International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459 (Online), Volume 4, Special Issue 1, February 2014)
International Conference on Advanced Developments in Engineering and Technology (ICADET-14), INDIA.
Lord Krishna College of Engineering (An ISO 9001:2008 Certified Institute) Ghaziabad, Uttar Pradesh, INDIA. Page 190
"Sharpening Skills.....
Serving Nation"
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459 (Online), Volume 4, Special Issue 1, February 2014)
International Conference on Advanced Developments in Engineering and Technology (ICADET-14), INDIA.
In figure line 4-5 is non-condensing line when the The difference between the saturation temperature for
condenser unit is not applied and line 4-5 is a condensing the existing condenser vacuum and the temperature of the
line when the condenser is used. Secondly, the exhaust condensate is termed condensate depression. [13, 14] This
steam condensate is free from impurities. Thermal paper deals with analysis and examine of some potential
efficiency of a condensing unit is higher than that of a non- parameter directly influence the condenser vacuum, which
condensing unit for the same available steam properties. In can be satisfactorily managed by maintaining the optimized
a reciprocating steam engine, the condenser pressure can be values of the other performance parameters. Some of such
reduced to about 12 to 15 cm. of Hg. The thermodynamic parameters are mentioned here under;
analysis of condensate application is discussed in a thermal
2.1 Cooling Water Inlet Temperature
power plant using regenerative Rankine cycle with a closed
feed water heater and pumped condensate is pumped from High cooling water inlet temperature (t1) leads to higher
the condenser through the Feed Water Heater (FWH) saturation temperature and corresponding rise in condenser
directly to the steam generator and to the turbine. As the saturation pressure (i.e. lower condenser vacuum) for a
initial pressure at the inlet of turbine is fixed and operating design specified cooling water temperature rise and
pressure of the condenser is low due to an increased terminal temperature difference. As the t1 is an
vacuum, the enthalpy drop of the expanding steam in the uncontrollable parameter for a once through type of cooling
turbine will increase. This increases the amount of water system and hence required to be incorporated in the
available work from the turbine. The low condenser other controllable operating parameters such as rise in
operating pressure enables higher turbine output, an cooling water flow subjected to maximum critical erosion
increase in plant efficiency and reduced steam flow for a limits, reduction of load not more than that corresponding
given plant output. It is, therefore, advantageous to operate heat loading, operating parameters of vacuum creating
the condenser at the lowest possible pressure (highest devices. In addition to the above (t1) is attempted to be
vacuum).[10-12] The condenser provides a closed space minimized through the cooling towers in which heat of
into which the steam enters from the turbine and is forced cooling water is rejected to ambient air.
to give up its latent heat of vaporization to the cooling These are two effects caused by the cooling water inlet
water. It becomes a necessary component of the steam temperature. The primary one is to alter the steam
cycle as it converts the used steam into water for boiler saturation temperature by the same amount as the change,
feed water and reduces the operational cost of the plant. assuming all the other factors remain constant. This, in its
Also, efficiency of the cycle increases as it operates with turn, will change the corresponding back pressure. The
the largest possible delta-T and delta-P between the source secondary effect is caused by the fact that the heat transfer
(boiler) and the heat sink (condenser). As the steam of the cooling water film in contact with condenser tubes
condenses, the saturated liquid continues to transfer heat to change with temperature of the water. The primary and
the cooling water as it falls to the bottom of the condenser, secondary changes are in opposite direction. The
or hot-well. This is called sub-cooling, which is desirable magnitude of the secondary effect is approximately equal
up to a certain extent. to the fourth root of the mean cooling water temperature.
Lord Krishna College of Engineering (An ISO 9001:2008 Certified Institute) Ghaziabad, Uttar Pradesh, INDIA. Page 191
"Sharpening Skills.....
Serving Nation"
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459 (Online), Volume 4, Special Issue 1, February 2014)
International Conference on Advanced Developments in Engineering and Technology (ICADET-14), INDIA.
Table 1
Effect of Variation in Cooling Water Inlet Temperature on Condenser Vacuum
2.2 Cooling Water Flow Higher pressure drop indicates internal tube surface
Reduced cooling water flow shall increase the cooling deposits, which adversely affects the cooling water flow
water temperature rise, which leads to higher saturation and heat transfer. Adequate flow can be maintained by
temperature at design terminal temperature difference and higher discharge pressure but heat transfer shall remain
corresponding saturation pressure. Cooling water pressure condenser vacuum control parameters. A frequent on line
drop across the condenser tubes reduces the cooling water tube cleaning and proper condenser maintenance can help.
flow.
Lord Krishna College of Engineering (An ISO 9001:2008 Certified Institute) Ghaziabad, Uttar Pradesh, INDIA. Page 192
"Sharpening Skills.....
Serving Nation"
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459 (Online), Volume 4, Special Issue 1, February 2014)
International Conference on Advanced Developments in Engineering and Technology (ICADET-14), INDIA.
The primary effect of a change of cooling water flow is the change of heat transfer rate, due to the changed
to alter its temperature rise. The secondary effect, which thickness of the cooling water boundary film. It is
operates in the same direction as the primary, results from approximately proportional to the square root of the flow.
Table 2
Effect of Variation in Cooling Water flow on Condenser Vacuum
Lord Krishna College of Engineering (An ISO 9001:2008 Certified Institute) Ghaziabad, Uttar Pradesh, INDIA. Page 193
"Sharpening Skills.....
Serving Nation"
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459 (Online), Volume 4, Special Issue 1, February 2014)
International Conference on Advanced Developments in Engineering and Technology (ICADET-14), INDIA.
Condenser vacuum falls in similar way as in case of Steam flow is a very important input parameter which is
inadequate cooling water flow followed by significant sub regulated as per the requirement of electricity demand.
cooling. Condensate pumps and associated condenser hot Load raising should preferably be restricted within the
well control system must be maintained healthy enough to condenser capability limit to prevent wastage of heat at
keep the condensate level within design specified ranges. higher potential.
2.3.2 Steam Flow 2.3.3 Internal/External Tube Deposits
Increasing steam flow shall increase the saturation Dirty condenser tubes reduce the heat transfer, which
temperature at and corresponding saturation pressure. adversely reflects upon condenser vacuum.
Table 3
Effect of Variation of load on Condenser Vacuum
48
47.5
Ts (Saturation Temp)
47
46.5
46
45.5
Series2
45
44.5
44
43.5
43
42.5
43568
44439
45328
46234
47159
48102
43568
42696
41842
41005
40185
39382
Qs (Steam Flow)
Lord Krishna College of Engineering (An ISO 9001:2008 Certified Institute) Ghaziabad, Uttar Pradesh, INDIA. Page 194
"Sharpening Skills.....
Serving Nation"
International Journal of Emerging Technology and Advanced Engineering
Website: www.ijetae.com (ISSN 2250-2459 (Online), Volume 4, Special Issue 1, February 2014)
International Conference on Advanced Developments in Engineering and Technology (ICADET-14), INDIA.
2.3.3 Operating Parameters of Vacuum Creating Devices [2 ] Geete and A. I. Khandwawala, Exergy Analysis of 120MW
Thermal Power Plant with Different Condenser Back Pressure and
The non-condensable are required to be removed Generate Correction Curves, International Journal of Current
continuously by the effective vacuum creating devices (i.e. Engineering and Technology, Vol.3, No.1, pp 164-167, March 2013.
Steam ejectors or vacuum pumps), mal operation of which [3 ] V. S. K. Karri, A Theoretical Investigation of Efficiency
reduce vacuum. Starting ejector can create vacuum up to Enhancement in Thermal Power Plant, Modern Mechanical
Engineering, Vol.2 No.3, 106-113, Aug. 2012.
540 mmHgCl. In addition to relying upon design specified
[4 ] A.K. Jain, An Optimal Preventive Maintenance Strategy for
vacuum value of the starting ejector, it is better to Efficient Operation of Boilers in Industry, International Institute for
sufficiently wait till its capacity is exhausted and stable Science, Technology and Education, Vol. 2, No. 4, 2012.
vacuum is maintained. 10 to 30 minutes after the [5 ] H. Gao, C. Liu, C. He, X. Xu, S. Wu and Y. Li, Performance
establishment of stable vacuum by starting ejector, the Analysis and Working Fluid Selection of a Supercritical Organic
main ejector should be cut into service followed by Rankine Cycle for Low Grade Waste Heat Recovery, Energies, 5,
3233-3247, 2012
immediate withdrawal of starting ejector. Parallel operation
[6 ] Vosough, A. Falahat, S. vosough, H.Nasresfehani, A. Behjat and R.
of both the ejector shall not only develop the lesser vacuum
Naserirad, Improvement Power Plant Efficiency with Condenser
but also damage the main ejector. Pressure, International Journal of Multidisciplinary Sciences and
Engineering, Vol.2, No. 3, 38-43, June 2011.
2.3.4 Terminal Temperature Difference
[7 ] R. K. Kapooria, K.S. Kasana and S. Kumar, Technological
Causes and remedial measures of the higher terminal investigations and efficiency analysis of a steam heat exchange
temperature difference are briefly mentioned here under; condenser: conceptual design of a hybrid steam condenser, Journal
a) Higher gaseous impurities in the steam can be managed of Energy in Southern Africa, Vol 19 No 3, 35-45, Aug.2008.
by better management of boiler and pre-boiler system [8 ] L. M. Romeo, I. Bolea, J. M. Escosa,Integration of power plant and
amine scrubbing to reduce CO2 capture costs, Applied Thermal
b) Air ingress can be avoided by frequent leak detection Engineering,Vol. 28, Issue 8-9, PP. 1039-1046, 2007.
test and effective steam sealing of low pressure turbine [9 ] J. Tarlecki, N. Lior, N. Zhang, Evaluation of Some Thermal Power
c) External tube deposits can gradually increase terminal Cycles for Use in Space, Department of Mechanical Engg. And
temperature difference which needs better de Applied Mechanics, Proc. ECOS. Crete, Greece. 12-14 July 2006.
mineralized water quality management [10 ] Uprating, Renovation & Modernization Of Ageing Thermal Power
d) Internal tube deposits causing higher terminal Plant, Report By N.K. Srivastava, Gen. Manager, and R&M Engg.
NTPC-INDIA, 2010.
temperature difference with higher cooling water
[11 ] Thermal Power Plant Performance Improvement Using Quality
pressure across the condenser can be effectively Initiatives, NTPC Report by S. Banerjee, S.N. Tripathi, Mohit
minimized by on-line condenser tube cleaning. Yadav, 2008.
[12 ] Renovation and Modernization of Thermal Power Plants in India
2.4 Concluding Remarks
planning and implementation guidelines, June 2010.
Feasibility analysis of the potential parameters reveals [13 ] Opportunities to Improve the Efficiency of Existing Coalfired
that the managerial determination blended with right men Power Plants, Workshop Report, July 1516, 2009.
and material can improve the performance of the thermal [14 ] National awards on energy conservation for industries, office & bpo
power stations. Sufficient guide lines have been provided to buildings, hotels & hospitals, municipalities, state designated
the user to quantify the loss under the prevailing operating agencies, thermal power stations, zonal railways, and manufacturers
of bee star labelled appliances/equipment 2011.
conditions and broadly analyze and divide the same
[15 ] Yadav, K.C. and Haleem A., 2004. Effective Management
distinctly either as inevitable or as avoidable so that the all Techniques For Improvement Condenser Vacuum, Global
improvement efforts can be made in right direction. Conference on Flexible Systems Management , Delhi, March 13-15,
2004, conducted by GLOGIFT & Department of Mechanical
REFERENCES Engineering, Faculty of Engineering and Technology, JMI, Okhla,
[1 ] M. Baweja, V.N. Bartaria, A Review on Performance Analysis of New Delhi (India).
Air-Cooled Condenser under Various Atmospheric Conditions,
International Journal of Modern Engineering Research (IJMER),
Vol.3, Issue.1, pp 411-414, Jan-Feb. 2013.
Lord Krishna College of Engineering (An ISO 9001:2008 Certified Institute) Ghaziabad, Uttar Pradesh, INDIA. Page 195