GC12 v3.0
http://simcons.in
Introduction
GC12 is a highly reliable Auto Mains Failure controller with automatic
generator start, stop and load switching suitable for a wide variety of diesel
generators.
GC12 monitors engine and 3-phase mains parameters and displays them on
the LCD screen. When a mains failure occurs, GC12 starts the generator and
transfers the load after a user defined time, and switches it back to the mains
supply when mains power is back. It can also be programmed to start the engine
when a backup battery drops below a certain voltage. It ensures the generator runs
in a healthy condition. If an abnormality occurs, it shuts the DG down
automatically and displays the fault on the LCD screen along with an LED
indication.
Enhanced features include Real Time Clock based operation, with a
scheduler, so that the generator can be operated only during the desired time
interval. It can also be operated in a cyclic run-rest pattern.
Configuration parameters can be set with an interactive menu, which has an
optional password protection. The generator can be set to work in automatic,
manual or remote mode operation. The operations are easy with a 9-key keyboard.
Alarm extension card from Simcons, AL12, can be used with GC12, to
provide potential free contact for alarms, viz. Mains Failure, DG running, Backup
Battery Low, Low Fuel, DG Battery Low, High Cabin Temperature and Common
Fault. It does need any other connections other than the one from GC12.
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
Features
3 phase mains and DG voltage monitoring with DG run time
Can be configured to work with single phase DG/MAINS
Potential free outputs for Mains Contactor, DG contactor, start, stop and
hooter outputs.
40 programmable parameters, easy navigation
Optional Alarm extension
Two line LCD display, LED indications
Easy user interface with 9 key keyboard and LCD screen.
User friendly menu with optional password protection
DG protection features: LLOP, under voltage, over voltage, overload, high
temperature, fuel, emergency stop, under speed, over speed etc.
Warning for crank failure, low battery, stop failure, battery low/high etc.
Analog fuel input
Auto, manual and remote mode operation
Scheduler based on Real Time Clock
Programmable run/rest time
Backup battery monitoring (can be programmed to start DG on low battery
overriding timers) with range 20VDC-70VDC (20VDC to 300VDC range
available upon special request)
Last 60 event records (20 different events/faults) with date, time stamp and
duration.
Easy mounting on panel
Specifications
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
Keyboard Functions
LED Indications
MANUAL
MODE
(Yellow
Indication):
The yellow LED
indicates the controller is in
Manual/remote mode.
SIMCONS
CONTROL SYSTEMS
LOAD
ON
DG
(Green
Indication): Generator Contactor is
Closed
LOAD ON MAINS (Green
Indication): Mains Contactor is
Closed
FAULT
(Red
Indication):
Generator fault condition/warning.
Refer the LCD display to identify
the fault.
4
GC12 v3x
http://simcons.in
Wiring Diagram
*Max potential that can be applied on pins DCCOM, MCIN or GCIN in is 40V AC/DC. Use
external relay card to switch 230V.
*Max current into or out of DCCOM:4A. Max current into or out of MCIN/GCIN:1A
Connector Description
Digital Outputs (Relay Outputs)
1.
2.
3.
4.
5.
6.
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
Inputs
9. Mains Contactor
Output(Normally Open)
10.Mains Contactor Signal
Input(Common)
11.DG Contactor Output(Normally
Open)
12.DG Contactor Signal
Input(Common)
24.No Connection
25.Remote Mode (Negative
Sensing). This input activates
the remote start and stop
features
26.Fuel (Analog/Negative sensing)
27.Emergency/Remote stop
(Negative Sensing)
28.LLOP (Negative Sensing)
29.High Coolant/Oil Temperature
(Negative Sensing)
30.Fault1(Negative Sensing)
38.Remote Start(Negative
Sensing)
Auxiliary Input
13.No Connection
14.Battery +VE
15.Battery VE
DG Voltage
Alarm Extension Port
16.DG B phase
17.DG Y phase
18.DG R phase
19.DG Neutral
31.RX
32.TX
33.GND
34.BOUT
Mains Voltage
Backup Battery Input
20.Mains B phase
21.Mains Y phase
22.Mains R phase
23.Mains Neutral
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
Programmable Parameters
Run - Rest Cycle
MainsUndrvoltHgh
Enabled/Disabled
MainsOverVoltage
220-300 Volts
Default: Disabled
MainsSinglePhase
Mains Imbalance
Enabled/Disabled
Enable/Disable
0-30%
Default: Enabled
MainsUndrvoltLow
DG Single Phase
90-220 Volts
Enabled/ Disabled
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
DG UnderVoltage
90-220 Volts
Generator Under Voltage. If a UV
condition occurs, the load is tripped
for 10 seconds. If UV occurs again in
a short time interval, the generator is
shut down automatically.
Default: 160 Volts
MainsFailDelay
0-250 Sec
Mains Fail Delay- Delay between
mains failure and crank attempt.
Default: 10 Sec
DG OverVoltage
FailDelyExtended
220-300 Volts
DG UnderSpeed
30-60Hz
Generator Under frequency/speed
DG Preheat Time
Default: 45 Hz
0-250 Sec
DG OverSpeed
50-70 Hz
Generator Over frequency/speed
Default: 55Hz
Cranking Time
LLOPCheckToCrank
1-20 Sec
Enabled/Disabled
Generator cranking time- Generator is
cranked for the specified duration.
Default: 2 Sec
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
Crank Attempts
1-5
Generator crank attempts. If generator
did not start after cranking, it is again
cranked to the number of crank
attempts.
Default: 3
SolnoidOnToStart
Enabled/Disabled
Configure fuel solenoid. Enabled fuel solenoid energized when running
DG. Disabled solenoid is energized
to stop the engine
DG BuildUp Delay
1-250 Sec
DG build-up delay delay during
which DG voltage, frequency and oil
pressure build up
Default: 10 Sec
Default: Disabled
DG Stopper Time
1-99 Sec
MainsRestorDelay
0-250 Sec
Mains Restore Delay- Delay between
mains recovery and mains contactor
closing.
Default: 5 Sec
LowFuelTripLevel
0-60 %
Low fuel percentage Fuel level
below which generator will be
stopped
Default: 10 %
LowFuelWarning
0-60 %
DG Recool Delay
0-250 Sec
SIMCONS
CONTROL SYSTEMS
GC12 v3x
http://simcons.in
HooterResetTime
4-99 Sec
Hooter reset time The time in which
the hooter will be turned on when a
fault condition occurs.
Default: 10 Sec
Time-24Hr Clock
7-24 Volts
00:00 to 23:59 Hr:Min
Date Settings
DG Bat HighLevel
FactoryDefaults?
Yes/No
Factory default settings Selecting
YES and pressing SET will cause all
the settings to be reset to factory
defaults.
Engine RPM/Hz
5-99
Engine RPM/frequency ratio. The
engine RPM is frequency*RPM ratio.
Default: 30
Calibration
Reserved. Factory calibration is done.
Scheduler
Password Options
Enabled/Disabled
If enabled, scheduler start time and
end time can be programmed. The
scheduled operating time must lie
within the 0-24 hours of a day. If
enabled, the Scheduled start time
and Scheduled stop time can be set.
SIMCONS
CONTROL SYSTEMS
10
GC12 v3x
http://simcons.in
Fan Output
Yes/No
Selecting Yes will configure the
PREHEATER relay output(PIN 3) to
FAN output for air cooled engines
Event Log
20V to 240V
Calibrate BtsBat
0000 *10mV to 3000*10mV
Calibrate the backup battery voltage.
For example, if the backup battery
voltage is 48.5V, enter 0485*10mV
and press SET.
BypasRestOnLoBat
Enabled/disabled
BtsBatMonitoring
Enabled/Disabled
Enabling
BTSBAT
Monitoring
monitors and displays the Backup
SIMCONS
CONTROL SYSTEMS
11
GC12 v3x