Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
ABSTRACT
Detailed computer analyses of a 765 kV typical transmission tower This paper deals with the earth directly under the base of the tower.
footing grounding performance during phase-to-ground fault condition are Specifically, it considers the effect of two layers of soil/rock, with their dif-
described and discussed. It is assumed the tower is erected on a two-layer ferent resistivity, on the step and touch potential around the base of the
earth structure. The tower resistance, worst touch and step potentials, are tower.
calculated for various soil conditions described by the top layer height and
both layer resistivities. Universal charts are presented to help the engineer
in predicting and designing transmission tower ground performance. Electrical Representation
The most frequent transmission fault is phase-to-ground, and it is
INTRODUCTION usually caused by lightning. See Figure 1. It is quite common for present-
day EHV systems to require a tower footing resistance which will result in
General less than one outage per hundred miles per year (outage rate). In order to
calculate this outage rate, the system impedance or resistance must be
In order to design and operate a transmission system with a low-outage determined. See Figure 2.
rate and safety to the maintenance personnel as well as the public, it is
necessary to study the grounding system. The grounding system is made up
of: PHASE CONDUCTOR
cOverhead ground wires (static wires).
If GROUND WIRE
* Tower body. SECTION IMPEDANCE Z i-1
* Foundation.
In to
order design and operate atransmission system withalow-outage
* Ground wires buried or driven at the base of the tower (including
counterpoise).
* Earth directly under the base of the tower. R i- -Ri Rjlj
* Earth between the point of fault and the source of fault current.
- I _SUBSTATION
TOWER.
lft:bl:b IANUti
GROUNDING
FIGURE .2
Electrical Representation
5000
4000
0
3000
z
0
(U
0
I
Er
ai)
II
2000 FIGURE 4
Illustration of Step & Touch Potential
necessary if high accuracy is not required[3], [4], [5]. A simplified
representation, Figure 6 as opposed to Figure 5a, is adequate and
gives acceptable accuracy. Table I shows a comparison of exact
versus simplified electrode representation.
1000 Earth Surface Potential In this study, the simplified representation shown in Figure 6 was
735 kV Steel Tower used to analyze the tower's grounding performance.
Y Yvitnu (rs.
With ine Af:_Fnt
v-ru00t onnno
Ground Rod Per L eg
IJ Y AXIS
-El- 4 - PROFILE
TOP VIEW 11.2m
I II I I
10 11 12
DISTANCE ALONG DIRECTION (METERS)
FIGURE 3
Earth Surface Potential
Ground Resistivity
A uniform earth approach is often inadequate because soil/rock is nor-
mally heterogeneous. We propose a methodology which simulates an 36-
equivalent two-layer soil. Mrs. M. Bouchard substantiates this
methodology in her recently published master's thesis[1].
Ground Electrode
Single-point forms of electrodes are not accurate nor acceptable to deter- LEGEND
mine the ground potential profiles. Accurate analytical methods are
capable of analyzing any electrode configuration embedded in a two-layer () 3 0A
soill31, 141, 151.
Figures 5a and 5b show the arrangement of a typical grillage foundation
for a 765 kV tower.
L 0c' 0A EQUIVALENT DIAMETER OF A
CYCLINDRICAL CONDUCTOR HAVING
The foundation structures are embedded in concrete. Recent studies THE SAME SURFACE AS THE
have indicated that concrete-encapsulated electrodes will have a resistance TYPICAL GROUND ROD U-, I-, OR L-SHAPED STRUCTURES
lower or equal to the value which will be obtained without use of con-
crete[61, [7], [8], [9], [10]. This is due to the fact that concrete, when TOWER LEG c SOIL SURFACE
wet due to moisture content of surrounding soil, has a low resistivity
-
2 - The deep layer soil, P2, was varied from 0 feet to 00 ohm-
meters. This translates when using the reflection factor, K, Z AXIS
'
GROUND
defined as ----, as K varying from -1 to +1. ROD
Si;IDE VIEW
3 - Top layer resistivity, ID, was assumed constant = to 100
ohm-meters. FIGURE 6
C - Fault Current. Simplified Representation of Tower Foundations
Carried by tower's grounding was assumed 1000 amperes (1 KA).
Results Obtained
I Tower's footing ground resistance.
R. See Figures 8a and 8b.
II Touch Potentials.
VT. See Figures 9a, 9b, and 11.
w
cc
w III Step Potentials.
z Vs. See Figures 10a, 10b, and 11.
0
z
w
PRESENTATION OF RESULTS
CO,
Lb.
0
w
Grounding Resistance of Tower
a.
Figure 8a presents universal charts for grounding resistance of steel
z tower when an extra 6-foot long ground rod is buried next to each leg ex-
0
CO
cavation. Figure 8b corresponds to the case where no additional rods or
a
z electrodes are installed, except the normal steel of the foundations.
w
a.
w
0) * When soil is uniform or when the first layer height is large, about
100 feet or more, we have a flat curve identified by 00'.
TOP VIEW * In an interval around the zero reflection factor, K = 0.0, about
K -.5 to K +.5, the resistance when plotted on a log paper
= =
varies linearly.
* Beyond K .5, the behavior of the curves depends on the sign of K.
=
ground rod, Figure 8a, 16.3 feet, the corresponding curves are
linear and close to the horizontal uniform soil curve.
Om
'//Sd/E#/ -,)_
h /= 100 OHM-METERS 7 '+
s/I/a/- t?/
2 0.61 m
5 1.52m
FIGURE 7
Soil Depth
X L t- s15 4.57m
When "h" is smaller than the above, the curves behave
asymptotically when approaching K = -1.0, zero resistivity w 1
deep layer, and all drop to almost zero. This is logical since z
when K = -1.0, the deep soil exhibits an infinite conductivity,
and since a portion of the grounding conductors of the tower is
in contact with this infinite conductivity layer, then the
Cso
CO,
w
__= 00 c ' 00m
Grounding Resistance
735 kV Steel Tower
0.1 - No Ground Rod
0.01
FIGURE 8b
Tower Footing Ground Resistance
provided they are approximately geometrically similar to the
735 kV presented here, can be studied as explained in Appendix
I.
Touch Potentials
The maximum touch potential a man can experience when a fault occurs
at a tower is when he is standing approximately one meter away from one
leg of a tower while simultaneously touching this leg. See Figure 4.
Om
/ 2 0,61m
0 _52
_1
o [;1 i ~~~~~~~~~~~~~5'
4.57 m
10'X
ReFLLINE A REGIO
R
Touch Potential
735 kV Steel Tower
tw2 .i No Ground Ro
10
FIGURE 9a FIGURE 9b
Touch Potentials (Ground Rod) Touch Potentials
EXPERIENTL
* In contrast with the resistance curves, when "h" is larger, to say 17 tower leg. Since a man can withstand a higher step than touch potential
feet (11 feet for the case no ground rod), the results are similar to
- [2H, the step potentials are less of a concern. However, Figures 10a and 10b
the uniform soil case, in contrast to 100 feet for the resistance, are presented here for reference.
provided the grounding conductors are not in contact with the deep
layer when K < 0. Conclusions similar to those presented in the section on Touch Poten-
* It is important to note that Figures 9a and 9b do not show com- tials are also applicable, including the part about percent values.
pletely what happens when soil is a two-layer structure. It is
customary to express the touch or step potentials in percent of the EXPERIMENTAL RESULTS
total potential rise, which is the product of the grounding
resistance, "R," by the fault current, "I" (RI)[2].
Mrs. Bouchard has prepared an extensive field resistance measurement
Figure 11 shows the touch potential in percent of RI when there are on actual Hydro-Quebec towers, including earth resistivity measurements,
6-foot long ground rods. This figure shows clearly that when soil is grounding measurements, and comparison with computer results. The
uniform, either for first layer or Coo for second layer, the percent results of her findings are available in her thesis [1t which is in French.
value is close to 42 percent. However, for a given first-layer height, However, she intends to publish a paper in which the main difficulties and
which corresponds here to approximately 15 feet, the deviation problems associated with field measurements will be described. Recom-
from the uniform case is spectacular. mendations and comments will also be detailed.
The major conclusion of her thesis is that when field measurements
Step Potentials could be made accurately, experimental and computer results were close,
average of 12 percent discrepancy. This coffes'ponds to the cases where soil
The maximum step potential a man can experience is shown in Figure 4. resistivity was low so that enough test cuffent could be driven in the soil.
When measurements were difficult, or therefore not reliable because of low
Because of the nature of the problem here, the step potentials are always test current injected, high stray and parasitical currents, errors reached an
smaller or equal to the touch potential, depending on the distance from the average of 50 percent. See Figure 12.
476
First
105T First
Layer
_ Height
0' Om
l
5' 1.52 m
-j
0~ -i
4.57m
z
10L
10 Ioo15 oo m
z 0
w
0.
0
wU
U) 735ukV
StreeliTower10A/
w
= =~~~~~Se
10 - .5
1. -===-=....-
. -2 Potential
10-
1. =. 2~ 00 2.
1.0
REFLECTION FACTOR K (p.u.) REFLECTION FACTOR K (p.u.)
(Feet)
K0 REFLECTION FACTOR
0
I
Z r-x-x ffi~~~~~~~~~~~~~~~~~~~~~~~~~i
K-0.0 -
100-
100'
W t ), w
1.- , Z5_
APPENDIX I
Vreal case =
10
Vbase f2 = 50 -m
h 1 foot
I= 2000A
k = -0.82
B. If tower has not the same dimensions as for A-1 or A-2 of the paper, 1and
if tower is geometrically similar to A-1 or A-2 (including radiuss of Then select on charts
grounding conductors), then provided that first-layer height is trains- hbase hreal x = 1 x 2 2
formed accordingly:
Rreal case
Rreal Rbase x (', real/PDase)
.1
x a
(3) hbase
k = -0.82
2
Lbas
Where a = Dimension factor = Lbase Read Rbase or Vbase
Lreal
Then according to Equation (3) or Equation (4)
and Rreal = Rbase x (500/100) x 2 = 10 Rbase
Vreal case = Vbase x ( real! base) x
(Ireal/lbase) x a (4) Vreal = Vbase x (500 x 100) x (2000/1000) x 2 = 20 Vbase
478
Discussion cised when using concrete foundations as both load carrying structures
and a current carrying grounding electrode.
G. B. Niles (Baltimore Gas and Electric Company, Baltimore, With regard to the current-carrying ability of reinforced concrete, we
Maryland): The authors have given a valuable contribution to the in- would like to reference the following published papers:
dustry through the introduction of their universal charts for the tower
resistance, worst touch and worst step potentials. My discussion
basically centers around two aspects: one being general areas dealing References
with this topic and, secondly with changes in foundations parameters.
The authors have pointed out a computer program should be used to [1]. E. B. Rosa, Burton McCollum, 0. E. Peters, "Electrolysis in Con-
determine the ground fault current distribution between the structure crete," Department of Commerce Technologic Papers of the
and ground wires but they then give out the rule of thumb 607o/40% Bureau of Standards, No. 18, 137 pgs., March 19,1913.
(structure/ground wires). Using the approximate formulas of Ruden [2]. E. J. Fagan, R. H. Lee, "The Use of Concrete Enclosed Rein-
forcing Rods as Grounding Electrodes," IEEE Transaction Ind.
burg [1] for a terminal structure with two overhead shield wires, this
discusser has found the percentage is closer to 10%/9007o (struc- Gen. Appl., Vol. IGA6, pgs. 337-348 July/August, 1970.
ture/ground wires). If the overhead wire is attached to the substation, [3]. P. Weiner, "A Comparison of Concrete Encased Grounding Elec-
then even more percentage would flow over the shield wires. Of course, trodes to Driven Ground Rods," IEEE Transaction Ind. Gen.
the number of shield wires is important along with the conductivity and App., Vol. IGA6, pgs. 282-287, May/June 1970.
total tower resistance. [4]. R. L. Miller, W. H. Hartt, R. P. Brown, "Stray Current and
By increasing the total tower resistance less fault current travels down Galvanic Corrosion of Reinforced Steel in Concrete," Material
the tower as mentioned in the paper. This is a solution for decreasing Performance, Vol. 15, No. 5, pgs, 20-27, May 1976.
the touch potentials, but at the same expense on the system by creating [5]. W. K. Dick, H. R. Holliday, "Impulse and Alternating Current
more back flashovers on the transmission facilities. Tests on Grounding Electrodes in Soil Environment," IEEE
The authors use the simplified representation in the foundation con- Power Engineering Society-Transactions, pgs. 102-108, January/-
ductors as shown in TABLE I. In all cases, the simplified approach February, 1978.
shows the tower's resistance to be higher by as much as 8.3%. Is this a [6]. Lightning Protection Institute, "Lightning Protection for Con-
general trend found from Mrs. Bouchard's work? If so, the potentials crete and Masonry Buildings," Concrete Construction, pgs.,
shown are not as severe as given. Would the authors comment on this 217-220, June 1971.
aspect? Manuscript received February 26, 1979.
Another point of clarification is the 1000 amps used as the fault cur-
rent in the tower. Do the authors split this evenly between the four legs
and treat the tower as four individual parameters or combine the total
F. Dawalibi and W. G. Finney: We would like to thank the discussers
effects?
for their encouragements, their valuable discussions and pertinent ques-
The authors use a maximum value of 1 m for touch and step potential
tions.
distance factors. Could the authors give a reduction percentage if the Mr. Dick's concern about possible damage to concrete by surge or
distance factor was say 2/3 m? Is the potential near the tower nearly
simply power frequency currents is real. However, in practice the oc-
linear so distance could be treated as a linear relationship? curence of such possible damages is greatly reduced (with respect to
Regarding the grillage foundation, would similar results apply with a laboratory or similar "isolated electrode" tests) because of the
concrete enclosed foundation with rebar? Could the two layer approach
be used to determine the effect of the concrete by assuming the earth is
overhead ground wire or counterpoise connections. Also the nature of
uniform but then treating the concrete as a separate layer resistance (in
soil in the vicinity of a tower will have significant effects on the response
of supporting concrete foundations. In other words, we believe that in
this case vertical layer)? Could the authors give to the degree the
some cases, foundations alone could provide the necessary ground for a
decrease of resistance and hence reduction in touch and step potential tower while in other cases a careful design is required in order to
due to this concrete foundation?
decrease the stresses on the foundations.
I assume the larger the structure, then less touch and step potential
Mr. Dick's concern about possible damage to concrete by surge or
rise for the same 1000 A fault conditions would be present. In the case of
a steel pole, the potentials would increase. What effect would guy wires
simply power frequency currents is real. However, in practice the occur-
rence of such possible damages is greatly reduced (with respect to
on steel poles create? Would the authors comment on the effects of
laboratory or similar "isolated electrode" tests) because of the
other kinds of foundation? In addition, what effect would counterpoise
overhead ground wire or counterpoise connections. Also the nature of
have on the potential rise?
soil in the vicinity of a tower will have significant effects on the response
The authors state experimental verification earth resistivity
of supporting concrete foundations. In other words, we believe that in
measurements were done by Mrs. Bouchard. Were any verification of some cases, foundations alone could provide the necessary ground for a
the step and touch potential computations checked in the field?
tower while in other cases a careful design is required in order to
decrease the stresses on the foundations.
References Our paper describes one part of the analysis required to produce an
[1]. Reinhold Rudenberg,Transient Performance of Electric Power optimum tower grounding design. As mentioned in the paper, it is
Systems, The M.I.T. Press, 1969. assumed that a 1 p.u. current enters the tower (1 KA).
The following additional studies must be carried out before the final
Manuscript received February 23, 1979. design is complete:
1) Determine fault current distribution between tower and
William K. Dick (ITT Blackburn Company, St. Louis, Mo.): The overhead ground wires.
authors present an interesting method for determining the performance
of transmission tower grounding systems with regard to ground
2) Determine if soil (or concrete) breakdown may occur because of
excessive gradients.
resistance and step and touch potential.
Another consideration of the performance of this grounding system If possible, damages are foreseen, adequate measures such as
must be the effect of current particularly with regard to possible skywires, counterpoises and optimized grounding systems should be
damage to the supporting concrete foundations which are part of the provided.
current path. Published papers document damage to concrete as a result We will try to answer all Mr. Niles' questions in the sequence they
of alternating current surges, alternating and direct leakage currents were raised.
and lightning currents. We have developed a fault current distribution computer program
The determination of these currents may be extremely complex due based on the analytical work described in [1,2,3]. The main conclusions
to: obtained is that the distribution between overhead wires and towers
1. Non-homogenous matrix of concrete.
may vary between a few percent to nearly 100/o depending on fault loca-
2. Non-uniform current density at the interface of the steel and the
tion, towers resistances and type of ground wire conductors used.
There is certainly a optimum choice (with respect to tower resistances
concrete.
3. The presence of arcing between the steel and the concrete.
and ground wires used) which minimizes '"rate of failures" on a given
transmission line and hazards in the vicinity of towers.
Therefore, until more information is documented concerning the The simplified representation in the foundation conductor was
aforementioned effects of current on concrete, caution should be exer- adopted in order to produce the universal charts of the paper. It is
479
believed that the charts will be useful as a quick-aid design to determine We believe that the degree of decrease is proportional to the rebar
tower performance of usual non-critical cases. For critical cases the length in the concrete, less the saturation (or mutual effects) caused by
detailed representation should be used, if the pessimistic values of the the proximity of ground and rebard conductors.
simplified representation are to be avoided. In this case, an adequate Concentrated ground, such as steel pole grounds, exhibit higher
computer program is required. touch and step potentials, based on constant tower current (compared
The 1000 A is not split evenly between the four legs. "MALT" com- to four-leg steel towers). However, everything being equal, steel pole
puter program calculates the distribution of current along ground con- ground resistance is also higher and fault current will be less. Adequate
ductors based on their subdivision into small segments. This distribu- analysis is required since final results depend heavily on fault location,
tion is usually non-uniform. If the four legs are not similar, the distribu- transmission line and grounding configurations.
tion will not be identical. Thus, the total combined effect of the four Detailed analysis of all possible designs is not possible in a short
legs is analysed. paper or in this discussion. With an adequate computer program,
At short distances from the tower leg, surface potential is not linear. however, actual designs can be evaluated and optimized.
At larger distances, the linear relationship, for distances of 1 m or less, Effects of counterpoises are described qualitatively in [2].
is very acceptable. However, an adequate computer program will give Finally no experimental verification of step and touch potentials was
the values for any distances. conducted during Mrs. Bouchard's test program. We know that such
It is possible to simulate the effects of concrete, if the interface bet- measurements have been made by others, but no comparison was made
ween concrete and soil can be considered as an equipotential surface. In with our analytical methods simply because earth resistivity data were
practice, this means that the volume of concrete is not too large with not available, or were inadequate (average values only) for meaningful
respect to the rebar volume. Concrete exhibits a resistivity value similar comparisons.
to the neighboring soil. In low resistivity soils (generally wet soils) con- References
crete resistivity is about 50 to 100 Q-m. In dry high resistivity soils, con-
crete resistivity will be 1000 to 10,000 Q-m. We believe that when the [11. F. Dawalibi, D. Mukhedkar, "Ground Fault Current Distribution
volume of conrete is not excessive (humidity penetrates deeply into the in Power Systems-The Necessary Link," IEEE Paper A, 754-4,
concrete) there will be a decrease of tower's resistance, mainly because Summer Meeting, Mexico, 1977.
of: [21 F. Dawalibi, "Ground Fault Current Distribution Between Soil
and Neutral Conductors," Paper F 79 757-6, PES Summer
-Presence of the rebar in the concrete area which acts as addition Meeting, Vancouver, 1979.
al length of ground conductors. [31 F. Dawalibi, D. Mukhedkar, D. Bensted, "Soil Effects on Ground
-High compactness of concrete and good contact between conrete Fault Currents," Paper submitted for presenation at the IEEE
and rebar. PES Winter Meeting, New York, 1980.
--Similar resistivity values of concrete and surrounding soil.
Manuscript received November 14, 1979.