S 1410 1.1 4-00110-c-0 0.74
30 02 71 2850 0.55 2-00055-c-0 0.28 60 10 160M 2920 15 2-01500-c-0 12
31 02 71 2850 0.55 2-00055-c-0 0.34 63 11 160L 2920 18.5 2-01850-c-0 15
33 03 80 2860 0.75 2-00075-c-0 0.44 67 12 180M 2930 22 2-02200-c-0 19
35 03 80 2860 0.75 2-00075-c-0 0.57 71 14 200L 2955 30 2-03000-c-0 25
012
37 03 80 2870 1.1 2-00110-c-0 0.71 10 160M 2930 11 2-01100-c-0 8.3
40 03 80 2870 1.1 2-00110-c-0 0.90 50
05 90L 1420 1.5 4-00150-c-0 0.99
42 04 90S 2870 1.5 2-00150-c-0 1.2
45 05 90L 2870 2.2 2-00220-c-0 1.5 10 160M 2920 15 2-01500-c-0 10.6
53
05 90L 1420 1.5 4-00150-c-0 1.2
33 03 80 2860 0.75 2-00075-c-0 0.56
35 03 80 2870 1.1 2-00110-c-0 0.70 10 160M 2920 15 2-01500-c-0 13
56
37 03 80 2870 1.1 2-00110-c-0 0.89 06 100L 1430 2.2 4-00220-c-0 1.6
40 04 90S 2870 1.5 2-00150-c-0 1.1 11 160L 2920 18.5 2-01850-c-0 17
016 60
42 05 90L 2870 2.2 2-00220-c-0 1.4 06 100L 1430 2.2 4-00220-c-0 2.0
45 05 90L 2870 2.2 2-00220-c-0 1.8 040 12 180M 2930 22 2-02200-c-0 21
63
47 06 100L 2900 3.0 2-00300-c-0 2.2 06 100L 1430 3 4-00300-c-0 2.5
50 06 100L 2900 3.0 2-00300-c-0 2.8 14 200L 2955 30 2-03000-c-0 27
67
25 02 71 2840 0.37 2-00037-c-0 0.21 07 112M 1435 4 4-00400-c-0 3.0
30 02 71 2850 0.55 2-00055-c-0 0.42 14 200L 2950 37 2-03700-c-0 32
31 03 80 2860 0.75 2-00075-c-0 0.52 71
07 112M 1435 4 4-00400-c-0 3.7
33 03 80 2860 0.75 2-00075-c-0 0.64
16 225M 2960 45 2-04500-c-0 40
35 03 80 2870 1.1 2-00110-c-0 0.80 75
08 132S 1450 5.5 4-00550-c-0 4.5
37 04 90S 2870 1.5 2-00150-c-0 1.2
17 250M 2970 55 2-05500-c-0 50
020 40 05 90L 2870 2.2 2-00220-c-0 1.5 80
09 132M 1450 7.5 4-00750-c-0 5.7
42 05 90L 2870 2.2 2-00220-c-0 1.9
45 06 100L 2900 3.0 2-00300-c-0 2.3 63 07 112M 1435 4 4-00400-c-0 3.1
47 07 112M 2850 4.0 2-00400-c-0 2.8 14 200L 2950 37 2-03700-c-0 35
67
50 07 112M 2850 4.0 2-00400-c-0 3.6 08 132S 1450 5.5 4-00550-c-0 3.9
53 08 132S 2855 5.5 2-00550-c-0 4.5 16 225M 2960 45 2-04500-c-0 43
56 08 132S 2855 7.5 2-00750-c-0 5.7 71 08 132S 1450 5.5 4-00550-c-0 4.9
31 03 80 2870 1.1 2-00110-c-0 0.70 07 112M 940 2.2 6-00220-c-0 1.4
33 03 80 2870 1.1 2-00110-c-0 0.86 17 250M 2970 55 2-05500-c-0 53
35 04 90S 2870 1.5 2-00150-c-0 1.1 050 75 09 132M 1450 7.5 4-00750-c-0 6.2
37 04 90S 2870 1.5 2-00150-c-0 1.3 07 112M 940 2.2 6-00220-c-0 1.7
40 05 90L 2870 2.2 2-00220-c-0 1.7 18 280S 2977 75 2-07500-c-0 66
06 100L 2700 3.0 2-00300-c-0 2.7 80 10 160M 1460 11 4-01100-c-0 7.7
42
03 80 1420 0.55 4-00055-c-0 0.31 08 132S 960 3 6-00300-c-0 2.1
07 112M 2850 4.0 2-00400-c-0 3.2 85 10 160M 1460 11 4-01100-c-0 10
45
03 80 1420 0.55 4-00055-c-0 0.37 90 11 160L 1455 15 4-01500-c-0 12
025 95 12 180M 1470 18.5 4-01850-c-0 15
08 132S 2855 5.5 2-00550-c-0 3.8
47 99 13 180L 1470 22 4-02200-c-0 19
03 80 1420 0.55 4-00055-c-0 0.44
08 132S 2855 5.5 2-00550-c-0 4.8 63 16 225M 2960 45 2-04500-c-0 43
50 67 17 250M 2970 55 2-05500-c-0 50
03 80 1420 0.75 4-00075-c-0 0.54
71 18 280S 2977 75 2-07500-c-0 61
08 132S 2855 7.5 2-00750-c-0 6.00
53 75 18 280S 2977 75 2-07500-c-0 71
04 90S 1410 1.1 4-00110-c-0 0.70
19 280M 2975 90 2-09000-c-0 86
56 10 160M 2930 11 2-01100-c-0 7.5
80 11 160L 1455 15 4-01500-c-0 11
60 10 160M 2930 11 2-01100-c-0 9.5
09 132M 960 4 6-00400-c-0 2.8
63 10 160M 2920 15 2-01500-c-0 12
82 20 315S 2982 110 2-11000-c-0 95
21 315M 2982 132 2-13200-c-0 108
Voltage code 063 85 11 160L 1455 15 4-01500-c-0 13
1 = 220-240VD/380-420VY 09 132M 955 5.5 6-00550-c-0 3.4
2 = 380-420VD/660-690VY 87 21 315M 2982 132 2-13200-c-0 122
5 = 500 VY (sizes 63-100) 12 180M 1470 18.5 4-01850-c-0 17
90
500 VD (sizes 112-355) 09 132M 955 5.5 6-00550-c-0 4.2
13 180L 1470 22 4-02200-c-0 21
95
10 160M 970 7.5 6-00750-c-0 5.9
* Please refer to pages 101 - 104 for motor details not included here.
For further motor data and information on motor versions, please 14 200L 1475 30 4-03000-c-0 26
99
contact ABB Motors. 11 160L 970 11 6-01100-c-0 7.4
HCBB - Moment of inertia - Sound data Page 17

Moment of inertia J (=1/4 GD2)


Fan Imp. Imp. Fan Imp. Imp. Fan Imp. Imp. Fan- Imp. Imp.
size dia. weight J size dia. weight J size dia. weight J size dia. weight J
aaa bb kg kg m 2
aaa bb kg kg m 2
aaa bb kg kg m 2
aaa bb kg kg m2
26 3.5 0.027 25 4.4 0.024 40 8.9 0.183 63 29.0 1.2
28 3.6 0.028 30 5.6 0.048 42 12.1 0.287 67 32.0 1.9
30 4.2 0.043 31 5.6 0.05 45 14.3 0.313 71 34.0 2
31 4.3 0.044 33 7.3 0.089 47 16.5 0.45 75 42.0 2.4
010
33 5.9 0.086 35 7.4 0.093 031 50 16.7 0.458 050 80 45.0 3.1
35 6.0 0.09 37 9.0 0.158 60 30.0 0.983 85 62.0 5.4
37 7.2 0.134 020 40 9.1 0.167 63 31.0 1.03 90 63.0 5.7
40 7.5 0.14 42 10.9 0.248 67 36.0 1.64 95 73.0 8.4
30 5.8 0.048 45 10.9 0.26 71 39.0 1.7 99 78.0 8.9
31 5.8 0.05 47 15.3 0.37 50 17.0 0.48 63 25.0 1.9
33 5.8 0.09 50 15.4 0.395 53 26.0 0.72 67 25.0 2.1
35 5.9 0.094 53 18.0 0.592 56 27.0 0.773 71 26.0 2.6
012
37 7.3 0.136 56 21.0 0.614 60 29.0 1.12 75 32.0 3.6
40 7.4 0.142 31 5.6 0.073 040 63 30.0 1.2 80 45.0 3.7
42 9.0 0.213 33 7.7 0.106 67 32.0 1.77 063 82 60.0 5.6
45 9.4 0.222 35 7.8 0.114 71 33.0 1.88 85 63.0 5.7
37 9.2 0.167 75 37.0 2.78 87 64.0 6.1
33 8.7 0.093
40 9.4 0.178 80 41.0 2.95 90 64.0 6.2
35 8.8 0.098
95 77.0 8.9
37 8.9 0.144 42 11.5 0.252
99 78.0 9.6
40 8.9 0.152 025 45 11.6 0.266
016
42 14.3 0.221 47 17.3 0.398
45 14.7 0.229 50 17.5 0.42
47 14.7 0.342 53 21.0 0.61
50 14.8 0.356 56 24.0 0.645
60 27.0 0.873
63 31.0 1

Sound data

Symbols Formulae:
Lwtot = total sound power level for
a, b, c
sound paths a, b and c ................. dB (ref. 10-12 W). Lwtot , see table 2, page 18 Lwa, see table 2, page 18
a
Lw a,b,c = sound power level for sound paths a, b and c, Ltotb = Lwtot + K2 + K3 Lwb = Lwtot + Kb
respectively by octave band ............................. dB. a b
Lwtot = Lwtot + K2 + K3 Lwc = Lwtot + Kc
Kb, Kc, K2, K3 = corrections for sound paths b and c respectively c a c
(for sound path a, the correction = 0) .............. dB.

Sound paths: a = to inlet or outlet duct.


Table 1. Correction K3, Kb and Kc
b = to surroundings (free-inlet fan).
c = to surroundings (fan connected to ducts
on both inlet and outlet sides). No. Cor- Cor- Correction Kb and Kc, dB
of Sound rec- rec-
NB!The stated values refer to sound power levels. Some fan manufac- poles path tion tion Octave band, mid-frequency, Hz
turers still quote sound pressure levels even though these vary with K3 63 125 250 500 1000 2000 4000 8000
the acoustic characteristics of the surroundings and distance from b -2 Kb -6 -4 -7 -14 -14 -18 -21 -30
the fan. Sound pressure levels, sometimes weighted as dB(A) or 6 c -2 Kc -7 -3 -6 -15 -15 -18 -23 -31
dB(C) values, are considerably lower than the corresponding sound
power level Lwt. To illustrate this: with a free inlet fan and hemis b -2 Kb -8 -6 -4 -11 -12 -14 -17 -22
4 c -1 Kc -9 -6 -4 -11 -12 -15 -20 -25
pherical sound propagation, at a distance of 3 m from the fan, the
dB(A) value is 17 - 25 dB lower (depending on fan speed and blade b -3 Kb -7 -8 -8 -6 -8 -12 -14 -17
2 c -1 Kc -9 -5 -8 -8 -8 -14 -17 -21
type) than the total sound power level.
b -3 Kb -3 -9 -10 -6 -12 -16 -21 -23
2* c +1 Kc -3 -8 -9 -10 -15 -21 -27 -29
Correction K2
* Applies only to size 063 and impeller diameter 63, 67, 71 and 75.
5
0 a
K2, dB

-5 b
-10 c

-15
0 4000 8000 12 000
Dpt, Pa
HCBB - Sound data cont. Page 18

Table 2. Sound power levels Lwa and Lwtot (sound path a)


a

Fan Im- No. Sound power level Lwa, dB Fan Im- No. Sound power level Lwa, dB
size peller of Lwtot size peller of Lwtot
Octave band, mid-frequency, Hz a Octave band, mid-frequency, Hz a
dia. pol. dia. pol.
aaa bb 63 125 250 500 1000 2000 4000 8000 dB aaa bb 63 125 250 500 1000 2000 4000 8000 dB
26 84 84 84 79 77 75 72 69 90 40 2 87 87 87 89 86 82 80 78 95
28 84 84 85 79 78 75 73 69 90 42 2 88 88 89 90 87 84 82 79 96
30 85 85 86 80 79 76 74 70 91 45 2 90 90 90 92 89 85 83 81 98
31 86 86 87 81 80 77 75 71 92 47 2 91 91 92 93 90 87 85 82 99
010 33 2 87 87 88 82 81 78 76 72 93 50 2 93 93 93 95 92 88 86 84 101
35 88 88 89 83 82 79 77 73 94 60 2 98 98 99 93 92 89 87 83 104
37 89 89 90 84 83 80 78 74 95 031 63 2 100 100 100 95 93 91 88 85 106
40 90 90 91 85 84 81 79 75 96 67 2 101 101 102 96 95 92 90 86 107
71 2 103 103 103 98 96 94 91 88 109
30 85 85 85 80 78 76 73 70 91 45 4 79 79 80 74 73 70 68 64 85
31 85 85 86 80 79 76 74 70 91 47 4 81 81 81 76 74 72 69 66 87
33 87 87 87 82 80 78 75 72 93 50 4 82 82 82 77 75 73 70 67 88
35 88 88 88 83 81 79 76 73 94
012 37 2 89 89 89 84 82 80 77 74 95 50 2 93 93 94 95 92 89 87 84 101
40 90 90 90 85 83 81 78 75 96 53 2 95 95 95 97 94 90 88 86 103
42 91 91 92 86 85 82 80 76 97 56 2 97 97 97 99 96 92 90 88 105
45 92 92 93 87 86 83 81 77 98 60 2 98 98 99 100 97 94 92 89 106
63 2 99 99 100 101 98 95 93 90 107
33 86 86 86 81 79 77 74 71 92 67 2 101 101 101 103 100 96 94 92 109
35 87 87 87 82 80 78 75 72 93 71 2 102 102 102 104 101 97 95 93 110
37 88 88 88 83 81 79 76 73 94 75 2 103 103 103 105 102 98 96 94 111
40 89 89 89 84 82 80 77 74 95 80 2 104 104 105 106 103 100 98 95 112
016 42 2 90 90 90 85 83 81 78 75 96 040 50 4 81 81 82 76 75 72 70 66 87
45 91 91 92 86 85 82 80 76 97 53 4 83 83 83 78 76 74 71 68 89
47 92 92 93 87 86 83 81 77 98 56 4 85 85 85 80 78 76 73 70 91
50 93 93 94 88 87 84 82 78 99 60 4 86 86 87 81 80 77 75 71 92
63 4 88 88 88 83 81 79 76 73 94
25 78 78 78 80 77 73 71 69 86 67 4 89 89 89 84 82 80 77 74 95
30 83 83 83 78 76 74 71 68 89 71 4 90 90 90 85 83 81 78 75 96
31 84 84 84 79 77 75 72 69 90 75 4 91 91 91 86 84 82 79 76 97
33 85 85 85 80 78 76 73 70 91 80 4 92 92 93 87 86 83 81 77 98
35 86 86 86 81 79 77 74 71 92
37 87 87 87 82 80 78 75 72 93 67 2 102 102 103 104 101 97 95 93 110
020 40 2 88 88 88 83 81 79 76 73 94 71 2 103 103 104 105 102 98 96 94 111
42 89 89 90 84 83 80 78 74 95 75 2 105 105 106 107 104 100 98 96 113
45 90 90 90 85 83 81 78 75 96 80 2 106 106 107 108 105 101 99 97 114
47 91 91 92 86 85 82 80 76 97 63 4 88 88 88 83 81 79 76 73 94
50 93 93 93 88 86 84 81 78 99 67 4 90 90 90 85 83 81 78 75 96
53 94 94 94 89 87 85 82 79 100 71 4 91 91 92 86 85 82 80 76 97
56 95 95 95 90 88 86 83 80 101 75 4 93 93 93 88 86 84 81 78 99
050 80 4 94 94 95 89 88 85 83 79 100
31 2 81 81 82 83 80 77 75 72 89 85 4 96 96 96 91 89 87 84 81 102
33 2 84 84 85 79 78 75 73 69 90 90 4 97 97 97 92 90 88 85 82 103
35 2 85 85 86 80 79 76 74 70 91 95 4 98 98 99 93 92 89 87 83 104
37 2 86 86 87 81 80 77 75 71 92 99 4 99 99 100 94 93 90 88 84 105
40 2 88 88 88 83 81 79 76 73 94 71 6 84 85 81 74 72 70 67 61 89
42 2 89 89 89 84 82 80 77 74 95 75 6 86 87 83 76 74 72 69 63 91
45 2 90 90 90 85 83 81 78 75 96 80 6 87 88 84 77 75 73 70 64 92
47 2 90 90 91 85 84 81 79 75 96
50 2 92 92 92 87 85 83 80 77 98 63* 2 110 105 104 108 100 96 91 91 114
025 53 2 94 94 94 89 87 85 82 79 100 67* 2 111 106 105 109 101 97 92 92 115
56 2 95 95 95 90 88 86 83 80 101 71* 2 113 108 107 111 103 99 94 94 117
60 2 97 97 97 92 90 88 85 82 103 75* 2 114 109 108 112 104 100 95 95 118
63 2 98 98 99 93 92 89 87 83 104 80 2 107 107 108 109 106 102 100 98 115
42 4 80 80 76 70 68 66 62 57 84 82 2 108 108 109 110 107 103 101 99 116
45 4 81 81 77 71 69 67 63 58 85 85 2 108 108 109 110 107 103 101 99 116
47 4 81 82 78 71 69 67 64 58 86 87 2 109 109 110 111 108 104 102 100 117
50 4 83 83 79 73 71 69 65 60 87 80 2 95 95 95 90 88 86 83 80 101
063 85 4 96 96 97 91 90 87 85 81 102
53 4 84 84 80 74 72 70 66 61 88
90 4 98 98 99 93 92 89 87 83 104
95 4 100 100 100 95 93 91 88 85 106
99 4 101 101 102 96 95 92 90 86 107
80 6 88 88 84 78 76 74 70 65 92
85 6 89 90 86 79 77 75 72 66 94
90 6 91 91 87 81 79 77 73 68 95
95 6 93 94 90 83 81 79 76 70 98
99 6 94 95 91 84 82 80 77 71 99

* Correction K3, Kb and Kc - see lowest part of Table 1


The above data are valid for the operating ranges shown in the charts on pages 14-15.
HCBB - Dimensions and weights - Fan Page 19

C E

A
F

D outs. B

X
N
K The sketches show a right-hand model.

Inspection cover location.


30o When delivered, the inspection cover
CLOutlet

Y is placed in the upper part of the ca-


CL Inlet o
sing, 30 above the horizontal centre
line.

Y
G1

G
n holes Z

P2 P3
P1

H2 H3 H3

J1 J2 J2

O1 O2 O2

M1 M2 N3

N1 N2

dd = 11 (0o) = Right-hand model dd = 12 (45o) dd = 13 (90o)


dd = 61 (0o) = Left-hand model dd = 62 (45o) dd = 63 (90o)

P4
P7 P8

H3 H4 H4

J2
J3 J3
O2
O3 O3
M3
N3 M3
N4
N4

dd = 14 (135o) dd = 17 (270o) dd = 18 (315o)


dd = 64 (135o) dd = 67 (270o) dd = 68 (315o)
HCBB - Dimensions Page 20

Dimensions HCBB
Fan Imp. dia.
E F H2 H3 H4 M1 M2 M3 N1 N2 N3 N4 P1 P2 P3 P4 P7 P8
size bb
26-31 246 234 360 325 390 319 285 400 549 504 510 637 606 725 644 609 619 610
010
33-40 297 308 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
30-35 270 257 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
012
37-45 327 340 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
33-40 297 278 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
016
42-50 361 371 510 455 555 486 447 599 845 791 775 972 871 1054 941 901 914 899
25 206 126 310 280 330 261 228 330 445 404 417 520 516 610 541 507 514 506
30-35 270 220 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
020
37-45 327 302 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
47-56 398 406 560 500 610 541 500 664 943 885 862 1082 958 1164 1041 999 1012 995
31 246 159 360 325 390 324 285 403 554 504 510 641 606 728 649 609 619 610
33-40 297 233 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
025 42-50 361 326 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
53-63 441 443 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
40 297 201 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
031 42-50 361 293 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
60-71 489 480 675 600 740 677 629 825 1182 1112 1071 1357 1164 1425 1277 1228 1245 1223
50 361 251 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
040 53-63 441 368 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
67-80 542 515 750 660 820 755 704 917 1319 1245 1194 1512 1292 1577 1415 1363 1385 1361
63 441 318 615 545 675 628 561 756 1078 992 961 1224 1056 1301 1173 1105 1125 1106
050 67-80 542 465 750 660 820 775 704 931 1339 1245 1194 1519 1292 1591 1435 1363 1385 1361
85-99 670 650 920 805 1005 960 884 1153 1669 1563 1489 1892 1590 1958 1765 1688 1714 1684
63-80 552 400 750 660 820 775 704 938 1339 1245 1204 1526 1302 1598 1435 1363 1385 1361
063
82-99 680 585 920 805 1005 960 884 1160 1669 1563 1499 1899 1600 1965 1765 1688 1714 1684

Dimensions L
Motor
Fan size
size
010 012 016 020 025 031 040 050 063
63 338 - - - - - - - -
71 364 384 - 444 - - - - -
80 387 407 433 467 508 558
90S - 420 446 480 521 571 - - -
90L - 445 471 505 546 - 661 - -
100L - - 499 533 574 624 689 - -
112M - - - 536 577 627 692 778 -
132S - - - 602 643 693 758 844 -
132M - - - - - - 758 844 944
160 - - - - 769 819 884 970 1070
180 - - - - - 896 961 1047 1147
200L - - - - - 989 1054 1140 1240
225M - - - - - - 1116 1202 1302
250M - - - - - - 1123 1209 1309
280S - - - - - - - 1397 1497
280M - - - - - - - - 1557
315S - - - - - - - - 1632
315MA - - - - - - - - 1632
HCBB - Dimensions and weights Page 21

Dimensions and weights, HCBB with 2-pole motor


Fan Imp. Weight, kg
A B C D O1 O2 O3 J1 J2 J3 N K G G1 P X Y Z n
size dia. incl. motor
26-28 100 80 105 104 460 430 480 205 190 215 199 262 180 - 142 31 34 88 9 2
30-31 100 80 105 104 460 430 480 205 190 215 214 277 198 - 160 34 34 88 9 2
010
33-35 100 80 106 104 520 480 550 235 215 250 214 278 176 - 138 49 34 88 9 2
37-40 100 80 106 104 520 480 550 235 215 250 234 298 192 - 154 53 34 88 9 2
30-31 125 100 115 129 480 450 510 215 200 230 224 297 218 - 170 41 34 88 9 2
33-35 125 100 115 129 480 450 510 215 200 230 244 317 242 - 194 44 34 88 9 2
012 37-40 125 100 116 129 570 520 610 260 235 280 244 318 218 - 170 61 33 88 9 2
42 125 100 116 129 570 520 610 260 235 280 275 349 256 - 208 68 33 88 9 2
45 125 100 116 129 570 520 610 260 235 280 275 349 256 - 208 71 33 88 9 2
33-37 160 125 128 164 520 480 550 235 215 250 256 343 252 - 190 57 33 88 9 2
40 160 125 128 164 520 480 550 235 215 250 288 375 278 - 216 62 33 88 9 2
016
42-45 160 125 128 164 610 560 650 280 255 300 288 375 276 - 214 88 34 88 9 2
47-50 160 125 128 164 610 560 650 280 255 300 314 401 310 - 248 97 34 88 9 2
25 200 160 145 205 410 380 420 180 165 185 254 357 298 - 220 34 34 88 9 2
30 200 160 145 205 480 450 510 215 200 230 254 357 290 - 212 45 34 88 9 2
31-35 200 160 145 205 480 450 510 215 200 230 274 377 312 - 234 48 34 88 9 2
37 200 160 146 205 570 520 610 260 235 280 305 409 330 - 251 68 33 88 9 2
020
40-42 200 160 146 205 570 520 610 260 235 280 305 409 330 - 251 77 33 88 9 2
45 200 160 146 205 570 520 610 260 235 280 332 436 368 - 289 86 33 88 9 2
47-50 200 160 146 205 670 610 710 310 280 330 339 443 358 - 279 117 34 88 9 2
53-56 200 160 146 205 670 610 710 310 280 330 396 500 412 - 333 137 34 88 9 2
31 250 200 165 255 460 430 480 205 190 215 294 418 354 - 265 45 34 88 9 2
33 250 200 166 255 520 480 550 235 215 250 294 418 348 - 269 61 33 88 9 2
35-37 250 200 166 255 520 480 550 235 215 250 325 449 376 - 297 67 33 88 9 2
40 250 200 166 255 520 480 550 235 215 250 325 449 376 - 297 67 33 88 9 2
025 42 250 200 166 255 610 560 650 280 255 300 352 476 414 - 335 100 32 88 9 2
45 250 200 166 255 610 560 650 280 255 300 359 483 428 - 330 104 34 88 9 2
47-50 250 200 166 255 610 560 650 280 255 300 416 540 482 - 387 125 33 88 9 2
53 250 200 166 255 710 650 770 330 300 360 416 540 460 - 381 157 32 110 11 2
56-63 250 200 166 255 710 650 770 330 300 360 512 637 550 - 482 232 34 110 11 2
40 315 250 191 320 520 480 550 235 215 250 377 526 426 - 348 81 33 88 9 2
42 315 250 191 320 610 560 650 280 255 300 372 509 444 - 343 108 34 88 9 2
45-47 315 250 191 320 610 560 650 280 255 300 428 566 488 - 399 125 34 88 9 2
50 315 250 191 320 610 560 650 280 255 300 428 566 488 - 399 129 34 88 9 2
031
60 315 250 192 320 770 720 820 355 330 380 537 687 568 - 492 272 34 110 11 2
63 315 250 192 320 770 720 820 355 330 380 537 687 568 - 492 278 34 110 11 2
67 315 250 192 320 770 720 820 355 330 380 575 725 590 - 530 307 34 110 11 2
71 315 250 192 320 840 790 890 390 365 415 614 765 552 - 568 379 34 110 11 2
50 400 315 223 405 610 560 650 280 255 300 568 750 526 - 524 192 33 110 11 2
53-56 400 315 223 405 710 650 770 330 300 360 569 752 570 - 524 240 34 110 11 2
60 400 315 223 405 710 650 770 330 300 360 569 752 570 - 524 245 34 110 11 2
040 63 400 315 223 405 820 750 870 385 350 410 608 792 564 - 562 275 34 110 11 2
67-71 400 315 224 405 930 840 1000 435 390 470 646 830 610 - 600 417 34 110 11 2
75 400 315 224 405 930 840 1000 435 390 470 668 852 658 - 622 427 34 110 11 2
80 400 315 224 405 1000 920 1060 470 430 500 728 910 808 146 680 531 30 110 11 2
67 500 400 267 505 930 840 1000 435 390 470 689 915 664 - 643 436 34 110 11 2
71 500 400 267 505 930 840 1000 435 390 470 711 937 796 146 665 491 32 110 11 2
050
75 500 400 267 505 1000 920 1060 470 430 500 770 995 869 145 722 561 32 110 11 2
80 500 400 267 505 1000 920 1060 470 430 500 862 1087 873 145 814 792 34 110 11 2
63 630 500 317 635 930 840 1000 435 390 470 761 1037 720 - 715 494 32 110 11 2
67 630 500 317 635 1000 920 1060 470 430 500 820 1098 1005 213 772 578 32 110 11 2
71 630 500 317 635 1000 920 1060 470 430 500 912 1190 829 185 854 783 39 144 14 2
063 75 630 500 317 635 1000 920 1060 470 430 500 912 1190 829 185 854 789 39 144 14 2
80 630 500 317 635 1000 920 1060 470 430 500 912 1190 829 185 854 886 39 144 14 2
82 630 500 317 635 1150 1050 1220 545 495 580 991 1269 1019 185 933 1117 38 144 14 2
85-87 630 500 317 635 1150 1050 1220 545 495 580 991 1269 1019 160 933 1190 38 144 14 2
HCBB - Dimensions and weights Page 22

Dimensions and weights, HCBB with 4-pole motor


Fan Imp. Weight, kg
A B C D O1 O2 O3 J1 J2 J3 N K G G1 P X Y Z n
size dia. incl. motor
42-45 250 200 166 255 610 560 650 280 255 300 294 418 352 - 265 83 34 88 9 2
47 250 200 166 255 610 560 650 280 255 300 294 418 352 - 265 87 34 88 9 2
025
50 250 200 166 255 610 560 650 280 255 300 294 418 352 - 265 92 34 88 9 2
53 250 200 166 255 710 650 770 330 300 360 325 449 348 - 250 126 34 88 9 2
45 315 250 191 320 610 560 650 280 255 300 319 468 398 - 300 81 33 88 9 2
031 47 315 250 191 320 610 560 650 280 255 300 319 468 398 - 300 92 33 88 9 2
50 315 250 191 320 610 560 650 280 255 300 350 499 426 - 328 97 33 88 9 2
50 400 315 223 405 610 560 650 280 255 300 383 565 502 - 354 94 33 88 9 2
53 400 315 223 405 710 650 770 330 300 360 383 565 480 - 338 139 33 110 11 2
56 400 315 223 405 710 650 770 330 300 360 410 592 500 - 366 149 33 110 11 2
040
60-63 400 315 223 405 710 650 770 330 300 360 410 592 500 - 366 156 33 110 11 2
67-71 400 315 223 405 930 840 1000 435 390 470 417 600 510 - 412 234 32 110 11 2
75-80 400 315 223 405 930 840 1000 435 390 470 475 658 556 - 458 259 42 124 11 2
63 500 400 267 505 710 650 770 330 300 360 459 684 570 - 415 171 33 110 11 2
67-71 500 400 267 505 930 840 1000 435 390 470 517 742 657 315 472 265 32 110 11 2
75 500 400 267 505 930 840 1000 435 390 470 517 742 657 315 472 273 32 110 11 2
050
80 500 400 267 505 930 840 1000 435 390 470 612 837 752 298 567 338 32 110 11 2
85-90 500 400 267 505 1100 1000 1180 520 470 560 612 837 744 - 567 431 33 110 11 2
95-99 500 400 267 505 1100 1000 1180 520 470 560 650 875 766 - 655 473 33 110 11 2
80 630 500 317 635 930 840 1000 435 390 470 662 937 722 - 607 343 40 144 14 2
85 630 500 317 635 1100 1000 1180 520 470 560 662 937 772 - 607 452 40 144 14 2
063 90 630 500 317 635 1100 1000 1180 520 470 560 700 975 826 - 655 476 33 110 11 2
95 630 500 317 635 1100 1000 1180 520 470 560 700 975 826 - 655 488 33 110 11 2
99 630 500 317 635 1100 1000 1180 520 470 560 739 1015 928 254 694 552 33 110 11 2

Dimensions and weights, HCBB with 6-pole motor


Fan Imp. Weight, kg
A B C D O1 O2 O3 J1 J2 J3 N K G G1 P X Y Z n
size dia. incl. motor
71 500 400 267 505 930 840 1000 435 390 470 460 685 624 - 430 246 35 110 11 2
050 75 500 400 267 505 930 840 1000 435 390 470 460 685 624 - 430 254 35 110 11 2
80 500 400 267 505 930 840 1000 435 390 470 517 742 657 315 472 274 34 110 11 2
80 630 500 317 635 930 840 1000 435 390 470 567 842 785 316 537 286 30 110 11 2
063 85-90 630 500 317 635 1100 1000 1180 520 470 560 567 842 730 - 522 394 35 124 11 2
95-99 630 500 317 635 1100 1000 1180 520 470 560 662 937 772 - 607 467 56 120 14 4
HCBB - Heat shield, Cleanout cover Page 23

Heat shield HCEZ-07-b-cc


Shields the motor from radiated heat.
Casing side
Table - Heat shield selection
cc = cc in the fan code, (IEC motor size)
Heat shield
Size No. of motor poles Variant
Single-speed Two-speed
cc = 01-09 All All b=1
cc = 10-14 2-8 All b=1
cc = 15 4-8 4/8 b=1
cc = 16 2 2/4 b=1
cc = 16 4-8 4/6, 4/8 b=2 Impeller
cc = 17 2 - b=1
cc = 17 4-8 4/6, 4/8 b=2
cc = 18 2 - b=1 Motor
cc = 19 2 - b=1
cc = 20 2 - b=1
cc = 21 2 - b=1
Shaft packing

Cleanout cover HCEZ-09-bb-c-ddd Table - Cleanout cover selection


Robust, designed for frequent inspections.
Double sheet construction and handle. Fan size Impeller dia. bb
26-31 02
010
33-40 03
30-35 05
012
37-45 06
33-40 07
016
42-50 08
25 09
30-35 10
020
37-45 11
47-56 12
31 13
33-40 14
025
42-50 15
53-63 16
40 17
031 42-50 18
60-71 19
50 20
040 53-63 21
67-80 22
63 23
050 67-80 24
85-99 25
63-80 26
063 82-99 27
HCBB - Dimensions and weights - Accessories Page 24

NB! Flanges comply to ISO 13351.


HCEZ-30 HCEZ-35 HCEZ-50, 51
B g n holes G n holes G n holes G
g

E1

A n1 x E C

E1

F1 n2 x F F1 t + 2,5 t t
+ 10
130 - 20
D

HCEZ- HCEZ- HCEZ-


30 35 50/51
Fan Weight Weight Weight
size A A1 B B1 C D E E1 F F1 G t g n n1 n2 kg kg kg
010 100 85 80 65 170 150 71 33.5 --- --- 10 5 19 8 1 1 0.6 0.5 1.1
012 125 110 100 85 195 170 71 46 71 33.5 10 5 19 12 1 1 0.8 0.7 1.5
016 160 145 125 110 230 195 100 49 71 46 10 5 19 12 1 1 0.9 0.8 1.7
020 200 185 160 145 270 230 100 69 100 49 10 5 19 12 1 1 1.1 1.0 2.1
025 250 235 200 185 330 280 125 81.5 125 56.5 10 6 19 12 1 1 2.1 1.9 3.9
031 315 295 250 230 395 330 125 51.5 125 81.5 10 6 19 14 2 1 2.8 2.4 5.0
040 400 380 315 295 480 395 125 94 125 51.5 10 6 19 16 2 2 3.5 2.9 6.0
050 500 480 400 380 620 520 125 94.5 125 107 12 8 32 18 3 2 8.5 7.6 15.5
063 630 600 500 480 750 620 125 97 125 94.5 12 8 32 22 4 3 10.5 9.2 18.8

HCEZ-20 HCEZ-21 HCEZ-40/41


weight 0.1 - 1.1 kg
HCEZ-25/27 HCEZ-29 HCEZ-45/46
t1
125
h


F
E
D1 D4 D2 D3 D D D1 D2
ins. ins. outs. ins. ins.

+10 +10
t 40 - 20 130 - 20
nxG 45
L K

HCEZ- HCEZ- HCEZ-


20/21 25/27/29 45/46
Fan Weight Weight Weight
size D E F G t t1 D1 D2 D3 D4 K L h n kg kg kg
010 105 139 170 9.5 5 -- 106 --- --- 230 --- 65 32.5 4 0.7 0.5 ---
012 130 165 195 9.5 5 -- 131 --- --- 255 --- 65 32.5 4 0.9 0.6 ---
016 165 200 240 12 5 -- 166 --- --- 295 --- 70 37.5 4 1.1 0.7 ---
020 205 241 280 12 5 -- 207 --- --- 335 --- 70 37.5 8 1.2 1.0 ---
025 255 292 330 12 6 -- 257 --- --- 400 --- 75 37.5 8 1.7 1.7 ---
031 320 366 405 12 6 -- 322 --- --- 470 --- 80 42.5 8 2.2 2.1 ---
040 405 448 490 12 6 2 407 400 528 528 192 192 42.5 12 5.9 3.4 8.4
050 505 551 600 12 8 2 507 500 628 628 192 192 47.5 12 6.8 4.8 11.3
063 635 698 750 14 8 2.5 637 630 809 809 218 218 57.5 16 11.8 5.9 14.5
HCBT Page 25
Ordering Key - HCBT - Direct-driven Page 26

HCBT-aaa-bb-cc-dd-ee-fff

Size 1) (aaa)
010, 012, 016, 020, 025, 031, 040, 050 och 063.

Impeller diameter, cm, 1) (bb)

Motor size - IEC (cc)


Motor size (cc) is as per the "design data" table on page 32.
NB! Motors must always be ordered separately and in accordance with the ordering key on page 32.

Designations for rotation and discharge (dd)

11 0o 12 45o 13 90o 14 135o 17 270o 18 315o


Right
(RD)

61 0o 62 45o 63 90o 64 135o 67 270o 68 315o


Left
(LG)

NB! The above diagrams show the drive side.

Fan version (ee)


01 = standard version.
02 = sparkproof version, (brass ring at the inlet and brass washers at the shaft inlet).

Material, finish (fff)


001 = Standard material, GA80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Not fully welded Max. temperature 150oC. 2)
032 = Standard material, GA80TD80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Not fully welded
300 = SS 2333 throughout. Not fully welded
400 = SS 2343 throughout. Not fully welded

1)
For variants in a size, impeller diameter, number of poles combination, please refer first to page 32, Design data.
2)
GP40-01 primer can be used where temperatures exceed 120C. This primer tolerates temperatures up to 150C
and vaporises at higher temperatures without emitting any toxic substances.
Ordering key - HCBT - Accessories Page 27

Heat shield for temperatures up to 200oC HCEZ-07-b-cc


Size: Refer to "Heat shield selection" table, page 38
Variants: Refer to "Heat shield selection" table, page 38

Cleanout cover HCEZ-09-bb-c-ddd


Cover size: Refer to table on page 38
Location
With discharge directions 11 and 61 c = 1
For other discharge directions c=2
Material and finish: Refer to the fff code in the main fan ordering key

Inlet taper piece without connecting flange 1) HCEZ-20-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key
1)
For direct connection to fans without inlet flange.

Inlet taper piece with connecting flange 2) HCEZ-21-bbb-ccc


Size (= 040 - 063)
Material and finish: Refer to the fff code in the main fan ordering key
2)
For connection to fans with inlet flange or to inlet vane assemblies or regulating dampers.

Counterflange, inlet, (not fitted) HCEZ-25-bbb-ccc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Inlet flange, (fitted) HCEZ-27-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Inlet connecting flange 3) HCEZ-29-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key
3)
NB! When connecting to size 031 inlet vane assemblies, size 040 inlet connecting flange must be used.

Fabric duct, inlet, without connecting flanges 4) HCEZ-aa-bbb


Temp. class
40 = max. 70oC.
41 = max. 200oC.
Size (= fan size)
4)
For connection to fans without inlet flange.

Fabric duct, inlet, with connecting flanges 5) HCEZ-aa-bbb-ccc


Temp. class
45 = max. 70oC.
46 = max. 200oC.
Size (= 040 - 063)
For material and finish (flanges), refer to the fff code in the main fan ordering key
5)
For connection to fans with inlet flange or to inlet vane assemblies.
NB! When connecting to size 031 inlet vane assemblies, size 040 must be used.
Ordering key - HCBT - Accessories, cont. Page 28

Flue gas duct, inlet, without connecting flanges 6) HCEZ-aa-bbb-cc


Temp. class
60 = max. 200oC.
Size (= fan size)
Material (wearing plate)
01 = Steal, primed.
03 = SS 2333.
04 = SS 2343.
6)
For connection to fans without inlet flange.

Flue gas duct, inlet, with connecting flanges 7) HCEZ-aa-bbb-ccc


Temp. class
65 = max. 200oC.
Size (= 040 - 063)
For material and finish, (flanges), refer to the fff code in the main fan ordering key
NB! Wearing plate is only available in steel, primed or stainless steel qualities depending on choice of ccc code.
7)
For connection to fans with inlet flange or to inlet vane assemblies.
NB! When connecting to size 031 inlet vane assemblies, size 040 must be used.

Protective screen, outlet HCEZ-30-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Counterflange, outlet, (not fitted) HCEZ-35-bbb-cc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Fabric duct, outlet, with connecting flanges HCEZ-aa-bbb-ccc


Temp. class
50 = max. 70oC.
51 = max. 200oC.
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key

Flue gas duct, outlet, with connecting flanges 8) HCEZ-aa-bbb-ccc


Temp. class
70 = max. 200oC.
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key
NB! Wearing plate is only available in steel, primed or stainless steel qualities depending on choice of ccc code.
8)
For connection to fans with inlet flange or to inlet vane assemblies.
NB! When connecting to size 031 inlet vane assemblies, size 040 must be used.

Regulating damper DMEG (see page 105)

Inlet vane control assembly HXEG (see pages 106 - 111).


HCBT - Description - Accessories, inlet and outlet Page 29

15 2, 3
Duct
13, 14
4 5

12 4
6, 7
5
4
6, 7
8, 9
10

4
6, 7
11
2, 3

2, 3
11
6, 7
10
NB! Flanges comply with ISO 13351

Inlet
1 HCEZ-20 Inlet taper piece with protective screen and fixing lugs for connection to inlet without connecting
flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HCEZ-40, 41 Fabric duct, inlet without connecting flange. 2)
3 HCEZ-60 Flue gas duct, inlet without connecting flanges. 2)
4 HCEZ-27 Inlet flange, (fitted).
5 HCEZ-21 Inlet taper piece with protective screen and connecting flange for installation to inlet with
connecting flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
6 HXEG Inlet vane control assembly, see pages 106 - 111. 1)
7 DMEG Regulating damper, see page 105. 1)
8 HCEZ-45, 46 Fabric duct, inlet with connecting flanges. 2)
9 HCEZ-65 Flue gas duct, inlet with connecting flanges. 2)
10 HCEZ-25 Counterflange, inlet, (not fitted).
11 HCEZ-29 Inlet connecting flange, for fitting ducts without connecting flanges.

Outlet
12 HCEZ-30 Protective screen, outlet.
13 HCEZ-50, 51 Fibre duct, outlet, with connecting flanges. 2)
14 HCEZ-70 Flue gas duct, outlet with connecting flanges. 2)
15 HCEZ-35 Counterflange, outlet, (not fitted).
1)
NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that the anti-vibration mountings can
cope with the increased component load on the fan.
2)
For size and temperature limits, please refer to the appropriate ordering keys.
HCBT - Air flow and dynamic pressure rise charts Page 30

The charts are valid for gas at a density of 1,2 kg/m2.


Gas flow, m3/h
300 400 500 1000 2000 3000 5000 10 000 20 000 30 000
10 000
Impeller diameter
71
2-pole motor
71 025
71 4-pole motor 63
6-pole motor 60
5000 56
016 53
4000 063
50 50
47 47 95
3000 45 45 040
90
Size 010 42 42 80
40 40 85
75
2000 40 37 80
37 71
37 35
67 99
35 33 35
33 63
Total pressure rise, Pa

31 33 95
31 60
30 31 90
1000 28 53 56
50 85
26 53
25 47 80
50
45
42
500
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s

2000

1000

400

Size 010 016 025 040 063


200
Dynamic pressure, Pa

100

40

20
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s

Moment of inertia (J) See page 33. Sound data See pages 33-34.
HCBT - Air flow and dynamic pressure rise charts Page 31

The charts are valid for gas at a density of 1,2 kg/m2.


Gas flow, m3/h
300 400 500 1000 2000 3000 5000 10 000 20 000 30 000
10 000
Impeller diameter
71
2-pole motor
71 031
71 4-pole motor
63
6-pole motor 020 60
5000 56 050
53 99
4000
50 50 95
Size 012 47
90
3000 47
45
45 85
42 45
42 80
40 42
40 37
2000 75
37 35 40
71
35 33
33 67
Total pressure rise, Pa

31 31
30 63
30
1000 28 80
50
75
25 47 71
45

500
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s

2000

1000

400

Size 012 020 031 050


200
Dynamic pressure, Pa

100

40

20
0.06 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 7 8 9 10
Gas flow, m3/s

Example: Flow 3.3 m3/s, total pressure rise 2500 Pa. Pressure losses across accessories:
HCEZ-20 and 21 inlet taper piece:
Select an HCBT-050 with an 80 cm diameter impeller 0.35 x dynamic pressure Pd.
and a 4-pole motor.

Dynamic pressure: 175 Pa.

Moment of inertia (J) See page 33. Sound data See pages 33-34.
HCBT - Design data Page 32

Fan Motor * Fan Motor *


Max. Max.
Motor Rated power Motor Rated power
Fan Imp. Motor- size out- Ordering demand Fan Imp. Motor- size out- Ordering demand
size dia. size as per R P M put key of fan, size dia. size as per R P M put, key of fan
aaa bb cc IEC kW APAL- kW aaa bb cc IEC kW APAL- kW
25 01 63 2820 0.25 2-00025-c-0 0.13 40 08 132S 2855 7.5 2-00750-c-0 5.9
26 01 63 2820 0.25 2-00025-c-0 0.17 42 10 160M 2930 11 2-01100-c-0 7.5
28 02 71 2840 0.37 2-00037-c-0 0.22 10 160M 2930 11 2-01100-c-0 9.1
45
30 02 71 2840 0.37 2-00037-c-0 0.27 05 90L 1420 1.5 4-00150-c-0 1.3
010 31 02 71 2850 0.55 2-00055-c-0 0.31 11 160L 2920 18.5 2-01850-c-0 14
031 47
33 02 71 2850 0.55 2-00055-c-0 0.40 06 100L 1430 2.2 4-00220-c-0 1.7
35 03 80 2860 0.75 2-00075-c-0 0.51 11 160L 2920 18.5 2-01850-c-0 16
50
37 03 80 2870 1.1 2-00110-c-0 0.64 06 100L 1430 2.2 4-00220-c-0 1.7
40 03 80 2870 1.1 2-00110-c-0 0.80
60 14 200L 2950 37 2-03700-c-0 31
28 02 71 2840 0.37 2-00037-c-0 0.34 63 14 200L 2950 37 2-03700-c-0 34
30 02 71 2850 0.55 2-00055-c-0 0.43
31 03 80 2860 0.75 2-00075-c-0 0.54 50 06 100L 1430 3 4-00300-c-0 2.6
33 03 80 2870 1.1 2-00110-c-0 0.68 53 07 112M 1435 4 4-00400-c-0 2.8
012 35 03 80 2870 1.1 2-00110-c-0 0.85 56 07 112M 1435 4 4-00400-c-0 3.5
60 08 132S 1450 5.5 4-00550-c-0 4.4
37 04 90S 2870 1.5 2-00150-c-0 0.95 040 63 09 132M 1450 7.5 4-00750-c-0 5.5
40 05 90L 2870 2.2 2-00220-c-0 1.2
42 05 90L 2870 2.2 2-00220-c-0 1.5 67 10 160M 1460 11 4-01100-c-0 6.9
45 06 100L 2900 3 2-00300-c-0 1.9 71 10 160M 1460 11 4-01100-c-0 8.3
75 11 160L 1455 15 4-01500-c-0 10
31 03 80 2870 1.1 2-00110-c-0 0.75 80 11 160L 1455 15 4-01500-c-0 12
33 04 90S 2870 1.5 2-00150-c-0 0.95
35 04 90S 2870 1.5 2-00150-c-0 1.2 63 10 160M 1460 11 4-01100-c-0 7.2
37 05 90L 2870 2.2 2-00220-c-0 1.5 67 11 160L 1455 15 4-01500-c-0 9.1
016 40 05 90L 2870 2.2 2-00220-c-0 1.8 12 180M 1470 18.5 4-01850-c-0 12
71
42 06 100L 2900 3 2-00300-c-0 2.3 09 132M 960 4 6-00400-c-0 3.5
45 07 112M 2850 4 2-00400-c-0 2.8 13 180L 1470 22 4-02200-c-0 15
75
47 08 132S 2855 5.5 2-00550-c-0 3.5 050 09 132M 955 5.5 6-00550-c-0 4.4
50 08 132S 2855 5.5 2-00550-c-0 4.3 13 180L 1470 22 4-02200-c-0 19
80
25 03 80 2860 0.75 2-00075-c-0 0.64 10 160M 970 7.5 6-00750-c-0 5.2
30 04 90S 2870 1.5 2-00150-c-0 1.1 85 14 200L 1475 30 4-03000-c-0 24
31 04 90S 2870 1.5 2-00150-c-0 1.3 90 15 225S 1480 37 4-03700-c-0 27
33 05 90L 2870 2.2 2-00220-c-0 1.6 95 16 225M 1480 45 4-04500-c-0 33
35 05 90L 2870 2.2 2-00220-c-0 1.9 99 17 250M 1480 55 4-05500-c-0 40
37 06 100L 2900 3 2-00300-c-0 2.3 14 200L 1475 30 4-03000-c-0 27
020 40 07 112M 2850 4 2-00400-c-0 2.8 80
11 160L 970 11 6-01100-c-0 7.6
42 08 132S 2855 5.5 2-00550-c-0 3.5
15 225S 1480 37 4-03700-c-0 33
45 08 132S 2855 5.5 2-00550-c-0 4.3 85
11 160L 970 11 6-01100-c-0 9.2
47 08 132S 2855 7.5 2-00750-c-0 5.2 063 16 225M 1480 45 4-04500-c-0 38
50 08 132S 2855 7.5 2-00750-c-0 6.4 90
13 180L 970 15 6-01500-c-0 13
53 10 160M 2930 11 2-00110-c-0 8
56 10 160M 2920 15 2-01500-c-0 9.8 17 250M 1480 55 4-05500-c-0 48
95
14 200L 985 18.5 6-01850-c-0 16
31 05 90L 2870 2.2 2-00220-c-0 2
33 06 100L 2900 3 2-00300-c-0 2.5 99 14 200L 980 22 6-02200-c-0 19
35 07 112M 2850 4 2-00400-c-0 3.4
37 08 132S 2855 5.5 2-00550-c-0 4.4
40 08 132S 2855 7.5 2-00750-c-0 5
Voltage code
08 132S 2855 7.5 2-00750-c-0 5.5
42 1 = 220-240VD/380-420VY
04 90S 1410 1.1 4-00110-c-0 0.75
10 160M 2930 11 2-01100-c-0 6.8 2 = 380-420VD/660-690VY
45
04 90S 1410 1.1 4-00110-c-0 0.9 5 = 500 VY (sizes 63-100)
025 500 VD (sizes 112-355)
10 160M 2930 11 2-01100-c-0 8.3
47
05 90L 1420 1.5 4-00150-c-0 1.1
10 160M 2920 15 2-01500-c-0 10
50
05 90L 1420 1.5 4-00150-c-0 1.3
11 160L 2920 18.5 2-01850-c-0 13
53
06 100L 1430 2.2 4-00220-c-0 1.6
56 11 160L 2920 18.5 2-01850-c-0 16 * Please refer to pages 101 - 104 for motor details not included here.
60 12 180M 2930 22 2-02200-c-0 20 For further motor data and information on motor versions, please
63 14 200L 2955 30 2-03000-c-0 24 contact ABB Motors.
HCBT - Moment of inertia - Sound data Page 33

Moment of inertia J (=1/4 GD2)


Fan Imp. Imp. Fan Imp. Imp. Fan Imp. Imp. Fan Imp. Imp.
size dia. weight J size dia. weight J size dia. weight J size dia. weight J
aaa bb kg kg m2 aaa bb kg kg m2 aaa bb kg kg m2 aaa bb kg kg m2
25 3.3 0.014 25 3.9 0.017 40 10.7 0.14 63 25.0 1.1
26 3.7 0.02 30 4.8 0.04 42 13.0 0.22 67 32.0 1.7
28 3.7 0.022 31 4.9 0.045 45 13.3 0.24 71 33.0 1.8
30 4.1 0.032 33 6.4 0.06 031 47 16.4 0.34 75 41.0 3.2
31 4.1 0.033 35 6.5 0.07 50 16.7 0.37 050 80 46.0 3.4
010
33 5.4 0.05 37 7.2 0.11 60 21.0 0.89 85 50.0 4.5
35 5.5 0.052 020 40 7.3 0.11 63 22.0 0.92 90 53.0 4.7
37 6.3 0.1 42 9.0 0.18 50 14.6 0.35 95 56.0 6.9
40 6.5 0.1 45 9.2 0.19 53 21.0 0.63 99 66.0 7.2
28 3.8 0.022 47 12.8 0.28 56 22.0 0.68 80 49.0 3.6
30 4.2 0.033 50 13.0 0.29 60 26.0 0.99 85 52.0 5.1
31 4.3 0.034 53 15.5 0.44 040 63 27.0 1 063 90 65.0 5.6
33 5.6 0.052 56 16.8 0.45 67 29.0 1.5 95 74.0 8
35 5.6 0.053 31 5.0 0.042 71 29.0 1.58 99 75.0 8.5
012
37 6.5 0.1 33 6.6 0.067 75 36.0 2.8
40 6.5 0.1 35 6.8 0.07 80 37.0 2.9
42 7.6 0.16 37 7.9 0.1
45 8.1 0.17 40 8.1 0.11
31 4.5 0.038 42 12.0 0.19
33 6.0 0.056 025 45 12.0 0.2
35 6.0 0.06 47 13.5 0.3
37 6.9 0.11 50 13.7 0.31
40 7.0 0.11 53 15.2 0.46
016
42 9.1 0.18 56 15.4 0.48
45 9.3 0.18 60 21.0 0.85
47 12.2 0.27 63 25.0 0.88
50 12.3 0.28

Sound data

Symbols Correction K2
Lwtot = total sound power level for a
a, b, c
sound paths a, b and c ................. dB (ref. 10-12 W). 0
-5
K2, dB

Lw a,b,c = sound power level for sound paths a, b and c, b


-10
respectively by octave band ............................. dB.
-15 c
Kb, Kc, K2, K3 = corrections for sound paths b and c respectively -20
(for sound path a, the correction = 0) .............. dB. 0 4000 8000 12 000
Dpt, Pa
Sound paths: a = to inlet or outlet duct.
b = to surroundings (free-inlet fan).
c = to surroundings (fan connected to ducts Formulae:
on both inlet and outlet sides).
Lwtot , see table 2, page 34 Lwa, see table 2, page 34
a
NB!The stated values refer to sound power levels. Some fan manufac-
turers still quote sound pressure levels even though these vary with Ltotb = Lwtot + K2 + K3 Lwb = Lwtot + Kb
a b
the acoustic characteristics of the surroundings and distance from
the fan. Sound pressure levels, sometimes weighted as dB(A) or Lwtot = Lwtot + K2 + K3 Lwc = Lwtot + Kc
c a c
dB(C) values, are considerably lower than the corresponding sound
power level Lwt. To illustrate this: with a free inlet fan and hemis
pherical sound propagation, at a distance of 3 m from the fan, the Table 1. Correction K3, Kb and Kc
dB(A) value is 17 - 25 dB lower (depending on fan speed and blade
type) than the total sound power level. No. Cor- Cor- Correction Kb and Kc, dB
of Sound rec- rec-
poles path tion tion Octave band, mid-frequency, Hz
K3 63 125 250 500 1000 2000 4000 8000
b 0 Kb -10 -6 -4 -9 -12 -18 -25 -30
6 c -2 Kc -10 -5 -4 -10 -11 -18 -22 -27
b 0 Kb -11 -9 -3 -7 -12 -17 -23 -28
4 c -1 Kc -12 -7 -4 -7 -11 -17 -21 -26
b +1 Kb -6 -6 -6 -9 -13 -17 -22 -30
2 c +1 Kc -7 -9 -5 -6 -14 -17 -22 -29
HCBT - Sound data cont. Page 34

Table 2. Sound power level Lwa and Lwtot (sound path a)


a

Fan Im- No. Sound power level Lwa, dB Fan Im- No. Sound power level Lwa, dB
size peller of Lwtot size peller of Lwtot
Octave band, mid-frequency, Hz a Octave band, mid-frequency, Hz a
dia. pol. dia. pol.
aaa bb 63 125 250 500 1000 2000 4000 8000 dB aaa bb 63 125 250 500 1000 2000 4000 8000 dB
25 90 90 90 89 83 76 69 61 96 40 2 97 99 100 97 91 85 78 72 105
26 89 92 92 89 83 77 70 64 97 42 2 100 100 100 99 93 86 79 71 106
28 90 93 93 90 84 78 71 65 98 45 2 102 102 102 101 95 88 81 73 108
30 91 94 94 91 85 79 72 66 99 47 2 104 104 104 103 96 89 83 75 110
010 31 2 92 94 95 92 86 80 73 67 100 031 50 2 105 105 105 104 98 91 84 76 111
33 93 95 96 93 87 81 74 68 101 60 2 107 109 110 107 101 95 88 82 115
35 94 96 97 94 88 82 75 69 102 63 2 108 111 111 108 102 96 89 83 116
37 95 97 98 95 89 83 76 70 103 45 4 88 90 91 88 82 76 69 63 96
40 96 98 99 96 90 84 77 71 104 47 4 89 91 92 89 83 77 70 64 97
50 4 90 92 93 90 84 78 71 65 98
28 93 93 93 92 85 78 72 64 99
30 92 94 95 92 86 80 73 67 100 50 4 91 94 92 87 83 76 69 63 98
31 93 95 96 93 87 81 74 68 101 53 4 91 94 94 91 85 79 72 66 99
33 93 96 96 93 87 81 74 68 101 56 4 93 95 96 93 87 81 74 68 101
012 35 2 94 97 97 94 88 82 75 69 102
60 4 94 97 97 94 88 82 75 69 102
37 95 98 98 95 89 83 76 70 103
040 63 4 96 99 99 96 90 84 77 71 104
40 96 99 99 96 90 84 77 71 104
67 4 98 101 99 94 91 84 76 70 105
42 97 99 100 97 91 85 78 72 105
71 4 100 103 101 96 92 85 78 72 107
45 98 100 101 98 92 86 79 73 106
75 4 101 104 102 97 94 87 79 73 108
80 4 102 105 103 98 95 88 80 74 109
31 95 95 95 94 87 80 74 66 101
33 94 96 97 94 88 82 75 69 102
63 4 97 100 98 93 89 82 75 69 104
35 95 97 98 95 89 83 76 70 103
67 4 98 101 101 98 92 86 79 73 106
37 96 98 99 96 90 84 77 71 104
71 4 100 102 103 100 94 88 81 75 108
016 40 2 96 99 99 96 90 84 77 71 104
75 4 101 104 104 101 95 89 82 76 109
42 97 100 100 97 91 85 78 72 105
80 4 103 106 106 103 97 91 84 78 111
45 98 101 101 98 92 86 79 73 106
050 85 4 105 108 106 101 98 91 83 77 112
47 99 102 102 99 93 87 80 74 107
90 4 107 110 108 103 99 92 85 79 114
50 100 102 103 100 94 88 81 75 108
95 4 108 111 109 104 100 93 86 80 115
99 4 109 112 110 105 102 95 87 81 116
25 88 91 91 88 82 76 69 63 96
71 6 93 96 94 89 85 78 71 65 100
30 93 93 93 92 86 79 72 64 99
75 6 94 97 95 90 86 79 72 66 101
31 95 95 95 94 87 80 74 66 101
80 6 96 99 97 92 88 81 74 68 103
33 96 96 96 95 88 81 75 67 102
35 97 97 97 96 89 82 76 68 103
80 4 104 107 105 100 97 90 82 76 111
37 96 98 99 96 90 84 77 71 104
85 4 105 107 108 105 99 93 86 80 113
020 40 2 97 99 100 97 91 85 78 72 105
90 4 107 109 110 107 101 95 88 82 115
42 98 100 101 98 92 86 79 73 106
95 4 108 111 111 108 102 96 89 83 116
45 99 101 102 99 93 87 80 74 107
063 80 6 96 99 97 92 89 82 74 68 103
47 99 102 102 99 93 87 80 74 107
85 6 98 101 99 94 90 83 76 70 105
50 100 103 103 100 94 88 81 75 108
90 6 99 102 100 95 92 85 77 71 106
53 101 104 104 101 95 89 82 76 109
95 6 101 104 102 97 94 87 79 73 108
56 102 105 105 102 96 90 83 77 110
99 6 103 106 104 99 95 88 81 75 110
31 2 92 94 95 92 86 80 73 67 100
33 2 95 95 95 94 88 81 74 66 101
35 2 96 96 96 95 89 82 75 67 102
37 2 98 98 98 97 90 83 77 69 104
40 2 99 99 99 98 91 84 78 70 105
42 2 98 100 101 98 92 86 79 73 106
45 2 99 101 102 99 93 87 80 74 107
47 2 100 102 103 100 94 88 81 75 108
025 50 2 101 104 104 101 95 89 82 76 109
53 2 102 105 105 102 96 90 83 77 110
56 2 104 106 107 104 98 92 85 79 112
60 2 105 107 108 105 99 93 86 80 113
63 2 106 109 109 106 100 94 87 81 114
42 4 88 91 89 84 81 74 66 60 95
45 4 89 92 90 85 81 74 67 61 96
47 4 90 93 91 86 82 75 68 62 97
50 4 91 94 92 87 83 76 69 63 98 The above data are valid for the operating ranges shown in
53 4 92 95 93 88 84 77 70 64 99 the charts on pages 30-31.
HCBT - Dimensions and weights - Fan Page 35

C E

A
F

D outs. B

X
N
K
The sketches show a right-hand model

Inspection cover location.


30
o
When delivered, the inspection cover
CLOutlet

Y is placed in the upper part of the ca-


CL Inlet o
sing, 30 above the horizontal centre
line.

Y
G1

G
n holes Z

P2 P3
P1

H2 H3 H3

J1 J2 J2

O1 O2 O2

M1 M2 N3

N1 N2

dd = 11 (0o) = Right-hand model dd = 12 (45o) dd = 13 (90o)


dd = 61 (0o) = Left-hand model dd = 62 (45o) dd = 63 (90o)

P4
P7 P8

H3 H4 H4

J2
J3 J3
O2
O3 O3
M3
N3 M3
N4
N4

dd = 14 (135o) dd = 17 (270o) dd = 18 (315o)


dd = 64 (135o) dd = 67 (270o) dd = 68 (315o)
HCBT - Dimensions Page 36

Dimensions HCBT
Fan Imp. dia.
E F H2 H3 H4 M1 M2 M3 N1 N2 N3 N4 P1 P2 P3 P4 P7 P8
size bb
25 206 176 310 280 330 261 228 330 445 404 417 520 516 610 541 507 514 506
010 26-31 246 234 360 325 390 319 285 400 549 504 510 637 606 725 644 609 619 610
33-40 297 308 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
28 225 191 330 300 355 289 255 363 494 452 461 576 555 663 589 554 560 552
012 30-35 270 257 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
37-45 327 340 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
31 246 204 360 325 390 319 285 400 549 504 510 637 606 725 644 609 619 610
016 33-40 297 278 425 380 460 393 357 488 680 632 628 786 722 868 773 736 747 735
42-50 361 371 510 455 555 486 447 599 845 791 775 972 871 1054 941 901 914 899
25 206 126 310 280 330 261 228 330 445 404 417 520 516 610 541 507 514 506
30-35 270 220 390 350 425 355 319 442 611 565 566 708 660 792 705 668 682 671
020
37-45 327 302 465 415 550 437 400 541 759 708 698 874 792 956 852 814 871 858
47-56 398 406 560 500 610 541 500 664 943 885 862 1082 958 1164 1041 999 1012 995
31 246 159 360 325 390 324 285 403 554 504 510 641 606 728 649 609 619 610
33-40 297 233 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
025
42-50 361 326 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
53-63 441 443 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
40 297 201 425 380 460 398 357 491 685 632 628 789 722 871 778 736 747 735
031 42-50 361 293 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
60-63 489 480 675 600 740 677 629 825 1182 1112 1071 1357 1164 1425 1277 1228 1245 1223
50 361 251 510 455 555 491 447 602 850 791 775 975 871 1057 946 901 914 899
040 53-63 441 368 615 545 675 608 561 742 1058 992 961 1210 1056 1287 1153 1105 1125 1106
67-80 542 515 750 660 820 755 704 917 1319 1245 1194 1512 1292 1577 1415 1363 1385 1361
63 441 318 615 545 675 628 561 756 1078 992 961 1224 1056 1301 1173 1105 1125 1106
050 67-80 542 465 750 660 820 775 704 931 1339 1245 1194 1519 1292 1591 1435 1363 1385 1361
85-99 670 650 920 805 1005 960 884 1153 1669 1563 1489 1892 1590 1958 1765 1688 1714 1684
80 552 400 750 660 820 775 704 938 1339 1245 1204 1526 1302 1598 1435 1363 1385 1361
063
85-99 680 585 920 805 1005 960 884 1160 1669 1563 1499 1899 1600 1965 1765 1688 1714 1684

Dimensions L
Motor-
Fan size
size
010 012 016 020 025 031 040 050 063
63 338 - - - - - - - -
71 364 384 - - - - - - -
80 387 407 433 467 - -
90S - 420 446 480 521 - - - -
90L - 445 471 505 546 596 - - -
100L - 473 499 533 574 624 689 - -
112M - - 502 536 577 - 692 - -
132S - - 568 602 643 693 758 - -
132M - - - - - - 758 844 -
160 - - - 727 769 819 884 970 1070
180 - - - - 846 - - 1047 1147
200L - - - - 939 989 - 1140 1240
225M - - - - - - - 1202 1302
250M - - - - - - - 1209 1309
HCBT - Dimensions and weights Page 37

Dimensions and weights, HCBT with 2-pole motorer


Fan Imp. Weight, kg
A B C D O1 O2 O3 J1 J2 J3 N K G G1 P X Y Z n
size dia. incl. motor
25 100 80 105 104 410 380 420 180 165 185 199 262 174 - 136 28 34 88 9 2
26 100 80 105 104 460 430 480 205 190 215 199 262 176 - 138 34 34 88 9 2
010 28-31 100 80 105 104 460 430 480 205 190 215 214 277 210 - 172 37 34 88 9 2
33 100 80 106 104 520 480 550 235 215 250 214 278 174 - 136 51 33 88 9 2
35-40 100 80 106 104 520 480 550 235 215 250 234 298 190 - 152 56 33 88 9 2
28 125 100 115 129 430 410 450 190 180 200 224 297 220 - 172 34 33 88 9 2
30 125 100 115 129 480 450 510 215 200 230 224 297 214 - 166 43 34 88 9 2
012 31-35 125 100 115 129 480 450 510 215 200 230 244 317 238 - 190 46 34 88 9 2
37-42 125 100 116 129 570 520 610 260 235 280 275 349 245 - 197 71 33 88 9 2
45 125 100 116 129 570 520 610 260 235 280 302 376 288 - 240 85 33 88 9 2
31 160 125 128 164 460 430 480 205 190 215 256 343 268 - 208 45 33 88 9 2
33-35 160 125 128 164 520 480 550 235 215 250 288 375 278 - 216 65 33 88 9 2
37-40 160 125 128 164 520 480 550 235 215 250 288 375 278 - 216 70 33 88 9 2
016 2
42 160 125 128 164 610 560 650 280 255 300 314 401 310 - 249 99 34 88 9
45 160 125 128 164 610 560 650 280 255 300 322 409 314 - 253 103 34 88 9 2
47-50 160 125 128 164 610 560 650 280 255 300 378 465 376 - 315 120 33 88 9 2
25 200 160 145 205 410 380 420 180 165 185 274 377 316 - 237 41 34 88 9 2
30-31 200 160 145 205 480 450 510 215 200 230 304 407 335 - 256 58 34 88 9 2
33-35 200 160 145 205 480 450 510 215 200 230 304 407 335 - 256 61 34 88 9 2
37 200 160 146 205 570 520 610 260 235 280 332 436 368 - 289 90 33 88 9 2
020 2
40 200 160 146 205 570 520 610 260 235 280 339 443 372 - 293 95 33 88 9
42-45 200 160 146 205 570 520 610 260 235 280 396 506 438 - 359 112 33 88 9 2
47-50 200 160 146 205 670 610 710 310 280 330 396 500 394 - 315 136 34 88 9 2
53-56 200 160 146 205 670 610 710 310 280 330 491 595 494 - 447 201 33 110 11 2
31 250 200 165 255 460 430 480 205 190 215 325 449 394 - 296 60 34 88 9 2
33 250 200 166 255 520 480 550 235 215 250 352 476 420 - 321 85 33 88 9 2
35 250 200 166 255 520 480 550 235 215 250 359 483 428 - 330 89 33 88 9 2
37-40 250 200 166 255 520 480 550 235 215 250 416 540 472 - 387 105 33 88 9 2
025 42 250 200 166 255 610 560 650 280 255 300 416 540 482 - 387 126 32 88 9 2
45-50 250 200 166 255 610 560 650 280 255 300 512 636 530 - 467 171 34 110 11 2
53-56 250 200 166 255 710 650 770 330 300 360 512 636 518 - 467 231 32 110 11 2
60 250 200 166 255 820 750 870 385 350 410 551 675 534 - 505 279 34 110 11 2
63 250 200 166 255 820 750 870 385 350 410 589 714 658 146 543 336 33 110 11 2
40 315 250 191 320 520 480 550 235 215 250 428 565 480 - 399 110 34 88 9 2
42-45 315 250 191 320 610 560 650 280 255 300 536 685 536 - 492 179 34 110 11 2
031 2
47-50 315 250 191 320 610 560 650 280 255 300 536 685 536 - 492 199 33 110 11
60-63 315 250 192 320 840 790 890 390 365 415 614 764 552 - 568 385 33 110 11 2

Dimensions and weights, HCBT with 4-pole motorer


Fan Imp. Weight, kg
A B C D O1 O2 O3 J1 J2 J3 N K G G1 P X Y Z n
size dia. incl. motor
42-45 250 200 166 255 610 560 650 280 255 300 325 449 356 - 257 100 35 110 11 2
025 47-50 250 200 166 255 610 560 650 280 255 300 325 449 356 - 257 103 34 110 11 2
53 250 200 166 255 710 650 770 330 300 360 352 476 356 - 257 147 34 110 11 2
45 315 250 191 320 610 560 650 280 255 300 350 499 426 - 328 101 33 110 11 2
031
47-50 315 250 191 320 610 560 650 280 255 300 377 526 452 - 328 120 33 110 11 2
50 400 315 223 405 610 560 650 280 255 300 410 592 524 - 368 127 33 110 11 2
53-56 400 315 223 405 710 650 770 330 300 360 416 599 492 - 336 173 33 110 11 2
60 400 315 223 405 710 650 770 330 300 360 474 657 556 - 400 191 34 110 11 2
040
63 400 315 223 405 710 650 770 330 300 360 474 658 556 - 400 200 33 110 11 2
67-71 400 315 224 405 930 840 1000 435 390 470 569 753 696 - 539 313 40 124 15 2
75-80 400 315 224 405 930 840 1000 435 390 470 569 753 696 - 539 343 40 124 15 2
63 500 400 267 505 710 650 770 330 300 360 612 837 752 - 582 256 40 124 15 2
67 500 400 267 505 930 840 1000 435 390 470 612 837 752 298 567 352 38 124 15 2
71 500 400 267 505 930 840 1000 435 390 470 651 876 774 - 620 388 37 124 15 2
75-80 500 400 267 505 930 840 1000 435 390 470 651 876 750 - 620 418 36 124 15 2
050 2
85 500 400 267 505 1100 1000 1180 520 470 560 689 914 798 - 658 570 40 124 15
90 500 400 267 505 1100 1000 1180 520 470 560 711 936 774 - 680 622 40 124 15 2
95 500 400 267 505 1100 1000 1180 520 470 560 711 936 774 - 680 631 40 124 15 2
99 500 400 267 505 1150 1050 1220 545 495 580 770 995 822 - 737 713 39 124 15 2
80 630 500 317 635 930 840 1000 435 390 470 739 1014 958 275 708 396 37 124 15 2
85 630 500 317 635 1100 1000 1180 520 470 560 761 1036 980 275 730 651 37 124 15 2
063 2
90 630 500 317 635 1100 1000 1180 520 470 560 761 1036 980 275 730 692 37 124 15
95 630 500 317 635 1150 1050 1220 545 495 580 820 1095 1037 289 787 743 33 144 14 2

Dimensions and weights, HCBT with 6-pole motorer


Fan Imp. Weight, kg
A B C D O1 O2 O3 J1 J2 J3 N K G G1 P X Y Z n
size dia. incl. motor
71 500 400 267 505 930 840 1000 435 390 470 517 742 657 315 472 301 35 110 11 2
050 75 500 400 267 505 930 840 1000 435 390 470 517 742 657 315 472 313 35 110 11 2
80 500 400 267 505 930 840 1000 435 390 470 612 837 752 298 567 345 34 110 11 2
80 630 500 317 635 930 840 1000 435 390 470 662 937 824 - 632 396 35 110 11 2
063 85 630 500 317 635 1100 1000 1180 520 470 560 662 937 772 - 607 499 37 120 15 4
90 630 500 317 635 1100 1000 1180 520 470 560 700 975 826 - 655 548 37 120 15 4
95-99 630 500 317 635 1100 1000 1180 520 470 560 739 1014 928 254 694 608 35 110 11 2
HCBT - Heat shield, Cleanout cover Page 38

Heat shield HCEZ-07-b-cc


Shields the motor from radiated heat.
Casing side
Table - Heat shield selection
cc = cc in the fan code, (IEC motor size)
Heat shield
Size No. of motor poles Variant
Single-speed Two-speed
cc = 01-09 Alla Alla b=1
cc = 10-14 2-8 Alla b=1
cc = 15 4-8 4/8 b=1
cc = 16 2 2/4 b=1
cc = 16 4-8 4/6, 4/8 b=2 Impeller
cc = 17 2 - b=1
cc = 17 4-8 4/6, 4/8 b=2
cc = 18 2 - b=1 Motor
cc = 19 2 - b=1
cc = 20 2 - b=1
cc = 21 2 - b=1
Shaft packing

Cleanout cover HCEZ-09-bb-c-ddd Table - Cleanout cover selection


Robust, designed for frequent inspections.
Double sheet construction and handle. Fan size Impeller dia. bb
25 01
010 26-31 02
33-40 03
28 04
012 30-35 05
37-45 06
33-40 07
016
42-50 08
25 09
30-35 10
020
37-45 11
47-56 12
31 13
33-40 14
025
42-50 15
53-63 16
40 17
031 42-50 18
60-71 19
50 20
040 53-63 21
67-80 22
63 23
050 67-80 24
85-99 25
63-80 26
063 82-99 27
HCBT - Dimensions and weights - Accessories Page 39

NB! Flanges comply to ISO 13351.


HCEZ-30 HCEZ-35 HCEZ-50, 51 HCEZ-70
B g n holes G n holes G
n holes G n holes G
g

E1

A n1 x E C A1 x B1

Sheet steel
insert

E1

F1 n2 x F F1 t t
t + 2,5 t
+ 10 + 10
130 - 20 130 - 20
D

HCEZ- HCEZ- HCEZ- HCEZ-


30 35 50/51 70
Fan Weight Weight Weight Weight
Size A A1 B B1 C D E E1 F F1 G t g n n1 n2 kg kg kg kg
010 100 85 80 65 170 150 71 33.5 --- --- 10 5 19 8 1 1 0.6 0.5 1.1 1.5
012 125 110 100 85 195 170 71 46 71 33.5 10 5 19 12 1 1 0.8 0.7 1.5 2.3
016 160 145 125 110 230 195 100 49 71 46 10 5 19 12 1 1 0.9 0.8 1.7 2.3
020 200 185 160 145 270 230 100 69 100 49 10 5 19 12 1 1 1.1 1.0 2.1 3.1
025 250 235 200 185 330 280 125 81.5 125 56.5 10 6 19 12 1 1 2.1 1.9 3.9 5.3
031 315 295 250 230 395 330 125 51.5 125 81.5 10 6 19 14 2 1 2.8 2.4 5.0 6.6
040 400 380 315 295 480 395 125 94 125 51.5 10 6 19 16 2 2 3.5 2.9 6.0 8.0
050 500 480 400 380 620 520 125 94.5 125 107 12 8 32 18 3 2 8.5 7.6 15.5 18.3
063 630 600 500 480 750 620 125 97 125 94.5 12 8 32 22 4 3 10.5 9.2 18.8 22.6

HCEZ-20 HCEZ-21 HCEZ-25/27 HCEZ-40/41 HCEZ-60


Weight 0.1 - 1.1 kg with sheet steel insert
HCEZ-29 HCEZ-45/46 HCEZ-65
t1 145 with sheet steel insert
125
60
h


F
E
D1 D5 D3 D D1 D3 D1 D2 D3
D4 D outs. D2
ins. ins. ins. ins. ins. ins.

+10 +10 +10 +10


t 40 - 20 130 - 20 40 - 20 130 - 20
nxG 45
L K

HCEZ- HCEZ- HCEZ- HCEZ- HCEZ-


20/21 25/27/29 45/46 60 65
Fan Weight Weight Weight Weight Weight
Size D E F G t t1 D1 D2 D3 D4 D5 K L h n kg kg kg kg kg
010 105 139 170 9.5 5 -- 106 85 --- --- 230 --- 65 32.5 4 0.7 0.5 --- 0.6 ---
012 130 165 195 9.5 5 -- 131 110 --- --- 255 --- 65 32.5 4 0.9 0.6 --- 0.8 ---
016 165 200 240 12 5 -- 166 145 --- --- 295 --- 70 37.5 4 1.1 0.7 --- 1.0 ---
020 205 241 280 12 5 -- 207 185 --- --- 335 --- 70 37.5 8 1.2 1.0 --- 1.1 ---
025 255 292 330 12 6 -- 257 235 --- --- 400 --- 75 37.5 8 1.7 1.7 --- 1.4 ---
031 320 366 405 12 6 -- 322 290 --- --- 470 --- 80 42.5 8 2.2 2.1 --- 1.7 ---
040 405 448 490 12 6 2 407 375 400 528 528 192 192 42.5 12 5.9 3.4 8.4 2.2 8.8
050 505 551 600 12 8 2 507 475 500 628 628 192 192 47.5 12 6.8 4.8 11.3 2.8 12.2
063 635 698 750 14 8 2.5 637 595 630 809 809 218 218 57.5 16 11.8 5.9 14.5 3.5 15.2
Belt-driven fans with impeller diameter 1000 mm
Page 40
Ordering Key - Belt-driven fans with impeller diameter 1000 mm Page 41

HCGB
HCL x
HCMx
HCH x -aaa-bb-cc-dd-ee-fff
Impeller
B = Backward-curved blades (Type B impellers are not available for the HCL fan).
P = Flat, backward-inclined blades.
T = Straight, radial blades.

Size (aaa), see page 58 and fan charts

Components included in delivery (bb)


02 = Fan without motor, anti-vibration mountings and belt drive.
03 = Fan with motor, anti-vibration mountings and belt drive, (all fitted).
NB! Motor and belt drive should be specified separately.

IEC motor size (cc)


03 = 80 10 = 160M 17 = 250M
04 = 90S 11 = 160L 18 = 280S
05 = 90L 12 = 180M 19 = 280M
For the various fans, motor size can be
06 = 100L 13 = 180L 20 = 315S
found from the tables on pages 48 - 49.
07 = 112M 14 = 200L 21 = 315M
08 = 132S 15 = 225S
09 = 132M 16 = 225M

Designations for rotation and discharge (dd)

11 0o 12 45o 13 90o 14 135o 17 270o 18 315o


Right
(RD) W W Z Z W W

61 0o 62 45o 63 90o 64 135o 67 270o 68 315o


Left
(LG) Z Z W W Z Z

NB! The above diagrams show the drive side

Fan version (ee)


01 = standard version.
02 = sparkproof version, (brass ring at the inlet and brass washers at the shaft inlet).

Material, finish 1) (fff)


001 = Standard material, GA80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Not fully welded Max. temperature 150oC. 2)
032 = Standard material, GA80TD80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Not fully welded
300 = Except for shaft, contact guard and motor actuator,
parts in gas contact, (stand included), in SS 2333. Not fully welded
400 = Except for shaft, contact guard and motor actuator,
parts in gas contact in acid-proof SS 2343,
stand in SS 2333. Not fully welded
1)
Removable contact guards around rotating parts are epoxy painted in a yellow, warning colour, (80 ).

2)
GP40-01 primer can be used where temperatures exceed 120C. This primer tolerates temperatures up to 150C and vaporises at higher
temperatures without emitting any toxic substances.
Ordering key - Accessories Page 42

Belt drive HCEZ-01-bbb-c-dd


Size: Refer to the "Belt drive selection" tables on pages 55 - 57
Form of delivery:
1 = fitted to the fan.
2 = not fitted
Fan size: Refer to the tables on pages 55 - 57
NB! The "Belt drive selection" tables cover rated motor powers up to 30 kW. Belt drives with higher rated motors must
be selected from the data selection program - see HC data selection program or contact Flkt Woods AB.

Cooling disc HCEZ-06-bb


Size: Refer to the "Cooling disc selection" table on page 53

Cleanout cover HCEZ-09-bb-c-ddd


Cover size: Refer to table on page 53
Location
With discharge directions 11 and 61 c=1
For other discharge directions c=2
Material and finish: Refer to the fff code in the main fan ordering key

Speed monitor HCEZ-13-bb


Size: Refer to the "Speed monitor selection" table on page 53

Inlet taper piece without connecting flange 1) HCEZ-20-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key
1)
For direct connection to fans without inlet flange.

Inlet taper piece with connecting flange 2) HCEZ-21-bbb-ccc


Size (= 040 - 100)
Material and finish: Refer to the fff code in the main fan ordering key
2)
For connection to fans with inlet flange or to inlet vane assemblies or regulating dampers.
NB! When connecting to size 031 inlet vane assemblies, size 040 inlet connecting flange must be used.

Counterflange, inlet, (not fitted) HCEZ-25-bbb-cc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Inlet flange, (fitted) HCEZ-27-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Inlet connecting flange HCEZ-29-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Fabric duct, inlet, without connecting flanges 3) HCEZ-aa-bbb


Temp. class
40 = max 70C.
41 = max 200C.
42 = max 350C
Size (= fan size)
3)
For connection to fans without inlet flange.
Page 43
Ordering key - Accessories, cont.

Fabric duct, inlet, with connecting flanges 4) HCEZ-aa-bbb-ccc


Temp. class
45 = max 70C.
46 = max 200C.
47 = max 350C.
Size (= 040 - 100)
For material and finish (flanges), refer to the fff code in the main fan ordering key
4)
For connection to fans with inlet flange.

Flue gas duct, inlet, without connecting flanges 5) HCEZ-aa-bbb-cc


Temp. class
60 = max 200C.
61 = max 350C.
Size (= fan size)
Material (wearing plate)
01 = Steal, primed.
03 = SS 2333.
04 = SS 2343.
5)
For connection to fans without inlet flange

Flue gas duct, inlet, with connecting flanges 6) HCEZ-aa-bbb-ccc


Temp. class
65 = max 200C.
66 = max 350C.
Size (= 040 - 100)
For material and finish, (flanges), refer to the fff code in the main fan ordering key
6)
For connection to fans with inlet flange.
NB! Wearing plate is only available in steel, primed or stainless steel qualities depending on choice of ccc code.

Protective screen, outlet HCEZ-30-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Counterflange, outlet, (not fitted) HCEZ-35-bbb-cc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Fabric duct, outlet, with connecting flanges HCEZ-aa-bbb-ccc


Temp. class
50 = max 70C.
51 = max 200C.
52 = max 350C..
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key

Flue gas duct, outlet, with connecting flanges 7) HCEZ-aa-bbb-ccc


Temp. class
70 = max 200C.
71 = max 350C..
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key
7)
NB! Wearing plate is only available in steel, primed or stainless steel qualities depending on choice of ccc code.

Regulating damper DMEG (see page 105)

Inlet vane control assembly HXEG (see pages 106 - 111)


Description - Accessories, inlet and outlet Page 44

2, 3
Duct

15
4 5
13, 14

4
6, 7
12 5
4
6, 7
8, 9
10

4
6, 7
11
2, 3

2, 3
11
6, 7
10
NB! Flanges comply with ISO 13351

Inlet
1 HCEZ-20 Inlet taper piece with protective screen and fixing lugs for connection to inlet without connecting
flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HCEZ-40, 41 Fabric duct, inlet without connecting flange. 2)
3 HCEZ-60 Flue gas duct, inlet without connecting flanges. 2)
4 HCEZ-27 Inlet flange, (fitted).
5 HCEZ-21 Inlet taper piece with protective screen and connecting flange for installation to inlet with
connecting flange. (Pressure loss across the accessory, 0.35 x dyn. press. pd).
6 HXEG Inlet vane control assembly, see pages 106 - 111. 1)
7 DMEG Regulating damper, see page 105. 1)
8 HCEZ-45, 46 Fabric duct, inlet with connecting flanges. 2)
9 HCEZ-65 Flue gas duct, inlet with connecting flanges. 2)
10 HCEZ-25 Counterflange, inlet, (not fitted).
11 HCEZ-29 Inlet connecting flange, for fitting ducts without connecting flanges.

Outlet
12 HCEZ-30 Protective screen, outlet.
13 HCEZ-50, 51 Fibre duct, outlet, with connecting flanges. 2)
14 HCEZ-70 Flue gas duct, outlet with connecting flanges. 2)
15 HCEZ-35 Counterflange, outlet, (not fitted).
1)
NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that the anti-vibration mountings can
cope with the increased component load on the fan.
2)
For size and temperature limits, please refer to the appropriate ordering keys.
Sound data Page 45

Symbols Formulae:
Lwtot = total sound power level for the relevant sound Lwtot = Lwtot + K1 + K2 + K3
path and appropriate throttling curve...................... dB o
Lwtot = total sound power level to inlet or outlet duct when For division into octave bands, use the formula:
o
the fan is operating on the throttling curve giving Lw = Lwtot + Kok
the lowest sound power level.................................. dB
Lw = Lwtot divided into octave bands .............dB (ref. 10-12 W) Sound paths: a = to inlet or outlet duct.
b = to surroundings (free-inlet fan).
K1 = corr. for diff. throttling curves and sound paths....... dB
c = to surroundings (duct-connected fan).
K2, K3 = correction for different sound paths........................ dB
Kok = approximate deviation from Lwtot NB! The stated values refer to sound power levels. Some fan manufac-
for the particular octave band................................. dB turers still quote sound pressure levels even though these vary with the
acoustic characteristics of the surroundings and distance from the fan.
L = throttling curve = 10 pd/Dpt Sound pressure levels, sometimes weighted as dB(A) or dB(C) values,
Dp
t = total pressure rise................................................... Pa are considerably lower than the corresponding sound power level Lwt.

HCGB - Total sound power level Lwtot


o
Approx. deviation Kok in L = 2-5 working range, correction K3 for
Gas flow, m3/h
2 5 10 20 50 100 200 300 x 103 sound paths a, b and c.
130
Sound Speed Kok, dB

a path range K3 Octave band, mid-frequency, Hz


120
0P
c

300 r/min dB 63 125 250 500 1000 2000 4000 8000


r i se
re 0
ssu 200
300-2300 0 -3 -6 -9 -12 -16 -23 -28 -33
Lwtoto, dB

110
a l pre a 2300-4700 0 -4 -9 -10 -6 -14 -18 -23 -23
Tot 0 800
c

100 4700-5700 0 -5 -10 -11 -10 -6 -13 -17 -20


c

00
600 4
c

100
c

300-2300 -3 -4 -5 -7 -11 -13 -21 -26 -33


200
c

b 2300-4700 -3 -3 -9 -10 -6 -12 -16 -21 -23


90 4700-5700 -2 -5 -11 -12 -11 -5 -12 -16 -21
0.5 1 2 4 10 20 40 60 100
Gas flow, m3/s
300-2300 -2 -5 -5 -7 -12 -14 -22 -29 -36
Correction K1 Correction K2 c 2300-4700 +1 -3 -8 -9 -10 -15 -21 -27 -29
4700-5700 -1 -6 -8 -12 -12 -5 -14 -19 -24
K2, dB
K1, dB

1.5 +5
c a Sound paths: a = to inlet or outlet duct.
1.0 , 0
a,b b = to surroundings (free-inlet fan).
0.5 -5 b
-10 c c = to surroundings (duct-connected fan).
0
2 3 4 5 0 1000 2000 3000
L Dpt, Pa

HC(M,H)B Type B impeller (for HCGB, see above)


Total sound power level Lwtot
o
Approx. deviation Kok in L = 2-5 working range, correction K3 for
Gas flow, m /h 3
sound paths a, b and c.
2 5 10 20 50 100 200 x 103
130
Sound Speed Kok, dB
P aI
120 12 000 path range K3 Octave band, mid-frequency, Hz
r ise r/min dB 63 125 250 500 1000 2000 4000 8000
s s ure
l pre 0 6000 300-1175 0 -4 -4 -8 -15 -17 -19 -22 -28
Tota
c

800
Lwtoto, dB

110 a 1175-2300 0 -6 -6 -5 -11 -13 -15 -18 -21


0
400 200
0
c
c
2300-4700 0 -8 -8 -7 -6 -9 -13 -12 -17
4700-6300 0 -10 -9 -8 -8 -6 -10 -12 -14
100 0 800
c

100
c

600 400 300-1175 -2 -6 -4 -7 -14 -14 -18 -21 -30


c
c

b 1175-2300 -2 -8 -6 -4 -11 -12 -14 -17 -22


90 2300-4700 -3 -7 -8 -8 -6 -8 -12 -14 -17
0.5 1 2 4 10 20 40 60
4700-6300 -2 -10 -10 -9 -8 -5 -9 -11 -15
Gas flow, m3/s

Correction K1 Correction K2 300-1175 -2 -7 -3 -6 -15 -15 -18 -23 -31


c 1175-2300 -1 -9 -6 -4 -11 -12 -15 -20 -25
2 5 2300-4700 -1 -9 -5 -8 -8 -8 -14 -17 -21
a
K1, dB

K2, dB

0 4700-6300 -1 -11 -7 -9 -10 -5 -11 -14 -18


c b
1 b, -5
a, c Sound paths: a = to inlet or outlet duct.
-10
b = to surroundings (free-inlet fan).
0 -15
2 3 4 5 4000 8000 12 000 c = to surroundings (duct-connected fan).
L Dpt, Pa
Sound data, cont. Page 46

HC(L,M,H)P - Type P impeller


Total sound power level Lwtot
o
Approx. deviation Kok in L = 2-5 working range, correction K3 for
Gas flow, m3/h sound paths a, b and c.
2 5 10 20 50 100 200 x 103
130 Sound Speed Kok, dB
P aI
000 path range K3 Octave band, mid-frequency, Hz
12
120 ri se
000
r/min dB 63 125 250 500 1000 2000 4000 8000
ure
c

ss 0 6
pre 800
c

al 300-1175 0 -10 -3 -7 -10 -13 -18 -21 -26


Tot 0 0
Lwtoto, dB

400 200 a 1175-2300 0 -10 -7 -4 -8 -10 -15 -18 -23


c c

110
2300-4700 0 -9 -8 -7 -5 -9 -13 -16 -21
800
c

0 4700-6500 0 -10 -9 -8 -8 -6 -10 -12 -15


100
c

400
c

100 600
c

300-1175 -3 -9 -4 -8 -9 -9 -14 -18 -23


b 1175-2300 -2 -10 -8 -6 -8 -7 -12 -15 -21
90 2300-4700 -2 -7 -6 -10 -8 -9 -10 -13 -19
0.5 1 2 4 10 20 40 60 4700-6500 -1 -9 -8 -12 -9 -7 -8 -10 -14
Gas flow, m3/s
300-1175 -4 -10 -5 -7 -8 -8 -14 -17 -22
Correction K1 Correction K2 c 1175-2300 -3 -10 -9 -6 -7 -7 -12 -15 -20
2300-4700 -2 -9 -5 -12 -6 -10 -11 -14 -19
2 5 4700-6500 -2 -10 -7 -13 -9 -7 -8 -10 -13
a
K2, dB

0
K1, dB

, c
1 a ,b -5 b Sound paths: a = to inlet or outlet duct.
c b = to surroundings (free-inlet fan).
-10
0 -15 c = to surroundings (duct-connected fan).
2 3 4 5 4000 8000 12 000
L Dpt, Pa

HC(L,M,H)T - Type T impeller


Total sound power level Lwtot
o Approx. deviation Kok in L = 2-5 working range, correction K3 for
sound paths a, b and c.
Gas flow, m /h 3

2 5 10 20 50 70 x 103 Kok, dB
130 Sound Speed
Pa
000 path range K3 Octave band, mid-frequency, Hz
12
ise
120 re r 600
0 r/min dB 63 125 250 500 1000 2000 4000 8000
c

su
res 0
al p 800 300-1175 0 -7 -4 -6 -11 -14 -22 -29 -35
c

Tot 0 0
4 0 200 a 1175-2300 0 -8 -5 -5 -8 -14 -20 -27 -33
c

0
c
Lwtoto, dB

110 2300-4700 0 -6 -6 -6 -7 -14 -21 -27 -35


800
c

0 4700-5800 0 -8 -7 -7 -7 -8 -13 -19 -25


100
c

400
c

600
c

100 300-1175 -0 -10 -6 -4 -9 -12 -18 -25 -30


b 1175-2300 -0 -11 -9 -3 -7 -12 -17 -23 -28
2300-4700 +1 -6 -6 -6 -9 -13 -17 -22 -30
90 4700-5800 +1 -8 -8 -6 -9 -8 -10 -14 -20
0.5 1 2 4 10 20
Gas flow, m3/s
300-1175 -2 -10 -5 -4 -10 -11 -18 -22 -27
c 1175-2300 -1 -12 -7 -4 -7 -11 -17 -21 -26
Correction K2 2300-4700 +1 -7 -9 -5 -6 -14 -17 -22 -29
Correction K1 a 4700-5800 +2 -10 -10 -5 -7 -9 -11 -15 -20
0
2
-5 Sound paths: a = to inlet or outlet duct.
K1, dB

c
K2, dB

b,
a, -10 b b = to surroundings (free-inlet fan).
1
-15 c = to surroundings (duct-connected fan).
c
0 -20
2 3 4 5 0 4000 8000 12 000
L Dpt, Pa
Dimensions and weights - Fan Page 47

C
E

D3*
A

F2 F
F1 D outs. B

D2 h8

X
J2 J1
N

K R

The sketches show a right-hand model.

CL Inlet
* Minimum permitted pulley diameter
= D3 (refer to tables on pages 48 - 49).
CL Outlet

Maximum permitted pulley diameter G3 G


P
= 2 x IEC motor size. G2 G1

Example: IEC 80 will be max. pulley diameter 160.

J2 J1
Inspection cover location
When delivered, the inspection cover is
Y Y
placed in the upper part of the casing,
30o above the horizontal centre line.
n holes Z
N2

N1 M2
N3
M1

P2
P3
P1

H2 H3 H3

dd = 11 (0o) = Right-hand model dd = 12 (45o) dd = 13 (90o)


dd = 61 (0o) = Left-hand model dd = 62 (45o) dd = 63 (90o)

N4
N4
M3
N3 M3

P4
P7 P8
H3 H4
H4

dd = 14 (135o) dd = 17 (270o) dd = 18 (315o)


dd = 64 (135o) dd = 67 (270o) dd = 68 (315o)
Dimensions Page 48

Impeller dia. Shaft journal dimensions


HCG HCL HCM HCH Impeller dia. HCG HCL HCM HCH D2 F1 F2
025 020 - - 250 025 020 - - 35 38 10
031 025 016 - 315 031 025 016 - 35 38 10
- - 020 - 355 - - 020 - 35 38 10
040 031 025 010 398 040 031 025 010 35 38 10
- - - 012 450 - - - 012 35 38 10
050 040 031 016 500 050 040 031 016 35 38 10
- - - 020 560 - - - 020 35 38 10
063 050 040 025 631 063 050 040 025 40 43 12
031 708 031 55 59 16
080 063 050 040 794 080 063 050 040 55 59 16
100 080 063 050 1000 100 080 063 050 60 65 18

Dimensions
HCG HCL HCM HCH H2 H3 H4 M1 M2 M3 P1 P2 P3 P4 P7 P8
025 020 - - 310 280 330 261 228 330 516 610 541 507 514 506
031 025 016 - 360 325 390 319 285 400 606 725 644 609 619 610
- - 020 - 390 350 425 355 319 442 660 792 705 668 682 671
040 031 025 010 425 380 460 393 357 488 722 868 773 736 747 735
- - - 012 465 415 550 437 400 541 792 956 852 814 871 858
050 040 031 016 510 455 555 486 447 599 871 1054 941 901 914 899
- - - 020 560 500 610 541 500 664 958 1164 1041 999 1012 995
063 050 040 025 615 545 675 608 561 742 1056 1287 1153 1105 1125 1106
031 675 600 740 677 629 825 1164 1425 1277 1228 1245 1223
080 063 050 040 750 660 820 755 704 917 1292 1577 1415 1363 1385 1361
100 080 063 050 920 805 1005 960 884 1160 1600 1965 1765 1688 1714 1684

HCGB
Fan Motor size
A B C D D3min E F K N Wt. imp.
size IEC
025 80-112 250 200 165 255 85 206 101 465 338 3,1
031 80-132 315 250 191 320 100 246 127 515 363 5,0
040 80-112 400 315 223 405 132 297 158 582 397 7,8
040 132-160 400 315 223 405 132 297 158 672 487 7,8
050 90-160 500 400 267 505 140 371 201 727 499 13,5
063 100-160 630 500 317 635 224 451 253 903 624 23,0
063 180-200 630 500 317 635 224 451 253 988 709 23,0
080 112-200 800 630 382 805 212 552 318 1076 730 42,0
080 225 800 630 382 805 212 552 318 1226 880 42,0
100 132-225 1000 800 467 1005 265 680 400 1265 835 71,0

HCL(P,T)
Fan Motor size D3min D3min Wt. imp. Wt. imp.
A B C D E F K N
size IEC HCLP HCLT HCLP HCLT
020 80-132 200 160 145 205 80 95 206 126 425 318 3.6 4.0
025 80-160 250 200 165 255 90 125 246 159 465 338 4.8 5.1
031 80-112 315 250 191 320 100 150 297 201 517 364 7.9 7.7
031 132-180 315 250 191 320 100 150 297 201 607 454 7.9 7.7
040 100-160 400 315 223 405 150 180 361 251 642 457 14.8 14.0
040 180-225 400 315 223 405 150 180 361 251 757 572 14.8 14.0
050 100-160 500 400 267 505 180 250 441 318 803 574 28.0 25.0
050 180-225 500 400 267 505 180 250 441 318 888 659 28.0 25.0
063 132-200 630 500 317 635 180 315 552 400 946 665 42.0 46.0
063 225-280 630 500 317 635 180 315 552 400 1096 815 42.0 46.0
080 160-225 800 630 382 805 280 400 680 500 1095 750 70.0 71.0
080 250-315 800 630 382 805 280 400 680 500 1246 900 70.0 71.0
Dimensions and weights Page 49

HCM(B,P,T)
Fan Motor size D3min D3min D3min Weight, impeller
A B C D E F K N
size IEC HCMB HCMP HCMT HCMB HCMP HCMT
016 80-132 160 125 128 164 - 90 95 246 204 390 301 - 4.9 3.9
020 80-112 200 160 145 205 - 100 106 270 220 425 318 - 6.5 6.5
020 132-160 200 160 145 205 - 100 106 270 220 516 408 - 6.5 6.5
025 80-112 250 200 165 255 - 112 125 297 233 467 339 - 8.5 7.5
025 132-200 250 200 165 255 - 112 125 297 233 557 429 - 8.5 7.5
031 100-160 315 250 191 320 118 150 180 361 293 577 424 16.7 14.5 14.6
031 180-225 315 250 191 320 118 150 180 361 293 692 539 16.7 14.5 14.6
040 100-160 400 315 223 405 160 190 250 441 368 718 532 30.0 25.0 24.0
040 180-225 400 315 223 405 160 190 250 441 368 803 617 30.0 25.0 24.0
050 132-200 500 400 267 505 160 200 280 542 465 846 615 43.0 43.0 47.0
050 225-280 500 400 267 505 160 200 280 542 465 996 765 43.0 43.0 47.0
063 132-225 630 500 317 635 212 250 400 680 585 965 685 72.0 73.0 74.0
063 250-315 630 500 317 635 212 250 400 680 585 1116 835 72.0 73.0 74.0

HCH(B,P,T)
Fan Motor size D3min D3min D3min Weight, impeller
A B C D E F K N
size IEC HCHB HCHP HCHT HCHB HCHP HCHT
010 80-112 100 80 105 104 75 - 95 297 308 347 279 7.6 - 5.9
010 132-160 100 80 105 104 75 - 95 297 308 437 369 7.6 - 5.9
012 80-112 125 100 115 129 80 - 106 327 340 367 289 9.4 - 7.6
012 132-180 125 100 115 129 80 - 106 327 340 458 379 9.4 - 7.6
016 100-160 160 125 128 164 90 - 125 361 371 452 362 14.2 - 11.7
016 180-225 160 125 128 164 90 - 125 361 371 567 477 14.2 - 11.7
020 100-160 200 160 145 205 125 - 140 398 406 487 379 18.1 - 14.7
020 180-250 200 160 145 205 125 - 140 398 406 603 494 18.1 - 14.7
025 100-160 250 200 165 255 140 170 180 441 443 603 474 25.0 23.0 21.0
025 180-250 250 200 165 255 140 170 180 441 443 688 559 25.0 23.0 21.0
031 132-200 315 250 191 320 140 170 180 489 480 695 540 32.0 34.0 29.0
031 225-280 315 250 191 320 140 170 180 489 480 845 690 32.0 34.0 29.0
040 160-200 400 315 223 405 160 212 224 542 515 761 573 41.0 41.0 36.0
040 225-315 400 315 223 405 160 212 224 542 515 911 723 41.0 41.0 36.0
050 160-225 500 400 267 505 224 280 280 670 650 865 635 76.0 67.0 64.0
050 250-315 500 400 267 505 224 280 280 670 650 1016 785 76.0 67.0 64.0

Dimensions, location of anti vibration mountings - HCGB


HCG IEC M N1 N2 N3 N4 J1 R J2 G G1 G2 G3 P X Y Z n L Wt.1)
80 850 861 828 806 930 200 225 600 294 - - 294 309 33 88 9 2 578 67
90 875 887 854 832 956 200 225 625 288 - - 288 309 33 88 9 2 583 69
025
100 925 934 901 879 1003 200 225 675 282 - - 282 309 34 88 9 2 583 72
112 965 972 939 917 1041 200 225 715 278 - - 278 309 34 88 9 2 603 76
80 920 972 938 899 1053 215 240 655 393 120 - 342 334 33 88 9 2 629 81
90 945 999 965 926 1080 215 240 680 378 120 - 332 334 33 88 9 2 634 83
031 100 995 1048 1014 975 1129 215 240 730 324 - - 324 334 34 88 9 2 634 86
112 1035 1089 1055 1016 1170 215 240 770 318 - - 318 334 34 88 9 2 654 90
132 1135 1166 1132 1093 1247 215 240 870 322 - - 322 334 34 88 9 2 654 98
80 985 1114 1078 1018 1209 235 260 700 430 - - 430 368 33 88 9 2 695 109
90 1010 1143 1107 1047 1238 235 260 725 416 - - 416 368 34 88 9 2 700 111
100 1060 1193 1157 1097 1288 235 260 775 404 - - 404 368 34 88 9 2 700 115
040
112 1100 1234 1198 1138 1329 235 260 815 396 - - 396 368 34 88 9 2 720 119
132 1200 1309 1273 1213 1404 235 260 915 424 - - 424 443 33 110 11 2 810 147
160 1250 1360 1324 1264 1455 235 260 965 436 - - 436 443 37 110 11 2 840 157
90 1105 1314 1275 1199 1444 265 290 790 546 - - 546 455 33 110 11 2 861 156
100 1155 1366 1327 1251 1496 265 290 840 528 - - 528 455 33 110 11 2 861 161
050 112 1195 1410 1371 1295 1540 265 290 880 518 - - 518 455 33 110 11 2 866 165
132 1295 1488 1449 1373 1618 265 290 980 496 - - 496 455 33 110 11 2 866 182
160 1350 1547 1508 1432 1677 265 290 1035 476 - - 476 455 36 110 11 2 896 201
100 1270 1585 1538 1428 1719 295 320 925 814 233 - 698 580 34 110 11 2 1051 254
112 1310 1630 1583 1473 1764 295 320 965 814 218 - 688 580 34 110 11 2 1051 259
132 1410 1714 1667 1557 1848 295 320 1065 814 167 167 814 580 34 110 11 2 1051 268
063
160 1460 1774 1727 1617 1908 295 320 1115 628 - - 628 580 40 124 15 2 1071 283
180 1505 1825 1778 1668 1959 295 320 1160 706 - - 706 664 40 124 15 2 1156 300
200 1590 1904 1857 1747 2038 295 320 1245 700 - 161 889 664 40 124 15 2 1156 320
112 1500 1893 1842 1690 2055 370 400 1070 872 - - 872 685 57 120 15 4 1232 384
132 1600 1981 1930 1778 2143 370 400 1170 838 - - 838 685 57 120 15 4 1242 399
160 1655 2049 1998 1846 2211 370 400 1225 800 - - 800 685 56 120 15 4 1242 412
080
180 1700 2103 2052 1900 2265 370 400 1270 790 - - 790 685 56 120 15 4 1242 421
200 1785 2185 2134 1982 2347 370 400 1355 770 - - 770 685 54 120 15 4 1242 446
225 1835 2240 2189 2037 2402 370 400 1405 886 - - 886 835 53 120 15 4 1422 497
132 1790 2328 2252 2048 2528 435 465 1295 1016 - - 1016 790 54 120 15 4 1442 564
160 1845 2400 2324 2120 2600 435 465 1350 970 - - 970 790 54 120 15 4 1442 578
100 180 1890 2458 2382 2178 2658 435 465 1395 956 - - 956 790 53 120 15 4 1442 589
200 1980 2548 2472 2268 2748 435 465 1485 930 - - 930 790 52 120 15 4 1442 612
225 2030 2608 2532 2328 2808 435 465 1535 920 - - 920 790 51 120 15 4 1462 631
1)
Weights are exclusive of motor and belt drive.
Dimensions and weights Page 50

Dimensions, location of anti vibration mountings - HCL(P,T)


Motor Wt.1)
HCL M N1 N2 N3 N4 J1 R J2 G G1 G2 G3 P X Y Z n L Wt.1)
IEC Imp. T
80 850 861 828 806 930 200 225 600 268 - - 268 289 33 88 9 2 538 65 69
90 875 887 854 832 956 200 225 625 264 - - 264 289 33 88 9 2 543 67 71
020 100 925 934 901 879 1003 200 225 675 262 - - 262 289 34 88 9 2 543 70 74
112 965 972 939 917 1041 200 225 715 258 - - 258 289 34 88 9 2 563 74 78
132 965 1005 972 950 1074 200 225 715 274 - - 274 289 34 88 9 2 563 77 81
80 920 972 938 899 1053 215 240 655 345 120 - 310 310 33 88 9 2 578 78 85
90 945 999 965 926 1080 215 240 680 330 120 - 300 310 33 88 9 2 583 80 87
100 995 1048 1014 975 1129 215 240 730 296 - - 296 310 34 88 9 2 583 83 90
025
112 1035 1089 1055 1016 1170 215 240 770 290 - - 290 310 34 88 9 2 603 87 94
132 1135 1166 1132 1093 1247 215 240 870 300 - - 300 310 34 88 9 2 603 95 102
160 1135 1187 1153 1114 1268 215 240 870 356 - 126 408 310 33 88 9 2 633 101 108
80 985 1114 1078 1018 1209 235 260 700 456 120 - 384 335 33 88 9 2 630 103 113
90 1010 1143 1107 1047 1238 235 260 725 342 - - 342 320 34 110 11 2 635 105 115
100 1060 1193 1157 1097 1288 235 260 775 363 - - 363 335 33 88 9 2 635 108 118
031 112 1100 1234 1198 1138 1329 235 260 815 356 - - 356 335 33 88 9 2 655 113 123
132 1200 1309 1273 1213 1404 235 260 915 386 - - 386 410 33 110 11 2 745 140 150
160 1250 1360 1324 1264 1455 235 260 965 406 - - 406 410 34 110 11 2 775 150 160
180 1290 1399 1363 1303 1494 235 260 1005 432 - - 432 410 34 110 11 2 775 157 167
100 1155 1366 1327 1241 1479 265 290 840 492 - - 492 428 36 110 11 2 775 139 158
112 1195 1410 1371 1285 1523 265 290 880 484 - - 484 428 35 110 11 2 780 144 163
132 1295 1488 1449 1363 1601 265 290 980 466 - - 466 428 34 110 11 2 780 153 172
040 160 1350 1547 1508 1422 1660 265 290 1035 460 - - 460 428 37 110 11 2 810 179 198
180 1390 1590 1551 1465 1703 265 290 1075 562 - - 562 542 37 110 11 2 925 197 216
200 1475 1667 1628 1542 1780 265 290 1160 554 - - 554 527 34 110 11 2 925 215 234
225 1475 1688 1649 1563 1801 265 290 1160 582 - - 582 527 34 110 11 2 955 227 246
100 1270 1585 1538 1418 1733 295 320 925 744 237 - 654 545 34 110 11 2 951 212 245
112 1310 1630 1583 1463 1778 295 320 965 744 222 - 644 545 34 110 11 2 951 217 250
132 1410 1714 1667 1547 1862 295 320 1065 744 180 180 744 545 34 110 11 2 951 235 268
050 160 1460 1774 1727 1607 1922 295 320 1115 598 - - 598 545 40 124 11 2 971 240 273
180 1505 1825 1778 1658 1973 295 320 1160 678 - - 678 630 40 124 11 2 1056 257 290
200 1590 1904 1857 1737 2052 295 320 1245 680 - 191 829 630 40 124 11 2 1056 276 309
225 1635 1955 1908 1788 2103 295 320 1290 688 - 203 829 630 40 124 11 2 1086 293 326
132 1600 1981 1930 1778 2143 370 400 1170 744 - - 744 660 57 120 15 4 1112 357 396
160 1655 2049 1998 1846 2211 370 400 1225 715 - - 715 660 56 120 15 4 1112 369 408
180 1700 2103 2052 1900 2265 370 400 1270 708 - - 708 660 55 120 15 4 1112 379 418
063 200 1785 2185 2134 1982 2347 370 400 1355 702 - - 702 660 54 120 15 4 1112 400 439
225 1835 2240 2189 2037 2402 370 400 1405 816 - - 816 770 53 120 15 4 1292 470 509
250 1900 2308 2257 2105 2470 370 400 1470 800 - - 800 770 53 120 15 4 1292 488 527
280 1975 2385 2334 2182 2547 370 400 1545 830 - - 830 770 60 120 15 4 1292 508 547
160 1845 2400 2324 2120 2600 435 465 1350 842 - - 842 705 60 120 15 4 1272 542 602
180 1890 2458 2382 2178 2658 435 465 1395 834 - - 834 705 60 120 15 4 1272 552 612
200 1980 2548 2472 2268 2748 435 465 1485 818 - - 818 705 60 120 15 4 1272 575 635
080 225 2030 2608 2532 2328 2808 435 465 1535 812 - - 812 705 60 120 15 4 1292 594 654
250 2095 2680 2604 2400 2880 435 465 1600 916 - - 916 855 60 120 15 4 1442 675 735
280 2175 2773 2697 2493 2973 435 465 1680 1155 225 225 1155 855 60 120 15 4 1442 701 761
315 2175 2815 2739 2535 3015 435 465 1680 918 - - 918 855 60 120 15 4 1472 715 775
1)
Weights are exclusive of motor and belt drive.
Dimensions and weights Page 51

Dimensions, location of anti vibration mountings - HCM(B,P,T)


Motor Wt.1)
HCM M N1 N2 N3 N4 J1 R J2 G G1 G2 G3 P X Y Z n L Wt.1)
IEC Imp. T
80 920 972 938 899 1053 215 240 655 260 - - 260 272 34 88 9 2 504 71 75
90 945 999 965 926 1080 215 240 680 256 - - 256 272 34 88 9 2 509 74 78
016 100 995 1048 1014 975 1129 215 240 730 254 - - 254 272 34 88 9 2 509 77 81
112 1035 1089 1055 1016 1170 215 240 770 250 - - 250 272 34 88 9 2 529 81 85
132 1135 1166 1132 1093 1247 215 240 870 266 - - 266 272 34 88 9 2 529 88 92
80 950 1041 1005 956 1128 230 255 670 318 120 - 292 281 33 88 9 2 538 81 87
90 980 1073 1037 988 1160 230 255 700 306 120 - 284 281 33 88 9 2 543 83 89
100 1025 1119 1083 1034 1206 230 255 745 282 - - 282 281 34 88 9 2 543 86 92
020
112 1070 1163 1127 1078 1250 230 255 790 276 - - 276 281 34 88 9 2 563 90 96
132 1160 1229 1193 1144 1316 230 255 880 340 - - 340 379 34 88 9 2 653 114 120
160 1160 1251 1215 1166 1338 230 255 880 350 - - 350 364 33 110 11 2 683 122 128
80 985 1114 1078 1018 1209 235 260 700 402 120 - 348 310 33 88 9 2 579 99 106
90 1010 1143 1107 1047 1238 235 260 725 384 120 120 384 310 33 88 9 2 584 101 108
100 1060 1193 1157 1097 1288 235 260 775 330 - - 330 310 36 110 11 2 584 105 112
112 1100 1234 1198 1138 1329 235 260 815 324 - - 324 310 34 88 9 2 604 109 116
025
132 1200 1309 1273 1213 1404 235 260 915 358 - - 358 385 33 110 11 2 694 135 142
160 1250 1360 1324 1264 1455 235 260 965 384 - - 384 385 34 110 11 2 724 146 153
180 1290 1399 1363 1303 1494 235 260 1005 414 - - 414 385 34 110 11 2 724 153 160
200 1290 1430 1394 1334 1525 235 260 1005 462 - - 462 385 34 110 11 2 724 164 171
100 1155 1366 1327 1241 1479 265 290 840 462 - - 462 394 35 110 11 2 710 133 145
112 1195 1410 1371 1285 1523 265 290 880 444 - - 444 394 35 110 11 2 715 137 149
132 1295 1488 1449 1363 1601 265 290 980 400 - - 400 379 33 110 11 2 715 142 154
031 160 1350 1547 1508 1422 1660 265 290 1035 432 - - 432 394 37 110 11 2 745 171 183
180 1390 1590 1551 1465 1703 265 290 1075 534 - - 534 509 37 110 11 2 860 189 201
200 1475 1667 1628 1542 1780 265 290 1160 562 - - 562 509 36 110 11 2 860 206 218
225 1475 1688 1649 1563 1801 265 290 1160 562 - - 562 494 34 110 11 2 890 219 231
100 1270 1585 1538 1418 1719 295 320 925 659 226 - 590 502 34 110 11 2 865 216 238
112 1310 1630 1583 1463 1764 295 320 965 659 211 - 580 502 34 110 11 2 865 220 242
132 1410 1714 1667 1547 1848 295 320 1065 659 175 - 556 502 34 110 11 2 865 231 253
040 160 1460 1774 1727 1607 1908 295 320 1115 546 - - 546 502 36 110 11 2 885 243 265
180 1505 1825 1778 1658 1959 295 320 1160 628 - - 628 587 35 110 11 2 970 260 282
200 1590 1904 1857 1737 2038 295 320 1245 606 - - 606 572 34 110 11 2 970 278 300
225 1635 1955 1908 1788 2089 295 320 1290 622 - 219 714 572 34 110 11 2 1000 295 317
132 1600 1981 1930 1768 2157 370 400 1170 678 - - 678 570 57 120 15 4 1012 366 391
160 1655 2049 1998 1836 2225 370 400 1225 654 - - 654 570 56 120 15 4 1012 378 403
180 1700 2103 2052 1890 2279 370 400 1270 654 - - 654 570 55 120 15 4 1012 387 412
050 200 1785 2185 2134 1972 2361 370 400 1355 654 - - 654 570 54 120 15 4 1012 408 433
225 1835 2240 2189 2027 2416 370 400 1405 768 - - 768 720 53 120 15 4 1192 477 502
250 1900 2308 2257 2095 2484 370 400 1470 754 - - 754 720 53 120 15 4 1192 494 519
280 1975 2385 2334 2172 2561 370 400 1545 796 - - 796 720 60 120 15 4 1192 514 539
160 1845 2400 2324 2120 2600 435 465 1350 766 - - 766 640 54 120 15 4 1142 533 575
180 1890 2458 2382 2178 2658 435 465 1395 758 - - 758 640 54 120 15 4 1142 520 562
200 1980 2548 2472 2268 2748 435 465 1485 748 - - 748 640 53 120 15 4 1142 566 608
063 225 2030 2608 2532 2328 2808 435 465 1535 748 - - 748 640 53 120 15 4 1162 584 626
250 2095 2680 2604 2400 2880 435 465 1600 854 - - 854 790 50 120 15 4 1312 663 705
280 2175 2773 2697 2493 2973 435 465 1680 868 - - 868 790 59 120 15 4 1312 686 728
315 2175 2815 2739 2535 3015 435 465 1680 874 - - 874 790 59 120 15 4 1342 703 745

1)
Weights are exclusive of motor and belt drive.
Dimensions and weights Page 52

Dimensions, location of anti vibration mountings - HCH(B,P,T)


Motor Wt.1)
HCH M N1 N2 N3 N4 J1 R J2 G G1 G2 G3 P X Y Z n L Wt.1)
IEC Imp. T
80 985 1114 1078 1018 1209 235 260 700 282 120 - 268 250 33 88 9 2 459 87 90
90 1010 1143 1107 1047 1238 235 260 725 262 - - 262 250 34 88 9 2 464 89 92
100 1060 1193 1157 1097 1288 235 260 775 260 - - 260 250 34 88 9 2 464 92 95
010
112 1100 1234 1198 1138 1329 235 260 815 256 - - 256 250 34 88 9 2 484 97 100
132 1200 1309 1273 1213 1404 235 260 915 294 - - 294 340 33 110 11 2 574 122 125
160 1250 1360 1324 1264 1455 235 260 965 336 - - 336 325 32 110 11 2 604 132 135
80 1030 1195 1158 1085 1299 250 275 730 292 - - 292 260 34 88 9 2 479 95 99
90 1055 1224 1187 1114 1328 250 275 755 286 - - 286 260 34 88 9 2 484 97 101
100 1105 1275 1238 1165 1379 250 275 805 282 - - 282 260 34 88 9 2 484 101 105
012 112 1145 1317 1280 1207 1421 250 275 845 278 - - 278 260 34 88 9 2 504 105 109
132 1245 1394 1357 1284 1498 250 275 945 250 - - 250 335 33 110 11 2 594 128 132
160 1295 1447 1410 1337 1551 250 275 995 350 - - 350 335 34 110 11 2 624 143 147
180 1295 1467 1430 1357 1571 250 275 995 368 - - 368 335 34 110 11 2 624 147 151
100 1155 1366 1327 1241 1479 265 290 840 342 - - 342 318 34 110 11 2 585 129 135
112 1195 1410 1371 1285 1523 265 290 880 336 - - 336 318 33 110 11 2 590 133 139
132 1295 1488 1449 1363 1601 265 290 980 330 - - 330 318 33 110 11 2 590 142 148
016 160 1350 1547 1508 1422 1660 265 290 1035 346 - 155 364 318 34 110 11 2 620 166 172
180 1390 1590 1551 1465 1703 265 290 1075 450 - - 450 434 34 110 11 2 735 183 189
200 1475 1667 1628 1542 1780 265 290 1160 479 - - 479 425 34 110 11 2 735 201 207
225 1475 1688 1649 1563 1801 265 290 1160 479 - - 479 387 34 110 11 2 765 213 219
100 1205 1464 1423 1321 1587 280 305 875 378 - - 378 335 33 110 11 2 619 150 159
112 1250 1513 1472 1370 1636 280 305 920 372 - - 372 335 33 110 11 2 624 154 163
132 1350 1594 1553 1451 1717 280 305 1020 346 - - 346 335 32 110 11 2 624 178 187
160 1405 1656 1615 1513 1779 280 305 1075 368 - - 368 335 34 110 11 2 654 189 198
020
180 1445 1699 1658 1556 1822 280 305 1115 476 - - 476 450 34 110 11 2 769 207 216
200 1525 1772 1731 1629 1895 280 305 1195 506 - - 506 450 34 110 11 2 769 228 237
225 1570 1822 1781 1679 1945 280 305 1240 514 - - 514 426 34 110 11 2 799 240 249
250 1570 1848 1807 1705 1971 280 305 1240 514 - 302 514 420 34 110 11 2 799 249 258
100 1270 1585 1538 1418 1719 295 320 925 510 - - 510 440 42 124 11 2 749 201 213
112 1310 1630 1583 1463 1764 295 320 965 500 - - 500 440 42 124 11 2 749 206 218
132 1410 1714 1667 1547 1848 295 320 1065 482 - - 482 440 41 124 11 2 749 216 228
160 1460 1774 1727 1607 1908 295 320 1115 482 - - 482 440 40 124 11 2 769 228 240
025
180 1505 1825 1778 1658 1959 295 320 1160 564 - - 564 525 42 124 11 2 854 244 256
200 1590 1904 1857 1737 2038 295 320 1245 560 - - 560 515 34 110 11 2 854 262 274
225 1635 1955 1908 1788 2089 295 320 1290 582 - 274 599 515 34 110 11 2 884 279 291
250 1635 1984 1937 1817 2118 295 320 1290 584 - 277 599 515 34 110 11 2 884 287 299
132 1500 1839 1791 1651 1987 335 365 1105 562 - - 562 495 40 124 11 2 861 295 308
160 1555 1906 1858 1718 2054 335 365 1160 550 - - 550 495 40 124 11 2 861 301 314
180 1595 1954 1906 1766 2102 335 365 1200 556 - - 556 495 40 124 11 2 861 310 323
031 200 1680 2035 1987 1847 2183 335 365 1285 568 - - 568 495 33 110 11 2 861 327 340
225 1730 2089 2041 1901 2237 335 365 1335 676 - - 676 645 43 124 11 2 1041 393 406
250 1795 2155 2107 1967 2303 335 365 1400 670 - - 670 645 43 124 11 2 1041 409 422
280 1795 2190 2142 2002 2338 335 365 1400 736 - 349 755 645 43 124 11 2 1041 419 432
160 1655 2049 1998 1836 2211 370 400 1225 602 - - 602 528 57 120 15 4 926 357 375
180 1700 2103 2052 1890 2265 370 400 1270 604 - - 604 528 57 120 15 4 926 366 384
200 1785 2185 2134 1972 2347 370 400 1355 610 - - 610 528 38 144 14 2 926 385 403
040 225 1835 2240 2189 2027 2402 370 400 1405 726 - - 726 678 38 144 14 2 1076 453 471
250 1900 2308 2257 2095 2470 370 400 1470 664 - - 664 678 60 120 15 4 1106 472 490
280 1975 2385 2334 2172 2547 370 400 1545 764 - - 764 678 39 144 14 2 1106 489 507
315 1975 2419 2368 2206 2581 370 400 1545 788 - - 788 678 58 120 15 4 1136 509 527
160 1845 2400 2324 2110 2593 435 465 1350 710 - - 710 590 55 120 15 4 1042 380 409
180 1890 2458 2382 2168 2651 435 465 1395 706 - - 706 590 54 120 15 4 1042 511 540
200 1980 2548 2472 2258 2741 435 465 1485 700 - - 700 590 53 120 15 4 1042 532 561
050 225 2030 2608 2532 2318 2801 435 465 1535 704 - - 704 590 52 120 15 4 1062 551 580
250 2095 2680 2604 2390 2873 435 465 1600 802 - - 802 740 50 120 15 4 1212 628 657
280 2175 2773 2697 2483 2966 435 465 1680 832 - - 832 740 59 120 15 4 1212 649 678
315 2175 2815 2739 2525 3008 435 465 1680 844 - - 844 740 57 120 15 4 1242 667 696
1)
Weights are exclusive of motor and belt drive.
Ordering key - Description and tables - Accessories Page 53

Cooling disc HCEZ-06-bb Table - Cooling disc selection


(for operating temperatures > 100oC).
Material: Cast aluminium; contact guard included as standard. Cooling disc
Fan size
size
The cooling disc is cast in two halves and can thus be fit- HCG HCL HCM HCH code bb
ted to already installed fans. Refer to the table below for
025 - 031 020 - 025 016 -
cooling disc selection. - - 020 -
01
040 031 025 010 - 012
050 040 031 016 - 020
063 050 040 025 02
080 063 050 031 - 040 03
100 080 063 050 04

Cleanout cover HCEZ-09-bb-c-ddd Speed monitor HCEZ-13-bb


Robust, designed for frequent inspections. For monitoring speed of rotation.
Double sheet construction and handle. An alarm can be activated, or the motor stopped,
when fan speed falls below the revolutions set via
the potentiometer.
Supply current, V(AC/DC) 20 - 264
Load voltage, (mA) 5 - 350 AC / 5 - 200 DC
Safety class IP 67
o o
Ambient temperature -25 C / +70 C

Table - Cleanout cover selection

Fan size Cover size


HCG HCL HCM HCH bb
Fan
025 020 09 shaft
016 28
031 025 13
020 10
010 03
025 14
040 031 17
012 13 Table - Speed monitor selection
016 08
031 18 Fan size size
050 040 20
HCG HCL HCM HCH code bb
020 12
025-063 020-050 016-040 010-025 01
025 16
080-100 063-080 050-063 031-050 02
040 21
063 050 23
031 19
040 22
050 24
080 063 26
050 25
063 27
080 29
100 30
Dimensions and weights - Accessories Page 54

NB! Flanges comply to ISO 13351.


HCEZ-30 HCEZ-35 HCEZ-50/51/52 HCEZ-70/71
B g n holes G n holes G n holes G n holes G
g

E1

A n1 x E C A1 x B1

Sheet steel
insert

E1

F1 n2 x F F1 t + 2,5 t t t
+ 10 + 10
130 - 20 130 - 20
D

HCEZ- HCEZ- HCEZ- HCEZ-


30 35 50/51/52 70/71
Fan Weight Weight Weight Weight
Size A A1 B B1 C D E E1 F F1 G t g n n1 n2 kg kg kg kg
010 100 85 80 65 170 150 71 33.5 --- --- 10 5 19 8 1 1 0.6 0.5 1.1 1.5
012 125 110 100 85 195 170 71 46 71 33.5 10 5 19 12 1 1 0.8 0.7 1.5 2.3
016 160 145 125 110 230 195 100 49 71 46 10 5 19 12 1 1 0.9 0.8 1.7 2.5
020 200 185 160 145 270 230 100 69 100 49 10 5 19 12 1 1 1.1 1.0 2.1 3.1
025 250 235 200 185 330 280 125 81.5 125 56.5 10 6 19 12 1 1 2.1 1.9 3.9 5.3
031 315 295 250 230 395 330 125 51.5 125 81.5 10 6 19 14 2 1 2.8 2.4 5.0 6.6
040 400 380 315 295 480 395 125 94 125 51.5 10 6 19 16 2 2 3.5 2.9 6.0 8.0
050 500 480 400 380 620 520 125 94.5 125 107 12 8 32 18 3 2 8.5 7.6 15.5 18.3
063 630 600 500 480 750 620 125 97 125 94.5 12 8 32 22 4 3 10.5 9.2 18.8 22.4
080 800 770 630 600 920 750 125 57 125 97 12 8 32 28 6 4 13.4 11.5 23.5 27.9
100 1000 970 800 770 1120 920 125 94.5 125 57 12 8 32 34 7 6 17.1 14.2 29.0 34.9

HCEZ-20 HCEZ-21 HCEZ-25/27 HCEZ-40/41/42 HCEZ-60/61


Weight 0.1 - 1.1 kg with sheet steel insert
HCEZ-29 HCEZ-45/46/47 HCEZ-65/66
t1 145 with sheet steel insert
125
60
h


F
E D
D1 D5 D3 D4 D1 D3 D2 D1 D2 D3
D outs. ins.
ins. ins. ins. ins. ins.

+10 +10 +10 +10


t 40 - 20 130 - 20 40 - 20 130 - 20
nxG 45
L K

HCEZ- HCEZ- HCEZ- HCEZ- HCEZ-


20/21 25/27/29 45/46/47 60/61 65/66
Fan Weight Weight Weight Weight Weight
size D E F G t t1 D1 D2 D3 D4 D5 K L h n kg kg kg kg kg
010 105 139 170 9.5 5 --- 106 85 --- --- 230 --- 65 32.5 4 0.7 0.5 --- 0.6 ---
012 130 165 195 9.5 5 --- 131 110 --- --- 255 --- 65 32.5 4 0.9 0.6 --- 0.8 ---
016 165 200 240 12 5 --- 166 145 --- --- 295 --- 70 37.5 4 1.1 0.7 --- 1.0 ---
020 205 241 280 12 5 --- 207 185 --- --- 335 --- 70 37.5 8 1.2 1.0 --- 1.1 ---
025 255 292 330 12 6 -- 257 235 --- --- 400 --- 75 37.5 8 1.7 1.7 --- 1.4 ---
031 320 366 405 12 6 --- 322 290 --- --- 470 --- 80 42.5 8 2.2 2.1 --- 1.7 ---
040 405 448 490 12 6 2 407 375 400 528 528 192 192 42.5 12 5.9 3.4 8.4 2.2 8.8
050 505 551 600 12 8 2 507 475 500 628 628 192 192 47.5 12 6.8 4.8 11.3 2.8 12.2
063 635 698 750 14 8 2.5 637 595 630 809 809 218 218 57.5 16 11.8 5.9 14.5 3.5 15.2
080 805 869 920 14 8 2.5 807 765 800 1029 1029 243 243 57.5 24 18.2 7.3 18.2 4.6 19.0
100 1005 1067 1120 14 8 2.5 1007 965 1000 1229 1229 243 243 57.5 24 24.3 12.4 28.4 5.6 30.8
Belt drive selection Page 55

HCEZ-01-bbb-c-dd

Belt drive size 010 - 620, refer to the tables below

Form of delivery
1 = fitted to the ordered fan.
9 = delivered requiring assembly.

Fan size 01 - 11, refer to the table below


Check -dd against the belt drive in question; see the belt drive tables.
Rated power of motor: 1.1 kW
Fan Code
speed sufl-
Motor
Belt drive HCEZ-01 Rated power of motor: 0.75 kW
fix Suitable for:
comprises the following: Fan Code
r/m bbb dd =
speed suf- 5060 050 01, 02, 04
1. Motor pulley. fix
Motor
Suitable for: 4730 051 01, 02, 04
2. Fan pulley. r/m bbb dd =
4460 052 01, 02, 04
4220 053 01, 02, 04
3. Motor bushing. 4210 010 01, 02, 04 3980 054 APAL-2- 01, 02, 04, 05
4. Fan bushing. 3970 011 01, 02, 04 3780 055 00110-c-0 01, 02, 04, 05
3770 012 APAL-2- 01, 02, 04 3580 056 01-05
5. V-belt. 3570 013 00075-c-0 01, 02, 04 3380 057 2 poles 01-05
3360 014 01, 02, 04 3210 058 01-05
3200 015 01, 02, 04 3040 059 Size 80 01-05
3030 016 2 poles 01, 02, 04, 05 2870 060 as per IEC 01-05
2860 017 01-05 2710 061 01-05
Fan size 2690 018 Size 80 01-05 2570 062 01-05
2540 019 as per IEC 01-05 2440 063 01-05
dd HCG HCL HCM HCH 2410 020 01-05 2300 064 01-05
01 025 020 - - 2290 021 01-05
2190 065 02-05
02 031 025 016 - 2200 022 01-05 2070 066 02-05
03 - - 020 - 2090 023 APAL-4- 01-05 1960 067 02-05
1970 024 00075-c-0 01-05 APAL-4-
04 040 031 025 010 1860 068 02-05
1870 025 01-05 00110-c-0
05 - - - 012 1760 069 02-05
1770 026 4 poles 01-05 1660 070 02-05
06 050 040 031 016 1670 027 02-05 1580 071
4 poles
02-05
07 - - - 020 1590 028 Size 80 02, 03, 05 1490 072 02-04
1500 029 as per IEC 02, 05 Size 90S
08 063 050 040 025 1410 073 02, 04
1420 030 02, 05 as per IEC
09 - - - 031 1330 074 04
1260 075 04
10 080 063 050 040 1200 076 04
11 100 080 063 050

Rated power of motor: 3 kW


Rated power of motor: 2.2 kW Fan Code
Fan Code speed suf-
Motor
speed suf- fix Suitable for:
Rated power of motor: 1.5 kW Motor
fix Suitable for: r/m bbb dd =
Fan Code r/m bbb dd = 6140 180 01, 02, 04
speed suf-
Motor 6040 130 01, 02, 04, 05 5800 181 01, 02, 04
fix Suitable for:
5700 131 01, 02, 04, 05 5460 182 01-05
r/m bbb dd = 5360 132 01, 02, 04, 05 5120 183 01-05
5380 090 01, 02, 04 5030 133 01-05 4780 184 01-05
5050 091 01, 02, 04 4690 134 01-05 4500 185 01-05
APAL-2-
4710 092 01, 02, 04 4430 135 01-05 4260 186 01-05
APAL-2- 00300-c-0
4440 093 01, 02, 04, 05 4190 136 01-05 4030 187 01-05
00220-c-0
4210 094 APAL-2 01, 02, 04, 05 3960 137 01-05 3820 188 01-05
2 poles
3970 095 00150-c-0 01-05 3760 138 01-05 3620 189 01-06
2 poles
3770 096 01-05 3550 139 01-05 3410 190 01-06
Size 100L
3570 097 01-05 3350 140 01-05 3220 191 01-07
Size 90L as per IEC
3360 098 2 poles 01-05 3190 141 01-06 3050 192 02-07
as per IEC
3200 099 01-05 3020 142 01-06 2900 193 02-07
3030 100 Size 90S 01-05 2850 143 02-06 2740 194 02-07
2860 101 as per IEC 01-05 2690 144 02-06 2600 195 02-07
2700 102 01-05 2550 145 02-06 2460 196 02-08
2690 103 02-05 2420 146 02-06 2330 197 02-08
2430 104 02-05 2290 147 02-06 2160 198 02-04, 06-08
2290 105 02-05 2110 148 02-06 2050 199 03, 04, 06-08
2200 106 02-05 2000 149 02-06 1920 200 04, 06-08
2090 107 02-05 1890 150 03-06 1820 201 APAL-4- 04, 06-08
1970 108 02-05 1780 151 APAL-4- 04, 06 1720 202 00300-c-0 04, 06-08
APAL-4-
1870 109 02-05 1690 152 00220-c-0 04, 06 1630 203 04, 06-08
00150-c-0
1770 110 02-05 1600 153 04, 06 1520 204 4 poles 04, 06-08
1670 111 03-05 1510 154 4 poles 04, 06 1430 205 04, 06-08
4 poles
1580 112 04 1430 155 04, 06 1330 206 Size 100L 06-08
1490 113 04 1360 156 Size 100L 04, 06 1250 207 as per IEC 06-08
Size 90L
1420 114 04 1280 157 as per IEC 04, 06 1180 208 06-08
as per IEC
1350 115 04 1210 158 06 1110 209 06, 08
1270 116 04 1140 159 06 1050 210 06, 08
1200 117 04 1070 160 06 1000 211 06, 08
Belt drive selection Page 56

Rated power of motor: 4 kW Rated power of motor: 5.5 kW Rated power of motor: 7.5 kW
Fan Code Fan Code Fan Code
speed suf- speed suf- speed suf-
Motor Motor Motor
fix Suitable for: fix Suitable for: fix Suitable for:
r/m bbb dd = r/m bbb dd = r/m bbb dd =
6370 230 01-05 6380 280 02-05 6340 330 03-05
6040 231 01-05 6030 281 02-05 6030 331 03-05
5700 232 01-05 5710 282 02-05 5710 332 03-06
5380 233 01-05 5420 283 02-05 5390 333 03-06
5070 234 01-05 5100 284 02-06 5080 334 03-06
4800 235 01-06 4840 285 02-06 4810 335 02-06
APAL-2-
4560 236 01-06 4570 286 APAL-2- 02-06 4510 336 APAL-2- 02-07
00400-c-0
4280 237 01-06 4340 287 00550-c-0 02-06 4280 337 00750-c-0 02-07
4030 238 01-06 4110 288 02-07 4000 338 02-07
2 poles
3760 239 01-06 3870 289 2 poles 02-07 3770 339 2 poles 02-07
3560 240 01-07 3670 290 02-07 3560 340 02-07
Size 112M
3360 241 02-07 3430 291 Size 132S 02-07 3360 341 Size 132S 02-08
as per IEC
3190 242 02-07 3240 292 as per IEC 02-07 3190 342 as per IEC 02-08
3020 243 02-07 3030 293 02-08 3020 343 02-08
2850 244 02-08 2860 294 02-08 2860 344 04, 06-08
2690 245 02-08 2680 295 02-08 2700 345 04, 06-08
2550 246 02-08 2520 296 04, 06-08 2550 346 04, 06-08
2400 247 04, 06-08 2380 297 04, 06-08 2410 347 04, 06-08
2240 248 04, 06-08 2280 298 04, 06-08 2250 348 04, 06-08
2110 249 04, 06-08 2200 299 04, 06-08 2170 349 04, 06-08
2010 250 04, 06-08 2090 300 04, 06-08 2050 350 04, 06-08
1890 251 04, 06-08 1970 301 04, 06-08 1950 351 06-08
1790 252 APAL-4- 04, 06-08 1860 302 04, 06-08 1810 352 06-08
1690 253 00400-c-0 04, 06-08 1740 303 APAL-4- 06-08 1700 353 APAL-4- 06-08
1600 254 06-08 1650 304 00550-c-0 06-08 1610 354 00750-c-0 06, 08
1510 255 4 poles 06-08 1540 305 06-08 1520 355 06, 08
1435 256 06-08 1450 306 4 poles 06, 08 1435 356 4 poles 06, 08
1360 257 Size 112M 06-08 1370 307 06, 08 1355 357 06, 08
1290 258 as per IEC 06, 08 1280 308 Size 132S 06, 08 1280 358 Size 132M 08
1220 259 06, 08 1200 309 as per IEC 06, 08 1220 359 as per IEC 08
1150 260 06, 08 1130 310 08 1150 360 08
1070 261 06, 08 1060 311 08 1040 361 08
1000 262 06, 08 1010 312 08 1020 362 08
960 313 08

Rated power of motor: 15 kW


Fan Code
Rated power of motor: 11 kW speed suf-
Motor Rated power of motor: 18.5 kW
Fan Code fix Suitable for:
speed suf- r/m bbb dd = Fan Code
Motor speed suf-
fix Suitable for:
6540 430 03-06 Motor
r/m bbb dd = fix Suitable for:
6170 431 03-06
6560 380 03-06 5840 432 03-06 r/m bbb dd =
6190 381 03-06 5510 433 03-07 5840 490 04, 06, 07
5860 382 03-06 5230 434 03-07 5540 491 04, 06, 07
5560 383 03-06 4930 435 04-07 5230 492 04, 06, 07
5230 384 03-06 4690 436 APAL-2- 04-07 4960 493 04, 06-08
4970 385 03-07 4450 437 01500-c-0 04-08 4670 494 04, 06-08
4720 386 03-07 4210 438 04-08 4420 495 APAL-2- 04, 06-08
APAL-2-
4450 387 03-07 3970 439 2 poles 04-08 4170 496 01850-c-0 04, 06-08
01100-c-0
4220 388 03-07 3740 440 04, 06-08 3890 497 06-08
4000 389 03-08 3540 441 Size 160M 04, 06-08 3650 498 2 poles 06-08
2 poles
3770 390 03-08 3320 442 as per IEC 04, 06-08 3470 499 06-08
3550 391 03-08 3070 443 04, 06-08 3260 500 Size 160L 06-08
Size 160M
3350 392 03, 04, 06-08 2920 444 04, 06-08 3080 501 as per IEC 06-08
as per IEC
3130 393 04, 06-08 2770 445 06-10 2920 502 06-09
2930 394 04, 06-08 2630 446 06-10 2770 503 06-09
2780 395 04, 06-08 2480 447 06-10 2630 504 06-09
2580 396 04, 06-10 2270 448 06-10 2480 505 06-10
2420 397 04, 06-10 2200 449 06-10 2350 506 06-10
2280 398 04, 06-10 2080 450 06, 08-10 2190 507 06, 08-10
2180 399 06-10 1970 451 06, 08-10 2060 508 06, 08-10
2040 400 06-10 1840 452 06, 08-11 1940 509 08-11
1950 401 06-10 1750 453 06, 08-11 1830 510 08-11
1830 402 06, 08-10 1640 454 08-11 1730 511 08-11
1720 403 06, 08-10 1550 455 08-11 1630 512 08-11
1630 404 06, 08-11 1470 456 APAL-4- 08-11 1550 513 08-11
APAL-4-
1540 405 06, 08-11 1370 457 01500-c-0 08-11 1470 514 08-11
APAL-4- 01850-c-0
1460 406 08-11 1290 458 08, 10, 11 1400 515 09-11
01100-c-0
1380 407 08-11 1225 459 4 poles 08, 10, 11 1320 516 10, 11
4 poles
1310 408 08-11 1160 460 10, 11 1250 517 10, 11
4 poles
1240 409 08-11 1100 461 Size 160L 10, 11 1180 518 10, 11
Size 180M
1170 410 08, 10, 11 1040 462 as per IEC 10, 11 1120 519 10, 11
Size 160L as per IEC
1110 411 08, 10, 11 990 463 10, 11 1060 520 10, 11
as per IEC
1050 412 10, 11 930 464 10, 11 1000 521 10, 11
990 413 10, 11 880 465 10, 11 940 522 10, 11
940 414 10, 11 830 466 10, 11 890 523 10, 11
880 415 10, 11 785 467 11 840 524 11
830 416 10, 11 740 468 11 790 525 11
790 417 10, 11 690 469 11 750 526 11
Belt drive selection Page 57

Rated power of motor: 22 kW Rated power of motor: 30 kW


Fan Code Fan Code
speed suf- speed suf-
Motor Motor
fix Suitable for: fix Suitable for:
r/m bbb dd = r/m bbb dd =
5860 540 04-07 4410 590 06-09
5560 541 04-07 4140 591 06-09
5230 542 04-07 3890 592 06-09
4970 543 04-07 3680 593 APAL-2- 06-09
4720 544 04-08 3480 594 03000-c-0 06-09
4450 545 APAL-2- 06-08 3310 595 06-10
4220 546 02200-c-0 06-08 3110 596 2 poles 06-10
3980 547 06-08 2960 597 06-10
3770 548 2 poles 06-08 2810 598 Size 200L 07-10
3560 549 06-08 2640 599 as per IEC 08-10
3350 550 Size 180M 06-08 2510 600 08-10
3130 551 as per IEC 06-10 2370 601 08-10
2930 552 06-10 2250 602 08-10
2730 553 06-10 2170 603 08-11
2560 554 06-10 2050 604 08-11
2410 555 06, 08-10 1930 605 08-11
2280 556 06, 08-10 1830 606 08-11
2190 557 08-10 1740 607 08-11
2100 558 08-11 1650 608 APAL-4- 08, 10, 11
1960 559 08-11 1560 609 03000-c-0 08, 10, 11
1840 560 08-11 1480 610 10, 11
1750 561 08-11 1400 611 4 poles 10, 11
1650 562 08-11 1320 612 10, 11
1560 563 APAL-4- 08, 10, 11 1250 613 Size 200L 10, 11
1470 564 02200-c-0 08, 10, 11 1180 614 as per IEC 10, 11
1390 565 10, 11 1120 615 10, 11
1320 566 4 poles 10, 11 1050 616 10, 11
1250 567 10, 11 990 617 11
1180 568 Size 180L 10, 11 930 618 11
1120 569 as per IEC 10, 11 880 619 11
1060 570 10, 11 830 620 11
1000 571 10, 11
940 572 11
890 573 11
840 574 11
790 575 11

Shaft centre to centre distances, fan / motor

Fan type - Size Motor c-c distance Fan type - Size Motor c-c distance Fan type - Size Motor c-c distance
size size size
HCG HCL HCM HCH IEC Min. * Max. * HCG HCL HCM HCH IEC Min. * Max. * HCG HCL HCM HCH IEC Min. * Max. *
80 410 500 90 640 735 112 915 1050
90 420 515 100 655 770 132 935 1100
025 020 -- -- 100 435 555 112 665 795 160 965 1125
112 445 582 132 685 845 180 990 1150
050 040 031 016
132 470 565 160 715 875 080 063 050 040 200 1010 1205
80 465 555 180 740 895 225 1035 1230
90 475 570 200 765 955 250 1065 1265
100 490 610 225 795 935 280 1100 1310
031 025 016 -- 315 1140 1285
112 500 635 100 705 825
132 525 695 112 720 850 132 1110 1280
160 565 670 132 735 900 160 1140 1300
80 500 590 -- -- -- 020 160 770 930 180 1165 1325
90 515 610 180 790 950 200 1190 1380
100 080 063 050
100 525 645 200 805 1000 225 1210 1405
-- -- 020 -- 225 835 1025 250 1240 1440
112 540 675
132 555 720 250 865 1010 280 1275 1490
160 590 695 100 765 885 315 1315 1460
80 540 630 112 775 910
90 550 645 132 795 960
100 565 680 160 825 980
063 050 040 025
112 575 710 180 850 1005 * Fitting and after installation tensioning
040 031 025 010 200 875 1065 tolerances must be observed. Check the
132 595 760
160 625 785 225 900 1090 belt supplier's recommendations.
180 650 805 250 930 1070
200 675 790 132 860 1025
80 585 675 160 895 1050
90 590 685 180 895 1050
100 605 725 -- -- -- 031 200 935 1130
-- -- -- 012 112 615 750 225 960 1155
132 635 800 250 995 1195
160 665 825 280 1030 1170
180 690 805
Key charts - belt-driven fans Page 58

HCGB, HCLP, HCM(B,P) and HCH(B,P) The charts are valid for gas at a density of 1.2 kg/m2.

Gas flow, m3/h


2000 3000 5000 10 000 20 000 50 000 100 000 200 000
12 000
10 000 H 01 02
01 6 0 08 09
CH 2 04 05 06 07 0 0 10
02 03 0 0 3 1 0
01 5 1
0
02 12
5 03 10 11 5
1 06 07 08 09 2
02 04 05 3 1 0 0 0
H 0 0 0
5000 C
M
01
6
4000 03 04 14
1 0 10 12 0
08 0 5
HC 06 0
Total pressure rise, Pa

05 3 09 16
3000 LP 02 0 0 11 0
02 5 2
0

H
2000 C
G
B
02 03 04 05 06 08 10 11 14 16
5 1 0 0 3 0 0 2 0 0
12
5

1000

800
0.3 0.4 0.5 1 2 3 4 5 10 20 30 40 50 80
Gas flow, m3/s

HCLT, HCMT and HCHT

Gas flow, m3/h


300 400 500 1000 2000 3000 5000 10 000 20 000 50 000
10 000

016

HCHT 010 012 020 025 031 040 050


5000

4000

HCMT 016 020 025 031 040 050 063


Total pressure rise, Pa

3000

2000

HCLT 020 025 031 040 050 063 080

1000

800
0.06 0.1 0.2 0.3 0.4 0.5 1 2 3 4 5 10 14
Gas flow, m /s 3
Fan charts - Belt-driven fans Page 59

Fan charts

In general, the charts specify three maximum speeds for Pressure losses across accessories:
maximum temperatures of 100, 200 and 350oC. Within HCEZ-20 and -21 inlet taper piece: 0.35 x dynamic pressure.
these limits, the maximum speed can be determined by
linear interpolation between 100 and 200oC or between HCEZ-20 HCEZ-21
200 and 350oC.

The charts are valid for gas at a density of 1.2 kg/m3.

Optimum working ranges are shaded in grey.

HCGB

Gas flow, m3/h Gas flow, m3/h


0 1000 2000 3000 4000 0 2000 4000 6000
1 1
2 025 031
3000 2
nm nm
ax = 5 ax =
3000 700 3 429
550 r/min 42 0 r/m 3
0 40000 in
0
500 380
0 2000 0
Total pressure rise, Pa

Total pressure rise, Pa

4 360 4
2000 0
450 340
0 0
320
400 0
0 300 5
5 280 0
3500 1000 26000
1000 24
3000 22 00
2500 20 00
180000
2000
10
10
0 0
0.0 0.1 0.4 0.6 0.8 1.0 1.2 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
0 2000 0 Gas flow, m3/s
2500 Gas flow, m3/s 1800 000
2
3000 220000
24
2600
Power demand, kW

Power demand, kW

3500
2800
0
4000 1 300
0
320
1 0
450 340
0
0
360
5000 2
380
0

00
40
nmax, r/min 00 nmax, r/min
55 00
2 < 200C: 5700 < 200C: 4290 42 n
min 3 i
350C: 4870 0 r/ 350C: 3925 r/ m
J (= 1/4 GD2): 0.025 kg m2 nmax = 570 J (= 1/4 GD2): 0.08 kg m2 nmax = 4290
Fan charts - Belt-driven fans Page 60

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCGB
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 0 5000 10 000 15 000

1
4000 1 040 2 050
nm nm
ax = 3 2 ax = 2
840 860
3000 280 r/min
r /m 0 3
360 in
3000 0 3 260
340 0
0 240
Total pressure rise, Pa

Total pressure rise, Pa


320 4 0 4
0 2000
3000 2200
2000 280 2000 5
2600 0 5
2400 1800
220 1000
1000 200 0
1800 0

10 10
0 0
0 1 2 3 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
0 0
Gas flow, m3/s Gas flow, m3/s
1800
1 200 0
2200
Power demand, kW

Power demand, kW
2
2400 1800
2
2600 2000
2800 4
3 0
300
0 220
4 0
320 6 240
0
0
5 340
0
260
0 0 8
6 36 nmax, r/min
nmax, r/min
< 100C: 2860 00
7 < 200C: 3840 200C: 2740 28
n 10 in
350C: 3115 /mi / m
J (= 1/4 GD2): 0.212 kg m2
nm =
ax 3 8 40 r 350C: 2360 nm = 2
ax 86 0 r
8 J (= 1/4 GD2): 0.51 kg m2

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 0 10 000 20 000 30 000 40 000
1
063 1
nma = 2
080
nm x 1730
ax = 22 3000 r/m
3000 40 in
2200 r/min 3
1600
200
0 4
1400
Total pressure rise, Pa

2000
Total pressure rise, Pa

2000 1800
5
1600 1200
1400
1000
1000 1200 1000
1000
10

0 0
0 1 2 3 4 5 6 7 8 0 2 4 6 8 10 12 14
0 0
Gas flow, m3/s Gas flow, m3/s
1000
2 1200
1000
Power demand, kW

Power demand, kW

4 1400
1200
6 1600 10
8 0 0
180 140
10
0
12 200
20 00
nmax, r/min 16
14 nmax, r/min
< 100C: 2240
200C: 2145 00 < 200C: 1730
16 22 350C: 1510 n
350C: 1840 i n nm = 1730 r/mi
2 2
nma = 22
x 40 r/m 2
28 J (= 1/4 GD ): 3.77 kg m
2 ax
18 J (= 1/4 GD ): 1.3 kg m
Fan charts - Belt-driven fans Page 61

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

Boundary between HCGB with impeller diameter 1000


HCGB mm and HCGB with impeller diameter >1000 mm.

Gas flow, m3/h Gas flow, m3/h


0 10 000 30 000 50 000 70 000 0 20 000 40 000 60 000 80 000 100 000
4000
1 100 1
nmax = 1
112
375 2 nmax = 1 2
3000 r/m 310
in r/m
1300 3 in 3
3000 1200
1200
4 4
1100
Total pressure rise, Pa

2000

Total pressure rise, Pa


1100
5 1000 5
1000 2000
900
900
800 800
1000 700
700 1000
600 600
500 10 500 10
400
0 0
0 10 20 0 10 20 30
0 500 0 400 500
600 Gas flow, m3/s Gas flow, m3/s
600
700 700
800 10
Power demand, kW

Power demand, kW
10 800
900
20 900
1000
1000
20 0 30
110
0
0 40 110
120
30 0
50 120
nmax, r/min 00 nmax, r/min
13
< 100C: 1375 < 100C: 1310
40 200C: 1240 60 200C: 1190
in i n
350C: 1065 nm = 1375 r/m 350C: 1020 nm = 1310 r/m
ax 2 2 ax
J (= 1/4 GD2): 10.3 kg m2 70 J (= 1/4 GD ): 18.7 kg m

Gas flow, m3/h Gas flow, m3/h


0 20 000 40 000 60 000 80 000 100 000 120 000 0 20 000 60 000 100 000 140 000
1
1
2 125 nmax = 1 2
140
nma =
3000 x 1090 010 r/mi
r/m 3 n
in 3000 3
1000
900
4 4
900
Total pressure rise, Pa

2000
Total pressure rise, Pa

800
2000
5 5
800
700
700
600
1000 600 1000
500
500
400 400
10 300 10
300
0 0
0.0
0 10 20 30 36 0 10 20 30 40 46
0 300 0 300
400 Gas flow, m3/s 400 Gas flow, m3/s
500 500
10 600
600
Power demand, kW
Power demand, kW

20
700
20 700
800
40
30
800
900
40
60
0
90
0
50 100
nmax, r/min nmax, r/min
nmax, r/min 80 < 100C: 1010
< 100C:1090
60 < 200C: 5700 200C: 915
200C:1000 in
350C: 4870 i n
350C: 865 nm = 1090 r/m 350C: 780 nm = 1010 r/m
1/4 GD2): 0.023 kg m2 ax ax
70 JJ (=
(= 1/4 GD2): 31.6 kg m2 100 J (= 1/4 GD2): 57.7 kg m2
Fan charts - Belt-driven fans Page 62

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCGB
Gas flow, m3/h
0 50 000 100 000 150 000 200 000

1
4000
nmax = 9 2 160
65 r /min
3
900
3000
4
800
Total pressure rise, Pa

5
2000 700

600

1000 500
400
300 10

0
0 10 20 30 40 50 60
0 300
400 Gas flow, m3/s
20 500
Power demand, kW

600
40
700
60

80 800

100
0
120 nmax, r/min 90
< 100C: 965
200C: 890
140 in
350C: 755 nm = 965 r/m
J (= 1/4 GD2): 110.5 kg m2 ax
160

HCLP
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 4000 0 1000 2000 3000 4000 5000 6000
4000 1 1
2 4000 2
nm nm
ax = 6
100 3 020 ax = 4
900
025
r /m 3
in r/m
600 4 480 in
0 0
3000 4
3000
5 5
500 400
0 0
Total pressure rise, Pa

Total pressure rise, Pa

2000 2000
400
0
3000

1000 3000 1000


10 2000 10

2300 1900

0 0
0 0.2 0.4 0.6 0.8 1.0 0 0.5 1.0 1.5 2. 0

0 0
2300 Gas flow, m3/s 1900 2000 Gas flow, m3/s
3000
Power demand, kW

Power demand, kW

1 3000
4000

1
2

5000 4000

4
6000 nm 4800
nmax is not temperature dependent nmax is not temperature dependent ax = 4900 r/min
J (= 1/4 GD2): 0.022 kg m2 nmax = 6100r/min J (= 1/4 GD2): 0.067 kg m2
2.8 5
Fan charts - Belt-driven fans Page 63

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCLP
Gas flow, m3/h
Gas flow, m3/h
0 5000 10 000 14 000 0 10 000 20 000
1 6000 2 n
nm 2 ma 3
6000 ax =
490 031 1 x=
38
70
040
0r 3 38 4
480 /m 5000 00 r /m
0 in in
5000 4 5
5 4000
4000 4000
300
0
Total pressure rise, Pa

Total pressure rise, Pa


3000
3000
3000
2000 2000
2000
2000 10 10
1000 1000
1900

0 0
0 1 2 3 3.8
0 1 2 3 4 5 6
0
19002000 Gas flow, m /s 0
Gas flow, m /s
2000
Power demand, kW

3000

Power demand, kW
10
4000 3000

10

nmax, r/min 20
00 nmax, r/min
< 200C: 4900 nm = 490048r/min < 100C: 3870
ax
350C: 4580 200C: 3580
J (= 1/4 GD2): 0.16 kg m2 350C: 3140 n
ma = 3800
18 J (= 1/4 GD2): 0.44 kg m2 x 3 87
0 r/min
28

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 30 000 0 10 000 20 000 30 000 40 000
5000 4800
1 2 1 2 n
n
2600
ma
x =
3
050 2000
ma
x =2
13
3
063
27 0r
50 4000 4
4000 r /m 4 /m
in
in
5
5
3000 3000

2000
Total pressure rise, Pa

Total pressure rise, Pa

2000 2000

1000
1000 10 1000 10
1000

0 0
0 1 2 3 4 5 6 7 8 0 2 4 6 8 10 12
0 0
1000 Gas flow, m3/s Gas flow, m3/s
1000
Power demand, kW

Power demand, kW

10

10
2000
20

20 30

nmax, r/min nmax, r/min


2000
< 100C: 2750 2600 < 100C: 2130
200C: 2540 40 200C: 1970
350C: 2230 n n
ma = 350C: 1730 ma =
30 x 2750 x 2130
J (= 1/4 GD2): 1.1 kg m2 r/min J (= 1/4 GD2): 2.9 kg m2 r/min
48
Fan charts - Belt-driven fans Page 64

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

Boundary between HCLP with impeller diameter 1000 mm


HCLP and HCLP with impeller diameter >1000 mm

Gas flow, m3/h Gas flow, m3/h


0 20 000 40 000 60 000 80 000 0 20 000 40 000 60 000 80 000
4800
2 2
5000 1 3 n
1700
n
ma
x =
080 1 ma
x =1
3 090
17 1400 49
70 4 4000 0r
160 r/m /m 4
0 in
4000 in
5 5
1400 3000
3000
Total pressure rise, Pa

Total pressure rise, Pa


1200 1000
2000
2000
1000

800 10
1000 1000 10
600 500

0 0
0 10 20 23 0 10 20 26
0 600 0
Gas flow, m3/s 500 Gas flow, m3/s
800
10 10
1000
Power demand, kW

Power demand, kW
20 20
1200 1000
30 30

1400 40
40

50
50

60
60 1600
nmax, r/min nmax, r/min
< 100C: 1770 70 < 100C: 1490 1400
70 1700
200C: 1640 200C: 1370
350C: 1440 n 80 350C: 1210
m ax = n
80 J (= 1/4 GD2): 8.8 kg m2 1770 r/min J (= 1/4 GD2): 15.3 kg m2 max =
1490 r/min
90

Gas flow, m3/h Gas flow, m3/h


0 50 000 100 000 130 000 0 50 000 100 000 150 000
4800
5000 2 n 2
1 ma 3 3
x =1
40
100 1 n
ma
x =
112
0r 4 4000 11 4
/m 80
in 110 r/m
4000 0 in
5 5
120
0 100
3000 0
3000
Total pressure rise, Pa

Total pressure rise, Pa

100
0
2000
2000
800

10 1000 10
1000 600 500

400
0 0
0 10 20 30 36 0 10 20 30 40

0 400 0
Gas flow, m3/s 500 Gas flow, m3/s
600

20 800 20
Power demand, kW

Power demand, kW

40 40
1000

60
60

80 1000
80 1200

100
nmax, r/min nmax, r/min
100
< 100C: 1400 1100
< 100C: 1180
200C: 1290 120 200C: 1090 n
350C: 1130 n 350C: 960 ma
120 ma x = 1 x = 118
J (= 1/4 GD2): 27.5 kg m2 400 r/min J (= 1/4 GD2) 47 kg m2 0 r/min
140
Fan charts - Belt-driven fans Page 65

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCLP
Gas flow, m3/h Gas flow, m3/h
0 100 000 200 000 0 100 000 200 000 260 000
5000
1 2 n 6000 2
ma 3
x =
10 125 1 n
ma
x =1
3 140
80 4 06
r/m 5000 0r 4
4000 100 in 100 /m
0 0 in
5
5
4000
3000
800
Total pressure rise, Pa

Total pressure rise, Pa


800
3000
2000

600 2000
600

1000 10
10
400 1000 400

0 0
0 10 20 30 40 50 56 0 10 20 30 40 50 60 70

0 0
400 Gas flow, m3/s 400 Gas flow, m3/s
20
600 600
Power demand, kW

Power demand, kW
40

60 100
800
80 800

100

120 200

140
nmax, r/min 1000 nmax, r/min
< 100C: 1080 < 100C: 1060 1000
160
200C: 1000 200C: 980 n
n ma
350C: 880 ma 350C: 800 x =1
180 x = 108 300 060 r/
J (= 1/4 GD2): 83 kg m2 0 r/min J (= 1/4 GD2): 166 kg m2 m in

Gas flow, m3/h


0 100 000 200 000 300 000

2
5000 1 nm
ax =
3
160
88 4
85 0 r/m
0 in
4000 800
5

3000 700
Total pressure rise, Pa

600
2000
500

1000 400 10

300

0
0 10 20 30 40 50 60 70 80 90

0 300 Gas flow, m3/s


400

500
Power demand, kW

100 600

700

200

800
nmax, r/min
< 100C: 880
200C: 820 850
300 350C: 720 n
J (= 1/4 GD2): 268 kg m2 ma =
x 880 r/min
Fan charts - Belt-driven fans Page 66

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCLT
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 4000 0 1000 2000 3000 4000 5000 6000
2800 2800
1
2 2
1 3
3
4
020 n
ma 4
025
n x =3
ma
x = 93
49 5 0r
5 /m
48 0 r/m 38
00
in
2000 0 in 2000 5
46 0 36
00 00
44
0 34
420 0 00
400 0 320

Total pressure rise, Pa


Total pressure rise, Pa

0
380 0 300
0 0
280
340 0
1000 0 1000
300 240
0 0
260 2000 10
0
2200 1600

0 0
0 0.2 0.4 0.6 0.8 1 0 0.5 1 1.s5

0 0
2200 Gas flow, m 3/s 1600 Gas flow, m3/s
2600 2000
1
300 240

Power demand, kW
Power demand, kW

1 0 0
340 2 280
0 0
30
38 0 0
00 3
2 32
40 00
00
4 34
42 00
0
44 0
3 00 36
5
00
46
n 00 n
m 6 m 38
ax 48 ax 00
4 = =
49 00 39
50 3 0
r/ 7 r/
nmax is not temperature dependent nmax is not temperature dependent

m
m

J (= 1/4 GD2): 0.017 kg m2 J (= 1/4 GD2): 0.043 kg m2

in
in

5 8

Gas flow, m3/h Gas flow, m3/h


0 5000 10 000 0 5000 10 000 15 000
2800 2800
1 2 2
3
n
3
031 1 n 4
040
ma ma
x =3 4 x =
12 2 48
0r 24 0
2000 30 / mi
n
5
2000 00 r/min 5
00
28 22
00 00
260
0 200
Total pressure rise, Pa

0
Total pressure rise, Pa

240
0 180
220 0
0
1000 200 1000 160
0 0
180 140 10
0 10 0
160 120
0 0
1200 1000

0 0
0 1 2 0 1 2 3 4

0 0
1200 Gas flow, m3/s 1000 Gas flow, m3/s
1200
1600 2
1800 1400
Power demand, kW
Power demand, kW

200 4 160
0 0
220
0 6 180
0
240
5 0 8 20
00
26
00 10
22
28 00
12
00
n 14 n
m 30 m 24
ax 00 ax
10 = = 00
31 16 24
20 80
r/m r/m
i 18 n i
nmax is not temperature dependent max is not temperature dependent
n

J (= 1/4 GD2): 0.14 kg m2 J (= 1/4 GD2): 0.353 kg m2


13 20
Fan charts - Belt-driven fans Page 67

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCLT
Gas flow, m3/h Gas flow, m3/h
0 10 000 20 000 0 10 000 20 000 30 000 40 000
2900 2900
2 2
1
n
3 050 1
n
3 063
ma ma 4
x =1 4 x =
97 15
0r 60 5
19 /m 5 15 r/m
00 in 00 in
2000 2000
18
00 14
170 00
0 130
160 0
Total pressure rise, Pa

Total pressure rise, Pa


150 120
0 0
140 110
0 0
1000 1000 100
120 0
0 900
10 10
1000 800
800 700
600

0 0
0 1 2 3 4 5 6 7 0 2 4 6 8 10
0 0
800 Gas flow, m 3/s 600 Gas flow, m3/s
700
1000 800
120 900
Power demand, kW

Power demand, kW
0 100
10 0
140 110
0 0
10
15 12
00 00
16 20
00 13
00
17
00
14
20 18 30 00
00
n 19
m n 15
ax 00 m 00
= ax
19 40 =
7 0 15
r/m 6 0
n is not temperature dependent i r/
nmax is not temperature dependent
30 J max

m
n

(= 1/4 GD2): 1.1 kg m2 J (= 1/4 GD2): 3.7 kg m2

in
50

Gas flow, m3/h


0 10 000 20 000 30 000 40 000 50 000 60 000
2800 2
1
n
3 080
ma
x =1 4
24
0r
12 /
00 min
2000 5

100
Total pressure rise, Pa

1000 800

10
600

400

0
0 5 10 15 18

0 400
Gas flow, m3/s
600
10
Power demand, kW

800
20

30
10
00
40

50

n
60 m
ax
=
12
12

4 0
00

70 r/
nmax is not temperature dependent
m

J (= 1/4 GD2): 7.23 kg m2


in

80
Fan charts - Belt-driven fans Page 68

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMB
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 14 000 0 10 000 20 000
1 2 2
n 8000 1 n
ma
x =
3 031 ma
x =
3 040
8000 44 45 33
00 20 7000 90
r/m 32 r/m
4 00
in in 4
40 6000 30
00 00
6000
5 5000 5
Total pressure rise, Pa

Total pressure rise, Pa


4000
4000 300
0
3000 200
0

2000 2000
2000
10 10
1400 1000
1000

0 0
0 1 2 3 4 0 1 2 3 4 5 6
0 1400 0 1000
Gas flow, m3/s Gas flow, m3/s
2000

2000
Power demand, kW

Power demand, kW
0
300
10

10

00 00
40 20 30

00
nmax, r/min nmax, r/min 32
0
20 < 100C: 4520
440 < 100C: 3390
200C: 4180 200C: 3140 in
350C: 3670
30 350C: 2750 r/m
n 90
J (= 1/4 GD2): 0.48 kg m2 max = 4520 r/min J (= 1/4 GD2): 1.18 kg m2 nmax = 33
25

Boundary between HCMB with impeller diameter 1000 mm


and HCMB with impeller diameter >1000 mm

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 30 000 0 10 000 20 000 30 000 40 000 50 000
9000
9000 2
2
8000
1 n
ma 3
050 1
n
ma
x =
3 063
x = 8000 22
27
10 22 60
7000 26 r /m 00 r /m 4
00 in 7000 in
4 20
6000 00
6000
5
5000 5
5000
Total pressure rise, Pa

Total pressure rise, Pa

200
4000 0
4000
3000 3000

2000 2000 1000


1000 10 10
1000 1000

0 0
0 1 2 3 4 5 6 7 8 9 0 2 4 6 8 10 12 14 16

0 0
1000 Gas flow, m3/s Gas flow, m3/s
1000
10
Power demand, kW

Power demand, kW

10 20

30
0
20 200
40

50
30
00
60 20

70
40
00

nmax, r/min nmax, r/min 00


26

< 100C: 2710 80 < 100C: 2260 22


200C: 2510 200C: 2090
in
350C: 2200 in 90 350C: 1830 nm = 2260 r/m
50
J (= 1/4 GD2): 3.13 kg m2 nm = 2710 r/m J (= 1/4 GD2): 9.6 kg m2 ax
ax
100
Fan charts - Belt-driven fans Page 69

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMB
Gas flow, m3/h Gas flow, m3/h
0 10 000 20 000 30 000 40 000 50 000 60 000 70 000 0 20 000 40 000 60 000 80 000 90 000
9000 9000
2 2
n
8000 1
n
ma
x= 3 071 8000 1 ma
x=
3 080
19 17
19 20 17 30
0 r/m 0 r /m
7000 18 0 i 4
7000 16 0 in
4
00 00

n
6000 6000
160 5 14 5
5000 0 5000 00

Total pressure rise, Pa


Total pressure rise, Pa

140
4000 0 4000 120
0

3000 120 3000


0 100
0
100
2000 0 2000 800
800 10
10 600
1000 600 1000

0 0
0 2 4 6 8 10 12 14 16 18 0 5 10 15 20 25

0 600 0 800 3/s


800 Gas flow, m 3/s Gas flow, m
800
1000
0
100

Power demand, kW
Power demand, kW

20 0
120
0
120
00
14 50
40
00
00 14
16
60

00 00
18 16
100
80
nmax, r/min nmax, r/min

00
< 100C: 1920 00 < 100C: 1730
19

17
in 200C: 1600 in
200C: 1780 r/m /m
100 350C: 1520 20 350C: 1350 3 0r
J (= 1/4 GD2): 16.3 kg m2 19 J (= 1/4 GD2): 25.8 kg m2 17
= =
ax 140
nm ax
nm

Gas flow, m3/h Gas flow, m3/h


0 20 000 40 000 60 000 80 000 100 000 0 50 000 100 000 140 000
9000
2 2
9000 1 n 1 n 3
ma
x =
3 090 8000 ma
x = 100
15 13
8000 90 70
r/ m 7000 r/m
in in 4
7000 4
14 12
00 6000 00
6000 5 5
5000
5000 120
Total pressure rise, Pa
Total pressure rise, Pa

0 100
0
4000
4000
100
0 3000 800
3000
800 2000
2000 600
600 10 10
1000 1000 400

0 0
0 10 20 30 0 10 20 30 39

0 0 400
600 Gas flow, m3/s Gas flow, m3/s
600
20 800
800
Power demand, kW
Power demand, kW

0
40 100

60 0
00 100
12
80
100
100
00 00
14 12
120

140
nmax, r/min nmax, r/min
< 100C: 1590 < 100C: 1370
160
200C: 1470 200C: 1260
350C: 1210 n 200 350C: 1080 n
180 ma =
J (= 1/4 GD2): 47 kg m2 x 1590 r/min J (= 1/4 GD2): 79 kg m2 ma =
x 1370 r/mi
n
Fan charts - Belt-driven fans Page 70

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMB
Gas flow, m3/h Gas flow, m3/h
0 5000 100 000 150 000 180 000 0 100 000 200 000
9000 9000
2 2
1 n 3
8000 1
n
m
12 ax =
3 112 8000 ma
x = 125
00 12 10
20 90
7000 r 7000 r /m
4 10 in 4
00
/m
in
6000 6000
100 5 5
0
5000 5000

Total pressure rise, Pa


Total pressure rise, Pa

80
0
4000 4000
800
3000 3000
600
2000 600 2000
10 400 10
1000 400 1000

0 0
0 10 20 30 40 50 0 10 20 30 40 50 60

0 400 0
Gas flow, m 3/s 400 Gas flow, m3/s
600
600

Power demand, kW
Power demand, kW

800
100
0
100 80

00
10

200
00
10
200
nmax, r/min nmax, r/min
00

< 100C: 1220 < 100C: 1090


12

200C: 1130 300 200C: 1010


n
350C: 960 mi 350C: 860 n
J (= 1/4 GD2): 156 kg m2 nm = 1220 r/ J (= 1/4 GD2): 248 kg m2
ma =
x 1090 r/min
ax
280

HCMP
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 0 1000 2000 3000 4000 5000 6000 7000
9000 11 000
1
2
8000 016 10 000
nm 020
1 ax =
65 3
7000 nm 2 00
ax = r /m
62 i
0 60
6000 60 0 r/m 3 00
n

00 4
in
5000
4 5
Total pressure rise, Pa
Total pressure rise, Pa

500
500 5000 0
4000 0
5

3000 400 400


0 0

2000
300 3000
0 10
10
1000 200 200
0 0
0 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 0 0.5 1.0 1.5 2.0

0 2000 0 2000 3
3000 Gas flow, m3/s Gas flow, m /s
3000

1 4000
Power demand, kW

4000
Power demand, kW

2 5
5000
5000

6000
4 10
6000
n
ma = n
x 6 2 00 m ax =
r/min
6500 r/min
5 tmax = 200C nmax = 6500 r/min
nmax is not temperature dependent tmax = 350C nmax = 5500 r/min
J (= 1/4 GD2): 0.056 kg m2 J (= 1/4 GD2): 0.09 kg m2
6 15
Fan charts - Belt-driven fans Page 71

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMP
Gas flow, m3/h Gas flow, m3/h
0 2000 4000 6000 8000 10 000 0 5000 10 000 15 000
10 000
1 2 2
7000 n 3
n
ma
x = 3 025 1
ma
380 x = 3 4
031
0 9 00
57 r /m
0 0 6000
r/ in
5
m
in
50 4 5000
00

300
5 4000 0

Total pressure rise, Pa


Total pressure rise, Pa

5000
400
0 3000

3000 2000 2000 10


10
2000 1000
150
0
0 0
0 0.5 1.0 1.5 2.0 2.5 3.0 0 1 2 3 4

0 1500 0
2000 Gas flow, m3/s Gas flow, m3/s

3000 2000

Power demand, kW
Power demand, kW

5
4000
10
3000

10

0
500

20
15 nmax, r/min
tmax = 200C nmax = 5700 r/min 200C: 3900 n 3800
ma
tmax = 350C nmax = 4800 r/min n 350C: 3700 x = 39 0
0 r/min
ma =
J (= 1/4 GD2): 0.17 kg m2 x 5700 r/min J (= 1/4 GD2): 0.43 kg m2
19 27

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 0 10 000 20 000 30 000 40 000
7000 8000
n 3 2 n
1 ma ma 3
6000
2 x =
30
00 4
040 7000
1 x =
25 050
r 20 4
/m 24 r/m
in 00 in
5 6000
5000 5

5000
4000 200
0
Total pressure rise, Pa

Total pressure rise, Pa

4000
3000 2000
3000
2000 10
2000 10

1000 1000
1000 1000

0 0
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 10 11 12
0 1000 3/s 0
Gas flow, m 1000 Gas flow, m3/s

10
Power demand, kW

Power demand, kW

10 2000
20

30
2000
20
40

50
nmax, r/min
30 nmax, r/min
< 100C: 2520
< 200C: 3000 n 200C: 2330 2400
350C: 2700 ma 60
x =3 350C: 2050 n
J (= 1/4 GD2): 1.06 kg m2 000 ma
r/min J (= 1/4 GD2): 2.8 kg m2 x = 252
0 r/min
70
Fan charts - Belt-driven fans Page 72

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

Boundary between HCMP with impeller diameter 1000 mm


HCMP and HCMP with impeller diameter >1000 mm

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 30 000 40 000 50 000 60 000 0 50 000 90 000
8000
2 n 3 2
ma 9000 n
7000
1 x =
20 4
063 1
ma
x =1
3
071
00 8000 90 4
r/m 0r
in 18 /m
00 in
6000 5 5
7000

5000 6000 160


0

5000

Total pressure rise, Pa


Total pressure rise, Pa

4000 140
0
4000
3000 1200
3000
1000 10 1000
2000 10
2000
800
1000 600
1000

0 0
0 5 10 15 0 5 10 15 20 25

0 0 600 3/s
Gas flow, m3/s 800 Gas flow, m
10 1000 1000

Power demand, kW
Power demand, kW

20
1200
30
50
40 1400

50

60 1600
100
70

80
0
90
nmax, r/min nmax, r/min 180
< 200C: 2000 < 200C: 1900 n
350C: 1750 n 150 ma
100 ma 350C: 1480 x = 19
J (= 1/4 GD2): 8.6 kg m2 x = 20 00 r/min
00 r/min J (= 1/4 GD2): 16 kg m2
110 170

Gas flow, m3/h Gas flow, m3/h


0 50 000 100 000 0 50 000 100 000 140 000
9000
2 n 2 n
ma 3 9000 ma 3
8000
1 x =
16 080 1
x =
15
40
090
16 90 4 8000 15 4
00 r/m 00 r/m
7000 in in
14
5 00
7000 5
6000 14
00 6000
5000 120
0
5000
Total pressure rise, Pa

Total pressure rise, Pa

120
4000 0
4000 100
0
3000 100
0
3000
10 800 10
2000 800
2000
600 600
1000 1000

0 0
0 10 20 30 0 10 20 30 40
0 0
600 Gas flow, m 3/s 600 Gas flow, m3/s
800
800
1000
Power demand, kW

Power demand, kW

50 1000
1200 100

1200
100
1400

150 200 1400


nmax, r/min nmax, r/min
< 100C: 1690 1600 < 100C: 1540
200C: 1560 n 200C: 1430 n 1500
ma ma
350C: 1270 x = 1690 350C: 1140 x = 15
r/min 40 r/min
200 J (= 1/4 GD2): 25 kg m2 J (= 1/4 GD2): 45 kg m2
300
Fan charts - Belt-driven fans Page 73

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMP
Gas flow, m3/h Gas flow, m3/h
0 50 000 100 000 150 000 0 100 000 200 000
2 3 2
8000 n 10 000 n 3
1 ma
x =
13 4
100 1 ma
x = 112
0 0r 9000 1 28 4
7000 /m 12 0r
120 in 00 /m
0 5 8000 in 5
6000
7000
5000 100 6000 100
0 0

Total pressure rise, Pa


Total pressure rise, Pa

4000 5000

800 4000 800


3000
3000 10
10
2000 600 600
2000
1000 400 400
1000

0 0
0 10 20 30 40 0 10 20 30 40 50 60

0 400 0 400
Gas flow, m3/s Gas flow, m3/s
600 600

Power demand, kW
Power demand, kW

800 100 800

100
200
1000
1000

300
200

1200 nmax, r/min


nmax, r/min < 100C: 1280
400 1200
< 100C: 1300 200C: 1190
200C: 1200 n 350C: 920 n
ma ma =
350C: 1050 x =1 J (= 1/4 GD2): 155 kg m2 x 1280
300 r/min r/min
300 J (= 1/4 GD2): 76 kg m2 500 Max. fan power = 300 kW

Gas flow, m3/h


0 100 000 200 000 300 000
10 000 2 n
ma 3
9000 x
11 = 11
00 20
125
1 r/m 4
8000 in
10 5
00
7000

6000
Total pressure rise, Pa

5000 800

4000

3000 600
10
2000
400
1000

0
0 10 20 30 40 50 60 70 80
0
400 Gas flow, m3/s

600
100
Power demand, kW

200 800

300

400 0
100
nmax, r/min
< 100C: 1120
500 200C: 1040
350C: 850
0
J (= 1/4 GD2): 247 kg m2 110
600 Max. fan power = 250 kW nmax = 1120 r/min
Fan charts - Belt-driven fans Page 74

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMT
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 3000 3600 0 2000 4000 6000
4800 4800
2 2 3
1 n
ma
3
016 1 n
4 020
x = ma
4000 48 4 4000 x =4 5
3 30
48 0 r/ 0r
00 m i 5 /m
n 400 in
0
3000 3000
40
00

Total pressure rise, Pa


Total pressure rise, Pa

2000 2000 300


0
10
300
0
10
1000 1000 2000
2000

0 0
0 0.2 0.4 0.6 0.8 1.0 0 1 1.75

0 0
2000 Gas flow, m3/s 2000 Gas flow, m3/s

Power demand, kW
Power demand, kW

1 3000 2

300
0
2 4

400
3 0
6

4
8 n 40
n ma 00
ma x =
x = 4
48 48 30
30 00 0r
5 n r/m nmax is not temperature dependent /m
max is not temperature dependent in in
J (= 1/4 GD2): 0.038 kg m2 10 J (= 1/4 GD2): 0.068 kg m2
5.6

Gas flow, m3/h Gas flow, m3/h


0 2000 4000 6000 8000 10 000 0 2000 4000 6000 8000 10 000 12 000 14 000 16 000
4600 4600
2 3 2
3
4
4000
1 n
ma
4
5
025 4000
1
5
031
x =3 n
840 ma
38 r/m x =3
00 in 05
0r
30 /
00 min
3000 3000 28
00
26
300 00
Total pressure rise, Pa

Total pressure rise, Pa

0 240
2000 0
2000 220
10 1
0
200
0
180
2000 0
1000 1600
1000
1400
1400 120
1000 0

0 0
0 1.0 2.0 2.9 0 1 2 3 4 4.6
0 0 1000
1400 Gas flow, m3/s 1200 Gas flow, m3/s
1400
2000 1600
5 1800
Power demand, kW

Power demand, kW

2000

10 220
0
300 24
0 00
15
10
26
00
20
n 28
n ma 00
m
ax x =
= 25 30
38 50
40 38 30
r/m 00 r/ 00
18 nmax is not2temperature2dependent in nmax is not temperature dependent
m

J (= 1/4 GD ): 0.11 kg m 30 J (= 1/4 GD2): 0.373 kg m2


i

31
Fan charts - Belt-driven fans Page 75

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCMT
Gas flow, m3/h Gas flow, m3/h
0 10 000 20 000 0 10 000 20 000 30 000 40 000
4600 4800
3 4 2 3

4000
1 2 n
ma
x =2 5 040 1 n
4
5
050
ma
42 4000 x =1
0 92
24 r/min 190 0 r/m
00 0 in
220
3000 0
3000
200
0

Total pressure rise, Pa


Total pressure rise, Pa

150
180 0
2000 0
2000 10
160 10
0
1400
1200 100
1000 1000 0
1000
800 700

0 0
0 1 2 3 4 5 6 7 0 5 10 11.5

0 800 0 700
1000 Gas flow, m3/s Gas flow, m3/s
1200 1000
10
1400

Power demand, kW
Power demand, kW

10
160 20
0

180 30
0 150
20 0
200 40
0

30 50
22
00
n 60 n
ma ma
40 x = x =
24 2 19 19
20 400 70 20 0
nmax is not temperature dependent r/ m nmax is not temperature dependent r/m 0
in in
J (= 1/4 GD2): 1.05 kg m2 J (= 1/4 GD2): 3.43 kg m2
50 80

Gas flow, m3/h


0 10 000 20 000 30 000 40 000 50 000 60 000
4800
2
1 3 4
n 5 063
ma
4000 x =1
53
150 0 r/
0 mi
n
14
00
3000
130
0
120
Total pressure rise, Pa

0
2000 110
0
100 10
0
900
800
1000
700
600

0
0 5 10 15 18

0
600 Gas flow, m3/s
800
20 900
Power demand, kW

100
0
40 110
0
120
0
60
13
00
80
14
00
n
100 ma
x =
15 15
00 00
nmax is not temperature dependent r/m
120 J (= 1/4 GD2): 7.73 kg m2
in
Fan charts - Belt-driven fans Page 76

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHB
Gas flow, m3/h Gas flow, m3/h
0 1000 2000 0 1000 2000 3000

14 000 1 14 000 1 2
2 3
3 010 n
ma
012
12 000 12 000 x =5
n 7 00
ma r/ m 4
x = 4 550 in
63 0
00
10 000 r/m 10 000
60 in 5 500 5
00 0
8000 55 8000
00 450

Total pressure rise, Pa


Total pressure rise, Pa

0
50
00 400
6000 6000 0
450
0 350
400 0
4000 0 4000
350 300
0 0
300 2500 10
0 10
2000 2500 2000 2000
2000

0 0
0 0.1 0.2 0.3 0.4 0.5 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9

0 2000 0 2000 3/s


2500 Gas flow, m3/s Gas flow, m
2500
3000
3000
1 3500

Power demand, kW
Power demand, kW

2 3500
4000
2 4000
4500
4
3 4500
5000

4 6
5500 5000

5
8
6000
6 n nm = 5500
max is not temperature dependent ax 6300 nmax is not temperature dependent nm =
r/ min ax 5700 r/
J (= 1/4 GD2): 0.138 kg m2 10 J (= 1/4 GD2): 0.222 kg m2 min

Gas flow, m3/h Gas flow, m3/h


0 1000 2000 3000 4000 5000 0 5000 9000
14 000 1 12 000 1 2 3
2
3 016 n
ma
x = 4
020
12 000 n 45
ma 4 00
x =5 10 000 44 r/m
10 5 0 in
0r 42 0 5
50 / 00
10 000 00 min 40
8000 00
45 38
00 00
8000 36
00
Total pressure rise, Pa

Total pressure rise, Pa

6000 34
40 0
00 32 0
6000 0
300 0
350 280 0
0 4000
26 0
4000 300
0 24 00 10
10 220 00
250 200 0
0 2000 0
2000 200
0
1500
0 0
0 0.5 1 1.5 0 1 2 2.5

0 1500 0
2000 Gas flow, m 3/s
2000 Gas flow, m3/s
2500 2200
2 2400
3000 2600
Power demand, kW

Power demand, kW

2800
4 3000
3500
3200
6
3400
4000 10 3600
8
3800
10 4500
4000

12 4200

14 nmax is not temperature dependent 5000 nmax is not temperature dependent 4400
J (= 1/4 GD2): 0.355 kg m2 20 J (= 1/4 GD2): 0.613 kg m2 nm =
nmax = 5100 r/min ax 4500
r/min
Fan charts - Belt-driven fans Page 77

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHB
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 13000 0 5000 10 000 15 000 20 000
12 000
2 2
nm 3
n
ma
3
025 10 000 1
ax =
33
4 031
1 380 x = 39 4
320 20
10 000 0 00 0 r/m
r /m in
360 in 5
0 8000 300
0 5
340
8000 0 280
320 0
0 260
300 6000 0

Total pressure rise, Pa


0
Total pressure rise, Pa

6000 280 240


0 0
260 2200
0
2400 4000 2000
4000
2200 1800
2000 10 10
1600
1800
1600 2000 1400
2000 1200
1400
1000

0 0
0 1 2 3 3.8 0 1 2 3 4 5

0 0 1000
1400 Gas flow, m3/s Gas flow, m3/s
1600 1400
1800 1600
2000 1800
2200
2000

Power demand, kW
Power demand, kW

2400
2200
2600 10
10 2800 2400

3000 0
260
3200 0
20 280
0
340
00
20 30
0
360
00
30 32
0
nmax is not temperature dependent 380 nmax is not temperature dependent n
2 2 nmax = 3900 r/min J (= 1/4 GD2): 1.7 kg m2 max = 3320 r/min
28 J (= 1/4 GD ): 1 kg m
36

Boundary between HCHB with impeller diameter 1000 mm


and HCHB with impeller diameter >1000 mm

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 30 000 0 10 000 20 000 30 000 40 000
2n 1 2 n
1 ma 3 ma 3
10 000 x =3
00 040 10 000 x =
23 050
0r 4 90 4
/m r/m
280 in 220 in
0 0
8000 5 8000
260 5
0 200
0
240
0
6000 6000 180
220 0
Total pressure rise, Pa

Total pressure rise, Pa

0
200 160
0 0
4000 180 4000
0 140
0
1600
1200
1400 10 10
2000 1200 2000 1000
1000 800

0 0
0 2 4 6 8 0 2 4 6 8 10 12
0 1000 0
Gas flow, m3/s 1000 Gas flow, m3/s
1400 1200
1600
10 1800 1400
Power demand, kW

Power demand, kW

20
2000 1600
0
20 220 180
0
0
240 40
0
30 200
00
26

60 00
22
00
40 28

nmax is not temperature in


50 dependent n 80 r/m
max = 3000 r/min nmax is not temperature dependent nm = 2390
J (= 1/4 GD2): 2.93 kg m2 J (= 1/4 GD2): 8.96 kg m2 ax
Fan charts - Belt-driven fans Page 78

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHB
Gas flow, m3/h Gas flow, m3/h
0 20 000 40 000 60 000 0 50 000 80 000
2n 2 n
1 ma 3 1 ma 3
10 000 x =1
90 063 10 000 x =
16 071
0r 90 4
180 4 16 r/m
0 /m 00
in in
170 150 5
8000 0 8000 0
5
160 140
0 0
150 130
0
6000 6000 0
140

Total pressure rise, Pa


Total pressure rise, Pa

0 120
130 0
0 110
120 0
4000 0 4000 100
110 0
0 900
1000
900 800 10
10
2000 800 2000 700
700 600
600 500

0 0
0 10 20 0 10 20

0 0 500
800 Gas flow, m3/s Gas flow, m3/s
900 800
1000
900
20 1100 1000

Power demand, kW
Power demand, kW

1200 1100
40 1300 50 0
0 120
140 0
0 130
60 150
00
00 14
16
80 100
00
00 15
17
100 00
00
18 16

120 nmax is not temperature 150 nmax is not temperature


dependent n
dependent in /mi
J (= 1/4 GD2): 24.4 kg m2 nm = 1900 r/m J (= 1/4 GD2): 44 kg m2 nm = 1690 r
ax 170 ax
140

Gas flow, m3/h Gas flow, m3/h


0 20 000 40 000 60 000 80 000 100 000 120 000 0 50 000 100 000 150 000
11 000
2 n 2n
3 ma
1 ma x =1 3
10 000 x =
15 080 10 000 1
130 34
0r
090
00 4 0 /m
140 r/m in 4
0 in 12
8000 00
8000 13 5
00 5
110
120 0
0
6000 6000 100
110 0
Total pressure rise, Pa
Total pressure rise, Pa

0
100 900
0
4000 900 4000 800
800 700
700 10 600 10
2000 600 2000
500
500 400

0 0
0 10 20 30 0 10 20 30 40

0 500 0 400
Gas flow, m3/s Gas flow, m3/s
600
700
800 700
800
Power demand, kW
Power demand, kW

900
1000 900
0
110 100 100
0

0
100 120 0
110
0
130
00
12
00 200
14
00
nmax is not temperature 13
nmax is not temperature dependent
in in
200 dependent r/ m J (= 1/4 GD2): 147 kg m2 r/m
J (= 1/4 GD2): 75 kg m2 nm = 1500 nm = 1340
ax
ax Max. fan power = 250 kW
280
Fan charts - Belt-driven fans Page 79

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHB
Gas flow, m3/h
0 50 000 100 000 150 000 190 000
11 000
2 n
ma 3
10 000 1 x=
12
00
100
r/m 4
110 in
0
8000 5
100
0

6000 900
Total pressure rise, Pa

800
4000 700
600
10
2000 500
400

0
0 10 20 30 40 50

0 400
Gas flow, m3/s
600
700
Power demand, kW

800
100

900

00
10
200

00
11

nmax is not temperature


300 dependent
in
J (= 1/4 GD2): 234 kg m2 r/m
nm = 1200
Max. fan power = 300 kW ax

HCHP
Gas flow, m3/h Gas flow, m3/h
0 5000 10 000 14 000 0 10 000 20 000
10 000 10 000
2 2
n
ma
3 nm 3
1
1 x =3
48 4
025 ax = 3
10 0
4 031
34 0 r/ r/m 5
00 mi 300 in
8000 n 5 8000 0
32 280
00
0
30
00 260
6000 6000 0
280
0 240
0
Total pressure rise, Pa
Total pressure rise, Pa

260
0 220
240 0
4000 0 4000 2000
220 10
0 10 1800
200
0
1800 1600
2000 1600 2000 1400
140 1200
1200 0 1000

0 0
0 1 2 3 4 0 1 2 3 4 5 6

0 1200 0 1000
Gas flow, m3/s 1200 Gas flow, m3/s
1600
2000 1800
Power demand, kW
Power demand, kW

2200 10
2000
2400
10 2200
2600
20
2400
2800

2600
3000
30
20

3200 2800

40 nmax, r/min
< 200C: 3100
n 3400 3000
max = 350C: 2950
nmax is not temperature dependent 348
30 J (= 1/4 GD2): 0.92 kg m2 0 r/m J (= 1/4 GD2): 1.6 kg m2 nmax = 3100 r/min
in 50
Fan charts - Belt-driven fans Page 80

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHP Boundary between HCHP with impeller diameter 1000 mm


and HCHP with impeller diameter >1000 mm

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 30 000 36 000 0 10 000 20 000 30 000 40 000 50 000
10 000 10 000
3 nm 4
1 2 4 1 ax =
n
ma
x =2 040 2 22
00 5 050
77 5 3 r/m
260 0r in
8000 /m 8000
0 in 200
0
240
0
180
6000 220 6000 0
0

Total pressure rise, Pa


Total pressure rise, Pa

200 160
0 0

4000 180 4000 1400


0 10
1600 10 1200
1400
2000 1000
2000 1200
1000 800
800 600

0 0
0 2 4 6 8 10 0 5 10 15

0 0 600
1000 Gas flow, m3/s Gas flow, m3/s
1000
1400 1200
10
1600

Power demand, kW
Power demand, kW

1400
20 1800

2000 1600
30 50
2200
40 1800

2400
50
2000
60 2600
nmax, r/min 100 nmax is not temperature
< 200C: 2770 dependent
70 350C: 2540 J (= 1/4 GD2): 8.1 kg m2
J (= 1/4 GD2): 2.7 kg m2 120 Max. fan power = 100 kW nmax = 2200 r/min
nmax = 2770 r/min
80

Gas flow, m3/h Gas flow, m3/h


0 20 000 40 000 60 000 80 000 0 50 000 100 000
10 000
nm 4 2 3
ax = 10 000
1
2
1
170 745 r 5 063 1 n
ma
x =1
4 071
3 0 /m 55 5
in 150 5r
8000 0 / mi
160 8000 n
0 140
150 0
0
140 130
6000 0
0 6000
130 120
0 0
Total pressure rise, Pa

Total pressure rise, Pa

120 110
0 0
4000 110 4000 100
0 10 0
1000 10
900
900 800
800
2000 2000 700
700 600
600
500

0 0
0 10 20 0 10 20 30
0 600 0
Gas flow, m3/s 600 Gas flow, m3/s
800
800
1000 900
Power demand, kW

Power demand, kW

1100 1000
50
1200 1100
1300 100
1200
1400
100
1300
1500

1400
1600
150
nmax, r/min 200 nmax, r/min
< 200C: 1745 < 200C: 1555 1500
350C: 1525 1700 350C: 1450
J (= 1/4 GD2): 22.8 kg m2 nmax = 1745 r/min J (= 1/4 GD2): 41 kg m2
190 nmax = 1555 r/min
Fan charts - Belt-driven fans Page 81

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHP
Gas flow, m3/h Gas flow, m3/h
0 40 000 80 000 120 000 0 40 000 80 000 120 000 160 000
2 3 2 3
10 000 nm 10 000 nm 4
1 ax =
138
4 080 ax =
12 090
5r
/m 5 1 12 35 r/m 5
in 00 in
8000 130 8000
0
110
120 0
0
100
6000 110 6000 0
0
Total pressure rise, Pa

Total pressure rise, Pa


100 900
0
4000 900 4000 800
10 10
800 700
700 600
2000 600 2000 500
500 400
400

0 0
0 10 20 30 40 0 10 20 30 40 50

0 400 0 400
600 Gas flow, m3/s Gas flow, m 3/s

600
700
800 700
Power demand, kW

Power demand, kW
900 800
100
100 1000 900

1100
200 1000

1200
200 1100

nmax, r/min 300 nmax, r/min


< 200C: 1385 1300 < 200C: 1235
350C: 1200 350C: 1100
1200
J (= 1/4 GD2): 70 kg m2 J (= 1/4 GD2): 138 kg m2
300 Max. fan power = 230 kW nmax = 1385 r/min Max. fan power = 250 kW nmax = 1235 r/min
380

Gas flow, m3/h


0 50 000 100 000 150 000 200 000
2 3
10 000 nm
1 ax =
11
4 100
00 5
r/m
in
8000
100
0

900
6000
Total pressure rise, Pa

800

4000 700
10
600

2000 500
400

0
0 10 20 30 40 50 60

0 400 Gas flow, m3/s


500
600
Power demand, kW

100
700

800
200

900

300

1000
nmax, r/min
< 200C: 1100
400
350C: 940
J (= 1/4 GD2): 220 kg m2
nmax = 1100 r/min
Max. fan power = 250 kW
Fan charts - Belt-driven fans Page 82

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHT
Gas flow, m3/h Gas flow, m3/h
0 500 1000 1500 0 1000 2000 3000
12 000
1 1

10 000 2 010 2
3
012
n 3 10 000
n
ma ma 4
x =5 x =5
80 4 30
8000 0r 0r
/m /m 5
in 8000 50 in
55 00
00 5
6
6000 50 450
Total pressure rise, Pa

Total pressure rise, Pa


00 6000 0
6
450 400
0 0
4000 400 350
0 4000 0
350 300
0 0
300 10
2000 0 2500
2500 10 2000
2000 2000

0 0
0 0.1 0.2 0.3 0.w4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8

0 0
2000 Gas flow, m 3/s 2000 Gas flow, m3/s
3000
3000
3500
Power demand, kW

Power demand, kW
2 3500
4000
5
450 400
0
0
4

500 45
0 00
10
6
55 n 55
00 ma 00
n x =
ma 53
x = 00
8 58 r/m
00 15 n in
nmax is not temperature dependent r /m max is not temperature dependent
J (= 1/4 GD2): 0.1 kg m2 in J (= 1/4 GD2): 0.17 kg m2

Gas flow, m3/h Gas flow, m3/h


0 1000 2000 3000 4000 5000 0 1000 2000 3000 4000 5000 6000 7000 8000
12 000
1 2 2 3
8000
3
4
016 1 nm
ax = 3 4 020
10 000 n 60 0
max = 7000 r/m 5
473 in
0 340
460 r/min 5 0 6
0 6000
8000 440 6 320
0 0
420 300
0 5000 0
400
0 280
6000 380 0
Total pressure rise, Pa

Total pressure rise, Pa

0
360 4000 260
340 0 0
320 0 2400
4000 300 0 3000 2200
2800 0 2000 10
10 1800
2400 2000
1600
2000 2000 1400
1000

0 0
0 0.5 1.0 1.5 0 1 2
0 0
2000 Gas flow, m3/s 1400 Gas flow, m3/s
2000
Power demand, kW

Power demand, kW

3000
240
3200 0
260
10 10 0
360 280
0 0
380
0
400 30
0 00
42
0 0 32
20 00
20 44 n
00
m
n ax 34
ma =
x = 46
00 36 00
47 00
30 r/m
nmax is not temperature dependent r/m nmax is not temperature dependent in
in
2
28 J (= 1/4 GD ): 0.28 kg m
2 J (= 1/4 GD2): 0.45 kg m2
30
Fan charts - Belt-driven fans Page 83

The charts are valid for gas at a density of 1.2 kg/m3. Optimum working ranges are shaded in grey.

HCHT
Gas flow, m3/h Gas flow, m3/h
0 2000 4000 6000 8000 10 000 12 000 0 10 000 20 000
8000
2 3
7000 nm 3 4 n 4
1
ax = 30
25
r/m
025 7000
1
2
max =
280 5 031
300 in 5 0r
0 /m
6000 260 in
280 6 0 6
0 6000

5000 260 240


0 0
5000
240 220
0 0
4000
Total pressure rise, Pa

Total pressure rise, Pa


220 4000 2000
0
3000 2000 9 1800
3000 10
1800 10 1600
2000 1600 1400
2000
1400
1200
1200
1000 1000 1000
1000

0 0
0 1 2 3 0 1 2 3 4 5

0 1000 3/s
0 1000
Gas flow, m Gas flow, m3/s
1400
1600
10 1600
Power demand, kW

Power demand, kW
1800
1800
2000
10
20 200
0
2200
220
2400 0
30

20 240
2600 0
40

260
280 n 0
n 0 ma
ma 50 x =
30 x = 28
30 0 0r
nmax is not temperature dependent 25 30 nmax is not temperature dependent /m
r /m 00 in
J (= 1/4 GD2): 0.87 kg m2 i 60 J (= 1/4 GD2): 1.6 kg m2
36

Gas flow, m3/h Gas flow, m3/h


0 10 000 20 000 30 000 0 10 000 20 000 30 000 40 000 50 000

nm 4 nm
7000
1
2
ax =
240
0r
040 7000 1
2
ax = 1
900
4
050
/m 3 r/m 5
3 in 5 180 in
6000 6000 0
220 6
0 6 170
0
5000 200 5000 160
0 0
150
4000 180 4000 0
0
Total pressure rise, Pa

140
Total pressure rise, Pa

9 0
1600 130
3000 0
3000 1200
10
1400 1100 10
2000 1200 2000 1000
1000 800
1000 800 1000 600

0 0
0 1 2 3 4 5 6 7 8 9 0 5 10
0 0 600
1000 Gas flow, m3/s 800 Gas flow, m3/s
1000
1400
Power demand, kW

Power demand, kW

1200
20
1600 130
0
140
180 50 0
0
150
40 0
200 160
0 0
17
00
60
n 22 n
m 00 100 ma
ax
= x = 18
24 19 00
00 00
r/m nmax is not temperature dependent
nmax is not temperature dependent J (= 1/4 GD2): 7.3 kg m2 r/m
in in
80 J (= 1/4 GD2): 2.9 kg m2 130 Max. fan power = 95 kW
Belt-driven fans with impeller diameter > 1000 mm Page 84
Ordering key - Belt-driven fans with impeller diameter > 1000 mm Page 85

HCGB
HCLP
HCMx
HCH x-aaa-bb-cc-dd-ee-fff

Impeller
B = Backward-curved blades
P = Flat, backward-inclined blades.

Size (aaa)

Components included in delivery (bb)


02 = Fan only. Steel base frame and anti-vibration mountings are not included.
03 = Fan mounted on steel base frame with anti-vibration mountings.
NB! For transport reasons, certain fans are delivered in ready to assemble units. Dimension prints for fitting
anti-vibration mountings are included. Where required, motor and belt drive for installation on the steel base
frame should be specified separately.

IEC motor size (cc)


00 = for code bb = 02.
03 = 80 10 = 160M 17 = 250M 24 = 355M
04 = 90S 11 = 160L 18 = 280S 25 = 355L
05 = 90L 12 = 180M 19 = 280M
06 = 100L 13 = 180L 20 = 315S
07 = 112M 14 = 200L 21 = 315M
08 = 132S 15 = 225S 22 = 315L
09 = 132M 16 = 225M 23 = 355S

Designations for rotation and discharge (dd)

11 0o 12 45o 13 90o 15 180o 17 270o 18 315o


Right *
(RD) W W Z Z W W

21 0o 22 45o 23 90o 25 180o


Right *
(RD) Z Z W W

61 0
o
62 45
o
63 90
o
65 180o 67 270
o
68 315
o

Left *
(LG) Z Z W W Z Z

71 0o 72 45o 73 90o 75 180o


Left * * Steel base frame not standard for the 180o discharge
(LG) W W Z Z
direction. Please contact Flkt Woods AB.

NB! The above diagrams show the drive side.


Ordering key - Belt-driven fans with impeller diameter > 1000 mm Page 86

HCGB
HCLP
HCMx
HCH x-aaa-bb-cc-dd-ee-fff

Fan version (ee)


01 = standard version.
02 = sparkproof version, (brass ring at the inlet and brass washers at the shaft inlet).

Material, finish 1) (fff)


001 = Standard material, GA80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.

002 = Standard material, GP40-01 int. and ext. Not fully welded Max. temperature 150oC. 2)

032 = Standard material, GA80TD80-RAL5007 int. and ext. Not fully welded Max. temperature 120oC.

072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.

112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.

300 = Parts in gas contact in SS 2333. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

315 = Parts in gas contact in SS 2333. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80TD80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

325 = Parts in gas contact in SS 2333. Other parts in 3)


Max. temperature 120oC.
standard material with GA80TD80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

335 = Parts in gas contact in SS 2333. Other parts in 3)


Max. temperature 120oC.
standard material with GA80TB80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

400 = Parts in gas contact in SS 2343. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

415 = Parts in gas contact in SS 2343. Other parts in Not fully welded Max. temperature 120oC.
standard material with GA80TD80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

425 = Parts in gas contact in SS 2343. Other parts in 3)


Max. temperature 120oC.
standard material with GA80TD80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

435 = Parts in gas contact in SS 2343. Other parts in 3)


Max. temperature 120oC.
standard material with GA80TB80-RAL 5007 finish.
NB! Shaft in standard material SS 2172.

1)
Removable contact guards around rotating parts are epoxy painted in a yellow warning colour, (80 ).

2)
GP40-01 primer can be used where temperatures exceed 120oC. This primer tolerates temperatures up to 150oC and vaporises at higher tempera
tures without emitting any toxic substances.

3)
Fully welded stand and, whenever applicable, fully welded steel base frame. NB! Parts in gas contact not fully welded.
Page 87
Ordering key - Accessories

Cooling disc (for operating temperatures above 100C) HCEZ-06-bb


Size: Refer to the "Cooling disc selection" table on page 99

Cleanout cover JCLB JLCB-a-b


Size
4 = standard, 8 = strengthened. For fan sizes 063 - 071.
5 = standard, 9 = strengthened. For fan sizes 080 - 160.
Material
1 = steel, (hot-dip galvanized).
4 = SS 2343 (not available for the strengthened version).

Speed monitor HCEZ-13-bb


Size: Refer to the "Speed monitor selection" table on page 99

Inlet taper piece with connecting flange HCEZ-21-bbb-ccc


Size (= fan size)
Material and finish: Refer to the fff code in the main fan ordering key

Counterflange, inlet, (not fitted) HCEZ-25-bbb-cc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.

Fabric duct, inlet, connecting flanges HCEZ-aa-bbb-ccc


Temp. class
45 = max. 70C.
46 = max. 200C.
47 = max. 350C.
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key

Flue gas duct, inlet, with connecting flanges 1) HCEZ-aa-bbb-ccc


Temp. class
65 = max. 200C.
66 = max. 350C.
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key
1)
NB! Wearing plate is only available in steel, primed or stainless steel qualities depending on choice of ccc code.

Protective screen, outlet HCEZ-30-bbb-ccc


Size (= fan size
Material and finish: Refer to the fff code in the main fan ordering key

Counterflange, outlet HCEZ-35-bbb-cc


Size (= fan size)
Material
01 = mild steel (unpainted) for welded connection.
03 = SS 2333.
04 = SS 2343.
Page 88
Ordering key - Accessories cont.

Fabric duct, outlet, with connecting flanges HCEZ-aa-bbb-ccc


Temp. class
50 = max. 70C.
51 = max. 200C.
52 = max. 350C.
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key

Flue gas duct, outlet, with connecting flanges 2) HCEZ-aa-bbb-ccc


Temp. class
70 = max. 200C.
71 = max. 350C.
Size (= fan size)
For material and finish, (flanges), refer to the fff code in the main fan ordering key
2)
NB! Wearing plate is only available in steel, primed or stainless steel qualities depending on choice of ccc code.

Regulating damper DMEG (see page 105)

Inlet vane control assembly HXEG (see pages 106 - 111).

Belt drive selection - Use either the HC selection program or contact Flkt Woods AB.
Description - Accessories, inlet and outlet Page 89

7 1

8, 9

10
2, 3
1

4, 5
6
Duc
t

2, 3
4, 5
6

NB! Flanges comply with ISO 13351

Inlet
1 HCEZ-21 Inlet taper piece with protective screen and flange for connection to inlet flange.
(Pressure loss across the accessory, 0.35 x dyn. press. pd).
2 HXEG Inlet vane control assembly, see pages 106-111. 1)
3 DMEG Regulating damper, see page 105. 1)
4 HCEZ-45, 46, 47 Fabric duct, inlet with connecting flanges. 2)
5 HCEZ-65, 66 Flue gas duct, inlet with connecting flanges. 2)
6 HCEZ-25 Counterflange, inlet, (not fitted).

Outlet
7 HCEZ-35 Counterflange, outlet, (not fitted).
8 HCEZ-50, 51, 52 Fibre duct, outlet, with connecting flanges. 2)
9 HCEZ-70, 71 Flue gas duct, outlet with connecting flanges. 2)
10 HCEZ-30 Protective screen, outlet.

1) NB! Inlet vane assemblies/regulating dampers must not be connected directly to the fan without checking that
the anti-vibration mountings can cope with the increased component load on the fan.
2) For size and temperature limits, please refer to the appropriate ordering keys.
Sound data Page 90

Symbols Formulae:
Lwtot = total sound power level for the relevant sound Lwtot = Lwtoto + K1 + K2 + K3
path and appropriate throttling curve...................... dB
Lwtot = total sound power level to inlet or outlet duct when For division into octave bands, use the formula:
o
the fan is operating on the throttling curve giving Lw = Lwtot + Kok
the lowest sound power level.................................. dB
Lw = Lwtot divided into octave bands .............dB (ref. 10-12 W) Sound paths: a = to inlet or outlet duct.
b = to surroundings (free-inlet fan).
K1 = corr. for diff. throttling curves and sound paths....... dB
c = to surroundings (duct-connected fan).
K2, K3 = correction for different sound paths........................ dB
Kok = approximate deviation from Lwtot NB! The stated values refer to sound power levels. Some fan manufac-
for the particular octave band................................. dB turers still quote sound pressure levels even though these vary with the
acoustic characteristics of the surroundings and distance from the fan.
L = throttling curve = 10 pd/Dpt Sound pressure levels, sometimes weighted as dB(A) or dB(C) values,
Dp
t = total pressure rise................................................... Pa are considerably lower than the corresponding sound power level Lwt.

HCGB - Total sound power level Lwtot


o
Approx. deviation Kok in L = 2-5 working range, correction K3 for
Gas flow, m /h 3

2 5 10 20 50 100 200 300 x 103 sound paths a, b and c.


130
Sound Speed Kok, dB

a path range K3 Octave band, mid-frequency, Hz


120
0P
c

e 300 r/min dB 63 125 250 500 1000 2000 4000 8000


i s
er
sur 200
0 300-2300 0 -3 -6 -9 -12 -16 -23 -28 -33
res
Lwtoto, dB

110 l p
o t a a 2300-4700 0 -4 -9 -10 -6 -14 -18 -23 -23
T 0 800
c

100 4700-5700 0 -5 -10 -11 -10 -6 -13 -17 -20


c

00
600 4
c

100
c

300-2300 -3 -4 -5 -7 -11 -13 -21 -26 -33


200
c

b 2300-4700 -3 -3 -9 -10 -6 -12 -16 -21 -23


90 4700-5700 -2 -5 -11 -12 -11 -5 -12 -16 -21
0.5 1 2 4 10 20 40 60 100
Gas flow, m3/s
300-2300 -2 -5 -5 -7 -12 -14 -22 -29 -36
Correction K1 Correction K2 c 2300-4700 +1 -3 -8 -9 -10 -15 -21 -27 -29
4700-5700 -1 -6 -8 -12 -12 -5 -14 -19 -24
K2, dB
K1, dB

1.5 +5
c a Sound paths: a = to inlet or outlet duct.
1.0 b, 0
a, b b = to surroundings (free-inlet fan).
0.5 -5
0 -10 c c = to surroundings (duct-connected fan).
2 3 4 5 0 1000 2000 3000
L Dpt, Pa

HC(M,H)B Type B impeller (for HCGB see above)


Total sound power level Lwtot
o
Approx. deviation Kok in L = 2-5 working range, correction K3 for
Gas flow, m /h 3
sound paths a, b and c.
2 5 10 20 50 100 200 x 103
130
Sound Speed Kok, dB
P aI
120 12 000 path range K3 Octave band, mid-frequency, Hz
r ise r/min dB 63 125 250 500 1000 2000 4000 8000
s s ure
l pre 0 6000 300-1175 0 -4 -4 -8 -15 -17 -19 -22 -28
Tota
c

800
Lwtoto, dB

110 a 1175-2300 0 -6 -6 -5 -11 -13 -15 -18 -21


0
400 200
0
c
c
2300-4700 0 -8 -8 -7 -6 -9 -13 -12 -17
4700-6300 0 -10 -9 -8 -8 -6 -10 -12 -14
100 0 800
c

100
c

600 400 300-1175 -2 -6 -4 -7 -14 -14 -18 -21 -30


c
c

b 1175-2300 -2 -8 -6 -4 -11 -12 -14 -17 -22


90 2300-4700 -3 -7 -8 -8 -6 -8 -12 -14 -17
0.5 1 2 4 10 20 40 60
4700-6300 -2 -10 -10 -9 -8 -5 -9 -11 -15
Gas flow, m3/s

Correction K1 Correction K2 300-1175 -2 -7 -3 -6 -15 -15 -18 -23 -31


c 1175-2300 -1 -9 -6 -4 -11 -12 -15 -20 -25
2 5 2300-4700 -1 -9 -5 -8 -8 -8 -14 -17 -21
a
K1, dB

K2, dB

0 4700-6300 -1 -11 -7 -9 -10 -5 -11 -14 -18


c b
1 b, -5
a, c Sound paths: a = to inlet or outlet duct.
-10
b = to surroundings (free-inlet fan).
0 -15
2 3 4 5 4000 8000 12 000 c = to surroundings (duct-connected fan).
L Dpt, Pa
Sound data, cont. Page 91

HC(L,M,H)P - Type P impeller


Total sound power level Lwtot
o
Approx. deviation Kok in L = 2-5 working range, correction K3 for
Gas flow, m3/h sound paths a, b and c.
2 5 10 20 50 100 200 x 103
130 Sound Speed Kok, dB
I
Pa
000 path range K3 Octave band, mid-frequency, Hz
12
120 e rise 0 r/min dB 63 125 250 500 1000 2000 4000 8000
u r 600
c

ess 000
l pr
c

a 8 300-1175 0 -10 -3 -7 -10 -13 -18 -21 -26


To t 0 0
Lwtoto, dB

400 200 a 1175-2300 0 -10 -7 -4 -8 -10 -15 -18 -23


c c

110
2300-4700 0 -9 -8 -7 -5 -9 -13 -16 -21
800
c

0 4700-6500 0 -10 -9 -8 -8 -6 -10 -12 -15


100
c

400
c

100 600
c

300-1175 -3 -9 -4 -8 -9 -9 -14 -18 -23


b 1175-2300 -2 -10 -8 -6 -8 -7 -12 -15 -21
90 2300-4700 -2 -7 -6 -10 -8 -9 -10 -13 -19
0.5 1 2 4 10 20 40 60 4700-6500 -1 -9 -8 -12 -9 -7 -8 -10 -14
Gas flow, m3/s
300-1175 -4 -10 -5 -7 -8 -8 -14 -17 -22
c 1175-2300 -3 -10 -9 -6 -7 -7 -12 -15 -20
Correction K1 Correction K2
2300-4700 -2 -9 -5 -12 -6 -10 -11 -14 -19
4700-6500 -2 -10 -7 -13 -9 -7 -8 -10 -13
2 5
a
K1, dB

K2, dB

0
b,c Sound paths: a = to inlet or outlet duct.
1 a, -5 b
b = to surroundings (free-inlet fan).
c
-10 c = to surroundings (duct-connected fan).
0 -15
2 3 4 5 4000 8000 12 000
L Dpt, Pa
Dimensions and weights - Fan Page 92

L1

B The sketches show a right-hand model.


E
C

D3*
A

F2 L2 H2 * Minimum permitted pulley diameter


F1 D1 = D3 (refer to tables on page 94).

H1
D2 j6

K2 K1

6 holes 25 2 x T3 T1 T2 Y2 holes 25 Dimensions and casing divisions S2

S1 N2
Designations M2
N1
for rotation and
discharge dd = M1
11, 61, 12, 62, V V Y1 x V3 V4
13, 63, 17, 67, 1 2
18, 68, 21, 71,
22, 72, 23, 73
U1 P2
U2 P1
T4

6 holes 25 2 x T3 T1 T2 Y2 holes 25 U U
dd = 11 (0o) = Right-hand model dd = 12 (45o)
o o
dd = 61 (0 ) = Left-hand model dd = 62 (45 )
Designations
for rotation and V5
discharge dd = V V
15, 65, 25, 75 1 2
Y1 x V3 S3
N3
N1
U1 V6 E
M1
T4

U2
P3 P4

** Steel base frame not standard for the 180 o

discharge direction.
U
Please contact Flkt Woods AB.
dd = 13 (90o) dd = 15 (180o) **
o o
dd = 63 (90 ) dd = 65 (180 ) **

S4 S5 S6

N3 N4 N1

M3 M1
E

P6 P1
P5

U
U U
o o o
dd = 17 (270 ) dd = 18 (315 ) dd = 21 (0 )
dd = 67 (270o) dd = 68 (315o) dd = 71 (0o)

S7
S8
N2
N3
M2
N1
E
M1

P2
P3 P4

U U
dd = 22 (45o) dd = 23 (90o) dd = 25 (180o) **
o o o
dd = 72 (45 ) dd = 73 (90 ) dd = 75 (180 ) **
Dimensions - Fan plus steel base frame Page 93

Motor size
Type of fan - size
160-225 250-355
HCG HCL HCM HCH M1 M2 M3 N1 N2 N3 N4 P1 P2 P3 P4 P5 P6 U U
112 090 071 -- 1065 995 1265 1860 1760 1700 2100 1670 2200 2000 1850 1870 1850 180 200
125 100 080 063 1190 1160 1430 2070 2010 1900 2360 1875 2470 2240 2080 2090 2060 180 200
140 112 090 071 1325 1290 1600 2320 2290 2120 2660 2100 2760 2330 2320 2320 2290 180 200
160 125 100 080 1490 1400 1790 2650 2570 2370 2960 2385 3140 2840 2650 2640 2600 200 240
-- 140 112 090 1665 1620 1990 2970 2880 2650 3310 2655 3490 3160 2950 2950 3000 200 240
-- 160 125 100 1860 1810 2230 3320 3210 2960 3700 2960 3900 3530 3340 3290 3240 200 240

Motor size Motor size Motor size


Type of fan - size 160-180 200-225 250-315 355 160-180 200-225 250-315 355 160-180 200-225 250-315 355
HCG HCL HCM HCH S1 S1 S1 S1 S2 S2 S2 S2 S3 S3 S3 S3
112 090 071 -- 2520 2630 3090 -- 2450 2560 3020 -- 2190 2300 2760 --
125 100 080 063 2690 2800 3290 3390 2660 2770 3260 3360 2320 2430 2920 3020
140 112 090 071 2900 3010 3480 3580 2870 2980 3440 3540 2500 2610 3080 3180
160 125 100 080 3090 3210 3660 3760 3000 3120 3570 3670 2640 2750 3210 3310
-- 140 112 090 3340 3460 4010 4110 3300 3420 3970 4070 2830 2940 3500 3600
-- 160 125 100 3640 3760 4290 4390 3590 3710 4240 4340 3070 3180 3720 3820

Motor size Motor size Motor size


Type of fan - size 160-180 200-225 250-315 355 160-180 200-225 250-315 355 160-180 200-225 250-315 355
HCG HCL HCM HCH S4 S4 S4 S4 S5 S5 S5 S5 S6 S6 S6 S6
112 090 071 -- 2240 2350 2820 -- 2340 2450 2820 -- 2250 2360 2720 --
125 100 080 063 2370 2480 2920 3020 2480 2590 3030 3130 2380 2490 2980 3080
140 112 090 071 2540 2650 3150 3250 2690 2800 3290 3390 2570 2680 3150 3250
160 125 100 080 -- -- 3260 3360 -- -- 3400 3500 2760 2880 3330 3430
-- 140 112 090 -- -- 3570 3670 -- -- 3740 3840 2980 3100 3650 3750
-- 160 125 100 -- -- 3710 3810 -- -- 3900 4000 3240 3360 3890 3990

Motor size Motor size


Type of fan - size 160-180 200-225 250-315 355 160-180 200-225 250-315 355
HCG HCL HCM HCH S7 S7 S7 S7 S8 S8 S8 S8
112 090 071 -- 2150 2260 2790 -- 2420 2530 2890 --
125 100 080 063 2350 2460 2950 3050 2570 2680 3180 3280
140 112 090 071 2580 2690 3150 3250 2770 2880 3350 3450
160 125 100 080 2770 2890 3340 3440 2940 3050 3510 3610
-- 140 112 090 2940 3050 3560 3660 3170 3290 3740 3840
-- 160 125 100 3180 3300 3780 3880 3450 3570 4100 4200

Impeller weights - Impeller diameters

Impeller weights, kg Impeller diameter


Fan HCMB HCHB Fan HCMB HCHB
HCGB HCLP HCGB HCLP
size HCMP HCHP size HCMP HCHP

063 - - - 132 063 - - - 1259


071 - - 114 181 071 - - 1122 1413
080 - - 143 245 080 - - 1259 1585
090 - 97 199 370 090 - 1122 1413 1779
100 - 135 270 471 100 - 1259 1585 1995
112 106 178 407 - 112 1122 1413 1779 -
125 148 249 517 - 125 1259 1585 1995 -
140 195 386 - - 140 1413 1779 - -
160 276 493 - - 160 1585 1995 - -
Dimensions and Weights - Fan Page 94

H1 V1 V2
Fan type - size Form 1) dd = Form 1) dd = Form 1) dd = V3 V4 V5 V6 Y1 Y2
11-15, 11-15, 11-15,
HCG HCL HCM HCH D2 F1 F2 21-25 17-18 H2 L2 T3 T4 U1 U2 21-25 17-18 21-25 17-18
112 090 071 -- 70 74.5 20 930 1085 1010 170 295 720 125 80 1023 1141 891 1009 410 1010 505 505 2 3
125 100 080 063 80 85 22 1050 1205 1133 175 335 800 125 80 1113 1223 981 1091 440 1100 550 550 2 3
140 112 090 071 90 95 25 1170 1330 1271 190 384 900 125 80 1253 1375 1121 1241 385 1235 618 618 3 4
160 125 100 080 100 106 28 1350 1520 1426 210 387 970 175 100 1382 1507 1188 1313 425 1365 683 1448 3 4
-- 140 112 090 100 106 28 1500 1700 1610 210 387 970 175 100 1532 1687 1338 1489 475 1515 758 1623 3 4
-- 160 125 100 100 106 28 1670 1890 1796 210 387 970 175 100 1742 1923 1548 1725 540 1725 863 1818 3 4
1)
Form means the designations for rotation and discharge

HCGB

K1 T2
Fan Imp. D3 Form 1) dd = Form 1) dd = Weight,
A B C D1 E K2 L1 T1
size dia. min. 11-13, 17, 18, 21-23 15, 25 11-13, 17, 18, 21-23 15, 25 kg 2)
112 1120 1120 900 573 1125 315 736 533 583 1263 2020 608 493 543 610
125 1250 1250 1000 623 1255 355 821 583 633 1415 2230 680 543 593 770
140 1400 1400 1120 683 1405 425 926 643 703 1578 2460 744 603 663 1040
160 1600 1600 1250 753 1605 500 1033 728 788 1758 2740 886 678 738 1370
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
HCLP

K1 T2
Fan Imp. D3 Form 1) dd = Form 1) dd = Weight,
A B C D1 E K2 L1 T1
size dia. min. 11-13, 17, 18, 21-23 15, 25 11-13, 17, 18, 21-23 15, 25 kg 1)
090 1120 900 710 478 905 315 736 433 483 1168 1830 513 398 448 610
100 1250 1000 800 523 1005 335 821 478 528 1315 2030 580 443 493 770
112 1400 1120 900 573 1125 400 926 528 588 1468 2240 634 493 553 1040
125 1600 1250 1000 623 1255 450 1033 603 663 1633 2485 761 553 613 1370
140 1800 1400 1120 683 1405 530 1153 663 723 1693 2605 821 613 673 1730
160 2000 1600 1250 753 1605 630 1287 728 788 1758 2740 886 678 738 2050
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
HCM(B,P)

D3 K1 T2
Fan Imp. Weight,
A B C D1 min. E Form 1) dd = K2 L1 T1 Form 1) dd =
size dia. kg 2)
HCMB HCMP 11-13,17,18,21-23 15,25 11-13,17,18, 21-23 15,25
071 1120 710 560 403 715 250 280 736 358 408 1093 1680 438 323 378 605
080 1250 800 630 438 805 315 315 821 393 443 1230 1850 495 358 408 745
090 1400 900 710 478 905 335 355 916 433 493 1373 2050 539 398 458 1015
100 1600 1000 800 523 1005 400 450 1023 503 563 1533 2285 661 453 513 1330
112 1800 1120 900 573 1125 450 450 1153 553 613 1583 2385 711 503 563 1685
125 2000 1250 1000 623 1255 500 500 1287 603 663 1633 2505 761 553 613 2030
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
HCH(B,P)

D3 K1 T2
Fan Imp. Weight,
A B C D1 min. E Form 1) dd = K2 L1 T1 Form 1) dd =
size dia. kg 2)
HCMB HCMP 11-13,17,18,21-23 15,25 11-13,17,18, 21-23 15,25
063 1250 630 500 373 635 250 335 821 328 378 1165 1745 430 293 343 710
071 1400 710 560 403 715 280 400 916 358 418 1298 1905 463 323 383 950
080 1600 800 630 438 805 335 400 1023 418 478 1448 2125 576 368 428 1260
090 1800 900 710 478 905 400 450 1143 458 518 1488 2205 616 408 468 1550
100 2000 1000 800 523 1005 500 540 1277 503 563 1533 2295 661 453 513 1920
1)
Form means the designations for rotation and discharge 2)
Weights are exclusive motor, belt drive and steel base frame.
Dimensions and weights - Steel base frame Page 95

Fan type Form 1) Motor- Form 1) Motor- Motor Weight,


HCG dd location dd location size A B C D E kg

11, 12, 63 W 13, 61, 62 Z 160-225 1836 1915 1010 800 1303 228
11, 12, 63 W 13, 61, 62 Z 250-355L 1846 2425 1010 990 1308 294
112
17, 18 W 67, 68 Z 160-225 1836 2025 1130 800 1303 315
17, 18 W 67, 68 Z 250-355L 1846 2537 1109 990 1308 375
11, 12, 63 W 13, 61, 62 Z 160-225 2038 2000 1100 880 1455 246
11, 12, 63 W 13, 61, 62 Z 250-355L 2048 2535 1100 990 1460 313
125
17, 18 W 67, 68 Z 160-225 2038 2110 1210 880 1455 340
17, 18 W 67, 68 Z 250-355L 2048 2590 1200 990 1460 400
11, 12, 63 W 13, 61, 62 Z 160-225 2261 2150 1235 980 1618 277
11, 12, 63 W 13, 61, 62 Z 250-355L 2271 2660 1235 990 1623 337
140
17, 18 W 67, 68 Z 160-225 2261 2260 1360 980 1618 400
17, 18 W 67, 68 Z 250-355L 2271 2800 1341 990 1623 435
11, 12, 63 W 13, 61, 62 Z 160-225 2491 2250 1365 1000 1773 355
11, 12, 63 W 13, 61, 62 Z 250-355L 2511 2720 1365 1020 1793 492
160
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2511 2845 1425 1020 1793 575
1)
Form means the designations for rotation and discharge
CL Inlet Fan

C
W = Motor on the right of the fan as viewed from the drive side.
Z = Motor on the left of the fan as viewed from the drive side.

CL Outlet Fan

Dimensions and weights apply equally to


fans with reversed motor location. A

W = Motor on the right of the fan as viewed from the drive side.
Z = Motor on the left of the fan as viewed from the drive side.
B
1)
Form means the designations for rotation and discharge

Fan type Form 1) Motor- Form 1) Motor- Motor Weight,


HCL dd location dd location size A B C D E kg

11, 12, 63 W 13, 61, 62 Z 160-225 1646 1915 1010 800 1208 218
11, 12, 63 W 13, 61, 62 Z 250-355L 1656 2425 1010 990 1213 284
090
17, 18 W 67, 68 Z 160-225 1646 2025 1130 800 1208 295
17, 18 W 67, 68 Z 250-355L 1656 2537 1109 990 1213 360
11, 12, 63 W 13, 61, 62 Z 160-225 1838 2000 1100 880 1355 239
11, 12, 63 W 13, 61, 62 Z 250-355L 1848 2535 1100 990 1360 303
100
17, 18 W 67, 68 Z 160-225 1838 2110 1210 880 1355 325
17, 18 W 67, 68 Z 250-355L 1848 2590 1200 990 1360 380
11, 12, 63 W 13, 61, 62 Z 160-225 2041 2150 1235 980 1508 267
11, 12, 63 W 13, 61, 62 Z 250-355L 2051 2660 1235 990 1513 325
112
17, 18 W 67, 68 Z 160-225 2041 2260 1360 980 1508 355
17, 18 W 67, 68 Z 250-355L 2051 2800 1341 990 1513 420
11, 12, 63 W 13, 61, 62 Z 160-225 2241 2250 1365 1000 1648 343
11, 12, 63 W 13, 61, 62 Z 250-355L 2261 2720 1365 1020 1658 472
125
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2261 2845 1425 1020 1658 550
11, 12, 63 W 13, 61, 62 Z 160-225 2361 2400 1515 1000 1708 354
11, 12, 63 W 13, 61, 62 Z 250-355L 2381 2970 1515 1020 1718 505
140
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2381 3120 1639 1020 1718 595
11, 12, 63 W 13, 61, 62 Z 160-225 2491 2610 1725 1000 1773 380
11, 12, 63 W 13, 61, 62 Z 250-355L 2511 3160 1725 1020 1783 539
160
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2511 3250 1837 1020 1783 630
Dimensions and weights - Steel base frame Page 96

Fan type Form 1) Motor- Form 1) Motor- Motor Weight,


HCM dd location dd location size A B C D E kg

11, 12, 63 W 13, 61, 62 Z 160-225 1496 1915 1010 800 1133 213
11, 12, 63 W 13, 61, 62 Z 250-355L 1506 2425 1010 990 1138 275
071
17, 18 W 67, 68 Z 160-225 1496 2025 1130 800 1133 290
17, 18 W 67, 68 Z 250-355L 1506 2537 1109 990 1138 350
11, 12, 63 W 13, 61, 62 Z 160-225 1668 2000 1100 880 1270 227
11, 12, 63 W 13, 61, 62 Z 250-355L 1678 2535 1100 990 1275 294
080
17, 18 W 67, 68 Z 160-225 1668 2110 1210 880 1270 310
17, 18 W 67, 68 Z 250-355L 1678 2590 1200 990 1275 370
11, 12, 63 W 13, 61, 62 Z 160-225 1851 2150 1235 980 1413 257
11, 12, 63 W 13, 61, 62 Z 250-355L 1861 2660 1235 990 1418 316
090
17, 18 W 67, 68 Z 160-225 1851 2260 1360 980 1413 340
17, 18 W 67, 68 Z 250-355L 1861 2800 1341 990 1418 405
11, 12, 63 W 13, 61, 62 Z 160-225 2031 2250 1365 1000 1538 332
11, 12, 63 W 13, 61, 62 Z 250-355L 2051 2720 1365 1020 1548 459
100
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2061 2845 1425 1020 1558 530
11, 12, 63 W 13, 61, 62 Z 160-225 2141 2400 1515 1000 1598 342
11, 12, 63 W 13, 61, 62 Z 250-355L 2161 2970 1515 1020 1608 489
112
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2161 3120 1639 1020 1608 575
11, 12, 63 W 13, 61, 62 Z 160-225 2241 2610 1725 1000 1653 368
11, 12, 63 W 13, 61, 62 Z 250-355L 2261 3160 1725 1020 1663 519
125
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2261 3250 1837 1020 1663 610

1)
Form means the designations for rotation and discharge

W = Motor on the right of the fan as viewed from the drive side. Dimensions and weights apply equally to
Z = Motor on the left of the fan as viewed from the drive side. fans with reversed motor location.

Fan type Form 1) Motor- Form 1) Motor- Motor Weight,


HCH dd location dd location size A B C D E kg

11, 12, 63 W 13, 61, 62 Z 160-225 1538 2000 1100 880 1205 224
11, 12, 63 W 13, 61, 62 Z 250-355L 1548 2535 1100 990 1210 288
063
17, 18 W 67, 68 Z 160-225 1538 2110 1210 880 1205 300
17, 18 W 67, 68 Z 250-355L 1548 2590 1200 990 1210 360
11, 12, 63 W 13, 61, 62 Z 160-225 1701 2150 1235 980 1338 250
11, 12, 63 W 13, 61, 62 Z 250-355L 1711 2660 1235 990 1343 307
071
17, 18 W 67, 68 Z 160-225 1701 2260 1360 980 1338 330
17, 18 W 67, 68 Z 250-355L 1711 2800 1341 990 1343 390
11, 12, 63 W 13, 61, 62 Z 160-225 1871 2250 1365 1000 1463 321
11, 12, 63 W 13, 61, 62 Z 250-355L 1831 2720 1365 1020 1413 445
080
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 1891 2845 1425 1020 1413 515
11, 12, 63 W 13, 61, 62 Z 160-225 1951 2400 1515 1000 1423 330
11, 12, 63 W 13, 61, 62 Z 250-355L 1971 2970 1515 1020 1513 476
090
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 1971 3120 1639 1020 1513 555
11, 12, 63 W 13, 61, 62 Z 160-225 2041 2610 1725 1000 1568 355
11, 12, 63 W 13, 61, 62 Z 250-355L 2061 3160 1725 1020 1555 505
100
17, 18 W 67, 68 Z 160-225 -- -- -- -- -- --
17, 18 W 67, 68 Z 250-355L 2061 3250 1837 1020 1558 590

1)
Form means the designations for rotation and discharge

W = Motor on the right of the fan as viewed from the drive side.
Z = Motor on the left of the fan as viewed from the drive side.
Location of fan and motor Page 97

c-c distance
Designations for rotation and discharge = dd
Fan type - Size Motor size 11, 61, 12, 62, 13, 63, 21, 71, 22, 72, 23, 73 17, 67, 18, 68
HCG HCL HCM HCH IEC Min. Max. Min. Max.
112 090 071 -- 160M-180L 1235 1355 1365 1480
200L-225M 1180 1355 1310 1475
250M-315L 1430 1690 1545 1790
125 100 080 063 160M-180L 1340 1455 1500 1585
200L-225M 1280 1450 1415 1575
250M-315L 1540 1795 1615 1850
355S-355M 1485 1810 1550 1860
140 112 090 071 160M-180L 1475 1585 1615 1720
200L-225M 1420 1580 1560 1710
250M-315L 1640 1890 1790 2025
355S-355M 1585 1905 1725 2040
160 125 100 080 160M-180L 1610 1715 -- --
200L-225M 1555 1710 -- --
250M-315L 1740 1985 1890 2120
355S-355M 1685 1995 1820 2130
140 112 090 160M-180L 1765 1870 -- --
200L-225M 1710 1860 -- --
250M-315L 1970 2210 2150 2375
355S-355M 1915 2220 2010 2300
160 125 100 160M-180L 1960 2060 -- --
200L-225M 1910 2050 -- --
250M-315L 2140 2370 2275 2480
355S-355M 2080 2380 2215 2500

c/c

dd = 11 (0o) = Right-hand model dd = 12 (45o) dd = 13 (90o) dd = 17 (270o)


dd = 61 (0o) = Left-hand model dd = 62 (45o) dd = 63 (90o) dd = 67 (270o)

dd = 18 (315o) dd = 21 (0o) dd = 22 (45o) dd = 23 (90o)


o o o o
dd = 68 (315 ) dd = 71 (0 ) dd = 72 (45 ) dd = 73 (90 )

Motor location:
W = as per diagram.
Z = reversed motor location.
Dimensions and weights - Slide rails Page 98

Slide rails XYLS for fitting to concrete beds


The slide rails are made of hot-dip galvanized steel. Each order comprises a complete set for one motor, namely: Slide
rails, retaining pawls with retaining bolts and bolts for fastening the motor in position.

XYLS-02, 03, 04

XF
XA min. max.
displacement
XA max.
XC

XYLS-02 XYLS-03 XYLS-04


Motor bolts, M 10 Motor bolts, M 12 Motor bolts, M 16

56 56 56

5 5
5

50 711 18
50 437 14 50 536 14
92 80
92 80 92 80
25
25 25 761
487 586
811
537 636

XYLS-05, 06

XF
XA min. max.
displacement
XA max.

XC

XYLS-05 XYLS-06
Motor bolts, M 20 Motor bolts, M 24

75 80
5 6

18 x 40 24 x 40
92 80 112 160 104 86 135 190

185 715 190 455 455


995 1200

Dimensions
For Max. Weight,
XYLS- motor displacement XA min. XA max. XC XF per pair,
size mm mm mm mm mm kg
100 198 173 371 74 55 8
02 112 171 185 356 74 55 8
132 144 199 343 74 55 8
160 193 230 423 74 65 10
03
180 167 244 411 74 65 10
200 252 302 554 84 95 12
04
225 214 321 535 84 95 12
250 374 178 552 70 20 32
05 280 340 196 536 70 20 32
315 277 233 510 70 20 32
315 476 235 711 91 30 48
06
355 393 276 669 91 30 48
Dimensions and weights - Assessories Page 99

Cleanout cover JLCB-a-b


The JLCB cleanout cover is ideal where inspections A
are frequent or where sealing requirements are high.
It is delivered mounted on the fan.
The cover is secured to the hatch by four bolts. B

CL

Size A B Weight, kg
4 293 400 7.0 Dimensions A and B refer to the hatch
5 413 560 16.0 opening in the fan casing.
8 293 400 13.7
9 413 560 29.5

Cooling disc HCEZ-06-bb Table - Cooling disc selection


(for operating temperatures > 100oC)
Cooling disc
Material: Cast aluminium; contact guard included as Fan size
size
standard. HCG HCL HCM HCH code bb
The cooling disc is cast in two halves and can thus be fit- 112 90 071 - 05
ted to already installed fans. Refer to the adjacent table 125 100 080 063 06
for cooling disc selection. 140 112 090 071 07
160 125-160 100-125 080-100 08

Speed monitor HCEZ-13-bb


For monitoring speed of rotation.
An alarm can be activated, or the motor stopped, when fan
speed falls below the revolutions set via the potentiometer.
Supply current, V(AC/DC) 20 - 264
Load voltage, (mA) 5 - 350 AC / 5 - 200 DC
Safety class IP 67
o o
Ambient temperature -25 C / +70 C

Table - Speed monitor selection.

Fan size
Fan size
shaft HCG HCL HCM HCH code bb
112 090 071 03
125-140 100-112 080-090 063-071 04
160 125-160 100-125 080-100 05
Dimensions and weights - Assessories Page 100

NB! Flanges conform to ISO 13351. HCEZ-50/51/52 HCEZ-70/71

60 B g n holes G n holes G n holes G n holes G


g

E1

A n1 x E A1 x B1

Sheet steel
insert

E1

F1 n2 x F F1 t + 2,5 t t
t
H H

Outlet - Protective screen HCEZ-30, counterflange HCEZ-35, fabric duct HCEZ-50/51/52 and flue gas duct HCEZ-70/71
Weight, kg
Size + 10
A A1 B B1 E E1 F F1 G H - 20 g n n1 n2 t HCEZ- HCEZ- HCEZ- HCEZ-
bbb 30 35 50/51/52 70/71
063 630 600 500 470 125 97 125 94.5 12 130 32 22 4 3 8 10.5 9.2 18.8 22.4
071 710 680 560 530 125 74.5 125 62 12 130 32 26 5 4 8 11.9 10.3 21.1 25.3
080 800 770 630 600 125 57 125 97 12 130 32 28 6 4 8 13.4 11.5 23.5 27.9
090 900 870 710 680 125 107 125 74.5 12 130 32 30 6 5 8 15.2 12.8 26.1 31.3
100 1000 970 800 770 125 94.5 125 57 14 130 32 34 7 6 8 17.1 14.2 29.0 34.9
112 1120 1080 900 860 125 97 125 112 14 160 37 36 8 6 8 20.0 16.5 33.9 40.7
125 1250 1210 1000 960 125 99.5 125 99.5 14 160 37 40 9 7 8 22.5 18.2 37.5 45.1
140 1400 1360 1120 1080 125 174.5 125 97 14 160 37 42 9 8 8 25.6 20.3 41.9 50.5
160 1600 1560 1250 1210 125 87 125 99.5 14 160 37 50 12 9 8 35.1 28.5 47.1 56.7

HCEZ-21 HCEZ-25 HCEZ-45/46/47 HCEZ-65/66

t1 t1 t2 t2

h h h h

E
D1 D3 D1 D1 D1 D2
ins. ins.
Sheet steel
insert

H1 H1
nxG
H2

Inlet - Inlet taper piece HCEZ-21, counterflange HCEZ-35, fabric duct HCEZ-45/46/47 and flue gas duct HCEZ-65/66
Weight, kg
Size + 10
D1 D2 D3 E G H1 H2 h n t1 t2 HCEZ- HCEZ- HCEZ- HCEZ-
bbb - 20 21 25 45/46/47 65/66
063 635 595 880 698 14 130 218 60 16 8 6 11.8 5.9 14.5 15.2
071 715 675 975 775 14 130 218 60 16 8 6 14.0 6.6 16.4 ---
080 805 765 1105 869 14 130 243 60 24 8 6 18.2 7.3 18.2 19.0
090 905 865 1225 958 14 130 243 60 24 8 6 21.0 11.2 26.4 --
100 1005 965 1350 1067 14 130 243 60 24 8 6 24.3 12.4 28.4 30.8
112 1125 1085 1510 1200 18 160 293 60 32 8 6 45.0 16.2 37.7 44.1
125 1255 1215 1700 1337 18 160 293 60 32 8 6 57.0 17.9 41.9 49.5
140 1405 1365 1880 1475 18 160 293 60 32 8 6 67.0 20.0 47.2 55.8
160 1605 1565 2100 1675 18 160 293 60 40 12 10 97.5 30.5 69.0 79.5
Electric motors Page 101

This catalogue section deals with 50 Hz., totally enclosed, foot-mounted, three-phase squirrel cage motors. The two-speed
motors are adapted for driving fans. Size 200 motors and upwards are provided, as standard, with thermistor type tempera-
ture monitors. Quotations for temperature monitors on other sizes supplied on request.
APAL Single-speed motors.
ARAL Two-speed motors with a speed ratio of 1:2 and one stator winding ("Dahlander-connected").
ATAL Two-sped motors with a speed ratio of 1:1.5 and separate stator windings.
For housing and insulation classes, please refer to page 102.

Calculation of starting times


PY/D = 2,6
Whenever fans or fan drives are presented with a specific motor, this x Pf
is rated for direct on-line starting. If a different motor is selected or if TMAX
star-delta starting is employed, permitted starting times must be TN
checked by calculation.
Use the following formulae to calculate the starting time for direct on- If star-delta starting is employed, the starter should be first set to the
line and star-delta starting: star setting for a period corresponding to the starting time calculated as
above and thereafter switched to the delta setting.
Direct on-line starting t = J x nf2 x 10-3
T T Symbols used
46 P MAX + S - Pf
TN TN
P = Rated output of the motor kW

J x nf2 x -3
10
Star-delta starting t= Pf = Fan power demand at rated speed kW
TMAX T
46 P 1 x + 1x S - Pf (incl. where belt-driven, belt-drive losses)
3 TN 4 TN
Permissible starting times PY/D = Minimum motor rating at which star-delta starting is possible kW
With regard to heat build-up, starting times must not exceed those
stated in the table below. TS
= Ratio of motor starting torque to normal torque
The values given in the table are for starts when the motor is in a TN
warm condition after operation.
For cold starts, the values can be doubled. TMAX.
= Ratio of max. motor torque to normal torque
Max. permitted starting times in seconds for individual starts TN

Numbers of poles nf = Rated speed of fan r/min


Motor size Starting method 2 4 6 8
J = The system's moment of inertia, referred to the fan shaft 1) kg m2
63 Direct on-line starting 25 40 - 40
71 Direct on-line starting 20 20 40 40 t = Starting time s
80 Direct on-line starting 15 20 40 40
1)
90 Direct on-line starting 10 20 35 40 The impeller's moment of inertia is stated in the relevant fan chart.
100 Direct on-line starting 10 15 30 40 The motor's moment of inertia can generally be disregarded.
Direct on-line starting 20 15 25 50
112
Star-delta starting 60 45 75 150

132
Direct on-line starting 15 10 10 20 Ordering key
Star-delta starting 45 30 30 60
Direct on-line starting 15 15 20 20 Motor, single-speed APAL-a-bbbbb-c-0
160
Star-delta starting 45 45 60 60 Motor, two-speed,
Direct on-line starting 15 15 20 20 speed ratio 1:1.5 ATAL-a-bbbbb-c-0
180
Star-delta starting 45 45 60 60
speed ratio 1:2 ARAL-a-bbbbb-c-0
Direct on-line starting 15 15 20 20
200
Star-delta starting 45 45 60 60 Number of poles 1) (see motor tables): 2, 4, 6, 8
Direct on-line starting 15 15 20 20
225
Star-delta starting 45 45 60 60 Rated output 1) (see motor tables):
Direct on-line starting 15 15 20 20 The first three digits of the "bbbbb" code give the number
250 of whole kW, the last two digits are decimals.
Star-delta starting 45 45 60 60
E.g. code 00175 denotes 1.75 kW.
Direct on-line starting 15 18 17 15
280
Star-delta starting 45 54 51 45
Voltage
Direct on-line starting 15 18 16 12
315 Single-speed motor Two-speed motor
Star-delta starting 45 54 48 36
1 = 220-240 VD/380-420 VY 2) 2 = 400 V
Direct on-line starting 15 20 18 30 2 = 380-420 VD/660-690 VY 5 = 500 V
355
Star-delta starting 45 60 54 90
5 = 500 VY (sizes 63-100)
500 VD (sizes 112-355)
Where starting is frequent, the motor cannot be run at the rated output
owing to the effect on the windings of starting heat losses. The per- 1) For the higher speed of a two-speed motor.
missible motor output can be calculated using the number of starts 2) Star-delta starting is not possible if the motor is star connected.
per hour, the load's moment of inertia and the load's rotational speed.
Please contact Flkt Woods AB. Slide rails, set XYLS-aa
NB! A motor can be started using a star-delta starter provided that the Size: 02, 03, 04, 05, 06
motor is delta-connected. During starting, the motor is star-connected
and torque is consequently reduced. Check that the motor's torque
curve is higher than the fan's torque curve throughout the range up to
90% of the synchronous speed. If no torque curves are available, the
following formulae are sufficiently accurate for determining the mini-
mum motor rating.
Electric motors Page 102

Single-speed motors, 50 Hz
Size designation Rated At rated output Size designation Rated At rated output
out- out-
ABB Designation put RPM Approx. Is2) Ts Tmax. Weight ABB Designation put RPM Approx. Is2) Ts Tmax Weight
IEC Motors A at IN TN TN IEC Motors A at IN TN TN
kW 400V 1) kg kW 400V1) kg

3000 rpm = 2 poles 1000 rpm = 6 poles

APAL- APAL-
63 M2AA 63 B 2-00025-c-0 0.25 2820 0.70 4.0 2.2 2.7 4.5 71 M2AA 71 6-00012-c-0 0.12 930 0.59 2.5 2.3 2.7 5.0
71 M2AA 71 A 2-00037-c-0 0.37 2840 0.93 4.5 2.2 2.7 5.5 71 M2AA 71 A 6-00018-c-0 0.18 920 0.75 2.5 2.0 2.4 5.5
71 M2AA 71 B 2-00055-c-0 0.55 2850 1.33 5.0 2.2 2.7 6.5 71 M2AA 71 B 6-00025-c-0 0.25 920 0.92 3.0 2.0 2.4 6.5
80 M2AA 80 A 2-00075-c-0 0.75 2860 1.7 5.0 2.2 2.7 9 80 M2AA 80 A 6-00037-c-0 0.37 920 1.25 3.5 2.1 2.5 8.5
80 M2AA 80 B 2-00110-c-0 1.1 2870 2.4 5.5 2.4 3.0 10 80 M2AA 80 B 6-00055-c-0 0.55 930 1.78 3.5 2.1 2.5 9.5
90 S M2AA 90 S 2-00150-c-0 1.5 2870 3.3 5.5 2.4 3.0 13 90 S M2AA 90 S 6-00075-c-0 0.75 930 2.36 4.0 1.9 2.3 13
90L M2AA 90 L 2-00220-c-0 2.2 2870 4.55 7.0 2.7 3.4 16 90 L M2AA 90 L 6-00110-c-0 1.1 930 3.25 4.0 1.9 2.3 16
100 L M2AA 100 L 2-00300-c-0 3 2900 5.95 7.5 2.7 3.6 21 100 L M2AA 100 L 6-00150-c-0 1.5 950 4.1 4.5 1.9 2.3 23
112 M M2AA 112 M 2-00400-c-0 4 2850 7.4 7.5 2.8 3.0 25 112 M M2AA 112 M 6-00220-c-0 2.2 940 5.4 5.6 2.1 2.7 27
132 S M2AA 132 SA 2-00550-c-0 5.5 2855 10.5 7.8 3.2 3.4 37 132 S M2AA 132 S 6-00300-c-0 3 960 6.9 6.1 2.4 2.6 39
132 S M2AA 132 SB 2-00750-c-0 7.5 2855 13.9 8.5 3.4 3.6 42 132 M M2AA 132 MA 6-00400-c-0 4 960 8.7 7.1 2.6 2.8 46
160 M M2AA 160 MA 2-01100-c-0 11 2930 20.0 6.3 1.9 2.5 73 132 M M2AA 132 MB 6-00550-c-0 5.5 955 11.9 6.9 2.8 2.8 54
160 M M2AA 160 M 2-01500-c-0 15 2920 26.5 6.6 2.3 2.5 84 160 M M2AA 160 M 6-00750-c-0 7.5 970 15.4 6.7 2.0 2.8 88
160 L M2AA 160 L 2-01850-c-0 18.5 2920 32.0 7.3 2.6 2.7 94 160 L M2AA 160 L 6-01100-c-0 11 970 23.0 7.1 2.2 2.8 102
180 M M2AA 180 M 2-02200-c-0 22 2930 38.5 7.2 2.5 2.7 119 180 L M2AA 180 L 6-01500-c-0 15 970 31.0 7.0 2.1 3.0 151
200 L M2AA 200 MLA 2-03000-c-0 30 2955 53 7.3 2.4 3.1 175 200 L M2AA 200 MLA 6-01850-c-0 18.5 985 36 7.0 2.5 2.7 165
200 L M2AA 200 MLB 2-03700-c-0 37 2950 64 7.3 2.5 3.2 200 200 L M2AA 200 MLB 6-02200-c-0 22 980 43 7.2 2.5 2.7 185
225 M M2AA 225 SMB 2-04500-c-0 45 2960 79 7.3 2.5 2.8 235 225 M M2AA 225 SMB 6-03000-c-0 30 985 56 6.6 2.5 2.7 225
250 M M2AA 250 SMA 2-05500-c-0 55 2970 95 7.5 2.0 3.0 285 250 M M2AA 250 SMA 6-03700-c-0 37 985 69 7.3 2.8 2.8 280
280 S M2CA 280 SA 2-07500-c-0 75 2977 131 7.4 2.0 2.9 480 280 S M2CA 280 SA 6-04500-c-0 45 990 85 7.0 2.6 2.6 440
280 M M2CA 280 SMA 2-09000-c-0 90 2975 152 7.2 2.1 2.7 545 280 M M2CA 280 SMA 6-05500-c-0 55 989 102 7.0 2.7 2.6 475
315 S M2CA 315 SA 2-11000-c-0 110 2982 194 7.6 2.0 3.0 695 315 S M2CA 315 SA 6-07500-c-0 75 992 143 7.5 2.3 2.7 630
315 M M2CA 315 SMA 2-13200-c-0 132 2982 228 7.4 2.2 3.0 770 315 M M2CA 315 SMA 6-09000-c-0 90 991 165 7.1 2.3 2.7 720
315 M M2CA 315 MB 2-16000-c-0 160 2981 269 7.5 2.3 3.0 840 315 M M2CA 315 MB 6-11000-c-0 110 991 201 7.3 2.5 2.8 805
355 S M2CA 355 SA 2-20000-c-0 200 2977 330 6.6 1.3 2.8 1220 355 S M2CA 355 SA 6-13200-c-0 132 992 235 6.8 1.7 2.6 1200
355 M M2CA 355 MA 2-25000-c-0 250 2980 410 6.6 1.3 3.0 1320 355 S M2CA 355 SB 6-16000-c-0 160 992 280 6.8 1.8 2.7 1320
355 M M2CA 355 MB 2-28000-c-0 280 2978 470 5.7 1.1 2.7 1320 355 M M2CA 355 MA 6-20000-c-0 200 993 350 7.5 2.0 2.8 1550
355 M M2CA 355 MB 6-25000-c-0 250 991 475 7.3 2.2 3.0 1550

1500 rpm = 4 poles 750 rpm = 8 poles

APAL- APAL-
63 M2AA 63 B 4-00018-c-0 0.18 1370 0.72 3.0 2.2 2.6 4.5 80 M2AA 80 A 8-00018-c-0 0.18 700 0.90 2.5 1.8 2.3 8.5
71 M2AA 71 A 4-00025-c-0 0.25 1400 0.83 3.5 2.2 2.7 5.5 80 M2AA 80 B 8-00025-c-0 0.25 700 1.18 2.5 1.9 2.4 9.5
71 M2AA 71 B 4-00037-c-0 0.37 1410 1.12 4.0 2.2 2.7 6.5 90 S M2AA 90 S 8-00037-c-0 0.37 700 1.60 3.0 1.9 2.4 13
80 M2AA 80 A 4-00055-c-0 0.55 1420 1.45 4.0 2.2 2.7 9 90 L M2AA 90 L 8-00055-c-0 0.55 700 2.35 3.0 1.9 2.4 16
80 M2AA 80 B 4-00075-c-0 0.75 1420 1.9 4.5 2.2 2.7 10 100 L M2AA 100 LA 8-00075-c-0 0.75 700 2.67 3.5 2.1 2.7 20
90 S M2AA 90 S 4-00110-c-0 1.1 1410 2.59 5.0 2.2 2.7 13 100 L M2AA 100 LB 8-00110-c-0 1.1 700 3.42 3.5 2.1 2.7 23
90 L M2AA 90 L 4-00150-c-0 1.5 1420 3.4 5.0 2.4 2.9 16 112 M M2AA 112 M 8-00150-c-0 1.5 695 4.5 4.1 1.9 2.4 28
100 L M2AA 100 LA 4-00220-c-0 2.2 1430 4.8 5.5 2.4 2.9 21 132 S M2AA 132 S 8-00220-c-0 2.2 720 5.9 5.3 1.9 2.5 46
100 L M2AA 100 LB 4-00300-c-0 3 1430 6.48 5.5 2.5 2.9 24 132 M M2AA 132 M 8-00300-c-0 3 720 7.8 5.5 2.4 2.6 53
112 M M2AA 112 M 4-00400-c-0 4 1435 8.6 7.0 2.9 3.1 27 160 M M2AA 160 MA 8-00400-c-0 4 715 10.0 5.2 2.1 2.4 75
132 S M2AA 132 S 4-00550-c-0 5.5 1450 11.1 7.3 2.2 3.0 40 160 M M2AA 160 M 8-00550-c-0 5.5 710 13.4 5.4 2.4 2.6 88
132 M M2AA 132 M 4-00750-c-0 7.5 1450 14.8 7.9 2.5 3.2 48 160 L M2AA 160 L 8-00750-c-0 7.5 715 18.1 5.4 2.4 2.8 118
160 M M2AA 160 M 4-01100-c-0 11 1460 22.5 6.7 2.9 2.8 75 180 L M2AA 180 L 8-01100-c-0 11 720 23.5 5.9 2.4 2.6 147
160 L M2AA 160 L 4-01500-c-0 15 1455 28.5 6.8 3.0 2.8 94 200 L M2AA 200 MLA 8-01500-c-0 15 740 29 7.4 1.8 3.0 175
180 M M2AA 180 M 4-01850-c-0 18.5 1470 35 7.0 3.1 2.7 124 225 S M2AA 225 SMA 8-01850-c-0 18.5 730 37 6.2 1.9 2.7 210
180 L M2AA 180 L 4-02200-c-0 22 1470 41 7.0 2.9 2.8 141 225 M M2AA 225 SMB 8-02200-c-0 22 730 45 6.0 1.9 2.7 225
200 L M2AA 200 MLA 4-03000-c-0 30 1475 56 6.7 2.6 2.8 180 250 M M2AA 250 SMA 8-03000-c-0 30 735 59 6.9 1.9 2.9 280
225 S M2AA 225 SMA 4-03700-c-0 37 1480 68 6.6 2.4 2.5 215 280 S M2CA 280 SA 8-03700-c-0 37 741 74 6.8 1.6 2.7 460
225 M M2AA 225 SMB 4-04500-c-0 45 1480 83 6.7 2.7 2.6 230 280 M M2CA 280 SMA 8-04500-c-0 45 741 90 7.1 1.8 2.8 500
250 M M2AA 250 SMA 4-05500-c-0 55 1480 98 7.5 2.3 2.8 275 315 S M2CA 315 SA 8-05500-c-0 55 741 107 7.1 1.8 2.8 630
280 S M2CA 280 SA 4-07500-c-0 75 1483 137 6.9 2.2 2.8 445 315 M M2CA 315 SMA 8-07500-c-0 75 740 142 7.1 1.8 2.8 715
280 M M2CA 280 SMA 4-09000-c-0 90 1484 163 7.6 2.5 2.9 490 315 M M2CA 315 MB 8-09000-c-0 90 740 169 7.3 1.9 2.8 800
315 S M2CA 315 SA 4-11000-c-0 110 1487 198 6.5 2.1 2.6 675 355 S M2CA 355 SA 8-11000-c-0 110 742 215 5.6 1.4 2.2 1200
315 M M2CA 315 SMA 4-13200-c-0 132 1486 238 6.3 2.2 2.7 730 355 M M2CA 355 MA 8-13200-c-0 132 743 265 5.8 1.5 2.3 1350
315 M M2CA 315 MB 4-16000-c-0 160 1486 282 7.0 2.4 2.7 850 355 M M2CA 355 MB 8-16000-c-0 160 742 310 6.4 1.8 2.5 1550
355 S M2CA 355 SA 4-20000-c-0 200 1487 345 7.0 2.1 2.7 1220
355 M M2CA 355 MA 4-25000-c-0 250 1487 430 7.2 2.3 2.8 1350
355 M M2CA 355 LA 4-31500-c-0 315 1488 545 7.4 2.4 2.8 1550
Voltage code
1 = 220-240 VD/380-420 VY, 50 Hz
2 = 380-420 VD/660-680 VY, 50 Hz
5 = 500 VY (sizes 63-100)
500 VD (sizes 112-355)

1) Conversion factor where the rated supply is other than 400V, 50Hz. Housing class IP 55
Dust-proof, spray-proof design. Sizes 63 - 355 are delivered as standard in a
Rated supply at 50 Hz design complying to IP 55.
and motor wound for: conversion factor
220 V 1.82 Drain holes
230 V 1.74 The basic versions of sizes 63 - 100 are supplied without drain holes but can be
415 V 0.96 provided with holes if required. The housing class then becomes IP 54 unless
500 V 0.80 special felt plugs are used.
660 V 0.61 Sizes 112 - 355 are supplied with closeable plastic plugs in the drain holes. The
690 V 0.58 plugs are in the open position when the motors are delivered.

2) Is Insulation class
= ratio of motor start current to motor full-load current.
IN All motors have class F insulation.
The standard rated outputs of motors from ABB Motors are, in most cases, based
3) Temperature rise as per insulation class F. on the temperature increases applying to insulation class B.
Where temperature rises are also to class F, this is specified in the tables.
Electric motors Page 103

Two-speed motors, adapted for fan drives, 50 Hz


Size designation Rated At rated output Size designation Rated At rated output
No out- No out-
ABB Designation of put RPM Approx. Is2) Ts Tmax. Weight ABB Designation of put RPM Approx Is2) Ts Tmax. Weight
IEC Motors poles A at IEC Motors poles A at IN TN TN
IN TN TN
kW 400V 1) kg kW 400V 1) kg

3000 and 1500 rpm synchronous, 2 and 4 poles. 1500 and 750 rpm synchronous, 4 and 8 poles.
One stator winding (YY/Y). One stator winding (YY/Y).

ARAL-2 ARAL-4
2 0.55 2800 1.4 4.0 1.5 2.0 4 0.37 1390 1.2 3.3 1.8 1.8
71 M2AA 71 B 00055-c-0 6.5 71 M2AA 71 B 00037-c-0 6.5
4 0.11 1440 0.5 3.0 1.4 2.4 8 0.09 980 0.49 2.0 1.4 2.8
2 0.75 2850 1.9 4.5 1.8 2.4 4 0.55 1380 1.6 3.1 1.5 1.8
80 M2AA 80 A 00075-c-0 9 80 M2AA 80 A 00055-c-0 8.5
4 0.15 1460 0.67 3.5 1.4 2.4 8 0.11 700 0.54 2.3 1.4 1.8
2 1.1 2860 2.6 5.0 1.8 2.4 4 0.75 1390 2.0 3.4 1.5 1.9
80 M2AA 80 B 00110-c-0 10 80 M2AA 80 B 00075-c-0 9.5
4 0.23 1460 0.88 3.7 1.3 2.4 8 0.16 700 0.70 2.4 1.2 1.9
2 1.5 2860 3.3 5.2 1.8 2.4 4 1.1 1410 2.8 4.2 1.8 2.3
90 S M2AA 90 S 00150-c-0 13 90 S M2AA 90 S 00110-c-0 13
4 0.33 1460 1.1 3.9 1.1 2.4 8 0.26 700 1.2 2.4 1.2 1.9
2 2.2 2860 4.6 5.9 2.1 2.6 4 1.5 1420 3.7 4.8 2.2 2.7
90 L M2AA 90 L 00220-c-0 16 90 L M2AA 90 L 00150-c-0 16
4 0.45 1460 1.4 4.4 1.2 2.6 8 0.31 710 1.5 2.8 1.7 2.5
2 3.5 2880 7.0 6.2 2.1 2.8 4 2.2 1430 5.1 5.1 1.9 2.5
100 L M2AA 100 LB 00350-c-0 25 100 L M2AA 100 LA 00220-c-0 20
4 0.7 1470 2.0 4.8 1.2 3.0 8 0.48 720 1.8 3.0 1.2 2.1
2 4.5 2875 8.4 7.0 1.8 2.3 4 2.8 1430 6.4 5.2 2.0 2.6
112 M M2AA 112 M 00450-c-0 32 100 L M2AA 100 LB 00280-c-0 23
4 1 1450 2.4 6.0 1.9 2.8 8 0.6 720 2.2 3.0 1.2 2.2
2 6.2 2880 11.8 7.0 2.0 2.6 4 3.5 1430 7.0 6.8 1.6 2.5
132 S M2AA 132 S 00620-c-0 42 112 M M2AA 112 M 00350-c-0 32
4 1.3 1455 3.5 6.5 2.6 3.3 8 0.7 720 2.5 4.4 1.7 2.7
2 8.3 2875 15.4 7.4 2.5 2.7 4 5.0 1450 9.9 6.4 1.5 2.3
132 M M2AA 132 M 00830-c-0 56 132 S M2AA 132 S 00500-c-0 48
4 1.7 1455 4.2 6.6 2.7 3.3 8 1.0 725 3.3 3.6 1.0 2.0
2 10 2910 19.0 5.9 1.5 2.3 4 6.8 1460 13.7 7.6 2.0 2.8
160 M M2AA 160 MA 01000-c-0 73 132 M M2AA 132 M 00680-c-0 59
4 2 1465 4.8 6.1 2.4 2.8 8 1.4 730 5.1 3.6 1.4 2.7
2 16 2915 28.5 6.6 1.8 2.4 4 10.5 1460 21 6.9 2.2 2.7
160 M M2AA 160 M 01600-c-0 94 160 M M2AA 160 M 01050-c-0 94
4 3.2 1465 7.0 6.3 2.5 2.8 8 2.2 735 7.4 3.7 1.5 2.3
2 19.5 2930 36 7.6 2.3 2.9 4 15.5 1460 30 6.9 2.2 2.6
160 L M2AA 160 L 01950-c-0 100 160 L M2AA 160 L 01550-c-0 117
4 4.5 1465 9.7 6.4 2.5 2.8 8 2.7 735 9.5 3.9 1.7 2.6
2 21.5 2935 38 7.0 2.1 2.6 4 17 1470 33 5.8 1.7 2.3
180 M M2AA 180 M 02150-c-0 137 180 M M2AA 180 M 01700-c-0 137
4 4.7 1465 10 5.3 2.1 2.3 8 3.4 730 11 4.3 1.2 1.9
2 26 2940 47 6.9 2.3 2.6 4 22 1475 43 6.7 2.0 2.6
180 L M2AA 180 L 02600-c-0 151 180 L M2AA 180 L 022000-c-0 161
4 5.2 1470 11 5.8 2.4 2.4 8 4.4 735 15 3.9 1.7 2.3
2 32 2940 58 7.1 2.0 2.5 4 29 1470 54 6.9 2.2 2.4
200 L M2AA 200 MLA 03200-c-0 180 200 L M2AA 200 MLA 02900-c-0 180
4 8 1465 16 6.2 2.0 2.2 8 6.5 730 17 4.2 1.9 1.9

200 L M2AA 200 MLB 03900-c-0 2 39 2950 69 7.4 2.0 2.6 4 33 1475 61 7.8 2.6 2.6
205 200 L M2AA 200 MLB 03300-c-0 205
4 10 1475 19 6.2 2.0 2.3 8 8 730 21 4.2 1.9 1.8
2 45 2955 76 7.4 2.0 2.6 4 42 1480 85 7.8 2.5 3.0
225 M M2AA 225 M 04500-c-0 235 225 M M2AA 225 SMB 04200-c-0 265
4 13 1475 25 5.3 2.0 2.1 8 10 740 27 5.0 2.2 2.3
4 50 1465 91 7.3 2.3 2.5
225 M M2AA 225 SMC 05000-c-0 265
8 11 735 28 4.7 2.0 2.0
4 60 1475 104 7.9 2.6 2.7
1500 and 1000 rpm synchronous, 4 and 6 poles. 250 M M2AA 250 SMB 06000-c-0
8 15 735 34 4.7 2.1 2.0
335

Two separate stator windings (Y/Y). 4 65 1484 121 7.5 2.7 2.9
280 S M2CA 280 SA 06500-c-0 445
8 15 743 38 5.3 2.8 2.3
4 80 1486 150 8.5 3.3 3.4
ATAL-4 280 M M2CA 280 SMA 08000-c-0 490
4 0.30 1400 0.9 3.3 1.5 2.0 8 20 743 50 5.4 2.9 2.6
71 M2AA 71 B 00030-c-0 6.5
6 0.10 950 0.56 2.3 1.4 2.1 4 90 1486 164 8.5 3.6 3.5
280 M M2CA 280 MB 09000-c-0 550
4 0.45 1400 1.3 3.7 1.7 2.1 8 23 742 56 5.4 2.8 2.6
80 M2AA 80 A 00045-c-0 8.5
6 0.15 960 0.73 2.6 1.3 2.2 4 110 1487 197 6.8 1.9 2.6
315 S M2CA 315 SMA 11000-c-0 730
4 0.65 1400 1.7 3.9 1.7 2.1 8 22 744 56 4.9 2.1 2.5
80 M2AA 80 B 00065-c-0 9.5
6 0.22 960 0.94 2.9 1.4 2.2 4 132 1486 235 6.8 2.0 2.6
315 M M2CA 315 MB 13200-c-0 850
4 1.0 1400 2.5 4.2 1.8 2.2 8 26 746 65 4.8 2.0 2.4
90 S M2AA 90 S 00100-c-0 13
6 0.3 940 1.2 2.6 1.0 1.7 4 160 1486 283 7.0 2.1 2.7
315 L M2CA 315 LA 16000-c-0 970
4 1.5 1400 3.5 4.3 1.7 2.1 8 32 743 80 4.8 2.1 2.5
90 L M2AA 90 L 00150-c-0 16
6 0.45 940 1.6 2.9 1.0 1.8 4 200 1489 340 6.8 1.4 2.8
355 M M2CA 355 MA 20000-c-0 1350
4 2.0 1430 4.5 5.0 1.8 2.4 8 40 745 90 4.8 1.3 2.5
100 L M2AA 100 LA 00200-c-0 20
6 0.6 960 2.0 3.3 1.0 1.9 4 250 1490 435 7.5 1.5 3.2
355 L M2CA 355 LA 25000-c-0 1550
4 2.5 1430 5.5 5.6 2.0 2.5 8 50 745 120 5.1 1.4 2.6
100 L M2AA 100 LB 00250-c-0 23
6 0.8 960 2.5 3.5 1.1 2.0
4 3.0 1445 6.3 6.0 1.3 2.3
112 M M2AA 112 M 00300-c-0
6 1.0 975 3.1 4.0 1.0 2.2
33 Voltage code
4 4.5 1460 9.2 6.5 1.5 2.3 2 = 400 V
132 S M2AA 132 A 00450-c-0 48
6 1.5 985 5.1 4.2 1.0 2.2
5 = 500 V
4 6.0 1460 12 7.1 1.8 2.5
132 M M2AA 132 M 00600-c-0 59
6 2.0 980 5.6 4.5 1.3 2.0
4 10.5 1460 21 6.4 2.0 2.5
160 M M2AA 160 M 01050-c-0 94
6 3.5 965 8.6 4.1 1.3 1.7 1) Conversion factor for 500 V supply = 0.80.
4 14.5 1460 28 6.9 2.2 2.6
160 L M2AA 160 L 01450-c-0 117
6 4.5 970 11 4.6 1.5 1.9 2) Is
4 16 1470 31 6.3 1.9 2.5 = ratio of motor start current to motorfull-load current.
180 M M2AA 180 M 01600-c-0
6 5 980 12.5 4.6 1.5 2.0
137 IN
4 20 1470 39 7.2 2.4 2.7
180 L M2AA 180 L 02000-c-0 161
4 6.5 980 16 5.0 1.8 2.0
4 23 1475 43 7.7 1.6 2.8
200 L M2AA 200 MLA 02300-c-0 175
6 7.2 985 15 7.8 1.9 2.9
4 30 1470 54 7.7 1.6 2.7
200 L M2AA 200 MLB 03000-c-0 200
6 9 985 18 7.9 1.7 2.5
4 34 1470 60 7.7 1.5 2.7
225 M M2AA 225 SMB 03400-c-0 225
6 11 985 21 6.7 1.3 2.3
4 42 1475 75 8.4 1.7 3.0
225 M M2AA 225 SMC 04200-c-0 255
6 14 985 27 6.8 1.4 2.3
4 63 1475 110 7.5 2.4 2.7
250 M M2AA 250 SMB 06300-c-0 335
6 18.5 985 40 7.3 3.0 2.6
4 77 1486 144 7.6 2.4 2.9 Voltage code
280 S M2CA 280 SA 07700-c-0 490
6 25 991 54 7.7 3.2 2.7
2 = 400 V
4 90 1485 161 7.4 2.3 2.7
280 M M2CA 280 MB 09000-c-0 550 5 = 500 V
6 28 991 58 7.7 3.2 2.8
Dimensions - Motors Page 104

IEC sizes 63-100 IEC sizes 112-132


L
L1, L2 AC

HD HD
HC

H H

K KA K BC A
A E C B
E C B B' AB
BB AB BB

IEC sizes 160-180 IEC sizes 200-250


L AC L AC

HD HD
AC

H H

K K A
A E C B
E C L AB
AB B'
B'
BB
BB

IECsizes 280-355 Shaft journal


F

HD
HC GA
H

DB
E C B A
B' AB D
BB
L

Size
as per Single- Two-
ABB Motors speed speed A1) AB AC B1) B'1) BB C D1) DB E EA F1) GA H1) HC HD K KA L L12) L23)
63 B All All 100 120 - 80 - 98 40 14 M5 30 - 5 16 63 123 150 7 10 213 - -
71 (A, B) All All 112 136 - 90 - 112 45 14 M5 30 - 5 16 71 141 172 7 11 239 - -
80 (A, B) All All 125 154 - 100 - 125 50 19 M8 40 - 6 21.5 80 159 192 10 14 272 - -
90 S All All 140 170 - 100 - 125 56 24 M8 50 - 8 27 90 179 212 10 14 295 - -
90 L All All 140 170 - 125 - 150 56 24 M8 50 - 8 27 90 179 212 10 14 320 - -
100 L(A) All All 160 197 - 140 - 172 63 28 M10 60 - 8 31 100 199 236 12 15 358.5 - -
112 M All All 190 222 221 140 - 168 70 28 M10 60 40 8 31 112 - 258 12 - - 3614) 3884)
132 S (A, B) All All 216 262 261 140 1784) 212 89 38 M12 80 50 10 41 132 - 295.5 12 - - 4474) 4474)
132 M All All 216 262 261 1404) 178 212 89 38 M12 80 50 10 41 132 - 295.5 12 - - 4474) 481,54)
160 5) 5) 5) 254 310 - 210 2544) 287.5 108 42 M16 110 - 12 45 160 - 368.5 15 - 602.5 - -
160 6) 6) 6) 254 310 - 2104) 254 287.5 108 42 M16 110 - 12 45 160 - 368.5 15 - 643.5 - -
180 7) 7) 7) 279 340 - 241 2794) 316 121 48 M16 110 - 14 51.5 180 - 403.5 15 - 680 - -
180 8) 8) 8) 279 340 - 2414) 279 316 121 48 M16 110 - 14 51.5 180 - 403.5 15 - 700.5 - -
200 ML. 2-8 All 318 380 386 2674) 305 365 133 55 M20 110 - 16 59 200 - 496.5 18 - 773 - -
225 SM. 4-8 4/8 356 418 425 286 3114) 360 149 60 M20 140 - 18 64 225 - 542 18 - 865 - -
225 SM. 2 2/4 356 418 425 2864) 311 360 149 55 M20 110 - 16 59 225 - 542 18 - 835 - -
225 SM. 4-8 4/6, 4/8 356 418 425 2864) 311 360 149 60 M20 140 - 18 64 225 - 542 18 - 865 - -
250 SM. 2 - 406 474 471 3114) 349 409 168 60 M20 140 - 18 64 250 - 590 22 - 872 - -
250 SM. 4-8 4/6, 4/8 406 474 471 3114) 349 409 168 65 M20 140 - 18 69 250 - 590 22 - 872 - -
280 SA 2 - 457 545 - 368 - 450 190 65 M20 140 - 18 69 280 558 730 24 - 1060 - -
280 SA 4-8 4/8, 4/6 457 545 - 368 - 450 190 75 M20 140 - 20 79.5 280 558 730 24 - 990 - -
280 SMA 2 - 457 545 - 368 419 501 190 65 M20 140 - 18 69 280 558 730 24 - 1060 - -
280 SMA 4-8 4/8 457 545 - 368 419 501 190 75 M20 140 - 20 79.5 280 558 730 24 - 1060 - -
280 MB - 4/6 457 545 - 419 - 501 190 75 M20 140 - 20 79.5 280 558 730 24 - 1120 - -
315 SA 2 - 508 622 - 406 - 535 216 65 M20 140 - 18 69 315 627 820 28 - 1095 - -
315 SA 4-8 - 508 622 - 406 - 535 216 80 M20 170 - 22 85 315 627 820 28 - 1125 - -
315 SMA 2 - 508 622 - 406 457 535 216 65 M20 140 - 18 69 315 627 820 28 - 1195 - -
315 SMA 4-8 - 508 622 - 406 457 535 216 80 M20 170 - 22 85 315 627 820 28 - 1125 - -
315 MB 2 - 508 622 - 457 - 540 216 65 M20 140 - 18 69 315 627 820 28 - 1195 - -
315 MB 4-8 - 508 622 - 457 - 540 216 80 M20 170 - 22 85 315 627 820 28 - 1225 - -
355 SA 2 - 610 714 - 500 - 584 254 70 M20 140 - 20 74.5 355 715 920 28 - 1310 - -
355 SA 4-8 - 610 714 - 500 - 584 254 100 M24 210 - 28 106 355 715 920 28 - 1380 - -
355 MA 2 - 610 714 - 560 - 644 254 70 M20 140 - 20 74.5 355 715 920 28 - 1370 - -
355 MA 4-8 - 610 714 - 560 - 644 254 100 M24 210 - 28 106 355 715 920 28 - 1440 - -
355 MB 2 - 610 714 - 560 - 644 254 70 M20 140 - 20 74.5 355 715 920 28 - 1370 - -
355 MB 4-8 - 610 714 - 560 - 644 254 100 M24 210 - 28 106 355 715 920 28 - 1440 - -
355 LA 4-8 - 610 714 - 630 - 714 254 100 M24 210 - 28 106 355 715 920 28 - 1520 - -

1) Tolerances 2) Single speed motors and two-speed motors 132S.


A, B ISO js14 3) Two speed motors exc. 132S.
D = 14-28 ISO j6 4) Not in conformity with IEC.
D = 38-48 ISO k6 5) M-2, MA-2, M-4, M-6, M-8, MA-8, L-2, L-4, L-6
D = 55-100 ISO m6 MA-2/4, M-2/4, L-2/4, M-4/6, M-4/8, LB-2 och LB-4
F ISO h9 6) L-8, L-4/6, L-4/8, LB-6 och LB-8
H = 63-250 +0 -0.5 7) M-2, M-4, L-6, L-8, M-2/4, M-4/6, M-4/8 och LB-2
H = 280-355 +0 -1.0 8) L-2/4, L-4/6, L-4/8, LB
Ordering key - Regulating damper DMEG Page 105

Regulating damper DMEG-aaa-bbb


Size
016, 020, 025, 031, 040, 050, 063.

Material, finish
o
001 = Standard material, GA80-RAL5007 int. and ext. Fully welded Max. temperature 120 C.
002 = Standard material, GP40-01 int. and ext. Fully welded Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Fully welded
300 = SS 2333 throughout. Fully welded
400 = SS 2343 throughout. Fully welded
1) o
GP40-01 primer can be used where temperatures exceed 120 C. This primer tolerates temperatures up to
150oC and vaporises at higher temperatures without emitting any toxic substances.
Counterflange HCEZ-25-bbb-cc
Size (= damper size)
Material
01 = unpainted steel (for welding in).
03 = SS 2333.
04 = SS 2343.

Description DMEG damper size 063


The DMEG damper is primarily a regulating and shut-off When connecting flue gas duct HCEZ-aa-bbb-ccc to a size
damper for flue gas installations. The blades are contra-rota- 063 regulating damper, the duct can only be fitted to the inlet
ting to ensure symmetrical gas flow and favourable control side and not the outlet side.
characteristics.
The damper can be regulated by hand or by motor. Dimensions and weights
Max. pressure difference: 5 kPa. A
Max. operating temperature: 350C
D
Leakage flow: approx. 2% of full flow.
B
The dampers basic components are: casing, two blades, Open
blade regulating mechanism and rubber-covered handle. A
wing nut is used to lock the damper in the desired position.

Total pressure drop


at various blade angles and for air with a density of 1.2 kg/m3.

Blade angle a degrees Gas flow


Total pressure drop, mm WG

0 10 20 30 40 50 60 7090
1000 a 100
Closed
Total pressure drop, Pa

500 50
400 40
300
n

30
ope

200 20
ully
er f

100
mp

10
Da

C
50 5
0,5 1 2 3 4 5 10 20 304050
Air velocity, m/s

Motor control details


Size A B C D Weight, kg
Damper motor is not included. 016 164 164 213 5
Size 016 020 025 031 040 050 063 020 204 - 193 213 6
Actuating torque, Nm 5 5 5 9 14 21 31 025 254 226 308 9
The actuating torque figures are valid up to a pressure drop 031 319 28 262 308 10
of 1 kPa across the damper. At greater pressure drops, the 040 404 70 310 308 13
actuating torque increases proportionally with the increased 050 504 120 361 308 20
pressure drop. Thus, where the pressure drop is 1.5 kPa, 063 634 185 427 308 26
actuating torque can be calculated by multiplying this figure
NB! Flanges conform to ISO 13351.
by a factor (k) of I.5. Where the drop is 2 kPa, k = 2, etc.
Inlet vane control assembly HXEG - General description Page 106

Description
The HXEG inlet vane control assembly is designed for flow control in centrifugal fans and is connected directly to the
fan inlet flange. The assembly is of a robust construction and provides highly economic flow control. The size range fol-
lows that of the HC fans and the flanges comply with ISO 13351. NB! The HXEG must not be connected directly to the
fan without checking that the anti-vibration mountings can cope with the increased component load on the fan.
- The HXEG is available in sizes 031-160. The max. permitted gas temperature is 350C.
- Robust construction, (handles pressures up to 20 kPa).
The assembly's chief components are: casing, guide vanes, hub and control mechanism. The casing has connecting
flanges on both ends. The guide vane shaft is supported on bearings in the hub and casing. The hub is supported by
radial stays. The assemblies can be connected to fans which, under fully throttled conditions at 20C, will give max.
pressure rise of 20 kPa.
Regulation is either by an actuator or manually with the lever.

Control
The assembly can be equipped with an actuator. Four different actuators are available as accessories: HXEZ05 (electric),
HXEZ-06 (electric), HXEZ-07 (pneumatic) and HXEZ-08 (electric).

Actuator
Actuators are double-acting and are console mounted on the assemblies.
Actuator specifications

HXEZ- Type Max. actuation pressure (N) Electrical details Environment Control

24 VDC, 9A -20/+40oC Can be provided


05 Electric 3000
IP 51 protected from the rain with a potentiometer

230 V 50/60Hz -20/+40oC Can be provided


06 Electric 2500
200 W, IP 51 protected from the rain with a potentiometer

Control signal 20-100 kPa


07 Pneumatic 2900 -20/+70oC
Working pressure 700 kPa

230 V 50/60Hz Equipped with


08 Elektric 2700 -20/+60oC
230 W, IP 54 100 ohm potentiometer

Sizes
HXEG 031, 040, 050, 063, 071, 080, 090, 100, 112, 125, 140 and 160.
The assemblies are suitable for standard fans. Assemblies and fans have common size codes.

Principles of operation
The guide vanes, which can be set in various positions, impart a rotary motion to the gas stream as it reaches the
impeller. This lowers the pressure and output characteristics of the fan and ensures good operating economy over a
relatively wide control range.

Pressure drop
The pressure drop with the vanes fully open is 0.2 pd where pd is the dynamic pressure.

Right-hand and left-hand models


Impeller
Assemblies are available as right-hand models (for right-
hand rotation fans i.e. fans where the impeller rotates
clockwise as seen from the drive side) or left-hand models
(for left-hand rotation fans i.e. fans where the impeller rota-
tes anti-clockwise as seen from the drive side).

Material and finish


Right-hand model Left-hand model
Refer to the ordering key on page 107.

Instructions
Installation and maintenance instructions are
included in the delivery.
Ordering key - Inlet vane control assembly HXEG and accessories Page 107

Inlet vane control assembly HXEG-aaa-bbb-c


Size (fan size)

Material, finish
001 = Standardmaterial, GA80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Fully welded Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Fully welded Max. temperature 120oC.
290 = Standard material, hot-dip galvanized. Fully welded
300 = SS 2333 throughout. Fully welded
400 = SS 2343 throughout. Fully welded

Version
1 = right-hand.
2 = left-hand.

Protective casing HXEZ-a-bbb-ccc-d


Variant
4 = For inlet vane control assemblies without actuators.
5 = For inlet vane control assemblies with actuators.

Size (fan size)

Material, finish
001 = Standard material, GA80-RAL5007 int. and ext. Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Max. temperature 120oC.
290 = Standard material, hot-dip galvanized.
300 = SS 2333 throughout.
400 = SS 2343 throughout.

Version
1 = right-hand.
2 = left-hand.

Actuator HXEZ-aa-bbb-ccc-d
Type of actuator. Refer to table on page 106
aa = 05, electric.
aa = 06, electric.
aa = 07, pneumatic.
aa = 08, electric.

Size (fan size)

Material, finish (bracket)


001 = Standard material, GA80-RAL5007 int. and ext. Max. temperature 120oC.
002 = Standard material, GP40-01 int. and ext. Max. temperature 150oC. 1)
072 = Standard material, GA80TD80-RAL5007 int. and ext. Max. temperature 120oC.
112 = Standard material, GA80TB80-RAL5007 int. and ext. Max. temperature 120oC.
290 = Standard material, hot-dip galvanized.
300 = SS 2333 throughout.
400 = SS 2343 throughout.
Version
1 = right-hand
2 = left-hand.

1)
GP40-01 primer can be used where temperatures exceed 120oC. This primer tolerates temperatures up to 150oC
and vaporises at higher temperatures without emitting any toxic substances.
Inlet vane control assembly HXEG - Dimensions and weights Page 108

HXEG HXEG 031 with inlet taper piece HXEG 040 - 160

G
50
Open Closed 8 holes 12
10,5 366 pitch

491 C
Hold, t = 8

315 D
400 K
ins. ins.

R holes F H vanes

E B
210
435 A

Gas flow Gas flow

Size A B C D E F G H K R Weight
031 - - - - 448 12 41.5 7 628 12 47
040 264 225 491 400 448 12 41.5 7 628 12 38
050 289 225 596 500 551 12 41.5 7 728 12 40
063 348 250 671 630 698 14 66.5 7 858 16 52
071 290 225 735 710 775 14 51.5 11 940 16 68
080 306 235 805 800 869 14 51.5 11 1030 24 76
090 322 235 885 900 958 14 56.5 11 1130 24 94
100 354 265 965 1000 1067 14 71.5 11 1230 24 108
112 368 280 1200 1120 1200 18 90.5 13 1375 32 141
125 387 300 1266 1250 1337 18 90.5 13 1507 32 171
140 454 335 1341 1400 1475 18 135.5 13 1657 32 211
160 493 375 1441 1600 1675 18 145.5 13 1857 40 298

ao Inlet vane Actuator travel


control assembly for different E
HXEG attachment points
C Max.
Size C Max. C Min. Max. Min. a
o

Left-hand model C Min. Right-hand model


031 200 172 469 400 28.2
60 040 200 172 469 400 28.2
050 200 168 552 450 23.8
063 200 161 650 515 19.6
071 200 156 711 555 17.7
080 200 156 777 600 16.0
E Min. E Max. 090 200 153 858 650 14.4
100 200 150 942 700 13.1
112 200 148 1031 760 11.8
125 200 146 1133 825 10.7
140 200 144 1255 902 9.6
160 200 142 1412 1002 8.5
Inlet vane control assembly HXEG - Dimensions and weights Page 109

Actuators HXEZ-05, -06, -07 and -08

570 570

ao ao

U U

10
Left-hand model Right-hand model

Gas flow

HXEZ-05, electric HXEZ-06, electric HXEZ-07, pneumatic HXEZ-08, electric


Size a U Wt. Size a U Wt. Size a U Wt. Size a U Wt.
031 24.8 532 14 031 24.8 532 14 031 24.8 532 16 031 24.8 532 22
040 24.8 532 14 040 24.8 532 14 040 24.8 532 16 040 24.8 532 22
050 21.2 601 14 050 21.2 601 14 050 21.2 601 16 050 21.2 601 22
063 17.8 707 16 063 17.8 707 16 063 17.8 707 18 063 17.8 707 24
071 16.2 770 16 071 16.2 770 16 071 16.2 770 18 071 16.2 770 24
080 14.8 839 16 080 14.8 839 16 080 14.8 839 18 080 14.8 839 24
090 13.4 923 16 090 13.4 923 16 090 13.4 923 18 090 13.4 923 25
100 12.2 1009 18 100 12.2 1009 18 100 12.2 1009 19 100 12.2 1009 26
112 11.2 1100 18 112 11.2 1100 18 112 11.2 1100 19 112 11.2 1100 26
125 10 1204 20 125 10 1204 20 125 10 1204 21 125 10 1204 28
140 9.2 1328 22 140 9.2 1328 22 140 9.2 1328 23 140 9.2 1328 30
160 8 1487 23 160 8 1487 23 160 8 1487 24 160 8 1487 30

Required operating force 10000

For dust laden flue gases, the operating forces


160
indicated on the chart increase by 5000
kPa 140
2,5 x a (Newton) 4000
125
where "a" is the size of the inlet vane control 600 3000
112
500
assembly 2000 100
400
Required operating force at radius Emin, N
Min. feed pressure for HXEZ-07 actuator, kPa

090
When the pneumatic actuator HXEZ-7 is used in 300
080
the above operating conditions, the forces given 200 1000 071
by the chart must be increased by 0.5 x a kPa. 063
Using the calculated actuating force as the star-
ting point, the necessary min. pressure can be 100 500 050
400
read directly from the chart. 040
300
031
50
200
40
Size

30
100

500 1000 2000 3000 5000 10000 20000


Total pressure rise, Pa, with fully throttled fan
Inlet vane control assembly HXEG- Example calculation Page 110

Control using the inlet vane control assembly. 100

The adjacent chart shows power demand as a function L = throttling curveA


of assembly controlled gas flow at constant fan speed.
80
Gas flow and power demand are stated as percentages
of flow and demand (respectively) with the inlet vane
control assembly fully open.
60
Further details regarding use of the chart are given in the
example calculation below.

Power demand, %
40
Fans HCBB, HCGB, HCMB and HCHB L2
(all trottling curves).
L3
20 L4
L5
L6
Fans HCLP, HCMP and HCHP
(all trottling curves).
0
0 20 40 60 80 100

L2 - L6 Fans HCBT, HCLT, HCMT and HCHT Gas flow %


( at the appropriate throttling curve).

Example calculation
A size 100 HCMB centrifugal fan is controlled by an inlet vane control assembly and is to operate at constant speed at
two points (load 1 and load 2). Determine the speed and power demand for both operating points.

Chart 1 Chart 2

Gas flow, m3/h

0 50 000 100 000 140 000


80
9000
Power demand, %, Pe / Peo x

1 n=
3 HCMB
13
8000 2
70
r/m 100
in
7000 4 60
12
00
6000
I 5
5000
Tota pressure rise, Pa

100 40 MB
4000
0
II HC

3000 800

2000
20
600
10
1000 400

0 0
0 10 20 30 39 0 20 40 60 80 100
0 400
600 Gas flow, m3/s Gas flow, %, q / qo x 100
800
Power demand, kW

00
10
qo and Peo are the gas flow and power demand respectively
100 when the inlet vane control assembly is fully open.
00
12

nmax
< 100C 1370 r/min
200C 1260 r/min in
r/m
200 350C 1080 r/min 70
13
J (= 1/4 GD2) = 79 kg m2 n=
220
Inlet vane control assembly HXEG - Example calculation, cont. Page 111

Given Load 1 Load 2

Gas flow at 0C. 1013 mbar Nm3/s 13 10

Gas temperature C 200 180

Gas density at 0C. 1013 mbar kg/Nm3 1.35 1.35

Barometric pressure mbar 990 990

Static pressure at the fan inlet Pa -2500 -2000

Total pressure rise across the fan unit Pa 3400 2500

Calculation

Absolute pressure at the fan inlet Pa1 Pa 99 000 - 2500 = 96 500 99 000 - 2000 = 97 000

Absolute temperature, T K 273 + 200 = 473 273 + 180 = 453

1.35 x 273 96 500 = 0.742 1.35 x 273


Gas density at the fan inlet, r kg/m3 x x
97 000 = 0.778
473 101 300 453 101 300

13 x 473 101 300 = 23.64 10 x 453 101 300 = 17.33


Actual gas flow at the fan inlet, q m3/s x x
273 96 500 273 97 000

1 1
Gas velocity at the fan outlet, v m/s 23.64 x = 29.6 17.33 x = 21.7
1 x 0.8 1 x 0.8
Size of the outlet, see fan dimension sketch

0.742 0.778
Dynamic pressure at the fan outlet, pd Pa x 29.62 = 325 x 21.72 = 183
2 2

Pressure drop across the open inlet vane control assembly Pa 0.2 X 325 = 65 0.2 X 183 = 37

Total pressure rise across the fan Pa 3400 + 65 = 3465 2500 + 37 = 2537

1.2 = 5604 1.2 = 3923


Total pressure rise across the fan at r = 1.2 kg/m3 Pa 3465 x 2537 x
0.742 0.776

Fan speed from chart 1, n rpm 1240 1240

Power demand from chart 1, r = 1.2 kg/m3 kW 155 -

0.742
Power demand at r = 0.742 kg/m3 kW x 155 = 95.8 -
1.2

Pd 283 = 2.69
Throttling curve number, L, L = 10 - 10 x
Pt 3923

Gas flow (qo) with the assembly fully open, the same
throttling curve and fan speed n (1240 rpm in this case) m3/s - 21.8

Power demand (Peo) with the assembly fully open, the sa-
me throttling curve and fan speed n (1240 rpm in this case) kW - 149

q/qo - 17.33 = 0.794


21.8

Pe/Peo - 0.695

Power demand at r = 1.2 kg/m3 kW - 0.695 X 149 = 103.6

0.778
Power demand at r = 0.778 kg/m3 kW x1036= 67.2
- 1.2
The calculation shows that fan speed should be 1240 rpm. The power demand at working point 1 will then be 95.8 kW and 67.2 kW at working point 2, (allowance must
also be made for losses in the bearings and belt drive).
Centrifugal fan HC - Fan theory Page 112

Symbols Note: Fans which are designed to be normally connec-


ted to ducting on the outlet side are sometimes operated
L = throttling curve or number
with-out outlet ducting. In these cases, the fan chart
n = fan speed rpm (which assumes connection to the ducting) can be used
P = theoretical power demand kW on condition that an outlet loss exceeding 1 x pd is taken
pa = absolute pressure Pa into account. For centrifugal fans, this loss can generally
be estimated as 1.2 x pd.
Pe = actual power demand kW
Unless otherwise specified, the fan chart's power demand
pd = dynamic pressure at the fan outlet Pa
curves are for the power supplied through the shaft to
Dpt = total pressure rise between the fan the impeller. Mechanical losses may be significant in
inlet and outlet Pa belt-driven fans and must be taken into account when
deciding motor rating. Values of 5 - 15 % can be used as
q = gas flow at fan inlet 3 3
m /s (m /h)
a guide; the upper value applies to rated powers in the
T = absolute temperature K region of 1 kW and should be successively reduced to
v = gas velocity at the fan outlet m/s 5% for ratings of 100 kW and above.
r = gas density kg/m3
Definition of fan efficiency
h = fan efficiency %
h= P x 100%
Pe
Principle of operation
Flow through a fan is characterised by an increase in total where Pe is the actual power demand and P the theoreti-
gas pressure as energy is imparted to the gas in crossing cal as defined by
the impeller. The velocity increase at the fan inlet translates q x Dpt
into a definite rise in dynamic pressure which results in an P= kW,
1000
equal magnitude decrease in static pressure. The increase
in total pressure occurs only at the fan impeller; in the scroll where q is given in m3/s and Dpt in Pa.
casing, the dynamic pressure is converted into static pres-
sure. The gas flow and the outlet area determine the dyna- Using the fan chart
mic pressure of the gas at the outlet; the total pressure deli- Gas flow in the fan chart always refers to the actual flow
vered at the fan outlet thus always includes a certain com- at the fan inlet.
ponent of dynamic pressure.
Gas density ro is often characterised by a temperature
Fan data To and pressure Pao different from temperature T and
pressure Pa at the fan inlet. The density at the fan inlet is
The fan chart calculated using the following formula:
Fan data is usually shown in the form of a chart. In this
chart, the total pressure rise generated by the fan is plot- To pa
r = ro x x
ted as a function of the gas flow at a number of fixed fan T pao
speeds. The corresponding power characteristics are usu- If the required flow qo has been specified at a temperatu-
ally shown in the same chart which also includes auxiliary re To and pressure pao which differs from the temperatu-
curves, (throttling curves), numbered from 1 to 10. These re T and pressure pa prevailing at the inlet, the flow q at
represent different system characteristics, for which the the fan inlet can be calculated in accordance with the for-
required pressure rise is proportional to the square of the mula:
gas flow. The throttling curve numbers are as follows:
T pao ro
q = qo x x ; or q = qo x r
To pa
Curve L = 10 represents the dynamic pressure at the fan Unless otherwise stated, the total pressure rise Dpt and
outlet.
power demand P given in the fan chart is for a gas densi-
For fans which can be connected to ducting on both the ty of 1.2 kg/m3 at the fan inlet, this corresponding to the
inlet and outlet sides, the fan chart shows the total pressure density of air at 20C, normal barometric pressure (1013
rise Dpt from the inlet to the outlet duct assuming that the mbar - 760 mm Hg) and a relative humidity of 50%.
cross-sectional area of the outlet ducts is the same as the If gas density r is other than 1.2 kg/m3, a required total
fan's nominal outlet area and that the outlet ducts have a pressure rise Dpt shall be read from the chart using the
straight length of at least 2.5 x outlet diameter: correction:
4 outlet area 1,2
2,5 x Dptchart = r x Dpt
p
The fan speed and power demand Pechart can then be
Free inlet fans suffer an inlet loss due partly to a certain read from the chart. Finally, actual power demand is
contraction at the connection piece and partly to the ne- obtained using the formula:
cessary use of a protective grill. These losses are speci-
r
fied in the catalogue sections dealing with the individual Pe = x Pechart
fans. 1,2
Centrifugal fan HC - Fan theory, cont Page 113

Fan data at other fan speeds Solution


If fan speed is changed but the installation is otherwise The key charts on page 58 determine the pressure class
unaltered, gas flow, pressure rise and power demand are and size of the fan variants. The charts are based on total
affected as follows: pressure rise across the fans at a gas density of 1.2 kg/m3.
q1 n1 In this example, allowance must be made for inlet losses
q2 = n2 (free inlet fan). These losses have here been put at 5%. The
2 given total pressure of 4000 Pa will thus increase by 5% plus
Dpt1 n1 a correction factor for density:
= n
Dpt2 2
1,2
3 4000 x 1,05 x = 4300 Pa
P1 n1 1,16
=
P2 n2 The chart shows that the HCM-050 fan is suitable for 6 m3/s
and 4300 Pa. HCM models are available with either B or P
Fan efficiency is not affected. impellers.
Example: a 10% increase in fan speed increases: In many cases, several types and sizes of fan will be suitable.
gas flow by 10% Choice will then be determined by requirements such as low
pressure by 21% power demand, low sound level, compactness, low installa-
power demand by 33% tion cost and the gas to be handled. For clean gas, the
The adequacy of a fan's power rating must always be HCMB-050 fan charts on page 68 apply.
checked before any increase in speed.
Ref. Data Unit Value
Given Gas flow m3/s 6
Sound data Given Total pressure Pa 4000
o
Given Temperature C 40
Sound data is given as sound power level (ref. 10-12 W). Given Density kg/m2 1.16
The sound power level per octave band is the sound emitted Total pressure at a density of 1.2 = 4000 x 1.2/1.16 Pa 500
by the fan and is independent of the acoustic characteristics Page 68 Dynamic pressure at a density of 1.2 Pa 4313
Page 59 Inlet losses, inlet taper piece
of the surroundings. This sound level is the correct basis for HCVZ-21 = 0.35 x 400 Pa 500
acoustic calculations. Page 112 Total pressure rise, including inlet losses,
at a density of 1.2 Pa 4313
Some fan manufacturers still publish sound pressure levels Page 68 Fan speed rpm 2300
even though these vary with distance from the fan and the Page 68 Fan power demand at a density of 1.2 kW 32
acoustic characteristics of the surroundings. Sound pressure Page 112 Fan power demand at a density of 1.16 kW 31
Belt losses (say 5%) kW 1.5
levels, sometimes weighted as dB(A) or dB(C) values, are Minimum necessary motor power kW 32.5
considerably lower than the corresponding sound power Page 68 Moment of inertia kgm2 3.2
level Lwt. To illustrate this: with a free inlet fan and hemisp- Page 45 Sound power level to the surroundings dB 102
Suitable motor size kW 37
herical sound propagation, at a distance of 3 m from the Page 101 Starting time s 3
fan, the dB(A) value is 17 - 25 dB lower (depending on fan
speed and blade type) than the total sound power level. Controlling centrifugal fans with inlet guide vanes
A centrifugal fan running at a constant speed can be controlled
Selection of fan type
by means of inlet guide vanes fitted at the fan inlet.
Centrifugal fans are available with either direct drive or belt When in use, the guide vanes impart a rotary motion to the
drive. Direct-driven fans are compact and inexpensive and gas flow corresponding to the impeller's direction of rotation.
have no transmission losses. Belt drive offers great flexibility This lowers the pressure characteristic of the fan unit (fan
and easy adjustment in setting the desired operating point. plus guide vanes) and leads to a consequent fall in the unit's
If variable air flow is required, centrifugal fans can be equipped power demand. Control by guide vanes is considerably more
with, for example, inlet guide vanes. Operating costs will economical than control by system throttling dampers.
then be comparatively low, (especially with moderate fan A chart on page 110 shows how power demand alters with
adjustment) and capital investment is also modest. If better the use of guide vanes.
economy in fan regulation is required, variable speed
motors are available. Centrifugal fans can be optimised for
high efficiency and low sound level, the different types of
impellers giving the fans an extremely wide field of application.

Selection of fan size


Several fan sizes can usually be selected for a given flow
and a given pressure rise.
HCEZ-21 Inlet taper piece
Example
Select a belt-driven fan for Fan Duct
a gas flow of 6 m3/s
a total pressure of 4000 Pa
a gas temperature of 40C
a barometric pressure of 1013 mbar
a density of 1.16 kg/m3
The fan is to be installed with a free inlet.
Vibration and insulation of structure borne sound Page 114

General Installation considerations


Machines with rotating parts generate vibrations which, For all vibration and noise insulation it is important to
when the machine is rigidly mounted, can be propagated ensure that the vibrating system is free to move in all
through floor and walls. These vibrations can be dama- directions. There must not be any rigid connections
ging and may also result in disturbing noise (structure between the vibrating system and the fabric of the buil-
borne sound) being generated. As a general rule, vibra- ding, (see the diagram below).
tions which may be damaging to property have the same Ducts connected to a fan should have soft, flexible con-
frequency as the machine's frequency of rotation. necting pieces. Furthermore, even where a fan has flexib-
However, structure borne sound may also be generated le connecting pieces, ducts in which there is a high level
by higher frequency vibrations from motors, gears and so of noise should not be rigidly connected to floors and
on. These vibrations can be considerably reduced by walls which are in direct communication with noise-sensi-
elastic mounting of the machine, i.e. insulating the tive areas. High noise levels in a duct may convert into
machine from its bed by means of elastic components. vibrations which, with rigid mounting, can be transmitted
Fans installed near to noise-sensitive areas must there- within the building as structure borne sound. Where a
fore be well dynamically balanced and also have good duct passes through a concrete wall, a layer of mineral
vibration and structure borne sound insulation. Insulation wool packed between wall and duct provides good struc-
is achieved using anti-vibration mountings and flexible ture borne sound insulation. If, for reasons of heat or
connecting pieces. Of the six different modes of vibration noise, a fan is insulated with mineral wool covered by an
possible in a machine, a conventional fan installation external metal housing, the housing must not extend
need generally only take vertical vibration into account. beyond the connecting pieces as direct contact can then
easily arise between the vibrating system and the fabric
Vibration insulation of the building.
Vibration insulation can be accomplished by mounting
the fan and motor on a common foundation resting on a
number of carefully designed and selected elastic com-
ponents.
An insulated system of this type will vibrate in such a
fashion that residual forces for imbalance will be absor- 5
bed by the forces for inertia inherent in the system mass.
6
The amplitude of vibration in an insulated system is hig-
her than in a rigidly mounted system but the force trans-
mitted to the foundation is considerably less, amounting, 3
in favourable cases, to no more than a few per cent of
the forces transmitted by a rigidly mounted system.
Standardised elastic components made from rubber are
normally used in the vibration insulation of fans. Where 4
2
fans operate at extremely low speeds, it may sometimes
1
be beneficial to use steel coil springs as these impart a
low, natural frequency.

Insulation of structure borne sound Schematic of fan, mounting and insulation.


In rigid installations, disturbing structure borne sound can
be generated even by low speed fans due to high-fre- 1. Anti-vibration mounting.
quency vibrations from motors, bearings, etc. 2. Foundation.
Consequently, when such fans are sited near noise sen- 3. Flexible connecting pieces.
sitive areas they must also have some form of insulation. 4. Pads of vibration insulating material.
Rubber components are best for this type of insulation as 5. Suspension with vibration insulating material.
their sound insulation properties are much better than 6. Mineral wool material typical thickness approx. 25 mm.
those of steel.
Fan torque curves
The following formulae show the necessary torque on starting a fan. Although gas resistance and
friction have been taken into account no allowance has been made for impeller acceleration.
Pmax.
Md max. = 9555 x Nm
nmax.
Pmax. = Fan power demand at final speed kW
nmax. = Final speed of the fan rpm
Md max.
Md = 2 x n2
n max.
Md min. is set at 5-10% of Md max.

The calculation assumes that the fan follows the same throttling curve throughout the entire
starting process.

Fan type ...................................................................

Start with closed/open vanes


Density .................. kg/m3
Speed n .................. rpm
Power demand at full speed P .................. kW
Moment of inertia J = WR2 .................. kgm2

Starting torque as a function of speed, disregarding acceleration of masses.

Torque
% of Md
100

50

0
0 50 100
Speed %
We Bring Air to Life

Solutions for all your air climate and air movement needs
Flkt Woods is a global
Flkt Woods is providing solutions for ventilation and air climate for buildings as
leader in air management. well as fan solutions for Industry and Infrastructure.
We specialise in the design
Air Handling Units (AHUs) Fans
and manufacture of a wide
Modular, compact and small AHU Advanced axial, centrifugal and
range of air climate and air units. Designed to ensure optimisa- boxed fans for general and specialist
movement solutions. And tion of indoor air quality, operational applications. Comprehensive range
our collective experience performance and service life. including high temperature and ATEX
compliant options. Engineered for
is unrivalled. Air Terminal Devices and Ducts energy efficiency and minimised life
Supply and exhaust diffusers and cycle cost.
Our constant aim is to
valves for installation onwalls, ceiling
provide systems that or floor are all included in our large
Chillers
precisely deliver required range and fit all types of applications. Air-cooled and water-cooled chillers
function and performance, with cooling capacity up to 1800kW.
Chilled Beams Designed to minimised annual energy
as well as maximise consumption in all types of buildings.
Active induction beams for ventilation,
energy efficiency. cooling and heating, and passive
convection beams for cooling. For
Controls and drives
suspended or flush-mounted ceiling Variable speed drives and control
installation and multi-service config- systems, all tested to ensure total
uration. With unique Comfort Control compatibility with our products.
and Flow Pattern Control features. Specialist team can advise on energy
Copyright 2010 Flkt Woods Group

saving and overall system integration.


Residential ventilation
A complete range of products for
Acoustical products
residential ventilation. Consists of A complete line of sound attenuating
ventilation units, exhaust air fans and products, including rectangular and
cooker hoods designed to optimise round silencers. Media Free silencers,
indoor comfort and save energy. custom silencers and acoustic
enclosure panels.
GB 2010.05-4003

Energy recovery
Dessicant-based product and systems
that recover energy, increase ventilation
and control humidity.
FWG-Centrifugal fans HC_Technical data

Flkt Woods AB
SE-351 87 Vxj, Sweden
Phone +46 470 71 77 00
www.flaktwoods.se

Potrebbero piacerti anche