Sei sulla pagina 1di 21

SECTION 5

Relief Systems
This section is concerned with the design and operation of quirements of the insurance covering the plant or installation.
pressure relieving systems for gas processing plants. The prin- State and federal regulations not only cover safety but also
cipal elements of pressure relief systems are the individual environmental considerations such as air and water pollution
pressure relief devices, the flare piping system, the flare sepa- and noise abatement. This section presents a convenient sum-
rator drum, and the flare including igniters, tips, sealing
devices, purge and steam injection for smokeless burning. Ap- mary of relief system information obtained from API and other
plication of relief devices must comply with appropriate ASME sources, abridged and modified for this data book. Final design
Vessel Codes. Design of relief systems must also comply with work should be consistent with the full scope of API, ASME,
applicable state and federal codes and laws as well as the re- and other code and specification requirements.

FIG. 5-1
Nomenclature

a = sonic velocity, m/s hG2 = enthalpy of vapor at downstream pressure,


A = required discharge area of the valve, cm2. Use kJ/kg
valve with the next larger standard orifice H = height of vapor space of vessel, m
size/area Hl = latent heat of the liquid exposed to fire, kJ/kg
AB = bellows area, cm2 HS = flare stack height, m
A = discharge area of the valve, cm2, for valve with I = radiation intensity at point X, W/m2
next standard size larger than required discharge k = specific heat ratio, Cp/Cv (see Section 13)
area K = coefficient of discharge, obtainable from the valve
Ac = total outside surface area of container, m2 manufacturer
AD = disk area, cm2 Kb = capacity correction factor due to back pressure
AN = nozzle seat area, cm2 Kp = capacity correction factor due to overpressure
AP = piston area, cm2 Ksh = correction factor due to the amount of superheat
Aw = total wetted surface area of vessel, m2 in the stream
A3 = vessel area exposed to fire, m2 Kv = capacity correction factor due to viscosity
B = liquid expansion coefficient, 1/C, at relieving Kw = capacity correction factor due to back pressure
temperature [or (Vol/Vol)/C] L = drum length, m
C = drag coefficient L/D = length to diameter ratio of pipe
Cp = specific heat at constant pressure, kJ/(kg K) Lf = length of flame, m
Cv = specific heat at constant volume, kJ/(kg K) M = Mach number at pipe outlet
C1 = coefficient determined by the ratio of specific MW = molecular mass of gas or vapor
heats of the gas or vapor at standard conditions MABP = maximum allowable back pressure, kPa (ga)
d = flare tip diameter, mm NHV = net heating value of flare gas, kJ/kg
D = particle diameter, mm P = set pressure, kPa (ga)
f = correction factor based on the ratio of specific heats PCF = critical-flow pressure, kPa (abs)
F = factor due to insulation (see Fig. 5-17) Pn = normal operating gas pressure, kPa (abs)
F = relief valve factor, dimensionless P1 = upstream relieving pressure, kPa (abs). This is
F2 = coefficient for subcritical flow (Fig. 5-12) the set pressure plus the allowable overpressure
FS = spring force, Newtons plus the atmospheric pressure
g = acceleration due to gravity, 9.81 m/s2 P2 = downstream pressure at the valve outlet, kPa (abs)
G = relative density of gas referred to air = 1.00 at Pb = back pressure, kPa (ga)
15C and 101.325 kPa (abs); or, if liquid, the rela- P = pressure drop, kPa
tive density of liquid at flowing temperature re- Pw = pressure drop, mm of water
ferred to water = 1.00 at 15C Q = heat input, W
hL1 = enthalpy of saturated liquid at upstream Qa = minimum required capacity expressed as m3/h of
pressure, kJ/kg air at standard conditions
hL2 = enthalpy of saturated liquid at downstream Qr = heat released, W
pressure, kJ/kg Qv = flow through valve, m3/h at standard conditions

5-1
FIG. 5-1 (Contd)
Nomenclature

r = ratio of downstream pressure to upstream pres- W =


flow, kg/h
sure, P2/P1 Whc =
hydrocarbon flow, kg/h
R = distance from flame center to point X, m Wstm =
steam flow, kg/h
J Wf =
flare gas flow rate, kg/h
Ro = universal gas constant = 8314
kg mol K Wr =
vapor rate to be relieved by the relief valve, kg/h
Re = Reynolds number (dimensionless) xi =
weight fraction of component i in total stream
S = specific heat, kJ/(kg C) X =
distance from the base of the stack to another
t = temperature, C point at the same elevation, m
T = absolute temperature of the inlet vapor, K Xc = see Fig. 5-21
Tn = normal operating gas temperature, K Yc = see Fig. 5-21
T1 = gas temperature, K, at the upstream pressure Z = compressibility factor at flowing conditions
Tw = vessel wall temperature, K Greek
Ud = maximum allowable vapor velocity for vertical = prefix, indicates finite increment
vessel, m/s = fraction of heat radiated
V = gas velocity, m/s L = density of liquid, kg/m3
Vex = exit velocity, m/s v = density of vapor, kg/m3
Vl = flow rate, liters/s at flowing tempera- = angle of flare flame from vertical, degrees
ture and pressure = viscosity at flowing temperature,
Vw = wind velocity, m/s mPa s

Nomenclature for this section is covered in Fig. 5-1. Pres- Blocked Discharge
sure relief valve is a generic term applied to relief valves,
safety valves, or safety relief valves. Definition by type of relief The outlet of almost any vessel, pump, compressor, fired
valve is covered in the relief device description. Relief valve heater, or other equipment item can be blocked by mechanical
characteristics related to pressure vessel requirements are il- failure or human error. In this case, the relief load is usually
lustrated in Fig. 5-2. the maximum flow which the pump, compressor, or other flow
source produces at relief conditions.
Fire Exposure
Fire is one of the least predictable events which may occur
RELIEF DEVICE DESIGN in a gas processing facility, but is a condition that may create
the greatest relieving requirements. If fire can occur on a
Pressure relief valves or other relieving devices are used to plant-wide basis, this condition may dictate the sizing of the
protect piping and equipment against excessive over-pressure. entire relief system; however, since equipment may be dis-
Proper selection, use, location, and maintenance of relief de- persed geographically, the effect of fire exposure on the relief
vices are essential to protect personnel and equipment as well system may be limited to a specific plot area. Vapor generation
as to comply with codes and laws. will be higher in any area which contains a large number of
uninsulated vessels. Various empirical equations have been
Determination of the maximum relief required may be dif- developed to determine relief loads from vessels exposed to
ficult. Loads for complex systems are determined by conserva- fire. Formula selection varies with the system and fluid con-
tive assumptions and detailed analysis. By general sidered. Fire conditions may overpressure vapor-filled, liquid-
assumption, two unrelated emergency conditions caused by filled, or mixed-phase systems.
unrelated equipment failures or operator error will not occur
simultaneously (no double jeopardy). The sequence of events
Tube Rupture
must be considered. The development of relief loads requires When a large difference exists between the design pressure
the engineer to be familiar with overall process design, includ- of the shell and tube sides of an exchanger (usually a ratio of
ing the type of pump drives used, cooling water source, spares 1.5 to 1 or greater), provisions are required for relieving the
provided, plant layout, instrumentation, and emergency shut- low pressure side. Normally, for design, only one tube is con-
down philosophy. sidered to rupture. Relief volume for one tube rupture can be
calculated using appropriate sizing equations in this section.
This section suggests methods to calculate relief capacity for When a cool media contacts a hot stream, the effects of flashing
most emergency conditions, including fire. A common refer- should be considered. Also the possibility of a transient over-
ence for determining individual relieving rates is contained in pressure caused by the sudden release of vapor into an all-liq-
Section 3 of API RP 521.1 The design of the proper relieving uid system should be considered.
device must take into consideration all of the following upset
conditions for the individual equipment item if such upset can Control Valve Failure
occur. Each upset condition must be carefully evaluated to de- The failure positions of instruments and control valves must
termine the "worst case" condition which will dictate the re- be carefully evaluated. In practice, the control valve may not
lieving device capacity. fail in the desired position. A valve may stick in the wrong

5-2
FIG. 5-2
Characteristics of Safety Relief Valves for Vessel Protection1

Notes:
1. The operating pressure may be any lower pressure required.
2. The set pressure and all other values related to it may be moved downward if the operating pressure permits.
3. This figure conforms with the requirements of the ASME Boiler and Pressure Vessel Code, Section VIII.
4. The pressure conditions shown are for safety relief valves installed on a pressure vessel (vapor phase).

Adapted from American Petroleum Institute

5-3
position, or a control loop may fail. Relief protection for these FIG. 5-3
factors must be provided. Relief valve sizing requirements for
Conventional Safety-Relief Valve
these conditions should be based on flow coefficients (manu-
facturer data) and pressure differentials for the specific con-
trol valves and the facility involved.
Thermal Expansion
If isolation of a process line on the cold side of an exchanger
can result in excess pressure due to heat input from the warm
side, then the line or cold side of the exchanger should be pro-
tected by a relief valve.
If any equipment item or line can be isolated while full of
liquid, a relief valve should be provided for thermal expansion
of the contained liquid. Low process temperatures, solar ra-
diation, or changes in atmospheric temperature can necessi-
tate thermal protection. Flashing across the relief valve needs
to be considered.
Utility Failure
Loss of cooling water may occur on an area-wide or plant-
wide basis. Affected are fractionating columns and other
equipment utilizing water cooling. Cooling water failure is
often the governing case in sizing flare systems.
Electric power failure, similar to cooling water failure, may
occur on an area-wide or plant-wide basis and may have a
variety of effects. Since electric pump and air cooler fan drives
are often employed in process units, a power failure may cause
the immediate loss of reflux to fractionators. Motor driven
compressors will also shut down. Power failures may result in
major relief loads.
Instrument air system failure, whether related to electric
power failure or not, must be considered in sizing of the flare
system since pneumatic control loops will be interrupted. Also
control valves will assume the position as specified on "loss of
air" and the resulting effect on the flare system must be con-
sidered.

RELIEVING DEVICES
Several pressure relief devices are certified and approved
under Section VIII of the ASME Boiler and Pressure Vessel
Code2 covering unfired pressure vessels. They include spring
loaded direct-acting relief valves, pilot operated relief valves,
and rupture disks. When the governing code is ANSI B31.33
or ANSI B31.84, other types of pressure relieving devices such
as monitoring regulators, series regulators, weight-loaded re-
lief valves, liquid seals, etc. are permitted. The discussion be-
low is limited to ASME, Section VIII, devices. The devices
must be compatible with the service and the overall design of
the system. See ASME, Section I, for fired boiler relieving cri-
teria.
Conventional Relief Valves
In a conventional relief valve, the inlet pressure to the valve
is directly opposed by a spring. Tension on the spring is set to
keep the valve shut at normal operating pressure but allow
the valve to open when the pressure reaches relieving condi-
tions. This is a differential pressure valve. Most conventional
safety-relief valves available to the petroleum industry have
disks which have a greater area, AD, than the nozzle seat area,
AN. The effect of back pressure on such valves is illustrated in
Fig. 5-3. If the bonnet is vented to atmospheric pressure, the
back pressure acts with the vessel pressure so as to overcome
the spring force, FS, thus making the relieving pressure less

5-4
than when set with atmospheric pressure on the outlet. How- FIG. 5-4
ever, if the spring bonnet is vented to the valve discharge
Balanced Safety-Relief Valve
rather than to the atmosphere, the back pressure acts with
the spring pressure so as to increase the opening pressure. If
the back pressure were constant, it could be taken into account
in adjusting the set pressure. In operation the back pressure CAP, SCREWED
is not constant when a number of valves discharge into a mani-
fold.
A cut-away of a conventional relief valve is shown in Fig.
5-3. Materials of construction for relief valves vary by service.
COMPRESSION SCREW
Balanced Relief Valves
Balanced safety-relief valves incorporate means for mini-
mizing the effect of back pressure on the performance charac- BONNET
teristics opening pressure, closing pressure, lift, and
SPRING
relieving capacity.
These valves are of two types, the piston type and the bel-
lows type, as shown diagrammatically in Fig. 5-4. In the piston STEM
type, of which several variations are manufactured, the guide
is vented so that the back pressure on opposing faces of the
valve disk cancels itself; the top face of the piston, which has
the same area, AP, as the nozzle seat area, AN, is subjected to GUIDE
atmospheric pressure by venting the bonnet. The bonnet-
vented gases from balanced piston-type valves should be dis-
posed of with a minimum restriction and in a safe manner. BELLOWS
In the bellows type of balanced valve, the effective bellows BODY
area, AB, is the same as the nozzle seat area, AN, and, by at-
tachment to the valve body, excludes the back pressure from
DISC HOLDER
acting on the top side of that area of the disk. The disk area
extending beyond the bellows and seat area cancel, so that DISC
there are no unbalanced forces under any downstream pres-
sure. The bellows covers the disk guide so as to exclude the GUIDE PIN
working fluid from the bonnet. To provide for a possible bel-
lows failure or leak, the bonnet must be vented separately
from the discharge. The balanced safety-relief valve makes
higher pressures in the relief discharge manifolds possible. NOZZLE
Both balanced-type valves shown in Fig. 5-4 should have bon-
net vents large enough to assure no appreciable back pressure Bellows Valve Cross Section
during design flow conditions. If the valve is in a location in
which atmospheric venting (usually not a large amount) pre- Courtesy Lonergan Company
sents a hazard, the vent should be piped to a safe location
independent of the valve discharge system. The user should
obtain performance data on the specific type of valve being Balanced Disk and
Vented Piston Type Bellows Type
considered.
Vented
Spring FS

Vented Bonnet
A cross section drawing of a balanced (bellows) relief valve Vented Bellows
FS

Bonnet
is shown in Fig. 5-4. Vent

Pilot Operated Relief Valves


Piston

P2
P2 P2 P2
A pilot operated relief valve consists of two principal parts,
a main valve and a pilot. The valve utilizes a piston instead of DISK DISK
a shaft. Inlet pressure is directed to the top of the main valve P2 P2
piston. More area is exposed to pressure on the top of the pis-
ton than on the bottom so pressure, instead of a spring, holds P1
AP = AN P1 AB = AN
the main valve closed. At the set pressure, the pilot opens, FS Spring Force
P1 AN = FS Set press. P1
reducing the pressure on top of the piston thereby allowing the AN Nozzle Seat Area
main valve to open fully. For some applications, pilot-operated Note: Back Pressure has very little effect on set pressure

relief valves are available in minimum friction, light-weight


diaphragm construction (in place of heavy pistons). Pilot op- Effect Of Back Pressure on Set Pressure of Balanced
6
erated valves can allow backflow if downstream pressure ex- Safety-Relief Valves
ceeds set points. Backflow prevention is required on valves
connected to common relief headers. A check valve, split piston Courtesy American Petroleum Institute

type valve, or backflow preventer in the pilot line can be used.


A typical pilot operated relief valve is shown in Fig. 5-5. This
style valve should be considered for applications involving

5-5
FIG. 5-5
FIG. 5-6
Pilot Operated Relief Valve
O-Ring Seals
Conventional and Bellow Valves
PILOT VALVE
FIRST STAGE

PILOT VALVE
SECOND STAGE

UPPER
PASSAGEWAY

LOWER
PASSAGEWAY

PRESSURE LINE

MAIN VALVE CHECK VALVE


(optional)

SENSING
LINE
DISCHARGE ORIFICE
PORT SEAT

SENSING
TUBE

INLET PORT

Courtesy GPE Controls

high back pressure, high operating pressure, or where pre-


mium seat tightness is desired.

Resilient Seat Relief Valves


DISC RETAINING RING DISC
With the use of metal-to-metal seat conventional or bal-
anced type relief valves where the operating pressure is close
to the set pressure, some leakage can be expected through the
seats of the valve (refer to API Standard 527)5. Resilient seat
relief valves with either an O-ring seat seal or plastic seats
can provide seat integrities which exceed API Standard 527
(Fig. 5-6); however, there are limitations of temperature and
material compatibility when using these valves, and manufac-
turer guidelines should be consulted. Although such valves
provide near zero leakage until seat damage occurs, the resil-
ient seats may erode rapidly once leakage begins.

Rupture Disk
A rupture disk consists of a thin diaphragm held between
flanges. The disk is designed to rupture and relieve pressure
within tolerances established by ASME Code. Rupture disks
can be used in gas processing plants, upstream of relief valves,
to reduce minor leakage and valve deterioration. In these in-
stallations, the pressure in the cavity between the rupture RETAINER
disk and the relief valve should be monitored to detect a rup- SCREW
tured disk. In some applications a rupture disk with a higher
pressure rating is installed parallel to a relief valve. A rupture O-RING SEAT SEAL O-RING RETAINER
disk is subject to fatigue failure due to operating pressure cy-
cles. To establish recommended replacement intervals, con- Courtesy Lonergan Company
sult rupture disk suppliers.

5-6
Rupture disks should be used as the primary relieving de- pressure]. Pressure buildup downstream of the relief valve
vice only if using a pressure relief valve is not practical. Some should never cause the vessel pressure to exceed the maxi-
examples of such situations are: mum allowable overpressure.
(a) Rapid rates of pressure rise. A pressure relief valve Sizing for Gas or Vapor Relief
system does not react fast enough or cannot be
made large enough to prevent overpressure, e.g., an The rate of flow through a relief valve nozzle is dependent
exchanger ruptured tube case or a runaway reac- on the absolute upstream pressure (as indicated in Eq 5-1,
tion in a vessel. Eq 5-2, and Eq 5-3) and is independent of the downstream
pressure as long as the downstream pressure is less than the
(b) Large relieving area required. Because of ex-
critical-flow pressure.6 However, when the downstream pres-
tremely high flow rates and/or low relieving pres-
sure increases above the critical flow pressure, the flow
sure, providing the required relieving area with a
through the relief valve is materially reduced (e.g., when the
pressure relief valve system is not practical.
downstream pressure equals the upstream pressure, there is
(c) A pressure relief valve system is susceptible to be- no flow).
ing plugged, and thus inoperable, during service.
The critical-flow pressure, PCF, may be estimated by the per-
fect gas relationship shown in Eq 5-5.
SIZING OF RELIEF DEVICES As a rule of thumb if the downstream pressure at the relief
After the required relief capacity of a relief valve has been valve is greater than one-half of the valve inlet pressure (both
determined, the minimum orifice area required must be cal- pressures in absolute units), then the relief valve nozzle will
culated. Industry standard for orifice designation, orifice area, experience subcritical flow.
valve dimensions, valve body sizes, and pressure ratings are Critical Flow Safety valves in gas or vapor service may
available. The standard orifices available by letter designa- be sized by use of one of these equations:
tion, orifice area, and valve body size are shown in Fig. 5-7.
100W (T1) (Z)

In addition to the standard sizes, many relief valves are A = Eq 5-1
manufactured with orifice areas smaller than "D", and some (C1) (K) (P1) (Kb)


MW
pilot-operated relief valves contain orifice areas larger than
"T." Manufacturers should be contacted for information on 100Qv (T1) (MW) (Z)

A = Eq 5-2
non-standard sizes. (22.4) (C1) (K) (P1) (Kb)
The set pressure and the overpressure allowed must be
within the limits permitted by the applicable codes. System



k+1
2
analysis must include downstream piping. For instance, con- C1 = 387 k k1 Eq 5-3
sider the use of a relief valve made for a vessel with a maxi- k + 1
mum allowable working pressure of 1000 kPa (ga). The relief
valve set pressure is 1000 kPa (ga), and the maximum allow- C1 and Kb can be obtained from Figs. 5-8, 5-9, 5-10, and 5-11.
able overpressure is 10% [100 kPa (ga)]. The vessel pressure For final design, K should be obtained from the valve
when relieving must be limited to 1100 kPa (ga) manufacturer. A value for K of 0.975 may be used for prelimi-
[1000 kPa (ga) set pressure plus 100 kPa (ga) maximum over- nary sizing.

FIG. 5-7
Relief Valve Designations

Orifice Orifice
Area Area
cm2 (in.2)
D 0.710 0.110
E 1.265 0.196
Standard Orifice Designation

F 1.981 0.307
G 3.245 0.503
H 5.065 0.785
J 8.303 1.287
K 11.858 1.838
L 18.406 2.853
M 23.226 3.60
N 28.000 4.34
P 41.161 6.38
Q 71.290 11.05
R 103.226 16.0
T 167.742 26.0

in. 1 2 1.5 2 1.5 2.5 1.5 3 23 2.5 4 34 46 68 6 10 8 10


mm 25 50 38 50 38 62 38 75 50 75 38 100 75 100 100 150 150 200 150 250 200 250
Valve Body Size (Inlet Diameter Outlet Diameter)

5-7
FIG. 5-8
Values of Coefficient C1

k C1 k C1 k C1 k C1 k C1 k C1
0.41 163.44 0.71 205.79 1.01 235.95* 1.31 259.32 1.61 278.26 1.91 294.09
0.42 165.16 0.72 206.94 1.02 236.83 1.32 260.01 1.62 278.83 1.92 294.57
0.43 166.86 0.73 208.09 1.03 237.69 1.33 260.70 1.63 279.40 1.93 295.06
0.44 168.52 0.74 209.22 1.04 238.55 1.34 261.38 1.64 279.96 1.94 295.53
0.45 170.16 0.75 210.34 1.05 239.40 1.35 262.07 1.65 280.53 1.95 296.01
0.46 171.78 0.76 211.45 1.06 240.24 1.36 262.74 1.66 281.09 1.96 296.49
0.47 173.38 0.77 212.55 1.07 241.08 1.37 263.41 1.67 281.64 1.97 296.96
0.48 174.94 0.78 213.63 1.08 241.91 1.38 264.07 1.68 282.20 1.98 297.43
0.49 176.49 0.79 214.71 1.09 242.73 1.39 264.74 1.69 282.74 1.99 297.90
0.50 178.01 0.80 215.77 1.10 243.55 1.40 265.39 1.70 283.29 2.00 298.37
0.51 179.51 0.81 216.83 1.11 244.35 1.41 266.05 1.71 283.83 2.01 298.83
0.52 180.99 0.82 217.88 1.12 245.16 1.42 266.70 1.72 284.38 2.02 299.28
0.53 182.45 0.83 218.91 1.13 245.95 1.43 267.34 1.73 284.91 2.03 299.74
0.54 183.89 0.84 219.93 1.14 246.74 1.44 267.98 1.74 285.45 2.04 300.20
0.55 185.34 0.85 220.95 1.15 247.53 1.45 268.61 1.75 285.98 2.05 300.65
0.56 186.71 0.86 221.95 1.16 248.31 1.46 269.24 1.76 286.51 2.06 301.10
0.57 188.10 0.87 222.94 1.17 249.08 1.47 269.87 1.77 287.03 2.07 301.56
0.58 189.46 0.88 223.93 1.18 249.84 1.48 270.50 1.78 287.55 2.08 302.00
0.59 190.81 0.89 224.90 1.19 250.60 1.49 271.12 1.79 288.07 2.09 302.44
0.60 192.15 0.90 225.87 1.20 251.36 1.50 271.73 1.80 288.59 2.10 302.89
0.61 193.46 0.91 226.83 1.21 252.11 1.51 272.35 1.81 289.10 2.11 303.33
0.62 194.75 0.92 227.78 1.22 252.85 1.52 272.95 1.82 289.62 2.12 303.77
0.63 196.04 0.93 228.72 1.23 253.59 1.53 273.55 1.83 290.12 2.13 304.20
0.64 197.31 0.94 229.65 1.24 254.33 1.54 274.16 1.84 290.63 2.14 304.63
0.65 198.56 0.95 230.58 1.25 255.05 1.55 274.75 1.85 291.13 2.15 305.07
0.66 199.80 0.96 231.49 1.26 255.78 1.56 275.34 1.86 291.63 2.16 305.50
0.67 201.02 0.97 232.40 1.27 256.50 1.57 275.94 1.87 292.13 2.17 305.92
0.68 202.24 0.98 233.30 1.28 257.21 1.58 276.52 1.88 292.62 2.18 306.35
0.69 203.43 0.99 234.18* 1.29 257.92 1.59 277.10 1.89 293.11 2.19 306.77
0.70 204.62 1.00 235.07* 1.30 258.62 1.60 277.68 1.90 293.60 2.20 307.20

*Interpolated values, since C1 becomes indeterminate as k approaches 1.00


Cp
k: Ratio of specific heat, k = C1: Coefficient determined by the ratio of the specific heats of the gas or vapor at standard condition.
Cv
Note: Calculated from EQ 5-3.

FIG. 5-9
Values of C1 for Gases

Mol mass Cp /Cv Mol mass Cp /Cv


Acetylene 26 1.28 Hydrochloric acid 36.5 1.40
Air 29 1.40 Hydrogen 2 1.40
Ammonia 17 1.33 Hydrogen sulfide 34 1.32
Argon 40 1.66 Iso-butane 58 1.11
Benzene 78 1.10 Methane 16 1.30
Carbon disulfide 76 1.21 Methyl alcohol 32 1.20
Carbon dioxide 44 1.28 Methyl chloride 50.5 1.20
Carbon monoxide 28 1.40 N-butane 58 1.11
Chlorine 71 1.36 Natural gas 19 1.27
Cyclohexane 84 1.08 Nitrogen 28 1.40
Ethane 30 1.22 Oxygen 32 1.40
Ethylene 28 1.20 Pentane 72 1.09
Helium 4 1.66 Propane 44 1.14
Hexane 86 1.08 Sulfur dioxide 64 1.26

5-8
FIG. 5-10
Constant Back Pressure Sizing Factor, Kb, for Conventional Safety-Relief Valves (Vapors and Gases Only)6

Example: Set pressure (MAWP) = 700 kPa gauge


Superimposed back pressure = 485 kPa gauge
Spring set = 200 kPa
Built-up back pressure = 100 kPa
(485 + 100 + 101)
Percent absolute back pressure = (100) = 76 percent
(700 + 100 + 101)
Follow dotted line Kb = 0.89 (from curve)
Capacity with back pressure = (0.89)(rated capacity without back pressure)
Note: This chart is typical and suitable for use only when the make of valve or the actual critical-flow pressure point for the vapor or gas
is unknown; otherwise, the valve manufacturer should be consulted for specific data.
Courtesy American Petroleum Institute

Subcritical Flow For downstream pressures, P2, in For safety-relief valves in steam service, the required area
excess of the critical-flow pressure, PCF, the relief valve orifice may be estimated from the following equations from the
area can be calculated from ASME Code:
100 W

1
ZT (For ASME Section VIII)
A = Eq 5-4

(548) (F2) (K) MW (P1) (P1 P2) (1.904) W
A = Eq 5-6
(P1) (Ksh) K
F2 is taken from Fig. 5-12.
(For ASME Section I)
k
2 k1 (2.115) W
PCF = P1 Eq 5-5 A = Eq 5-7
(P1) (Ksh) K
k + 1
See Fig. 5-13 for superheat correction factors. For saturated
steam at any pressure, Ksh = 1.0.
Sizing for Steam Relief
Safety-relief valves in steam service are sized by a modifi-
cation of Napiers steam flow formula. Valve manufacturers
can supply saturated steam capacity tables. A correction fac-
tor, Ksh, must be applied for safety valves in superheated
steam service.

5-9
FIG. 5-11
Variable or Constant Back-Pressure Sizing Factor, Kb, for Balanced Bellows Safety-Relief Valves (Vapors and Gases)6

Note: The above curves represent a compromise of the values recommended by a number of relief valve manufacturers and may be used when the make of valve
or the actual critical-flow pressure point for the vapor or gas is unknown. When the make is known, the manufacturer should be consulted for the correction
factor.

Sizing for Liquid Relief ated at relief valve setting and maximum temperature.6
These calculations assume the liquid is non-compressible.
Turbulent Flow Conventional and balanced bellows (B) (Q)
relief valves in liquid service may be sized by use of Eq 5-8. Vl = Eq 5-10
1000 (G) (S)
Pilot-operated relief valves should be used in liquid service
only when the manufacturer has approved the specific appli- Coefficients for this equation may be found in Fig. 23-2.
cation.
Typical values of the liquid expansion coefficient, B, at 15C
(7.07) (Vl)
G
A = Eq 5-8 are:
(K) (Kp) (Kw) (Kv)

( P Pb)
API Gravity Relative Density B, 1/C
Water 1.000 0.00018
Laminar Flow For liquid flow with Reynolds numbers
3 - 34.9 1.052 - 0.850 0.0007
less than 4,000, the valve should be sized first with Kv = 1 in
order to obtain a preliminary required discharge area, A. From 35 - 50.9 0.850 - 0.775 0.0009
manufacturer standard orifice sizes, the next larger orifice 51 - 63.9 0.775 - 0.724 0.0011
size, A, should be used in determining the Reynolds number, 64 - 78.9 0.724 - 0.672 0.0013
Re, from the following relationship: 79 - 88.9 0.672 - 0.642 0.0014
(Vl) (112 654) (G) 89 - 93.9 0.642 - 0.628 0.0015
Re = Eq 5-9 94 - 100 0.628 - 0.611 0.0016

A
n-Butane 0.584 0.0020
After the Reynolds number is determined, the factor Kv is Isobutane 0.563 0.0022
obtained from Fig. 5-15. Divide the preliminary area (A) by Propane 0.507 0.0029
Kv to obtain an area corrected for viscosity. If the corrected
area exceeds the standard orifice area chosen, repeat the pro-
cedure using the next larger standard orifice. For atmospheric conditions, such as solar radiation, the sur-
face area of the item or line in question should be calculated.
Sizing for Thermal Relief Solar radiation should be determined for the geographic area
The following may be used to approximate relieving rates of [typically 7871040 W/m2] and applied to the surface area to
liquids expanded by thermal forces where no vapor is gener- approximate Q (W).

5-10
FIG. 5-12
Values of F2 for Subcritical Flow6

When the flow rate is calculated, the necessary area for re- hL1 hL2
lief may be found from the turbulent liquid flow equations. Weight Percent Flashing = (100) Eq 5-11
hG2 hL2
Sizing for Mixed Phase Relief The above sizing method for mixed flows and flashing liq-
uids assumes sonic velocity does not exist. For sizing near
When a safety relief valve must relieve a liquid and gas, it sonic conditions where maximum flow may occur, use the
may be sized by: method of Fauske7 for sizing.
Determining the rate of gas and the rate of liquid that
must be relieved. Sizing for Fire
Calculating the orifice area required to relieve the gas as The method of calculating the relief rate for fire sizing may
previously outlined. be obtained from API RP 5211, API Standard 25108, NFPA 589,
and possibly other local codes or standards. Each of these ref-
Calculating the orifice area required to relieve the liquid erences approach the problem in a slightly different manner.
as previously outlined.
Summing total areas calculated for liquid and vapor to Many systems requiring fire relief will contain liquids
obtain the total required orifice area. and/or liquids in equilibrium with vapor. Fire relief capacity
in this situation is equal to the amount of vaporized liquid
When the material to be relieved through a safety valve is generated from the heat energy released from the fire and ab-
a flashing liquid, it is difficult to know what percentage of the sorbed by the liquid containing vessel. The most difficult part
flashing actually occurs in the valve in order to estimate the of this procedure is the determination of heat absorbed.
total required orifice area using the above four steps. A con-
servative approach is to assume an isenthalpic expansion and NFPA 589 applies to LP-gas (propane and butane) systems.
that all the vapor is formed in the valve. Then, using enthalpy It presents the relief capacity requirements for vessels in
values, calculate the amount of vapor formed using Eq 5-12. terms of the rate of discharge of air, Qa, and area of the vessel
Once the amounts of vapor and liquid assumed present in the according to the equation:
valve are determined, the total required orifice area can be
calculated. Qa = (639.4) (Ac)0.82 Eq 5-12

5-11
FIG. 5-13
Superheat Correction Factors for Safety Valves in Steam Service6

Total Temperature Superheated Steam, C


Set Pressure
149 204 260 316 371 427 482 538 593 649
kPa (ga)
Correction Factor, Ksh
100 1 0.98 0.93 0.88 0.84 0.8 0.77 0.74 0.72 0.7
140 1 0.98 0.93 0.88 0.84 0.8 0.77 0.74 0.72 0.7
275 1 0.99 0.93 0.88 0.84 0.81 0.77 0.74 0.72 0.7
415 1 0.99 0.93 0.88 0.84 0.81 0.77 0.75 0.72 0.7
550 1 0.99 0.94 0.88 0.84 0.81 0.77 0.75 0.72 0.7
690 1 0.99 0.94 0.89 0.84 0.81 0.77 0.75 0.72 0.7
830 1 0.99 0.94 0.89 0.84 0.81 0.78 0.75 0.72 0.7
970 1 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 100 1 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 250 1 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 380 1 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 520 1 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.7
1 660 1 0.95 0.9 0.85 0.81 0.78 0.75 0.72 0.7
1 790 1 0.95 0.9 0.85 0.81 0.78 0.75 0.72 0.7
1 930 1 0.96 0.9 0.85 0.81 0.78 0.75 0.72 0.7
2 070 1 0.96 0.9 0.85 0.81 0.78 0.75 0.72 0.7
2 410 1 0.96 0.9 0.86 0.82 0.78 0.75 0.72 0.7
2 760 1 0.96 0.91 0.86 0.82 0.78 0.75 0.72 0.7
3 450 1 0.96 0.92 0.86 0.82 0.78 0.75 0.73 0.7
4 140 1 0.97 0.92 0.87 0.82 0.79 0.75 0.73 0.7
5 520 1 0.95 0.88 0.83 0.79 0.76 0.73 0.7
6 900 1 0.96 0.89 0.84 0.78 0.76 0.73 0.71
8 620 1 0.97 0.91 0.85 0.8 0.77 0.74 0.71
10 350 1 0.93 0.86 0.81 0.77 0.74 0.71
12 070 1 0.94 0.86 0.81 0.77 0.73 0.7
13 790 1 0.95 0.86 0.8 0.76 0.72 0.69
17 240 1 0.95 0.85 0.78 0.73 0.69 0.66
20 690 1 0.82 0.74 0.69 0.65 0.62
Adapted from American Petroleum Institute

This relief capacity is at 120 percent of maximum allowable surface, in m2. Wetted surface is the surface wetted by liquid
working pressure (20% overpressure is permissible for fire when the tank is filled to the maximum operating level. It
only). includes at least that portion of a tank within a height of 8 m
above grade. In the case of spheres and spheroids, the term
API Standard 25108 applies to LP-gas (propane and butane) applies to that portion of the tank up to the elevation of its
in the design of marine and pipeline terminals. This standard maximum horizontal diameter or a height of 8 m, whichever
expresses relieving requirements for fire in terms of standard is greater. Grade usually refers to ground grade but may be
cubic meters of air per minute determined at 120% of maxi- any level at which a sizable area of exposed flammable liquid
mum allowable working pressure. is present.
Qa = (639.4) (F) (0.6) (Aw)0.82 Eq 5-13 The amount of vapor generated is calculated from the latent
Note: The 0.6 factor in Eq 5-13 is applicable only for contain- heat of the material at the relieving pressure of the valve. For
ers larger than 454 m3 and if the equipment location has both fire relief only, this may be calculated at 121% of maximum
good drainage and firefighting facilities. allowable working pressure. All other conditions must be cal-
culated at 110% of maximum allowable working pressure for
After determination of Qa, the required relief valve nozzle single relief devices. When the latent heat is determined, re-
size is calculated using Eq 5-2 with the appropriate properties quired relieving capacity may be found by:
of air.
W = 3.6 Q / Hl Eq 5-15
API RP 520 Part I6, applies to refineries and process plants.
It expresses relief requirements in terms of heat input from The value W is used to size the relief valve orifice using Eq 5-1
the fire to the vessel. or Eq 5-4.
The latent heat of pure and some mixed paraffin hydrocar-
Q = (43 200) (F) (Aw)0.82 Eq 5-14
bon materials may be estimated using Fig. 12 of API RP 5206.
The F factor in equations 5-13 and 5-14 is determined from Latent heat data may also be obtained by performing flash
Fig. 5-16. Aw in equations 5-13 and 5-14 is the total wetted calculations. Mixed hydrocarbons will boil over a temperature

5-12
range depending on the liquid composition; therefore, consid- FIG. 5-14
eration must be given to the condition which will cause the
largest vapor generation requirements due to the heat input Variable or Constant Back-Pressure Sizing Factor Kw for
of a fire. Precise unsteady state calculations are seldom nec- 25 Percent Overpressure on Balanced Bellows
essary. Safety-Relief Valves (Liquids Only)6
The latent heat will approach a minimum value near the
critical. When no better information is available, a conserva-
tive minimum value of 110 kJ/kg is typically used.
For vessels containing only vapor, API RP 520 has recom-
mended the following equation for determining required relief
area based on fire2:
183.3 (F) (A3)
A = Eq 5-16
P
1
F may be read from Fig. 5-17.
When a vessel is subjected to fire temperatures, the result-
ing metal temperature may greatly reduce the pressure rating
of the vessel. Design for this situation should consider an
emergency depressuring system or a water spray system to
keep metal temperatures cooler. Refer to API RP 520 Part I,
Appendix D. A discussion on vapor depressuring may be found
in API RP 521, paragraph 3.19.

RELIEF VALVE INSTALLATION


Relief valve installation requires careful consideration of in-
let piping, pressure sensing lines (where used), and startup
procedures. Poor installation may render the safety relief
valve inoperable or severely restrict the valves relieving ca- Note: The above curve represents a compromise of the values recommended
pacity. Either condition compromises the safety of the facility. by a number of relief-valve manufacturers. This curve may be used when
the make of the valve is not known. When the make is known, the manu-
Many relief valve installations have block valves before and facturer should be consulted for the correction factor.
after the relief valve for in-service testing or removal; however,
these block valves must be sealed or locked opened.
Courtesy American Petroleum Institute
Inlet Piping
The proper design of inlet piping to safety relief valves is Balanced relief valve set pressure will not be as significantly
extremely important. Relief valves should not be installed at affected by back pressure as direct spring operated valves.
physically convenient locations unless inlet pressure losses Balanced relief valves will suffer reduced lift as back pressure
are given careful consideration. The ideal location is the direct increases. This is shown in application of the Kb factor for bal-
connection to protected equipment to minimize inlet losses. anced valves (Fig. 5-11).
API RP 520, Part II recommends a maximum inlet pressure The valve relieving capacity of any relief valve is restricted
loss to a relief valve of three percent of set pressure. This is by back pressure if the discharge pressure exceeds the criti-
also an ASME Code requirement. This pressure loss shall be cal-flow pressure.
the total of the inlet loss, line loss, and the block valve loss (if
used). The loss should be calculated using the maximum rated Discharge piping must be at least the same size as the valve
flow through the safety relief valve. outlet but is generally larger in diameter than the valve outlet
size to limit back pressure.
Discharge Piping
A useful article on the sensitivity of relief valves to proper
An adequate discharge pipe size for direct spring operated inlet and outlet piping design has been published by Van
valves is critical. Improperly sized, it may cause valve failure. Boskirk.13
Pressure losses may occur in discharge headers causing exces-
sive back pressure and excessive back pressure may cause the Reactive Force
relief valve to close. When the valve closes, the back pressure On high pressure valves, the reactive forces during relief are
in the discharge header decreases, and the valve re-opens. substantial and external bracing may be required. See equa-
Rapid cycling can occur as this process is repeated. In addition, tions in API RP 520 for computing this force.
set pressure of other conventional valves connected to the
same discharge system may be adversely affected by such ex- Rapid Cycling
cessive back pressure. See Fig. 5-18.
Rapid cycling can occur when the pressure at the valve inlet
Lift and set pressures of pilot operated relief valves with the decreases at the start of relief valve flow because of excessive
pilot vented to the atmosphere are not affected by back pres- pressure loss in the piping to the valve. Under these
sure; however, if the discharge pressure can exceed the inlet conditions, the valve will cycle at a rapid rate which is referred
pressure (e.g., tanks storing low vapor pressure material), a to as "chattering." The valve responds to the pressure at its
back-flow preventer (vacuum block) must be used. inlet. If the pressure decreases during flow below the valve

5-13
FIG. 5-15
Capacity Correction Factor Due to Viscosity
KV = VISCOSITY CORRECTION FACTOR

Re-REYNOLDS NUMBER
Courtesy American Petroleum Institute

reseat point, the valve will close; however, as soon as the flow take place because of the very large magnitude of the impact
stops, the inlet pipe pressure loss becomes zero and the pres- forces involved.
sure at the valve inlet rises to tank pressure once again. If the
vessel pressure is still equal to or greater than the relief valve Seat Leakage of Relief Valves
set pressure, the valve will open and close again. The inlet Seat leakage is specified for conventional direct spring op-
pressure loss should be limited to 3%. erated metal-to-metal seated valves by API RP 527. The im-
An oversized relief valve may also chatter since the valve portant factor in understanding the allowable seat leak is that
it is stated at 90% of set point. Therefore, unless special seat
may quickly relieve enough contained fluid to allow the vessel
pressure to momentarily fall back to below set pressure only lapping is specified or soft seat designs used, a valve operating
to rapidly increase again. Rapid cycling reduces capacity and with a 10% differential between operating and set pressures
may be expected to leak.
is destructive to the valve seat in addition to subjecting all the
moving parts in the valve to excessive wear. Excessive back There are no industry standards for soft seated valves. Gen-
pressure can also cause rapid cycling as discussed above. erally leakage is not expected if the valve operates for one
minute at 90% of set pressure and, in some cases, no leakage
Resonant Chatter at 95%, or even higher. Longer time intervals could promote
leakage. Application of soft seated valves is limited by operat-
Resonant chatter can occur with safety valves when the inlet
ing temperatures. Manufacturer guidelines should be con-
piping produces excessive pressure losses at the valve inlet
and the natural acoustical frequency of the inlet piping ap- sulted.
proaches the natural mechanical frequency of the valves basic
moving parts. The higher the set pressure, the larger the valve RELIEF SYSTEM PIPING DESIGN
size, or the greater the inlet pipe pressure loss, the more likely
resonant chatter will occur. Resonant chatter is uncon-
trollable; that is, once started it cannot be stopped unless the
Grouping of Systems
pressure is removed from the valve inlet. In actual application, It is not unusual to relieve non-flammable and non-toxic ma-
however, the valve can self-destruct before a shutdown can terials, such as air, steam, carbon dioxide, and water directly

5-14
FIG. 5-16 Load Determination
Environmental Factors8 The maximum relief load anticipated for each relief system
may be determined by tabulating the relief loads discharging
Environment F Factor to each header system at the conditions expected to exist in
Bare metal vessel 1.0
the system. For further discussion, see Section 5.2 of API RP
521.
Insulation thickness: a,b
(mm) Back Pressure Consideration
25 0.30 After load determination, it is necessary to decide on the
50 0.15 location of the flares, and size of the headers and flare lines.
100 0.075 Location and height of the flares must consider radiation heat
150 0.05 and emissions. This will involve fixing the maximum back
pressure for the system and choosing between conventional,
200 0.037
pilot operated, or balanced safety valves for the various relief
250 0.03 stations. Factors which tend to justify balanced valves are a
300 or morec 0.025 potential for high flare header back pressure and economic
Concrete thickness, in mm Double above F factor line sizing criteria.
for equal thickness.
Sizing Methods
Water-application facilitiesd 1.0
Depressuring and emptying facilities e
1.0
Line sizing for flare headers and relief lines requires the use
of compressible flow equations. Computer programs are avail-
Underground storage 0.0 able for use in sizing flare headers. A calculation method is
Earth-covered storage above grade 0.03 outlined below:
Notes: 1. Start at the flare tip, where the outlet pressure is atmos-
a
To take credit for reduced heat input, the insulation shall resist dislodg- pheric, use design flows and work toward the individual
ment by fire-hose stream, shall be noncombustible, and shall not decompose relief valves (pressure drop across the tip will vary with
at temperatures up to 540 C. If insulation does not meet these criteria, the make check with the manufacturer). Typical tip drop
environmental F factor for a bare vessel should be used.
is 1400 mm water (see Eq 5-24). Flare tip velocity can
b
These factors are based on an arbitrary thermal conductivity value of vary from Mach 0.2 for open pipe flares to Mach 0.5 or
0.6 W/(m C) and a temperature differential of 870 C when using a heat
input value of 66 250 W/m2 in accordance with conditions assumed in API
greater for engineered flare tips and wind shields. Pres-
RP 520. Where these conditions do not exist, engineering judgment should sure drop through seals must also be included.
be exercised either in selecting a higher F factor or in providing other means 2. Establish equivalent pipe lengths between points in the
of protecting tanks from fire exposure.
c
system and establish losses through fittings, expansion,
The insulation credit is arbitrarily limited to the F factor shown for 300 mm and contraction losses.
of insulation even though greater thickness may be used. A further credit,
if taken, would result in a relieving device size which would be impractically 3. Limit the maximum allowed velocity at any part of the
small but may be used if warranted by design considerations. flare system to Mach 0.7 (average velocity of Mach 0.4 is
d
Water films covering the metal surfaces can, under ideal conditions, absorb recommended).
substantially all incident radiation. However, the reliability of effective
water application is dependent upon many factors. Freezing weather, high 4. Estimate properties of gases in the headers from the fol-
winds, clogging of system, unreliability of water supply, and tank surface lowing mixture relationships (i indicates the ith compo-
conditions are a few factors which may prevent adequate or uniform water nent).
coverage. Because of these uncertainties, the use of an environment F factor
other than 1.0 for water spray is generally not used. MW = Wi/ (W / MW)i Eq 5-17
e
Depressuring devices may be used, but no credit for their use should be
allowed in sizing pressure relief valves for fire exposure.
T = WiTi/ Wi Eq 5-18
Adapted from American Petroleum Institute
= xi i (MW )i / xi (MW )i
0.5 0.5
Eq 5-19
5. Calculate the inlet pressure for each section of the line
to the atmosphere. To protect personnel, precautions need to by adding the calculated pressure drop for that section
be taken in venting hot, cold, or high pressure materials. to the known outlet pressure.
In certain cases, hydrocarbon relief vapor streams may be 6. Calculate sections of pipe individually using the inlet
discharged to the atmosphere. However, the decision to dis- pressure of a calculated section as the outlet pressure for
charge hydrocarbons or other flammable or hazardous vapors the new section.
to the atmosphere must ensure that disposal can be accom- 7. Continue calculations, working towards the relief valve.
plished without creating a hazard, such as formation of flam- 8. Check calculated back pressure at the relief valve
mable mixtures at grade level or on elevated structures, against the maximum allowable back pressure (MABP).
exposure of personnel to toxic or suffocating atmosphere, ig- The calculated back pressure should be less than the
nition of relief streams at the point of emission, excessive noise MABP.
levels, corrosion, or air pollution.
9. Limit the MABP to about 40% of the set pressure for
Depending on plot plan, the range of equipment design pres- balanced-bellows relief valves (consult valve manufac-
sures, desirability of isolating certain streams, etc., it may turer), and 10% of the set pressure for conventional relief
prove desirable to provide two or more flare systems, such as valves.
separation of high pressure and low pressure headers. Other 10. Adjust line size of headers until the calculated back pres-
factors influencing this decision include stream temperatures, sure does not exceed the MABP for each valve in the sys-
compositions, quantities, and economics. tem.

5-15
FIG. 5-17
Relief-Valve Factors for Noninsulated Vessels in Gas Service Exposed to Open Fires6

Notes:
1. Fig. 5-9 gives k values for some gases; for others, the values can be determined from the properties of gases as presented in any acceptable reference work.
2. These curves are for vessels of carbon steel.

0.1489 T
1.25
3. These curves conform to the relationship F = 0.6506
CK T1
4. The curves are drawn using 600 C as the vessel wall temperature. This value is a recommended maximum temperature for the usual carbon steel plate
materials whose physical properties at temperatures in excess of 600 C show signs of undesirable tendencies. Where vessels are fabricated from alloy materials,
the value for Tw should be changed to a more proper recommended maximum.
It is recommended that the minimum value of F = 0.01 (when it is unknown use 0.045).
Adapted from American Petroleum Institute

The method outlined above employs sizing equations which out drum to permit condensed liquid to drain into the drum
assume isothermal flow in the flare header. This is adequate for removal. Liquid traps in flare lines should be avoided. If
for most uses; however, if the actual flow condition differs liquid traps are unavoidable, a method for liquid removal
greatly from isothermal, the use of more complex equations should be provided. The locating of the flare knockout drum
and methods is required to predict pressure and temperature also needs to take into account radiation effect from the burn-
profiles for the headers. ing flare.
The choice of piping material other than carbon steel may A seal may be provided in the flare system between the
be dictated by temperatures and pressures in some parts of knockout drum and the flaretip to prevent flashbacks. For
the flare system. Flare systems relieving fluids that produce added safety, a small amount of fuel gas may be used to con-
cryogenic temperatures may require special metallurgy. tinuously purge the system and eliminate the entrance of air
(oxygen).
KNOCKOUT DRUMS Sizing
Gas streams from reliefs are frequently at or near their dew
point, where condensation may occur. A knockout drum is usu- The diameter of a vertical knockout drum can be calculated
ally provided near the flare base, and serves to recover liquid from the maximum allowable vapor velocity using the follow-
hydrocarbons, prevent liquid slugs, and remove large (300-600 ing equation:
micron diameter) liquid particles. The knockout drum reduces



hazards caused by burning liquid that could escape from the (g) (D) (L v)
flare stack. All flare lines should be sloped toward the knock- Ud = (1.15) Eq 5-20
(v) (C)

5-16
FIG. 5-18 Fired or Endothermic Flares These flares are a
form of elevated incinerator for use on low heat waste streams,
Typical Effects of Variable Back Pressure on Capacity of such as sulfur plant tail gas. When the heat content of the
Conventional Safety-Relief Valves6 waste stream is below 4280 kJ/m3, a fired flare with a high
energy assist gas may be required for complete combustion.
Thermal Radiation
Thermal radiation is a prime concern in flare design and
location. Thermal radiation calculations must be done to avoid
dangerous exposure to personnel, equipment, and the sur-
rounding area (trees, grass). The following calculation proce-
dure is a convenient means to find the height of the flare stack
and the intensity of radiation at different locations. The fol-
lowing calculation procedure is a convenient means to find the
height of a flare stack and the intensity of the radiation at
different locations. For flares with a smokeless capacity ex-
ceeding approximately 10 percent, methods which account for
gas composition, mixing, and smoke as presented in API 521
or as summarized in reference 14 should be used. Flare ven-
dors should be consulted for large flowrates or when smokeless
requirements exceed approximately 10 percent. Calculations
given by API 521 or other methods may yield different an-
swers.
A list of vendor recommended fractions of heat radiated for
the most frequently flared gases is shown in Fig. 5-20.
Spherical Radiation Intensity Formula:
(Wf) (NHV) ()
I = Eq 5-21
14.4 (R2)

This equation may be used to calculate the allowable velocity This equation has been found to be accurate for distances as
based on a particle size of 300 to 600 microns . The value of C close to the flame as one flame length.
in Eq 5-20 is determined using Fig. 5-19. API RP 521 is a com- Equation 5-21 is valid so long as the proper value of emis-
mon reference for designing flare knockout drums. sivity, , is inserted. Classically, has been considered a fuel
property alone. Brzustowski et al.10 experimentally observed
a dependence of on jet exit velocity. Other authors have pre-
FLARE SYSTEMS sented models that consider the carbon particle concentration
in the flame. A list of vendor recommended emissivity values
Sizing and safety in designing a flare facility involve consid- for the most frequently flared gases is shown in Fig. 5-20.
eration of thermal radiation, explosion hazards, liquid carry- To calculate the intensity of radiation at different locations,
over, noise, and ground level concentration of toxic material. it is necessary to determine the length of the flame and its
angle in relation to the stack (see Fig. 5-21). A convenient ex-
Types pression to estimate length of flame, Lf, is shown below, based
Flares can be classified as: on information from equipment suppliers.
1. Pipe Flares Vertical or horizontal pipes with external



Pw
ignition pilot. Lf = (0.12) (d) Eq 5-22
1400
2. Smokeless Flares Vertical, single, or multiple burners
designed to properly mix adequate oxygen from the air
with relieved vapors for complete combustion. or from API 521

3. Endothermic Flares Elevated incinerators for low Lf = 2.14 ( Qr 106 )0.474 Eq 5-22a
heat content streams.
For conventional (open pipe) flares, an estimate of total flare
Pipe Flares This type of flare is used for hydrocarbon pressure drop is 1.5 velocity heads based on nominal flare tip
vapor streams such as methane, hydrogen, and carbon mon- diameter. The pressure drop equivalent to 1 velocity head is
oxide which produce limited smoke when burned. Heavier hy- given by:
drocarbons may be burned but with smoking. Velocity for
"open-pipe" flares should be limited to Mach 0.4 to minimize (0.102) V2 V2
Pw = = Eq 5-23
flame lift-off. 2 19.62
Smokeless Flares Smokeless flares are used for Pw is the pressure drop at the tip in mm of water. After de-
smokeless disposal of hydrocarbon streams. These flares use termining tip diameter, d, using Eq 5-24, and the maximum
a variety of methods such as steam, high pressure fuel gas, required relieving capacity, flame length for conditions other
water spray, an air blower, or high velocity vortex action to mix than maximum flow can be calculated using Eq 5-22 and Eq
air with the gas. 5-23.

5-17
FIG. 5-19
Determination of Drag Coefficient1
DRAG COEFFICIENT, C

(0.13) (105)5 (v) (D3) (Lv)


(0.95) (10 ) (V) (D3) (L - V)
2
2 Courtesy American Petroleum Institute

Common practice is to use tip velocities of up to Mach 0.5 The distance from any point on the ground level to the center
for short term emergency flows and Mach 0.2 for maximum of the flame is:
continuous flowing.

R =
(X Xc)2 + (Hs + Yc)2 Eq 5-30



0.5
3.23 105 W Z T
d =
1000 Eq 5-24 Equations 5-21 and 5-30 allow radiation to be calculated at

P2 M k MW any location.
Sonic velocity of a gas is given by: The stack height results from considering the worst position
vertically below the center of the flame for a given condition
of gas flow and wind velocities (see Fig. 5-21).



Ro
a = k T Eq 5-25 R2 = (Hs + Yc)2 Eq 5-31
MW
R = (Hs + Yc) Eq 5-32
The center of the flame is assumed to be located at a distance
equal to 1/3 the length of the flame from the tip. Hs = (R Yc) Eq 5-33
The angle of the flame results from the vectorial addition of FIG. 5-20
the velocity of the wind and the gas exit velocity.
Emissivity Values for Flared Gases
Vw
= tan1 Eq 5-26
Vex Carbon Monoxide 0.075
Hydrogen 0.075



P Hydrogen Sulfide 0.070
Vex = 168 Eq 5-27
1400 Ammonia 0.070
Methane 0.10
Note: API gives a greater lean angle
Propane 0.11
The coordinates of the flame center with respect to the tip Butane 0.12
are: Ethylene 0.12
Xc = (Lf / 3) (sin ) Eq 5-28 Propylene 0.13

Yc = (Lf / 3) (cos ) Eq 5-29 The maximum value of for any gas is 0.13.

5-18
Hs = R [(Lf / 3) (cos )] Eq 5-34
FIG. 5-21
This method assumes that for different wind velocities the
length of the flame remains constant. In reality this is not true. Dimensional References for Sizing a Flare Stack
When the wind blows at more than 25 m/s, the flame tends to
shorten. For practical design, this effect is neglected.
The radiation levels commonly used for designs are:
(These do not include solar heat.)

For equipment protection 15 750 W/m2
Personnel, few seconds escape
only 9 450 W/m2 Lf
Personnel, one minute exposure 6 300 W/m2 WIND
Personnel, several minutes
short exposure 4 725 W/m2
Personnel, continuous exposure 1 575 W/m2 yC
Equipment protection should be evaluated on a case by case
basis, as various pieces of equipment have different protection
XC
needs.
d
Solar radiation adds to the calculated flame radiation and
is dependent upon specific atmospheric conditions and site lo- HS + Y C R
cation. A typical design range is 787-1040 W/m2. HS

The cooling effect of fluids flowing inside piping, along with


wind cooling, can be used to reduce thermal radiation effects.

Smokeless Operation
Most smokeless flares utilize outside motive forces to pro- X - XC
duce efficient gas/air mixing and turbulence from the momen-
tum transferred by the high velocities of the external motive
jet streams (steam, fuel, gas, etc.). The assist medium mass X
requirements are low for steam and fuel gas because of their
high velocity relative to the flare gas. Typical values for steam Courtesy American Petroleum Institute

or fuel gas are from 0.1 to 0.23 kg of assist gas per kg of hy-
drocarbon flow.
Eq 5-35 predicts steam use for a given hydrocarbon molecu-
lar mass gas to be burned in a smokeless flare. Seals
10.8 An effective seal is required to prevent air from entering the
Wstm = Whc 0.68 Eq 5-35 flare system and forming an explosive mixture prior to the
MW designed ignition point. Refer to API RP 521 for recommended
The water spray and air blower methods provide necessary seal methods.
mixing with low velocities and greater mass flow rates. For water
spray flares, typical water rates are 0.5 to 2.3 kg of water per kg Location and Regulations
of hydrocarbon. These rates are highly dependent upon the Flare design must comply with local, state, and federal regu-
method of water injection and the degree of atomization of the lations regarding pollution, noise, and location. Permits are
water stream. Wind also has a significant effect on water spray usually required prior to construction.
flares and may greatly reduce their effectiveness. The blower
assisted flare uses approximately 1.4 to 3.2 kg of air per kg of
hydrocarbon to produce smokeless operation. Forced draft from
a blower assists combustion and air/gas turbulence, assisting SPECIAL RELIEF SYSTEM
smokeless operation. Tip velocities up to Mach 0.5 are common. CONSIDERATIONS
Pilots and Ignition Equipment
Reliable pilot operation under all wind and weather condi- The following equipment considerations should be followed
tions is essential. Flaring operations are for the most part in- for relief system design.
termittent and non-scheduled. The flare must be instantly
available for full emergency duty to prevent any possibility of Fired Heaters If there is a possibility that the process
a hazardous or environmentally offensive discharge to the at- side of a fired heater may be blocked in, then a relief valve
mosphere. Wind-shields and flame-retention devices may be should be provided to protect the heater.
used to ensure continuous piloting under the most adverse
conditions. Most pilots are designed to operate at wind veloci- Pumps Relief valves are required on the discharge of
ties of 100 miles per hour and higher. each positive displacement pump. Normally, these reliefs are
piped back to the process upstream of the pump rather than
Most flares employ a remote pilot ignition system. to the flare system. Isolation valves around the relief valves

5-19
may not be required if the pump itself can be isolated for main- API Std. 527 Commercial Seat Tightness of Safety-Relief
tenance. Valves with Metal-to-Metal Seats Permissible leakage of
conventional and bellows valves and testing procedure.
Vessels and Tanks Vessels or tanks which are subject
to atmospheric "breathing" due to cooling of gas or liquid con- API Std. 528 Standard for Safety Relief Valve Nameplate
tents are normally protected by "breather" valves or vacuum Nomenclature Standard covering information that should
relief valves. Vessels in higher pressure service are normally go on the nameplate of a safety relief valve.
designed for full vacuum if upset conditions can cause a vac- API Std. 620 Recommended Rules for Design and Con-
uum situation otherwise vacuum relief valves must be pro- struction of Large Welded-Low-Pressure Storage Tanks
vided to meet code requirements. Covers tanks at less than 15 psig. Section 6 of this document
gives recommendations on relief valve types and sizing.
Compressors Each positive displacement compressor
must have a relief valve on the discharge of each stage up- API Std. 2000 Venting Atmospheric and Low-pressure
stream of the block and check valves in order to protect the Storage Tanks (Non-Refrigerated and Refrigerated) Covers
compressor. These reliefs are normally piped to a closed sys- tanks at less than 15 psig. Capacity requirement calculations
tem. for both pressure and vacuum. Also fire-sizing method for low
pressure tanks.
Low Temperature Flaring
API Std. 2508 Design and Construction of Ethane and
When low temperature streams are relieved, the flare sys- Ethylene Installations at Marine and Pipeline Terminals,
tem piping and equipment exposed to cryogenic temperature Natural Gas Processing Plants, Refineries, Petrochemical
may require stainless steel or other acceptable alloys. Plants, and Tank Farms Covers the design, construction,
and location of refrigerated (including autorefrigerated) lique-
The system should be designed for the coldest process fied ethane and ethylene installations, which may be associ-
stream to be relieved plus the lower temperature effect of the ated with one or more of the following: railroad, truck,
expanding fluid (Joule-Thomson effect). Materials selection pipeline stations, or marine loading or unloading racks or
should be made according to applicable code recommenda- docks.
tions.
API Std. 2510 Design and Construction of LPG Installa-
Applicable Codes, Standards, and tions at Marine and Pipeline Terminals, Natural-Gas-Process-
Recommended Practices ing Plants, Refineries, Petrochemical Plants, and Tank
Farms.
The designers of relief systems should be familiar with the
following documents related to pressure relief valves in proc- API Bulletin 2521 Use of Pressure Vacuum Vent Valves
ess plants and natural-gas systems. for Atmospheric Pressure Tanks to Reduce Evaporation Loss.
NFPA Publications NFPA 58 and 30 These cover
ASME Codes ASME Boiler and Pressure Vessel Code storage and handling of liquefied petroleum gases. Sec-
Section I and Section VIII . tion B.10 covers safety devices installation and testing.
In the "scope," certain vessels are excluded from ASME Code NFPA 59 Covers LP-gas, Utility Plants
requirements, including all vessels under 15 psig operating
pressure. NFPA 59A Covers Liquid Natural Gas, Storage and Han-
dling
ANSI Codes ANSI B31.1 Power Piping.
OSHA Publications OSHA Title 29, Part 1910 -
ANSI B31.3 Chemical Plant & Petroleum Refinery Pip- Part 1910 includes handling, storage, and safety require-
ing. ments for LPG and ammonia.

ANSI B31.8 Gas Transmission & Distribution Systems. CGA (Compressed Gas Association) Publica-
tions Series of standards covering transportation, han-
API Publications API RP 520 Part I, Design This dling, and storage of compressed gases including:
API design manual is widely used for fire sizing of relief valves Pamphlet S-1.2 Safety Relief Device Standards
on both liquid and gas filled vessels:
Part 2: Cargo and portable tanks for compressed gases.
API RP 520 Part II, Installation This includes: (a) rec-
Pamphlet S-1.3 Safety Relief Service Standards
ommended piping practices, (b) calculation formulae for reac-
tive forces, and (c) precautions on preinstallation handling Part 3: Compressed Gas Storage Containers.
and dirt.
API RP 521 Guide for Pressure - Relieving and Depressuring REFERENCES
Systems, 2nd Edition An excellent document on every-
thing from causes of overpressure through flare stacks. 1. API RP 521 Guide for Pressure-Relieving and Depressuring
Systems, American Petroleum Institute, 1220 L Street, NW,
API Guide for Inspection of Refinery Equipment Chap- Washington, DC 20005.
ter XVI Pressure Relieving Devices Gives (a) guide for in- 2. ASME Boiler and Pressure Vessel Code, Section I and Sec-
spection of record keeping, and (b) frequency of inspection. tion VIII, American Society of Mechanical Engineers (ASME),
API Std. 526 Flanged Steel Safety Relief Valves for Use New York, NY.
in Petroleum Refineries Gives industry standards as to di- 3. ANSI B31.3 Chemical Plant and Petroleum Refinery Piping,
mensions, pressure-temperature ratings, maximum set pres- The American Society of Mechanical Engineers (ASME), 345
sures, body materials. East 47th Street, New York, NY 10017.

5-20
4. ANSI B31.8 Gas Transmission and Distribution Piping, The 13. Van Boskirk, B. A., "Sensitivity of Relief Valves to Inlet and Out-
American Society of Mechanical Engineers (ASME), 345 East let Line Lengths," Chemical Engineering, 23 August, 1982, pages
47th Street, New York, NY 10017. 77-82.
5. API Standard 527 Commercial Seat Tightness of Safety Relief 14. Schwartz, Robert E. and White, Jeff W., "Predict Radiation From
Valves with Metal-to-Metal Seats, American Petroleum Insti- Flares," Chemical Engineering Progress, Vol. 93, pp. 42-49, July
tute, 1220 L Street, NW, Washington, DC 20005. 1997.
6. API RP 520 Recommended Practice for the Design (Part I) and
Installation (Part II) of Pressure Relieving Systems in Refiner-
BIBLIOGRAPHY
ies, American Petroleum Institute, 1220 L Street, NW, Washing-
ton, DC 20005. 1. Chiu, C. H. "Apply Depressuring Analysis to Cryogenic Plant
7. Min, T. C., Fauske, H. K., Patrick, M., Industrial Engineering Safety", Hydrocarbon Processing, November 1982, Pages 255-
Chemical Fundamentals, (1966), pp. 50-51. 264.
8. API 2510 Design and Construction of LPG Installations at 2. Kandell, Paul "Program Sizes Pipe and Flare Manifolds for Com-
Marine and Pipeline Terminals, Natural-Gas-Processing Plants, pressible Flow", Chemical Engineering, June 29, 1981, Pages 89-
Refineries, Petrochemical Plants, and Tank Farms, American Pe- 93.
troleum Institute, 1220 L Street, NW, Washington, DC 20005. 3. Powell, W. W., and Papa, D. M., "Precision Valves for Industry",
9. NFPA 30, 58, 59 & 59A, National Fire Protection Association Anderson, Greenwood Company, Houston, Texas, 1982, Pages 52-
(NFPA), Batterymarch Park, Quincy, Massachusetts 02269. 61.
10. Brzustowski, T. A., "Flaring In The Energy Industry", Process 4. Straitz III, J. F., "Solving Flare-Noise Problems", Inter. Noise 78,
Energy Combustion Science, Pergamon Press, Great Britain, San Francisco 8-10, May 1978, Pages 1-6.
V. 2, pp. 129-144, 1976. 5. Straitz III, J. F., "Flaring for Safety and Environmental Protec-
11. Straitz III, J. F., Nomograms "Determining Proper Flame Tip tion", Drilling-DCW, November 1977.
Diameter and Height", Oil Gas and Petroleum Equipment, Tulsa, 6. Straitz III, J. F., "Make the Flare Protect the Environment", Hy-
Oklahoma, July and August, 1979. drocarbon Processing, October 1977.
12. "Recommendations and Guidelines Gasoline Plants, Pamphlet 7. Tan, S. H., "Flare Systems Design Simplified", Hydrocarbon
301", Oil Insurance Association, 175 West Jackson Blvd., Chi- Processing (Waste Treatment & Flare Stack Design Handbook)
cago, Illinois 60604, August 1971. 1968, Pages 81-85.

5-21

Potrebbero piacerti anche