Sei sulla pagina 1di 2

DSEGenset

DSE7510
ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2

AUTO START & LOAD SHARE CONTROL MODULE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
FEATURES EMC Generic Emission Standard for
the Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
The DSE7510 is an Automatic A sophisticated module monitoring MODULE CAPABILITIES including Electrical Business Equipment
Engine Control Module, designed an extensive number of engine Fixed export with mains (utility)
TEMPERATURE
to provide advanced load share parameters, the DSE7510 will supply BS EN 60068-2-1
functionality for diesel and gas annunciate engine shutdowns, Synchronising up to 16 gen-sets o
Ab/Ae Cold Test -30 C
generating sets that include warnings, and engine status BS EN 60068-2-2
Bb/Be Dry Heat +70 oC
electronic and non-electronic information on the back-lit LCD The module has sophisticated
engines. screen, by illuminated LED, on a engine and power monitoring, high VIBRATION
BS EN 60068-2-6
remote PC, by audible alarm and level instrumentation and flexible Ten sweeps in each of three
The modules load share functions via SMS text alerts (GSM modem timers and alarms, making the major axes
include automatic synchronising required). The module includes system suitable for a wide range of 5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
with built-in synchroscope and RS232 and RS485 ports as well as synchronising applications.
closing onto dead bus. Direct and dedicated terminals for system HUMIDITY
BS EN 60068-2-30
flexible outputs from the module expansion. DSE7560 is required to synchronise Db Damp Heat Cyclic 20/55 oC
are provided to allow connection to with the mains (utility). @ 95% RH 48 Hours
the most commonly used speed BS EN 60068-2-78
Cab Damp Heat Static 40 oC
governors and automatic voltage @ 93% RH 48 Hours
regulators (AVRs).
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A


WIDE VARIETY OF GEN-SET APPLICATIONS
MODEM MODBUS PC
DSE130
DSE157
9 3 3

232 485

DSE RS232 AND P810 CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER


EXPANSION RS485 INPUTS SENDERS STOP SUPPLY 8-35V

DSE7510 MSC
DEUTZ
ISUZU
PERKINS
CATERPILLAR
MTU
7 7510 7510 7560 VOLVO
CUMMINS
OTHER
SCANIA

BUS VOLT FREE GENERATOR SENSING FUEL & CRANK CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP

CURRENT VOLTS
D+
+ W/L

1ph 2 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N E N
N

ISSUE 6

DSEGenset

DSE7510
SPECIFICATION

DC SUPPLY
8 V to 35 V continuous

AUTO START & LOAD SHARE CONTROL MODULE CRANKING DROPOUTS


Able to survive 0 V for 50 mS, providing
FEATURES supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries

MAXIMUM OPERATING CURRENT


460 mA at 12 V, 245 mA at 24 V

MAXIMUM STANDBY CURRENT


375 mA at 12 V, 200 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (START)
15 A DC at supply voltage

OUTPUTS C & D
8 A 250 V (Volt free)

AUXILIARY OUTPUTS E,F,G


2 A DC at supply voltage

GENERATOR
KEY LOAD SHARE FEATURES Configurable timers and alarms KEY BENEFITS VOLTAGE RANGE
Fixed export with mains (utility) Multiple date and time scheduler 132 x 64 pixel ratio display for 15 V - 333 V AC (L-N)
Synchronising up to 16 generators Event log (25) clarity FREQUENCY RANGE
Sequential start CAN and Magnetic Pick-up/Alt. Real-time clock provides 3.5 Hz to 75 Hz
Auto ID negotiation sensing accurate event logging
MAGNETIC PICK UP
Direct governor and AVR Engine protection alarms Remote monitoring of module VOLTAGE RANGE
communication and control Low fuel alarms using comprehensive DSE7500 +/- 0.5 V to 70 V
Manual voltage, frequency and Charge Alternator failure warning PC software
FREQUENCY RANGE
speed adjustment Manual speed control (on Sends SMS messages to notify 10,000 Hz (max)
Volts and frequency matching compatible CAN engines) engineers of specific generator
Dead bus sensing Engine exercise scheduler problems (GSM modem and BUILT-IN GOVERNOR CONTROL
Fully Isolated
Generator load demand Automatic load transfer SIM card required) Minimum Load Impedance:
kW and kV Ar load sharing kW overload protection Ethernet communications (via 1000
kW on mains (utility) level Unbalanced load protection DSE860/865 modules), provides Gain Volts 0 V - 10 V DC
Offset Volts + / - 10 V DC
Automatic hours run balancing Independent Earth Fault trip advanced remote monitoring at
R.O.C.O.F & Vector Shift Audible alarm low cost BUILT-IN AVR CONTROL
Mains (utility) decoupling test Backed-up real-time clock Modules can be integrated into Fully Isolated
Minimum Load Impedance: 1000
facility Fully configurable via by building management systems Gain Volts 0 V - 10 V DC
DSE7500 PC software (BMS) Offset Volts + / - 10 V DC
KEY FEATURES Configurable display languages Surplus energy / power can be DIMENSIONS
4-Line back-lit LCD text display Remote SCADA monitoring via sold back to the grid (subject to OVERALL
Five key menu navigation DSE7500 PC software local mains/utility supplier) 240 mm x 172 mm x 57 mm
9.4 x 6.8 x 2.2
Front panel editing with PIN User selectable RS232 and Licence-free PC software
protection RS485 communications IP65 rating (with supplied PANEL CUTOUT
Multiple display languages SMS Messaging (additional gasket) offers advanced 220 mm x 160 mm
8.7 x 6.3
LED and LCD alarm indication external modem required) resistance to water ingress
Customisable status screens Built-in governor and AVR control MAXIMUM PANEL THICKNESS
9 configurable inputs 8 mm
0.3
5 configurable outputs

RELATED MATERIALS OTHER RELATED MATERIALS


TITLE PART NOS TITLE PART NOS
DSE7510 Installation Instructions 053-052 DSE7560 Data Sheet 055-067
DSE7500 Quick Start Guide 057-100 DSE124 Data Sheet 055-082
DSE7510 Operator Manual 057-088 CAN and DSE Wiring Guide 057-004
DSE7500 PC Software Manual 057-078
Load Share Design and Commissioning 057-047
Guide to Synchronising and Load Sharing 057-045/6

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-065/01/16 (7)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457