SR469 - Motor Settings Auto-Config Report

OVERVIEW

Device Summary Generated at : Oct 19 2016 08:45:11


File Name C:\Users\Usuario\Desktop\469 a
justes para pruebas.469
Order Code 469
Firmware Version 5.0x

Input Parameters

Motor Name Plate Information


Full Load Amps 100 A

Locked Rotor Amps as % of FLA 600 %

Motor Nameplate Voltage 4160 V

Service Factor 1.0

HOT Safe Stall Time 10 sec

COLD Safe Stall Time 13 sec

Motor Temperature
Insulation Class F

Insulation Class Temperature Rise 105 C

Motor Class B

Motor Class Temperature Rise 80 C

Motor Cooling Time Constants (Running) 1 min

Motor Cooling Time Constants (Stopped) 1 min

Number of Stator RTDs 6

Stator RTD Type 100 Ohm Platinum

Number of Bearing RTDs 2

Bearing RTD Type 100 Ohm Platinum

Bearing RTD Alarm Temperature 70 C

Bearing RTD Trip Temperature 90 C

There are no Ambient RTDs configured

System Information
System Frequency 50 Hz

Phase Rotation ABC

Switching Device Contactor

Breaker/ Starter Status 52A

Version 5.25Page 1
SR469 - Motor Settings Auto-Config Report

Input Parameters(Continued)

System Information

You have selected the operating device as Contactor .As contactors are not normally rated to

interrupt fault level currents the Short Circuit Protection will not be enabled

Current Sensing
Phase CT Primary 250 A

Ground CT Connection Core Balance

Ground CT Secondary 5

Ground CT Primary 50 A

Phase CT Primary exceeds 200% of the Full Load Amps

Differential CT(s) not configured

Current Element - Differential DISABLED

Voltage Sensing
Voltage Transformer Connection Type Open Delta

VT Ratio 34.667

VT's connected on Line Side

Voltage Element - Frequency DISABLED

Motor Starting
Acceleration Time at minimum voltage 7 Sec

Acceleration Time at Rated Voltage 5 Sec

Number of starts per hour

Time between motor start commands

Motor Restart Time

Jogging Block DISABLED

Restart Block DISABLED

Version 5.25Page 2
SR469 - Motor Settings Auto-Config Report

Calculated Settings

The following motor and system parameters will be programmed to the settings file

System Setup
Motor Full Load Amps 100 A

Motor Nameplate Voltage 4160 V

Nominal System Frequency 50 Hz

System Phase Sequence ABC

Phase CT Primary 250 A

Ground CT Primary 50 A

Ground CT Type 5 A Secondary

Phase Differential CT Type None

VoltageTransformer Connection Type Open Delta

Voltage Transformer Ratio 34.667 :1

Digital Inputs
Starter Status Switch Start Aux a

469 Thermal Model


Curve Style Standard

Overload Pickup Level 1.15 FLA

Unbalance k Factor 6

Cool Time Constant Running 1 min

Cool Time Constant Stopped 1 min

Hot/Cold Safe Stall Ratio 0.77

RTD Blasing On/Yes

RTD Blas Minimum 40 C

RTD Blas Center Point 130 C

RTD Blas Maximum 155 C

Thermal Capacity Alarm Latched

Thermal Capacity Alarm Relays Alarm

Thermal Capacity Alarm Level 75 % used

Thermal Capacity Alarm Events On/Yes

Overload Trip Relays Trip

Standard Overload Curve Number 4

The above Thermal Model Protection Setpoints will be used to protect your motor.

The overload curve has been calculated based on hot and cold safe stall times provided.

The curve selection assumes a uniform motor curve supplied by motor manufacturer.

The curve recommended by the Motor Settings Auto-Config should be compared to

curve supplied by the manufacturer to ensure motor protection.

Version 5.25Page 3
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Short Circuit Trip


Short Circuit Trip Off

Short Circuit Trip Backup Off/No

Short circuit protection has been disabled as you have selected the

operating device as Contactor.

Most Contactors are not rated to interrupt the availabe fault current.

Fuses should be provided to provide the Short Circuit Protection.

Overload Alarm
Overload Alarm Unlatched

Overload Alarm Relays Alarm

Overload Alarm Events On/Yes

Overload Alarm Delay 1 s

Mechanical Jam
Mechanical Jam Trip Latched

Mechanical Jam Trip Relays Trip

Mechanical Jam Pickup 3.00 xFLA

Mechanical Jam Delay 2 s

Current Unbalance
Current Unbalance Alarm Unlatched

Current Unbalance Alarm Relay Alarm

Current Unbalance Alarm Pickup 15 %

Current Unbalance Alarm Delay 7 s

Current Unbalance Alarm Events On/Yes

Current Unbalance Trip Latched

Current Unbalance Trip Relays Trip

Current Unbalance Trip Pickup 20 %

Current Unbalance Trip Delay 2 s

Ground Fault
Ground Fault Alarm Unlatched

Ground Fault Alarm Relays Alarm

Ground Fault Alarm Pickup 0.1 CT

Intentional GF Alarm Delay 200 ms

Ground Fault Alarm Events On/Yes

Version 5.25Page 4
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Ground Fault
Ground Fault Trip Latched

Ground Fault Trip Relays Trip

Ground Fault Trip Pickup 0.15 CT

Intentional GF Trip Delay 0 ms

Differential
Phase Differential Trip Off

Acceleration Timer
Accleration Timer Trip Latched

Acceleration Timer Trip Relays Trip

Acceleration Timer from Start 8.40 s

Start Inhibit
Start Inhibit Block On/Yes

Jogging Block
Jogging Block Off/No

Restart Block
Restart Block Off/No

RTD Types
Stator RTD Type 100 Ohm Platinum

Bearing RTD Type 100 Ohm Platinum

RTD Alarms
Open RTD Sensor Alarm Latched

Open RTD Sensor Alarm Relays Alarm

Open RTD Sensor Alarm Events On/Yes

RTD Short/Low Temp Alarm Latched

RTD Short/Low Temp. Alarm Relays Alarm

RTD Short/Low Temp. Alarm Events On/Yes

Version 5.25Page 5
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Stator RTDs

RTD #1 RTD #2
Application Stator Application Stator
Name Stator1 Name Stator2
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 130 C Alarm Temperature 130 C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 155 C Trip Temperature 155 C

RTD #3 RTD #4
Application Stator Application Stator
Name Stator3 Name Stator4
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 130 C Alarm Temperature 130 C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 155 C Trip Temperature 155 C

RTD #5 RTD #6
Application Stator Application Stator
Name Stator5 Name Stator6
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 130 C Alarm Temperature 130 C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 155 C Trip Temperature 155 C

Bearing RTDs

RTD #7 RTD #8
Application Bearing Application Bearing
Name Bearing1 Name Bearing2
Alarm Unlatched Alarm Unlatched
Alarm Relays Alarm Alarm Relays Alarm
Alarm Temperature 70C Alarm Temperature 70C
Alarm Events On/Yes Alarm Events On/Yes
Trip Latched Trip Latched
Trip Relays Trip Trip Relays Trip
Trip Temperature 90C Trip Temperature 90C

Version 5.25Page 6
SR469 - Motor Settings Auto-Config Report

Calculated Settings (Continued)

Under Voltage
Undervoltage Active Only If Bus Energized Off/No

Undervoltage Alarm Unlatched

Undervoltage Alarm Relays Alarm

Undervoltage Alarm Pickup 0.9 Rated

Starting Undervoltage Alarm Pickup 0.85 Rated

Undervoltage Alarm Delay 10 s

Undervoltage Alarm Events On/Yes

Undervoltage Trip Latched

Undervoltage Trip Relays Trip

Undervoltage Trip Pickup 0.85 Rated

Starting Undervoltage Trip Pickup 0.8 Rated

Undervoltage Trip Delay 3 s

Over Voltage
Overvoltage Alarm Unlatched

Overvoltage Alarm Relays Alarm

Overvoltage Alarm Pickup 1.05 Rated

Overvoltage Alarm Delay 10 s

Overvoltage Alarm Events On/Yes

Overvoltage Trip Unlatched

Overvoltage Trip Relays Trip

Overvoltage Trip Pickup 1.1 Rated

Overvoltage Trip Delay 3 s

Phase Reversal
Voltage Phase Reversal Trip Latched

Voltage Phase Reversal Trip Relays Trip

Version 5.25Page 7