Basics of Flow Measurement with the Orifice Flow Meter I

Tweet Share8
2

Search

Google Custom Search

The differential pressure measurement method is a universally utilized measuring principle for flow measurement. The orifice flow
meter is a type of differential pressure flow meter that can be used for measuring gases and liquids.

As shown in Flow Instrumentation: principles and Formulas, we know that the relationship between flow and differential pressure in a
flow restriction device like the orifice meter is given by:



Q = K P

Where
k = a constant
P = differential pressure across device
= density of the fluid.

In the above formula, fluid density is a key factor in flow measurement computation in both liquids and gases. If fluid density is
subject to change over time, we will need some means to continually calculate so that our inferred flow measurement will remain
accurate. Variable fluid density is typically experienced in gas flow measurement, since all gases are compressible by definition. A
simple change in static gas pressure within the pipe is all that is needed to make change, which in turn affects the relationship
between flow rate and differential pressure drop. Therefore in gas flow measurement, change in fluid density with static pressure is
compensated for.

In liquid flow measurement, the scenario is different. Liquids by definition are considered to be incompressible for all practical
purposes since a change in pressure has little or no effect on the density hence they are neglected in flow measurement applications.

Both liquid and gas density change with temperature as a result, they are compensated for in a differential pressure flow
measurement system like the orifice plate flow meter.

Flow Measurement Setup


The complete flow measurement installation of an orifice flow meter system consists of the following elements:
1. The Orifice plate (the differential pressure source)
2. Orifice plate fittings(more convenient for large pipe size)
3. Pressure piping (impulse lines)
4. Isolation and Equalizing Valves Manifold for Impulse lines and Transmitter
5. Differential pressure transmitter
6. Pressure transmitter
7. Temperature sensor/Transmitter
8. A flow computer
9. A DCS, PLC/HMI System etc.

http://www.instrumentationtoolbox.com/2013/04/basics-of-flow-measurement-with-orifice.... 2/1/2017
Basics of Flow Measurement with the Orifice Flow Meter I ~ Learning Instrumentation A... Page 2 of 5

The Orifice plate


The orifice plate is the primary element in the measurement system and it is the source of the differential pressure being used to
infer flow measurement. You can learn more about orifice plates from:
Introduction to orifice plates
Basics of the orifice flow meter

Orifice Plate Fittings


Orifice plates for flow measurement could be installed between flanges, typically in an orifice flange union arrangement for small
pipe sizes used for low flow rates.
For relatively low flow rates, an alternative arrangement is the integral orifice plate. This is where a small orifice plate directly
attaches to the differential pressure-sensing element, eliminating the need for impulse lines.

For large pipe sizes and higher flow rates, it is more convenient to use an orifice plate within an orifice fitting. The fitting makes
easy removal, inspection and replacement of the orifice plate possible during inspection and maintenance operation.

Pressure Piping (Impulse lines)


Two impulse lines upstream and downstream the orifice plates (installed either between flanges or in an orifice fitting) are
connected to the high and low ports of the differential pressure transmitter to measure the differential pressure generated by the
orifice plate.

Isolation and Equalising Valves Manifold for Impulse lines and Transmitter.
The two impulse lines from the orifice fitting/orifice plate are isolated from the differential pressure transmitter by shut-off valves.
The differential pressure transmitter, protected by a valve combination consisting of three to five valves (often in a single assembly
referred to as a 3-valve or 5-valve manifold) is installed before the transmitter. The valves shut off the transmitter and allow the
pressures in each line to be equalized, enabling the transmitter to be zeroed.

Differential Pressure Transmitter


The differential pressure transmitter measures the differential pressure drop created by the orifice plate. The transmitter must be
capable of withstanding the high static pressure in the installation piping. It must also be very sensitive so that it can measure low
differential pressures at low flow rates as high differential pressures are not desirable because it results in a high pressure loss.
Additional features that differential pressure transmitters for flow measurement should possess include:
(a) Its material make up should be chemically resistant to corrosive media
(b) It should be able to convert the differential pressure into an analog(4 20mA) or digital output signal.
(c) It should be able to extract the square root in order to achieve a direct linear output proportional to the flow rate. This is
necessary because flow rate is proportional to the square root of differential pressure for an orifice plate meter and other
differential pressure flow meters.
(d) It should be resistant to interference, explosion proof and intrinsically safe.
(e) It should include some self diagnostics features for maintenance purpose and be easy to operate.
(f) It should be capable of modern communication technologies e.g Foundation Fieldbus , Profibus PA etc.

The location of the transmitter in a differential pressure flow measurement installation should be carefully considered in order not to
introduce measurement errors. As a rule, in gas flow measurement with the orifice flow meter, the transmitter should be installed
above the pipe in order to prevent any condensate from entering the pressure lines. For liquid measurement systems, the transmitter
is installed below the pipe to prevent gas bubbles from entering the measuring system.

Pressure Transmitter.
A pressure transmitter is required to continuously measure static pressure in gas flow measurement setup. This is because static
pressure variations significantly affect the density of gases and needs to be compensated for. Liquid systems do not have this
problem.

Temperature Sensor/Transmitter

http://www.instrumentationtoolbox.com/2013/04/basics-of-flow-measurement-with-orifice.... 2/1/2017
Basics of Flow Measurement with the Orifice Flow Meter I ~ Learning Instrumentation A... Page 3 of 5

Temperature measurement is required in both liquid and gas flow measurement systems due to the fact that both liquid and gas
density vary with temperature. So a continuous measurement of the temperature of the process is required in order to compensate
for this variation. RTD sensors/transmitter are commonly used for the continuous measurement of the temperature. The sensor and
its Thermowell is usually positioned downstream of the orifice plate so that the turbulence it generates will have negligible impact
on the fluid dynamics at the orifice plate. The American Gas Association (AGA) allows for upstream placement of the sensor
Thermowell, but only if located located 10 diameters upstream of a flow conditioner.

Flow Computer
The flow computer receives measurement signals from the differential pressure transmitter, the pressure transmitter and the
temperature transmitter. All signals are used to compute the mass and volumetric flow rates according to a set algorithm
programmed into the flow computer. In particular, gas flow measurement applications require an online Gas Chromatograph and
Densitometer that calculates the density of the gas flow stream at flowing conditions in order to accurately determine the mass and
volumetric flow rates.

DCS, PLC/HMI, Controller System


Most times, the signal from the flow computer is required in a central control system located in a centralized control room. The flow
signal could be sent for display in a DCS or PLC/HMI system or a controller for control action.

Go to the concluding part: Basics of Flow Measurement with the Orifice Flow Meter II

Related Posts: Orifice Plates

Basics of Flow Measurement with the Orifice

Flow Meter II

Basics of Flow Measurement with the Orifice

Flow Meter I

Basics of The Orifice Plate Flow Meter

Types of Orifice Plates Used in Flow

Measurement

How Conditioning Orifice Plates Work

Basics of Permanent Pressure loss in Differential

Pressure Flow Meters

How to Specify an Orifice Plate

AGA 3 Gas Flow Equation for Orifice Plates

How to Size an Orifice Plate Flow Meter with

Software

A Guide to Sizing Orifice Plate Flow Meters

The Orifice Flow Meter Equation

Learning Instrumentation And Control Engineering

http://www.instrumentationtoolbox.com/2013/04/basics-of-flow-measurement-with-orifice.... 2/1/2017
Basics of Flow Measurement with the Orifice Flow Meter I ~ Learning Instrumentation A... Page 4 of 5

Email This BlogThis! Share to Twitter Share to Facebook


+2 Recommend this on Google

Labels: Orifice Plates

Newer Post Older Post Home

USEFUL ENGINEERING LINKS

Flow Meter Selection Guide


How to Calibrate a Pressure Gauge
Sizing Orifice Plates with Daniel Flow
Calculator
Basics of Control Valve Positioners
Control Valve Actuator Bench Set
How to Setup a HART Transmitter
Basics of Ultrasonic Flow Meters
How to Specify a Thermowell
AGA 3 Gas Flow Equation
Learning Electrical Engineering

RECENT POSTS
How to Calibrate a Thermocouple
1 Transmitter
To calibrate a thermocouple transmitter
will ... read more
Dec 17 2016

How to Specify a Digital Pressure Gauge


2 Digital Pressure Gauge (Photo Credit: ... read
more
Dec 12 2016

Process Safety Basics of UEL & LEL of


3 Hazardous Gases
In todays highly complex industrial
environment, ... read more
Dec 11 2016

Basics of Instrument Loop Diagrams


4 Instrument loop diagrams are also called ...
read more
Dec 10 2016

Instrument Abbreviations Used in


5 Instrumentation Diagrams (P&IDs) III
To further understand instrument
abbreviations ... read more
Dec 10 2016

Instrumentation Blog

SPONSORED LINKS

POPULAR POSTS

Common P&ID symbols used in Developing


Instrumentation Diagrams
Instrument Abbreviations Used in
Instrumentation Diagrams (P&ID)
How to Calibrate Your DP Transmitter
How a Pressure Switch Works
Piping and Instrumentation Diagrams:Tutorials
I
How to Read and Interpret Piping and
Instrumentation Diagrams (P&ID)
Basics of Piping and Instrumentation Diagrams
(P&IDs)
How a Current to Pressure Transducer (I/P)
Works
How to Calibrate a Pressure Gauge With a
Dead Weight Tester
DP Transmitter valve manifolds

TRANSLATE
Select Language
Powered by Translate

http://www.instrumentationtoolbox.com/2013/04/basics-of-flow-measurement-with-orifice.... 2/1/2017
Basics of Flow Measurement with the Orifice Flow Meter I ~ Learning Instrumentation A... Page 5 of 5

SUBSCRIBE AND GET INSTANT UPDATES

Submit

CATEGORIES
Control Valves ( 25 ) Temperature sensors
( 22 ) Flow meters ( 20 ) Calibration ( 19 )
Instrumentation Diagrams ( 19 ) DP
Transmitters ( 14 ) Level Measurement ( 14 )
Orifice Plates ( 11 ) Thermocouples ( 11 )
Transmitters ( 10 ) Pressure Switch ( 9 ) RTD
( 9 ) Pneumatic Systems ( 7 ) pressure sensors
( 7 ) Electrical Noise ( 6 ) Electricals ( 6 )
HART Protocol ( 6 ) Pressure Gauges ( 6 )
Process Control ( 6 ) 4 - 20mA Signals ( 4 )
Basics of Instrumentation ( 4 ) Digital or
Analog Multimeters ( 2 ) Fluke pressure
calibrator ( 2 ) Thermowells ( 2 ) Electric
Motors ( 1 ) Measurement terminology ( 1 )
Motor Nameplate ( 1 )

ADVERTISEMENT

EXPLORE INSTRUMENTATIONTOOLBOX.COM
Flow Meters :

Theory of Fluid Flow Meters Differential Pressure (DP) Transmitters :


Piping and Instrumentation Diagrams :
Electronic Flow Meters
An Introduction to DP Transmitters
Mechanical Flow Meters How to Read and Interpret P&IDs
Troubleshooting Guide of DP Transmitters
Differential Pressure Flow Meters Understanding P&ID Drawings
How to Calibrate Your DP Transmitter
Mass Flow Meters Basic Functions of Instruments in a P&ID
Common Terms Used in DP Transmitter Calibration
Flow Meter Selection Guide P&IDs: Piping Line Number Identification
DP Transmitter Valve Manifolds
How a Turbine Flow Meter Works Basics of P&IDs
Applications of DP Transmitters
Principles of Flow Metering Instrument Abbreviations Used in P&IDs
Electronic Transmitters Wire Configuration
Common Process Equipment Symbols I
How to Calibrate DP Transmitters
Common Process Equipment Symbols II
Pressure and Process Switches : Common Terms Used to Interpret P&ID Drawings
How a Pressure Switch Works Thermocouples :
How a Differential Pressure Switch Works P&IDs Tutorials:
Temperature Measurments with Thermocouples
Pressure Switch Designs and Applications
Practical Application Tips For Thermocouples
How to Select a Pressure Switch P&IDs: Tutorials I
Selection Factors for Thermocouples
Understanding Pressure Switch Terminology P&IDs Tutorials II: Pressure Control
How to Convert Thermocouple Milivolts to Temperature
Calibrating a Pressure Switch with a Fluke Calibrator P&IDs Tutorial III: Flow and Level Control
Reducing Noise in Thermocouple Installations
How to Calibrate and Adjust a Pressure Switch
Process Switches Symbols

2009 - 2017 instrumentationtoolbox.com. All Rights Reserved. Powered by Blogger.

http://www.instrumentationtoolbox.com/2013/04/basics-of-flow-measurement-with-orifice.... 2/1/2017

Potrebbero piacerti anche