SERVICE REPORT

Costumer: Sun Power Manufacturing Limited


Address: 100 East Main Street, Special Export Processing Zone Laguna Techno Park
Project: Preventive Maintenance of 34.5kV Main Switchgear

SPECIFICATIONS:
FEEDER No. 2
Vacuum Circuit Breaker
Brand: MEIDENSHA Type: VJ - 32
Serial No.: 4W4871YS Rated Current:
1250A
Rated Voltage: 36kV Breaking Capacity:
25kA

INSULATION RESISTANCE TEST RESULTS


Instrument Used: METRIL Insulation Resistance Tester 5kV
Particular Resistance @1minutes Test Voltage
L1 - L2 747G 5000V
L1 - L3 632G 5000V
L2 - L3 474G 5000V

L1 - ground 624G 5000V


L1 - ground 683G 5000V
L1 - ground 677G 5000V

Load 1 Load 2 1.20T 5000V


Load 1 Load 3 1.14T 5000V
Load 2 Load 3 1.29T 5000V

Load 1 - ground 603G 5000V


Load 2 - ground 453G 5000V
Load 3 - ground 646G 5000V

Findings:
High value of insulation found on line side Phase to Phase, line side Phase to
Ground, load side phase to phase, and load side Phase to Ground

Recommendation(s):
Conduct Annual Testing to Monitor the Integrity of the Circuit Breaker.
CONTACT RESISTANCE TEST RESULTS
Instrument Used: Teldar instruments Co. Transformer Winding resistance
Meter
Particular Milli-ohms (m) Test Current
L 1 To Load 1 0.0708m 10.2A
L 2 To Load 2 0.0714m 10.2A
L 3 To Load 3 0.0695m 10.2A

Findings:
No abnormalities found on contact resistance value.

Recommendation(s):
Conduct Annual Testing to Monitor the Integrity of the Circuit Breaker.

CONTACT TIMING TEST RESULTS


Instrument Used: Teldar Instruments Co. RELAY TEST SET (REL 220)
Particular Opening Closing Time Remarks
Time
Phase A
Phase B
Phase C

Findings:

Recommendation(s):

Test Conducted By: Noted By: Approved By:

Technician Project Engineer Project Manager

Received By:

Clients Representative Signature


Over Printed Name