Sei sulla pagina 1di 13

Grease

Interceptors

CEU 199
Continuing Education from the
American Society of Plumbing Engineers

May 2013

ASPE.ORG/ReadLearnEarn
READ, LEARN, EARN

Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education
article. Using information from other materials may result in a wrong answer.

The purpose of a grease interceptor is to intercept and collect one particular manufacturer. The purpose of the equipment
grease from a commercial or institutional kitchens waste- descriptions contained in this chapter is to expose the reader
water passing through the device, thereby preventing the to the basic types of FOG treatment equipment presently
deposition of pipe-clogging grease in the sanitary drainage available as they currently are defined and listed within
system and ensuring free flow at all times. Grease intercep- model codes. The text is not intended to imply that any one
tors are installed in locations where liquid wastes contain particular type of device is superior to another for a given
grease. These devices are required to receive the drainage application. That being the case, the plumbing engineer
from fixtures and equipment with grease-laden wastes lo- must exercise care when proposing to specify FOG treatment
cated in food preparation facilities such as restaurants, hotel equipment that could be considered proprietary, in conjunc-
kitchens, hospitals, school kitchens, bars, factory cafeterias, tion with a government-controlled or publicly funded project
and clubs. Fixtures and equipment include pot sinks, soup that may prohibit the specifying of such equipment due to a
kettles or similar devices, wok stations, floor drains or sinks lack of competition by other manufacturers.
into which kettles are drained, automatic hood wash units,
pre-rinse sinks, and dishwashers without grinders. Residen- Principles OF OPERATION
tial dwellings seldom discharge grease in such quantities as Most currently available grease interceptors operate on the
to warrant a grease interceptor. principle of separation by flotation alone (GGI) or fluid me-
Grease interceptors typically come in one of two basic chanical forces in conjunction with flotation (HGI).
types. The first type is called a hydromechanical grease inter- The performance of the system depends on the difference
ceptor (HGI), previously referred to as a grease trap. These between the specific gravity of the water and that of the
are prefabricated steel manufactured units, predominately grease. If the specific gravity of the grease is close to that of
located indoors at a centralized location in proximity to the the water, the globules will rise slowly. If the density differ-
fixtures served or at the discharging fixture point of use. ence between the grease and the water is larger, the rate of
They are relatively compact in size and utilize hydraulic flow separation will be faster.
action, internal baffling, air entrainment, and a difference Since the grease globules rise rate is inversely propor-
in specific gravity between water and FOG (fats, oils, and tional to the viscosity of the wastewater, the rate of separation
grease) for the separation and retention of FOG from the fix- will be faster when the carrier fluid is less viscous and vice
ture waste stream. The standard governing the installation, versa. Grease globules rise more slowly at lower temperatures
testing, and maintenance of HGIs is PDI G101: Testing and and more rapidly at higher temperatures. Grease, especially
Rating Procedure for Hydro Mechanical Grease Interceptors. when hot or warm, has less drag, is lighter than water, and
The second type is the gravity grease interceptor (GGI). does not mix well with water. The final velocity for a spheri-
These are engineered, prefabricated, or field-formed concrete- cal particle, known as its floating velocity, may be calculated
constructed units that typically are located outside due to using Newtons equation for the frictional drag with the
their large size and receive FOG discharge waste from all driving force, shown in Equation 8-1.
required fixtures within a given facility. These units essen- Equation 8-1
tially utilize gravity flow and retention time as the primary
means of separating FOG from the facility waste stream Cd A p v2
=(p1 p) g V
prior to it entering the municipal drainage system. The 2
standard for the design and construction of gravity grease This yields the following mathematical relationship:
interceptors is IAPMO/ANSI Z1001: Prefabricated Gravity
Grease Interceptors. Equation 8-2
Other FOG retention and removal equipment can be cat- 4 g p1 p
egorized as grease removal devices (GRDs) and FOG disposal v= 3 Cd p
D
systems (FDSs).
where
Note: It is important for the plumbing engineer to un-
Cd =Drag coefficient
derstand that the topic of FOG retention and removal is a A =Projected area of the particle, pD2/4 for a sphere
continuing and ever-changing evolution of both technology v =Relative velocity between the particle and the fluid
and the latest equipment available at the time. Types of p =Mass density of the fluid
interceptors currently on the market may be proprietary p1 =Mass density of the particle
in nature and may include features specifically inherent to g =Gravitational constant, 32.2 ft/s/s

Reprinted from Plumbing Engineering Design Handbook, Volume 4. 2012, American Society of Plumbing Engineers.

2 Read, Learn, Earn MAY 2013


D =Diameter of the particle Retention Period
V =Volume of the particle, 13pr3 for a sphere (r=radius The retention period (P) is the theoretical time that the water
of the particle) is held in the grease interceptor. The volume of the tank for
Experimental values of the drag coefficient have been the required retention period can be computed as follows:
correlated with the Reynolds number, a dimensionless term Equation 8-4
expressing the ratio of inertia and viscous forces. (Note:
Equation 8-2 applies to particles with diameters 0.4 inch [10 V= QP
mm] or smaller and involving Reynolds numbers less than 7.48
As an example of the use of Equation 8-4, for a retention
1. For larger diameters, there is a transition region; thereaf-
period (P) equal to two minutes and a flow rate (Q) of 35
ter, Newtons law applies.) The expression for the Reynolds
gallons per minute (gpm), the tank volume is:
number, R=r v D/m, contains, in addition to the parameters
V = (35 x 2) / 7.48 = 9.36 ft3
defined above, the absolute viscosity. The drag coefficient has
Retention periods should be based on peak flows. In Inter-
been demonstrated to equal 24/R (Stokes law). When this
national Standard (SI) units, the denominator in Equation 8-4
value is substituted for Cd in Equation 8-2, the result is the
becomes approximately unity (1).
following (Reynolds number < 1):
Equation 8-3 Flow-Through Period
The actual time required for the water to flow through an
g (p1 p) D2
v= existing tank is called the flow-through period. How closely
18m
this flow-through period approximates the retention period
The relationship in Equation 8-3, which identifies the depends on the tank. A well-designed tank should provide a
principle of separation in a gravity grease interceptor, has flow-through period of at least equal to the required reten-
been verified by a number of investigations for spheres and tion period.
fluids of various types. An examination of this equation shows
Factors Affecting Flotation in the Ideal Basin
that the vertical velocity of a grease globule in water depends
When designing the ideal separation basin, four parameters
on the density and diameter of the globule, the density and
dictate effective FOG removal from the water: grease/oil
viscosity of the water, and the temperature of the water and
droplet size distribution, droplet velocity, grease/oil concen-
FOG material. Specifically, the grease globules vertical veloc-
tration, and the condition of the grease/oil as it enters the
ity is highly dependent on the globules diameter, with small
basin. Grease/oil can be present in five basic forms: oil-coated
globules rising much more slowly than larger ones. Thus,
solids, free oil, mechanically emulsified, chemically emulsi-
larger globules have a faster rate of separation.
fied, and dissolved. When designing the ideal basin, consider
The effect of shape irregularity is most pronounced as the
only free grease/oil.
floating velocity increases. Since grease particles that need to
The ideal separation basin is one that has no turbulence,
be removed in sanitary drainage systems have slow floating
short-circuiting, or eddies. The flow through the basin is
velocities, particle irregularity is of small importance.
laminar and distributed uniformly throughout the basins
Figure 8-1 shows the settling velocities of discrete spheri-
cross-sectional area. The surface-loading rate is equal to the
cal particles in still water. The heavy lines are for settling
overflow rate. Free oil is separated due to the difference in
values computed using Equation 8-3 and for drag coefficients
specific gravity between the grease/oil globule and the water.
depending on the Reynolds number. Below a Reynolds num-
Other factors affecting the design of an ideal basin are influ-
ber of 1, the settlement is according to Stokes law. As noted
ent concentration and temperature.
above, as particle sizes and Reynolds numbers increase, there
is first a transition stage, and then Newtons law
applies. At water temperatures other than 50F
(10C), the ratio of the settling velocities to those
SG-0.85
at 50F (10C) is approximately (T+10)/60, where
T is the water temperature. Sand grains and
heavy floc particles settle in the transition region;
however, most of the particles significant in the
investigation of water treatment settle well within SG-0.90
the Stokes law region. Particles with irregular
shapes settle somewhat more slowly than spheres
of equivalent volume. If the volumetric concentra- SG-0.95
tion of the suspended particles exceeds about 1
percent, the settling is hindered to the extent that
the velocities are reduced by 10 percent or more.
Flotation is the opposite of settling insofar as
the densities and particle sizes are known.

Figure 8-1 Rising and Settling Rates in Still Water


MAY 2013 Read, Learn, Earn3
READ, LEARN, EARN: Grease Interceptors
globule to rise the distance needed
for capture (see Figure 8-3). If the
grease/oil globule rate of rise (Vt) ex-
ceeds the retention time required for
separation, the basin will experience
pass-through or short-circuiting.
Retention time can be expressed as:
Equation 8-5
V=QT
where
V =Volume of basin
Q =Design flow
T =Retention time
As previously noted, particles that
rise to the surface of a liquid are said
to possess rise rates, while particles
Figure 8-2 Cross-Section of a Grease Interceptor Chamber that settle to the bottom exhibit set-
tling rates. Both types obey Stokes
It is important to evaluate and quantify a basin design law, which establishes the theoreti-
both analytically and hydraulically. Figure 8-2 shows a cross- cal terminal velocities of the rising and/or settling particles.
section of a basin chamber. The basin chamber is divided into With a value of 0.015 centimeter for the diameter (D) of the
two zones: liquid treatment zone and surface-loading area globule, the rate of rise of oil globules in wastewater may be
(grease/oil mat). The mat zone is that portion of the basin expressed in feet per minute as:
where the separated grease/oil is stored. L is the length of the Equation 8-6
chamber or basin, and D is the liquid depth or the maximum
distance the design grease/oil globule must rise to reach the 0.0241 (Sw So)
Vt=
grease mat. Vh is the horizontal velocity of the water, and u
Vt is the vertical rise rate of the design grease/oil globule. where
As noted, the separation of grease/oil from water by grav- Vt =Rate of rise of oil globule (0.015 centimeter in
ity differential can be expressed mathematically by Stokes diameter) in wastewater, feet per minute
law, which can be used to calculate the rise rate of any grease/ Sw =Specific gravity of wastewater at design temperature
oil globule on the basis of its size and density and the density of flow
and viscosity of the water. (See Figure 8-1 for the rise rate So =Specific gravity of oil in wastewater at design
temperature of flow
versus globule size at a fixed design temperature.)
u =Absolute viscosity of wastewater at design
The primary function of a grease interceptor is to separate temperature, poises
free-floating FOG from the wastewater. Such a unit does not
separate soluble substances, and it does not break emulsions. Grease Interceptor Design Example
Therefore, it never should be specified for these purposes. The following example illustrates the application of the above
However, like any settling facility, the interceptor presents an equations for the design of a grease interceptor.
environment in which suspended solids are settled coincident Without additional data describing the distribution of oil
with the separation of the FOG in the influent. droplets and their diameters within a representative waste-
The ability of an interceptor to perform its primary func- water sample, it is not possible to quantitatively predict
tion depends on a number of factors. These include the type the effect that increased interceptor size or reduced flow
and state of FOG in the waste flow, the characteristics of and subsequent increased retention time within the grease
the carrier stream, and the design and size of the unit. Due interceptor will have on the effluent concentration of the
to the reliance on gravity differential phenomena, there is interceptor. However, experimental research on oil droplet
a practical limitation to interceptor effectiveness. In terms rise time (see Table 8-1) illustrates the effect that increased
of grease/oil globule size, an interceptor will be effective interceptor size or reduced flow and subsequent increased
over a globule diameter range having a lower limit of 0.015 retention time within the grease interceptor will have on
centimeter (150 microns). oil droplet removal. Following the logic in Table 8-1 allows
Gravity separation permits the removal of particles that the designer to improve the grease interceptor by increasing
exhibit densities different from their carrier fluid. Separation the interceptor volume or reducing flow and subsequently
is accomplished by detaining the flow stream for a sufficient lowering horizontal velocity and increasing retention time
time to permit particles to separate out. Separation, or reten- within the grease interceptor.
tion, time (T) is the theoretical time that the water is held Other data for this example is as follows:
in the basin. A basin must be designed such that even if the
grease/oil globule enters the chamber at the worst possible Specific gravity of grease/oil in wastewater: 0.9 (average)
location (at the bottom), there will be enough time for the Temperature of wastewater and oil mixture: 68F (average)

4 Read, Learn, Earn MAY 2013


Rate of rise of oil globules in wastewater: use Equation 8-6 each droplet will (in accordance with Stokes law) rise toward
Dimensions of a typical 20-gpm capacity grease interceptor: the surface or fall to the bottom at a rate depending on its
own diameter.
Capacity: 21.33 gallons In strong concentrations of very small particles, as in
Dimensions: 22 inches long, 14 inches wide, 20 inches high turbid waters, hindered flotation takes place. This condi-
Fluid level: 16 inches tion means that the faster-rising particles collide with the
slower-rising particles with more or less agglomeration due
Flow rate: 20 gpm to adhesion. The resulting larger particles float faster. These
Inlet/outlet: 2 inches coalesce into larger droplets with a higher rate of rise. The
Grease interceptors are to operate when completely full odds of such a collision depend on the droplet size distribution
and when the interceptor is in a horizontal position. and the quantity of droplets in the mixture. This condition
is particularly noticeable where the suspended particles are
Inlet and outlet pipes are running full, and the interceptor highly flocculent (i.e., composed of masses of very finely
is fully charged. divided material). Therefore, a tank that is deep enough
Grease/oil globules must rise a minimum distance of 3 to permit agglomeration will have a blanket (or mass) of
inches from a point at the bottom of the inlet head of the flocculent material receiving the suspended solids from the
interceptor to a point directly below the interceptor effluent material rising from below or from the currents passing
outlet. through it. Thus, the tank will lose masses of the agglomer-
Solution ated solids to the storage space above.
First, determine the rate of rise of oil globules: 150 mi- While varying flotation rates among the particles are prob-
cron=0:01:03 minutes. ably the most important factor in agglomeration, the varying
Then determine the wastewater flow rate through a 20- liquid velocities throughout the tank have a similar effect,
gpm capacity grease interceptor: causing fast-moving particles to collide with slower-moving
particles. Since flocculation can be assumed to continue
Vh=L/T=1.83 ft2/1.03 minutes=1.776 ft/min
throughout the entire flotation period, the amount of floc-
Wetted cross-sectional area of the separation basin: culation depends on the detention period. Accordingly, with
WH=14 in. 16 in. =224 in.26.94410-3=1.55 a given overflow rate, a tank of considerable depth should
ft2 be more efficient than a shallow unit. On the other hand, a
Wastewater flow rate:1.55 ft21.776 ft/min=2.76 ft3/ decrease in the overflow rate might have the same effect. A
min7.48=20.66 gpm flotation test might determine the point of agglomeration
for a known water sample.
This example proves the critical elements in designing the
ideal basin. Grease/oil droplet size and velocity determine the Practical Design
minimum outlet elevation needed to capture the targeted
While acquaintance with the theory of flotation is important
grease/oil globule. This also establishes retention time as a
to the engineer, several factors have prevented the direct ap-
key element in the design of a basin.
plication of this theory to the design of grease interceptors.
The hydraulic environment of the separation chamber of
Some turbulence is unavoidable at the inlet end of the tank.
the grease interceptor induces the separation of grease/oil
This effect is greatly reduced by good inlet design (including
and the deposition of solids. Stokes law governs the rise and
baffling) that distributes the influent as uniformly as practi-
fall rates of an oil droplet or solid particle in the fluid stream.
cable over the cross-section of the tank. There is also some
The principles of flotation discussed above are applicable
interference with the streamline flow at the outlet, but this
strictly to particles that are separate and distinct. If the
condition is less pronounced than the inlet turbulence and
wastewater mixture contains variously sized grease/oil drop-
is reduced only by using overflow weirs or baffles. Density
lets and solid particles distributed throughout the mixture,
currents are caused by differences in the temperature, the

Figure 8-3 Trajectory Diagram

MAY 2013 Read, Learn, Earn5


READ, LEARN, EARN: Grease Interceptors
density of the incoming wastewater, and the interceptors Grease Interceptor Types
contents. Incoming water has more suspended matter than
the partially clarified contents of the tank. Therefore, the Hydromechanical Grease Interceptors
influent tends to form a relatively rapid current along the For more than 100 years, grease interceptors have been used
bottom of the tank, which may extend to the outlet. This in plumbing drainage systems to prevent grease accumulations
condition is known as short-circuiting and occurs even with from clogging interconnecting sanitary piping and sewer lines.
a uniform collection at the outlet end. However, it wasnt until 1949 that a comprehensive standard
Flocculation of suspended solids has been mentioned. Its for the basic testing and rating requirements for hydrome-
effects, however, are difficult to predict. chanical grease interceptors was developed. This standard is
In general, the engineer depends on experience as well known as PDI G101. It has been widely recognized and is refer-
as the code requirements of the various local health depart- enced in most plumbing codes, replicated in ASME A112.14.3:
ments for the preferred retention and overflow rates. Depth Grease Interceptors, referred to in manufacturers literature,
already has been discussed as having some effect on the and included in the basic testing and rating requirements of
tanks efficiency. A smaller depth provides a shorter path for Military Specification MIL-T-18361. A specifying engineer or
the rising particle to settle, which gives the basin greater ef- purchaser of a hydromechanical grease interceptor can be
ficiency as the surface-loading rates match the overflow rates assured that the interceptor will perform as intended when
based on a given retention time. The tanks inlets and outlets it has been tested, rated, and certified in conformance with
require careful consideration by the designer. The ideal inlet PDI G101, ASME A112.14.3, and ASME A112.14.4: Grease
reduces the inlet velocity to prevent the pronounced currents Removal Devices.
toward the outlet, distributes the inlet water as uniformly Conventional manually operated hydromechanical inter-
as practical over the cross-section of the tank, and mixes the ceptors (see Figure 8-4A) are extremely popular and generally
inlet water with the water already in the tank to prevent are available with a rated flow capacity up to 100 gpm (6.31
the entering water from short-circuiting toward the outlet. L/s) for most applications. For flow rates above 100 gpm (6.31
L/s), large capacity units up to 500 gpm (31.5 L/s) commonly
are used. The internal designs of these devices are similar.
The inlet baffles, usually available in various styles and
arrangements, act to ensure at least 90 percent efficiency
Table 8-1 Droplet Rise Time of grease removal through the HGI, per PDI G101 testing
Travel Time for 3-inch Distance at requirements for units of 100 gpm and less. Care should
688F (hr:min:sec) be taken to avoid long runs of pipe between the source and
Droplet Diameter Oil (rise time) the interceptor to avoid FOG accumulation and mechanical
(microns) SG 0.85 emulsification prior to entering the interceptor.
300 0:00:12
Grease removal from manually operated hydromechani-
150 0:00:42
cal grease interceptors is typically performed by opening the
125 0:01:00
90 0:01:54
access cover and manually skimming the accumulated grease
60 0:04:12 from the interior water surface (along with the removal of a
50 0:06:18 perforated filter screen for cleaning if so equipped).
40 0:09:36 Semiautomatic Units
30 0:17:24
Semiautomatic units are typically a hydromechanical in-
20 0:38:46
terceptor design, with FOG accumulation on the surface
15 1:08:54
10 2:35:02
of the water inside the interceptor. However, these types of
5 10:02:09 HGIs are not used as widely as they once were due in part to
1 258:23:53 advances in grease retention equipment technology. In addi-
Droplet Diameter Oil (rise time) tion, the FOG removal process involves the running of hot
(microns) SG 0.90 water through the interceptor to raise the water level and
300 0:00:15 force the FOG into the draw-off recovery cone or pyramid
150 0:01:03 and then out through the attached draw-off hose to a FOG
125 0:01:27 disposal container until the running water becomes clear. As
90 0:02:54 compared to the operational qualities of the interceptor types
60 0:06:36 and technologies currently available, this process wastes
50 0:09:18 potable water at a time when water conservation should be
40 0:14:24
of critical concern to the plumbing engineer, especially in
30 0:25:48
certain areas of the country where the cost of water may be
20 0:58:08
15 1:43:22 at a premium for a facility owner.
10 3:52:33 Separators
5 15:30:14 Grease separators are available from some manufacturers.
1 387:35:49
They separate FOG-laden wastes discharged from fixtures
via gravity action. These types of devices are similar to HGIs

6 Read, Learn, Earn MAY 2013


in their construction, function, and cleaning. Unlike HGIs, When GRDs are considered for installation, the manu-
they are not PDI G101 certified and do not contain or rely facturer should be consulted regarding electrical, service,
on external flow control devices for proper functioning. In- and maintenance requirements. The plumbing engineer
ternally, they are constructed in such a way that there is no must coordinate these requirements with the appropriate
straight-through travel of wastewater from inlet to outlet. trades to ensure a proper installation. Furthermore, owing
Flow through the unit is directed in a specific pattern and/or to these requirements, it is essential that those responsible
use of components (engineered by the device manufacturer) for operating GRDs be trained thoroughly in their operation.
as required to minimize flow velocities and allow for the
proper separation of FOG material from the wastewater.
Provided that the device has been properly sized and installed
correctly, the inlet simply closes when the separators hold-
ing capacity is reached if short-circuiting devices or methods
have not been otherwise utilized. As such, this type of device
has essentially a built-in flow control and needs no external
flow control. These devices can be selected where allowable
by local authorities and where the installation of a PDI G101-
certified device is not required for approval.
Grease Removal Devices
Grease removal devices are typically hydromechanical in-
terceptors that incorporate automatic, electrically powered
skimming devices within their design. The two basic varia-
tions of this type of interceptor are timer-controlled units
and sensor-controlled units. (A)
In timer-controlled units (see Figure 8-4B), FOG is
separated by gravity flotation in the conventional manner, at
which point the accumulated FOG is skimmed from the sur-
face of the water in the interceptor by a powered skimming
device and activated by a timer on a time- or event-controlled
basis.
The skimmed FOG is essentially scraped or wiped from
the skimmer surface and directed into a trough, from which
it drains through a small pipe from the interceptor into a
disposal container located adjacent to the interceptor. Most
GRDs are fitted with an electric immersion heater to elevate
the temperature in the interceptor to maintain the contained
FOG in a liquid state for skimming purposes.
A variation of this type of interceptor utilizes a FOG re- (B)
moval pump that is positioned in a tray inside the interceptor
and controlled from a wall unit that contains a timer device.
The pump is attached to a small translucent tank with a drain
outlet that is located adjacent to the interceptor.
To operate these units, a timer is set to turn on the skim-
mer or FOG removal pump within a selected period. In a
short time, the accumulated FOG is drained into the adjacent
container, to be disposed of in a proper manner.
Sensor-controlled units employ computer-controlled
sensors or probes, which sense the presence of FOG and
automatically initiate the draw-off cycle at a predetermined
percentage level of the interceptors rated capacity. FOG is
then drawn from the top of the FOG layer in the interceptor.
The draw-off cycle continues until the presence of water is
detected by the sensor, which stops the cycle to ensure that
only water-free FOG is recovered. If required, an immersion
heater is activated automatically at the onset of the draw-off
cycle to liquefy FOG in the interceptor. In addition, if either
the units grease collection reservoir (where the recovered
grease is stored pending removal) or the interceptor itself (C)
is near capacity with potential overloading sensed, warning Figure 8-4 (A) Hydromechanical Grease Interceptor; (B) Timer-
measures and unit shutdown are activated automatically. controlled Grease Removal Device; (C) FOG Disposal System
MAY 2013 Read, Learn, Earn7
READ, LEARN, EARN: Grease Interceptors
FOG Disposal Systems the interceptor supports a metering pump, timer, controls,
A FOG disposal system is very similar to a hydromechanical and a bottle filled with a bacteria culture provided by the
interceptor in its operation. However, in addition to reducing system manufacturer.
FOG in effluent by separation, it automatically reduces FOG As the FOG material collects in the biofilm, bacteria from
in effluent by mass and volume reduction, without the use of the culture bottle (injected by the metering pump) break the
internal mechanical devices or manual FOG removal. This bonds between fatty acids and glycerol and then the bonds
system is specifically engineered, and one type is configured between the hydrogen, carbon, and oxygen atoms of both,
to contain microorganisms that are used to oxidize FOG thereby reducing FOG volume. Drainage continues through
within the interceptor to permanently convert the FOG ma- the media chamber around the outlet baffle, where it then is
terial into the by-products of digestion, a process otherwise discharged to the sanitary system.
referred to as bioremediation. (It should be noted that this Though FOG disposal systems significantly reduce the
is also the same process used by municipal wastewater treat- need for manual FOG removal or the handling of mechanical-
ment plants.) Other FOG disposal systems utilize thermal ly removed FOG materials, the need for monitoring effluent
or chemical methods of oxidation. quality, routine maintenance to remove undigested materi-
Figure 8-4C is an example of a bioremediation type of als, and inspections to ensure all components are clean and
interceptor. The interceptor is divided into two main cham- functioning properly are required and should be performed
bers, separated by baffles at the inlet and outlet sides. The on a regular basis.
baffle located at the inlet side of the interceptor acts to dis- Furthermore, it is essential that the plumbing engineer
tribute the inflow evenly across the horizontal dimension coordinate all electrical and equipment space allocation
of the interceptor. However, unlike conventional HGIs, a requirements with the appropriate trades to allow for the
media chamber is its main compartment, which contains proper installation and functioning of a FOG disposal system.
a coalescing media that is engineered to cause FOG to rise Gravity Grease Interceptors
along the vertical surfaces of the media structure, where it Gravity grease interceptors commonly are made of 4-inch
comes into contact with microorganisms inhabiting a biofilm (101.6-mm) minimum thickness concrete walls, with inte-
attached to the media. A wall-mounted shelf located above rior concrete barriers that act to sectionalize the
interior into multiple chambers that dampen flow
and retain FOG by flotation. Figure 8-5A shows a
typical installation. However, standards allow other
materials such as fiberglass, plastic, and protected
steel. Generally, these units are used outside build-
ings as inground installations rather than as inside
systems adjacent to or within kitchen areas. These
units generally do not include the draw-off or flow-
control arrangements common to hydromechanical
units.
The unit should be installed as close to the source
of FOG as possible. If this cannot be achieved due
to field conditions or other site constraints, a heat
trace system can be installed along the drain piping
(A) that is routed to the inlet side of the GGI to help
keep the FOG-laden waste from solidifying before
it enters the interceptor. Increasing the slope of the
drain piping to the interceptor also can be considered
in lieu of heat tracing where allowable by local codes
and authorities having jurisdiction.
If a unit is located in a traffic area, care must be
taken to ensure that the access covers are capable
of withstanding any possible traffic load. It is also
important that the interceptor be located in such a
way as to allow easy cleanout.
Prefabricated GGIs also tend to be internally
and externally configured with unique, pre-installed
features designed to meet the local jurisdictional
requirements of any given project location. The
plumbing engineer must verify the local require-
ments to which these units must conform to ensure
(B)
proper unit selection.
Figure 8-5 (A) Gravity Grease Interceptor; (B) Passive, Tank-Type Field-formed concrete gravity grease interceptors
Grease Interceptor are basically identical to the prefabricated units as
8 Read, Learn, Earn MAY 2013
described above, with the exception that they usually are and the exterior of the interceptor.The exterior corrosion
constructed at the project site. Though likely more expensive protection is a two-part, polyurethane, high-build coating with
to install than a prefabricated unit, one reason for its instal- interior coating options of polyurethane, epoxy, or a proprie-
lation could be unique project site constraints. For example, a tary material (depending on influent wastewater temperature,
GGI may need to be installed in a very tight area, too close to wastewater characteristics, etc.). When protected steel tank
existing property lines or adjacent structures to allow hoist- GGIs are considered for installation, the manufacturer should
ing equipment the necessary access to an excavated area that be consulted regarding venting and hold-down requirements
otherwise would be sufficient for a standard prefabricated for buoyancy considerations.
GGI installation.
Following is a list of recommended installation provisions Installation
for prefabricated and field-formed GGIs located outside a Most local administrative authorities require in their jurisdic-
building. tions codes that spent water from food service fixtures and
The unit should be installed as close to the source of equipment producing large amounts of FOG discharge into an
FOG as possible. If this cannot be achieved due to field approved interceptor before entering the municipalitys sani-
conditions or other site constraints, a heat trace system tary drainage system. These requirements (generally code
can be installed along the drain piping that is routed to and pretreatment regulations, with pretreatment coordina-
the inlet side of the GGI. tors having the final word) can include multi-compartment
pot sinks, pre-rinse sinks, kettles, and wok stations, as well
The influent should enter the unit at a location below the
as area floor drains, grease-extracting hoods installed over
normal water level or near the bottom of the GGI to keep
frying or other grease-producing equipment, and dishwash-
the surface as still as possible.
ing equipment.
The inlet and the outlet of the unit should be provided If floor drains are connected to the interceptor, the engi-
with cleanouts for unplugging both the sewers and the neer must give special consideration to other adjacent fixtures
dip pipes. that may be connected to a common line with a floor drain
The effluent should be drawn from near the bottom of upstream of the interceptor. Unless flow control devices are
the unit, via a dip pipe, to remove as much floating grease used on high-volume fixtures or multiple fixtures flowing
and solids as possible. upstream of the floor drain connection, flooding of the floor
A large manhole, or removable slab, should be provided drain can occur. A common misapplication is the installation
for access to all chambers of the grease interceptor for of a flow control device at the inlet to the interceptor that may
complete cleaning of both the floating and the settled restrict high-volume fixture discharge into the interceptor,
solids. but floods the floor drain on the common branch. Floor drains
connected to an interceptor require a recessed (beneath the
The top, or cover, should be gas-tight and capable of
floor) interceptor design.
withstanding traffic weight.
An acceptable design concept is to locate the interceptor
A difference in elevation between the inlet and the outlet as close to the grease-producing fixtures as possible. Under-
of 3 to 6 inches (76.2 to 152.4 mm) should be provided the-counter or above-slab interceptor installations are often
to ensure flow through the grease interceptor during possible adjacent to the grease-producing fixtures. This type
surge conditions without the waste backing up in the of arrangement often avoids the individual venting of the
inlet sewer. As the grease begins to accumulate, the top fixtures, with a common vent and trap downstream of the
of the grease layer will begin to rise above the normal grease interceptor serving to vent the fixtures and the grease
water level at a distance of approximately 1 inch (25.4
interceptor together. Therefore, a p-trap is not required on the
mm) for each 9 inches (228.6 mm) of grease thickness.
fixture outlet. However, provided this particular arrangement
After installation, testing of the GGI for leakage should is allowed by governing codes and local jurisdictions, special
be a specification requirement prior to final acceptance. attention should be paid to air inlet sources for the air-injected
In addition to concrete GGIs, gravity grease interceptors flow control if no p-trap is attached to the fixture outlet to
in the form of prefabricated round, cylindrical protected steel avoid circuiting the building vent to the fixture.
tanks are also available (see Figure 8-5B). These units often If the grease interceptor is located far from the fixtures
are referred to as passive grease interceptors, but they fall it serves, the grease can cool and solidify in the waste lines
into the same category as gravity grease interceptors because upstream of the grease interceptor, causing clogging condi-
they operate in virtually the same manner. Interceptors of tions or requiring more frequent cleaning of the waste lines.
this type are available with single and multiple chambers (de- However, a heat trace system can be installed along the main
pending on local jurisdictional requirements), with internal waste line that is routed to the inlet side of the interceptor
baffles, vent connections, and manhole extensions as required to help keep the FOG-laden waste from solidifying before
to allow for proper operation. They are manufactured in it enters the interceptor. Long horizontal and vertical runs
single- and double-wall construction and can be incorporated also can cause mechanical emulsification of entrained FOG,
with steam or electric heating systems to help facilitate FOG which makes it difficult to separate.
separation and extraction from the unit. Some practical considerations are also important if an
Protected steel tank GGIs are built to UL specifications interceptor is to be located near the fixtures it serves. If the
for structural and corrosion protection for both the interior interceptor is an under-the-counter, above-the-slab device,

MAY 2013 Read, Learn, Earn9


READ, LEARN, EARN: Grease Interceptors
the engineer should leave enough space above the cover to when flow control devices are used because of the lower flow
allow complete cleaning and FOG removal from the unit. in the waste line downstream of the flow control device. Such
Some ordinances also require that interceptors not be flow may not be enough to ensure self-cleaning velocities of
installed where the surrounding temperatures under normal 3 feet per second (fps) (0.9 m/s).
operating conditions are less than 40F (4.4C). While flow control is necessary to ensure that an intercep-
Some administrative authorities prohibit the discharge tor will meet PDI G101 standards and function as designed,
of food waste disposers through HGIs and GRDs because of it should be stated that they can also be problematic due to
the clogging effect of ground-up particles. Other jurisdictions their nature and purpose. Along with the issues previously
allow this setup, provided that a solids interceptor or strainer mentioned, these devices clog fairly rapidly if not maintained
basket is installed upstream of these devices to remove any on a regular basis due to their construction. It is not uncom-
food particulates prior to entering the interceptor. It is recom- mon for these devices to be removed entirely and discarded
mended that food waste disposers be connected to HGIs and by facility maintenance personnel in an effort to alleviate
GRDs (in conjunction with a solids strainer) when allowed by clogging and minimize maintenance expenses. Whether legal
the authority having jurisdiction due to the fact that disposer or not, this defeats the purpose of having the device in the
waste discharge is a prime carrier of FOG-laden material. first place, resulting in an interceptor installation that may
The same situation is similar with respect to dishwashers. not function as intended.
Some administrative authorities prohibit the discharge of An alternative to utilizing a flow control device may be
dishwasher waste to HGIs and GRDs, while other jurisdictions to select an interceptor whose flow characteristics exceed
allow it, provided that the dishwashers are without pre-rinse the design flow rate established for a facility or fixture. In
sinks. It is recommended that dishwashers not be connected the case of a single fixture or point-of-use application, Equa-
to HGIs or GRDs. Although the high discharge waste tem- tion 1-11 from Plumbing Engineering Design Handbook,
perature from a dishwasher may be beneficial to the FOG Volume 1 could be used to determine the actual flow rate of
separation process by helping maintain the FOG in a liquid a fixture. The subsequent selection of an interceptor would
state, the detergents used in dishwashing equipment can then be of a capacity greater than that of the discharge flow
inhibit the devices ability to separate FOG altogether, which rate of the fixture to ensure proper operation and removal of
allows FOG to pass through the device where it eventually FOG. The same method or a central interceptor installation
can revert to its original state and cause problems within the could be used for a group of fixtures, except that the Man-
municipal sanitary system. ning formula could then be used to determine the necessary
influent flow rate. While either method typically results in
Flow Control the selection of an interceptor that is somewhat oversized,
Flow control devices are best located at the outlet of the the elimination of a flow control device and longer durations
fixtures they serve. However, flow control fittings are not between interceptor cleanings could be achieved, thus offset-
common for floor drains or for fixtures that would flood ting initial installation cost over time.
if their waste discharge was restricted (such as a grease-
extracting hood during its flushing cycle). Guidelines for Sizing
A few precautions are necessary for the proper applica- The following recommended sizing procedure for grease in-
tion of flow control devices. The engineer should be sure that terceptors may be used as a general guideline for the selection
enough vertical space is available if the flow control device is of these units. The engineer should always consult the local
an angle pattern with a horizontal inlet and a vertical outlet. administrative authorities regarding variations in the allow-
A common difficulty encountered is the lack of available able drain-down times acceptable under the approved codes.
height for an above-slab grease interceptor adjacent to the Calculation details and explanations of the decision-making
fixture served when the vertical height needed for the drain processes have been included in full in the examples as an aid
outlet elbow, pipe slope on the waste arm from the fixture, to the engineer using these guidelines in specific situations.
vertical outlet flow control fitting, and height from the grease Example 8-1
interceptor inlet to the floor are all compensated.
The air intake (vent) for the flow control fitting may Assume an HGI or a GRD for a single-fixture installation
terminate under the sink as high as possible to prevent with no flow control. Size the grease interceptor for a three-
overflow or terminate in a return bend at the same height on compartment pot (scullery) sink, with each compartment
the outside of the building. When the fixture is individually being 182412 inches.
trapped and back-vented, air intake may intersect the vent 1. First, determine the sink volume:
stack. All installation recommendations are subject to the C u b i c c o n t e n t s o f o n e s i n k c o m p a r t m e n t =
approval of the code authority. The air intake allows air to be 182412=5,184 in.3
drawn into the flow control downstream of the orifice baffle,
thereby promoting air-entrained flow at the interceptors Cubic contents of three sink compartments=
rated capacity. The air entrained through the flow control 35,184=15,552 in.3
also may aid the flotation process by providing a lifting effect Contents expressed in gallons= 1 5 , 5 5 2
for the rising grease. in.3/231=67.3 gallons
It is particularly important to install the grease 2. Then add the total potable water supply that could be
interceptor near the grease-discharging fixture discharged independent of a fixture calculated above,

10 Read, Learn, Earn MAY 2013


including manufacturer-rated appliances such as water- of different flow rates depending on which particular type of
wash exhaust hoods and disposers (if allowed to discharge interceptor is being considered for installation.)
to the interceptor). Lastly, in certain projects the plumbing engineer may be
3. Next, determine the fixture load. A sink (or fixture) called on to select an interceptor in which the flow rates for
seldom is filled to the brim, and dishes, pots, or pans dis- a facility are not readily quantifiable at the time of design,
place approximately 25 percent of the water. Therefore, such as for a future expansion, restaurant, or food court area
75 percent of the actual fixture capacity should be used within a new development. In this case, tables or formulas
to establish the drainage load: can be used in an effort to help quantify the maximum flow
0.7567.3 gal=50.8 gal rate that will be encountered for a specific pipe size at a
given slope and velocity that ultimately discharges to the
4. Calculate the flow rate based on drain time, typically one interceptor. This information can be used to select the proper
minute or two minutes. The flow rates are calculated interceptor capacity for the intended flow rates anticipated.
using the following equation:
Drainage load, in gallons / Drainage load, in minutes Code Requirements
Therefore, the flow rate for this example would be: The necessity for the plumbing engineer to verify all state
and local jurisdictional requirements prior to the start
50 gpm (3.15 L/s) for one-minute drainage or 25 gpm of any food service facility design cannot be emphasized
(1.58 L/s) for two-minute drainage. enough. Although state and model plumbing codes provide
5. Last, select the interceptor. Choose between a hydro- information with respect to interceptor requirements and
mechanical interceptor with a rated capacity of 50 gpm regulations, local health departments and administrative
for one-minute flow or 25 gpm for two-minute flow or authorities having jurisdiction have likely established their
a gravity interceptor with a capacity of 1,500 gallons own set of guidelines and requirements for an interceptor on
(50-gpm flow rate30-minute detention time). a specific project and, therefore, also should be consulted at
Local administrative authorities having jurisdiction the start of the design. It is up to the plumbing engineer to
should be consulted as they may dictate a specific formula or pull together the various agency requirements in an effort
sizing criteria that would ultimately determine the specific to design a code-compliant system, while incorporating any
flow parameters for which the interceptor could be selected. additional governing requirements and regulations.
It is extremely important to determine not only the governing Following are itemized lists incorporating the major provi-
model code requirements regarding specific interceptor crite- sions of the model plumbing codes and are included herein as
ria, but also local jurisdictional requirements promulgated by an abbreviated design guide for the engineer when specifying
the pretreatment authority since they sometimes contradict sizing. It is important to review the applicable code in effect
each other, especially where local jurisdictions adopt certain in the area for any variation from this generalized list.
amendments and regulations that may supersede any model UPC Requirements for Interceptors
code requirements.
Grease extraction water-wash hood equipment may be 1. Grease interceptors are not required in individual dwell-
used. It should be noted that while these systems are used ing units or residential dwellings.
in some cases, grease hoods that incorporate troughs that 2. Water closets, urinals, and other plumbing fixtures con-
entrap grease, which are sloped to drip cups at the ends of veying human waste shall not drain into or through any
the hood, are used quite prevalently. These cup drains are interceptor.
removed by hand, and the FOG material contained is disposed 3. Each fixture discharging into an interceptor shall be
of in a proper manner and never discharges to the interceptor. individually trapped and vented in an approved manner.
It is important to verify which types of systems will be used
4. Grease waste lines leading from floor drains, floor
with respect to grease hood equipment prior to the selection
sinks, and other fixtures or equipment in serving estab-
of the interceptor so the proper capacity can be determined. lishments such as restaurants, cafes, lunch counters,
It also should be noted that the phrase sizing an intercep- cafeterias, bars, clubs, hotels, hospitals, sanitariums,
tor is used throughout the industry quite loosely. However, factory or school kitchens, or other establishments where
grease interceptors are not sized. They are selected based on grease may be introduced into the drainage or sewage
specific flow parameters and requirements as determined by system shall be connected through an approved intercep-
the plumbing engineer during the design process for each tor.
individual facility. Furthermore, the design flow rates and
5. Unless specifically required or permitted by the author-
pipe sizing criteria for food preparation facilities should not
ity having jurisdiction, no food waste disposal unit or
be determined by using the fixture unit method typically used
dishwasher shall be connected to or discharge into any
for other types of facilities due to the fact that the probabil- grease interceptor. Commercial food waste disposers
ity of simultaneous use factors associated with fixture unit shall be permitted to discharge directly into the building
values do not apply in food preparation facilities where in- drainage system.
creased and continuous flow rates are encountered. Also, the
facility determines the peak flows used to select the proper 6. The waste discharge from a dishwasher may be drained
interceptor for the intended application, not the other way into the sanitary waste system through a gravity grease
around (i.e., a single facility does not discharge at a multitude

MAY 2013 Read, Learn, Earn11


READ, LEARN, EARN: Grease Interceptors
interceptor when approved by the authority having ju- 5. Hydromechanical grease interceptors shall have the
risdiction. minimum grease retention capacity for the flow-through
7. Flow control devices are required at the drain outlet of rates indicated in Table 8-2.
each grease-producing fixture connected to a hydrome-
chanical grease interceptor. Flow control devices having Operation and Maintenance
adjustable (or removable) parts are prohibited. The flow Operational methods can create problems for the engineer
control device shall be located such that no system vent even if all of the design techniques for grease interceptors
shall be between the flow control and the interceptor presented have been observed. Failing to scrape dinner plates
inlet. (Exception: Listed grease interceptors with integral and other food waste-bearing utensils into the food waste
flow controls or restricting devices shall be installed in an disposer prior to loading them into dishwasher racks means
accessible location in accordance with the manufacturers that the liquid waste discharged from the dishwasher to the
instructions.) grease interceptor also carries solid food particles into the
8. A vent shall be installed downstream of hydromechanical grease interceptor unit. The grease interceptor is not a food
grease interceptors. waste disposer.
9. The grease collected from a grease interceptor must Another common problem is insufficient grease removal.
not be introduced into any drainage piping or public or The period between removals differs for each interceptor
private sewer. type and is best left to the experience of licensed professional
cleaning services. However, if the flow rate of the unit is
10. Each gravity grease interceptor shall be so in-
constantly exceeded (no flow control) with high-temperature
stalled and connected that it shall be at all times
water, such as a heavy discharge from a dishwasher, the
easily accessible for inspection, cleaning, and removal of
grease in the unit may periodically be liquefied and washed
intercepted grease. No gravity grease interceptor shall be
installed in any part of a building where food is handled. into the drainage system downstream of the grease intercep-
tor. In this case, the operator or cleaning service may never
11. Gravity grease interceptors shall be placed as close as realize that the unit needs cleaning because it never reaches
practical to the fixtures they serve. its grease storage capacity. The difficulty is that when the
12. Each business establishment for which a gravity grease temperature of the grease/water mixture finally cools in the
interceptor is required shall have an interceptor that drainage system downstream of the grease interceptor, clog-
shall serve only that establishment unless otherwise ging ultimately occurs.
approved by the authority having jurisdiction. Adequate maintenance is critical to an efficient grease
13. Gravity grease interceptors shall be located so as to be interceptor installation. One of the most common problems
readily accessible to the equipment required for mainte- is the disposal of the accumulated grease. The grease re-
nance and designed to retain grease until accumulations moved must be disposed of in various ways depending on
can be removed by pumping the interceptor. local requirements. Grease should not be poured down any
other drain or in any sewer line or buried in the ground. It
IPC Requirements for Hydromechanical should be disposed of
Grease Interceptors
via garbage pickup or Table 8-2 Minimum Grease
1. Grease interceptors are not required in individual dwell- some similar approved Retention Capacity
ing units or private living quarters. operation. Total Flow- Grease Retention
2. A grease interceptor or automatic grease removal device Through Rating Capacity
shall be required to receive the drainage from fixtures (gpm) (pounds)
and equipment with grease-laden waste located in food 4 8
preparation areas such as restaurants, hotel kitchens, 6 12
hospitals, school kitchens, bars, factory cafeterias, and
7 14
clubs. The fixtures include pre-rinse sinks, soup kettles
or similar devices, wok stations, floor drains or sinks to 9 18
which kettles are drained, automatic hood wash units, 10 20
and dishwashers without pre-rinse sinks.
12 24
3. Where food waste disposal units are connected to grease 14 28
interceptors, a solids interceptor shall separate the
discharge before connecting to the interceptor. Solids 15 30
interceptors and grease interceptors shall be sized and 18 36
rated for the discharge of the food waste grinder. 20 40
4. Grease interceptors shall be equipped with devices to 25 50
control the rate of water flow so that the water flow does 35 70
not exceed the rated flow. The flow control device shall
be vented and terminate not less than 6 inches above 50 100
the flood rim level or be installed in accordance with 75 150
manufacturers instructions. 100 200

12 Read, Learn, Earn MAY 2013


ASPE Read, Learn, Earn Continuing Education
You may submit your answers to the following questions online at aspe.org/readlearnearn. If you score 90 percent or higher on the test,
you will be notified that you have earned 0.1 CEU, which can be applied toward CPD renewal or numerous regulatory-agency CE pro-
grams. (Please note that it is your responsibility to determine the acceptance policy of a particular agency.) CEU information will be kept
on file at the ASPE office for three years.
Notice for North Carolina Professional Engineers: State regulations for registered PEs in North Carolina now require you to complete ASPEs
online CEU validation form to be eligible for continuing education credits. After successfully completing this quiz, just visit ASPEs CEU Valida-
tion Center at aspe.org/CEUValidationCenter.
Expiration date: Continuing education credit will be given for this examination through May 31, 2014.

CE Questions Grease Interceptors (CEU 199)


1. Hydromechanical grease interceptors utilize which of the 7. A _______ reduces FOG in effluent by mass and volume
following to separate and retain FOG from the waste stream? reduction, without the use of internal mechanical devices or
a. air entrainment manual FOG removal.
b. internal baffling a. hydromechanical grease interceptor
c. hydraulic flow action b. grease removal device
d. all of the above c. FOG disposal system
d. gravity grease interceptor
2. The floating velocity of a spherical globule of grease can be
calculated using _______. 8. Gravity grease interceptors may be made of what material?
a. Darcy-Weisbach equation a. concrete
b. Manning formula b. protected steel
c. Newtons equation c. fiberglass
d. Stokes law d. all of the above
3. The vertical velocity of a grease globule in water depends on 9. What is the recommended difference in elevation between the
what? inlet and outlet of a gravity grease interceptor to ensure flow
a. density and viscosity of the water during surge conditions?
b. density and diameter of the globule a. 1 to 3 inches
c. temperature of the water and FOG material b. 2 to 4 inches
d. all of the above c. 2 to 6 inches
d. 3 to 6 inches
4. The ability of an interceptor to separate free-floating FOG
from the wastewater depends on what? 10. Some ordinances prohibit the installation of grease
a. characteristics of the carrier stream interceptors where the surrounding temperatures under
b. design and size of the unit normal operating conditions are less than _______.
c. type and state of FOG in the waste flow a. 40F
d. all of the above b. 45F
c. 50F
5. How long does it take a 125-micron-diameter droplet of oil
d. 55F
with a specific gravity of 0.90 to rise 3 inches at 688F?
a. 1 minute 11. The UPC prohibits ________ from draining into a grease
b. 1 minute, 3 seconds interceptor.
c. 1 minute, 27 seconds a. urinals
d. 2 minutes, 54 seconds b. floor drains
c. floor sinks
6. _______ occurs when the influent forms a relatively rapid
d. all of the above
current along the bottom of the interceptor tank toward the
outlet. 12. Per the IPC, a hydromechanical grease interceptor with a
a. flocculation 14-gpm flow-through rating shall have a minimum grease
b. short-circuiting retention capacity of _______.
c. suspension a. 24 pounds
d. agglomeration b. 28 pounds
c. 30 pounds
d. 36 pounds

MAY 2013 Read, Learn, Earn13

Potrebbero piacerti anche