Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1-1. SCOPE. This section covers procurement of all cast-in-place concrete, including
concrete materials, limiting requirements, mixture design, and performance
requirements, and delivery to the site through discharge at the end of the delivery truck
chute. Work beyond the end of the delivery truck chute is covered in Sections 03100,
03200, 03250, and 03350.
1-1.01. Terminology. When the phrase "as required" is stated in this section, it shall
mean, "as required in the attached Data Sheet" or "as required in Tables 1A, 18, 2A
and 2B."
1-2. GENERAL. All cast-in-place concrete shall be as specified herein.
1-2.01. Concrete Classifications. Concrete classifications shall be defined and used as
indicated for the following classes:
Concrete Classifications
A.
Structural Concrete
Class Class Description
Al.
A2.
A3.
A4.
Mortar Puddle.
A5.
03300-1
CAST-IN-PLACE
CONCRETE
A.
Structural Concrete
Class Class Description
B.
C.
D.
Miscellaneous Concrete
D1.
Ductbanks, Pipe
Encasement
D2.
D3.
D4.
D5.
D6.
D7.
Lean Concrete
Blocking,
Concrete
Fill,
and
Pipe
1-3. SUBMITTALS.
1-3.01. Drawings and Data. All submittals of drawings; manufacturers' certificates of
compliance, recommendations, and test data; reports; catalog data sheets; and other
data shall be in accordance with the submittals section, unless otherwise specified
herein.
As required, reports and certifications on proposed materials and mixture proportions for
each concrete mixture design shall be submitted for review within 30 days after the
preconstruction conference and prior to conducting the laboratory trial batches for each
mixture design.
1-3.02. Manufacturers Certificate of Compliance. A manufacturer's certificate of
compliance, which includes the name of the project and copies of independent test
results confirming compliance with specified requirements, shall be submitted to the
ENGINEER for the following materials when used:
03300-2
CAST-IN-PLACE
CONCRETE
Cement.
Admixtures.
Fly Ash.
1-4. STORAGE AND HANDLING. Cement and fly ash shall be stored in suitable
moistureproof enclosures. Cement and fly ash which have become caked or lumpy
shall not be used.
Aggregates shall be stored so that segregation and the inclusion of foreign materials are
prevented. The bottom 6 inches of aggregate piles in contact with the ground shall not
be used.
PART 2
PRODUCTS
CAST-IN-PLACE
CONCRETE
cement plus fly ash shall be used to determine the water-cementitious materials ratio.
Limiting maximum water-cement ratios are indicated in Tables 1A and 1B.
2-1.03. Fly Ash Content. As required, CONTRACTOR may substitute fly ash for up to
the percentage of the portland cement indicated in Tables 1A and 1B and not less than
15 percent, on the basis of 1.0 lbs of fly ash added for each lb of cement reduction.
2-1.04. Aggregates. Aggregates shall comply with ASTM C33 except as specified
herein. Fine aggregate shall be clean natural sand. Artificial or manufactured sand will
not be acceptable. Coarse aggregate shall be crushed rock, washed gravel, or other
inert granular material, meeting Class 4S requirements, except that clay and shale
particles shall not exceed values indicated in Tables 1A and 1B.
When ASTM C33 gradations are specified, final gradation of the coarse aggregate shall
conform to maximum nominal size grading requirements of ASTM C33, when one size
of aggregate or a combination of two or more sizes is used.
When the 18-8 combined aggregate gradation is required, the combined aggregates
shall be well graded from the coarsest to the finest with not more than 18 percent nor
less than 8 percent (18-8 requirement), unless otherwise acceptable to the Engineer, of
the combined aggregate retained on any individual sieve with the exceptions that the
No. 50 may have less than 8 percent retained, sieves finer than No. 50 shall have less
than 8 percent retained, and the coarsest sieve may have less than 8 percent retained.
Aggregates used in concrete shall have a combined aggregate distribution similar to the
aggregates used in the concrete trial mixtures. Reports of individual aggregates shall
include sieve sizes 1-1/2 inch, 1 inch, 3/4 inch, 1/2 inch, 3/8 inch, No. 4, No. 8, No. 16,
No. 30, and No. 50 in accordance with ASTM El 1.
When available aggregates are elongated or slivered and cause interference with
mixture mobility, or available aggregate gradations will not comply with the 18-8
requirement and when permitted by ENGINEER, the combined aggregate percentages
may be changed to not more than 22 percent nor less than 6 percent retained on any
individual
sieve.
Specified sand equivalent for fine aggregate shall be not less than indicated in Tables
1A and 1B for an average of 3 samples tested in accordance with ASTM D2419.
The maximum coarse aggregate content consistent with workability and minimizing
shrinkage shall be used in the mixture. To comply with the specified concrete shrinkage
test requirements, the clay and shale content of the aggregates may need to be
reduced by washing the aggregate.
2-1.05. Ratio of Fine to Total Aggregates. The ratio of fine to total aggregates, based
on solid volumes (not weights), shall be as follows:
03300-4
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. EN09021.01
CAST-IN-PLACE
CONCRETE
Minimurn
Ratio
Mvaximurn
Ratio
3/8 inch
0.45
0.60
1/2 inch
0.40
0.55
3/4 inch
0.35
0.50
1 inch
0.30
0.46
1-1/2 inch
0.25
0.40
Ratio
Ratio
2-1.06. Slump. Concrete slump shall be kept as low as possible, consistent with proper
handling and thorough consolidation. Unless otherwise noted, required, or authorized
by ENGINEER, slump shall be at least 2 inches and shall not exceed the maximum
slump as indicated in Tables 1A and 1B.
When superplasticizer is dispensed at the ready-mix plant, the concrete mixture design
shall be based on a maximum slump as indicated in Tables 1A and 18; and when
superplasticizer is dispensed at the site, slump shall not exceed the maximum slump as
indicated in Tables 1A and 1B before superplasticizer is added.
2-1.07. Initial Set- The initial set, as determined by ASTM C403, shall be attained
5-1/2 hours 1 hour after the water and cement are added to the aggregates for each
concrete mixture. The quantity of retarding admixture shall be adjusted to compensate
for variations in temperature and job conditions.
2-1.08. Total Air Content. The total volumetric air content of concrete after placement
shall be as indicated in Tables 1A and 18, and.within 1 percent. Air-entraining
admixture may be omitted from concrete for interior slabs which are to be trowel
finished, and from Classes D1, D2, and D7 concrete.
2-1.09. Admixtures. Unless otherwise acceptable to the ENGINEER, all admixtures
shall be from one manufacturer and shall be compatible. Admixtures that are compatible
with other admixtures and concrete materials shall not have an adverse affect on the
required properties of the concrete nor the specified limiting requirements. The
admixture content, batching method, and time of introduction to the mixture shall comply
with these specifications and -with the manufacturer's recommendations for minimum
shrinkage. The admixture manufacturer shall provide qualified field services as
necessary, at no additional cost to AGENCY.
03300-5
CAST-IN-PLACE
CONCRETE
2-1.11. Strength. In addition to the other limiting requirements to achieve durability and
minimize shrinkage, the minimum acceptable compressive strengths of concrete tested
at the end of the delivery truck chute using 6 by 12 inch site-cast cylinders, as
determined by ASTM C39, shall be as indicated in Tables 1A and 1B.
Adequate test cylinders taken at the point of placement will also be made to verify that
the construction contractor's concreting procedures comply with applicable industry
standard procedures.
03300-6
CAST-IN-PLACE
CONCRETE
2-1.12. Pumped Concrete. Coarse aggregate size for pumped concrete mixtures shall
be limited to a maximum of 1-1/2 inch.
The slump of concrete, with or without a superplasticizer, that is discharged into the
pump may exceed the specified maximum slump value by the amount of slump loss in
the pumping system, up to a maximum of 1 inch. The slump loss shall be determined
by tests made at each end of the pumping system.
2-1.13. Water-Soluble Chloride. Maximum water-soluble chloride ion concentrations in
hardened concrete at an age of 28 days shall not exceed the limits expressed as a
percentage of mass of cement as indicated in Tables 1A and 1B.
Test results shall be reported as the percentage of water-soluble chloride ions in the
concrete and as a percentage of chloride ion relative to the mass of cement in the
concrete.
Testing of the concrete components, except aggregates, for water-soluble chloride ions
will be done at the discretion of CONTRACTOR. Copies of the reports on such tests
shall be furnished to ENGINEER.
The hardened concrete and each gradation of aggregate used in the concrete shall be
tested each time a chloride ion test is conducted on a concrete mixture.
*
2-1.14. Laboratory Shrinkage Limits. Based on the modified ASTM C157 test
procedures as specified herein, the shrinkage limits of concrete shall be the average
drying shrinkage of each set of three test specimens cast in the laboratory from a trial
batch as measured at the 21 days drying age, and shall not exceed the values in Tables
1A and 1B.
The average drying shrinkage of each set of test specimens cast in the field from
concrete delivered to the site, and sampled at the end of the delivery truck chute, as
measured at the 21 days drying age shall not exceed the values in Tables 1A and 1B.
2-1.15. Mineral Colored Concrete. Not Used.
2-1.16. Concrete Mixtures.
2-1.16.01. Structural Concrete. All Class A concrete shall be structural concrete that
conforms to all specified limiting requirements in Tables 1A and 1B and this
specification.
2-1.16.02. Small Aggregatge Concrete. Structural small aggregate concrete shall be
used in all areas where the clear distance between reinforcement, conduit, or
embedded items is less than the least dimension of coarse aggregate particles in the
03300-7
CAST-IN-PLACE
CONCRETE
structural concrete. Structural small aggregate concrete shall conform to all specified
limiting requirements, except maximum nominal size of coarse aggregate. Maximum
nominal size of coarse aggregate shall be 1/2 inch for concrete mixtures to be placed
and consolidated in portions of structures congested with reinforcing steel, conduits,
and embedded items.
2-1.16.03. Miscellaneous Concrete for Pipe Blockinq, Pipe Encasement, Concrete Fill,
and Duct Banks. Concrete for buried pipe blocking, pipe encasement, concrete fill, and
duct banks shall conform to the limiting requirements in Tables 1A and 1B.
2-1.16.04. Underwater Concrete. Unless otherwise permitted by ENGINEER, concrete
shall not be deposited underwater. The underwater concrete mixture shall be designed
and concrete shall be controlled within the specified limits for structural concrete except
as modified by the limits in Tables 1A and 1B.
2-1.17. Cold Weather Concrete. Except as modified herein, cold weather concrete
shall comply with ACI 306R. The temperature of concrete at the point of delivery at the
end of the delivery truck chute shall be not less than that indicated in ACI 306R for
corresponding outdoor temperature (in shade) at the time of placement:
When delivered, heated concrete shall be not warmer than 80'F.
2-1.18. Hot Weather Concrete. Except as modified herein, hot weather concrete shall
comply with ACI 305R. At air temperatures of 90'F or above, concrete shall be kept as
cool as possible before and during delivery. The temperature of the concrete at the
time of delivery at the end of the delivery truck chute shall not exceed the values
indicated in Tables 1A and 1B.
2-2. MATERIALS.
Cement
ASTM C 150, Type II or Type II.
Low Alkali.
Fly Ash
CAST-IN-PLACE
CONCRETE
As
specified
in
Requirements paragraph.
Water
Potable.
Limiting
Admixtures
Water Reducing/Normal Set
Water Reducing/Retarding
Air-Entraining
Superplasticizing/ Retarding
Mineral Coloring
Not Used.
2-3. PROPORTIONING.
2-3.01. Mixture Design. Using concrete materials acceptable to ENGINEER, a
tentative concrete mixture shall be designed and tested in the laboratory for each size
and combined gradation of aggregates and for each consistency as indicated and
intended for use on the work and as specified.
As required, concrete proportions shall be established based on laboratory trial mixtures
that meet the following requirements:
03300-9
CAST-IN-PLACE
CONCRETE
a.
b.
c.
e.
f.
Mixtures shall be adjusted in the field as necessary, within the limits specified, to meet
the requirements of these specifications.
03300-10
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. EN09021.01
CAST-IN-PLACE
CONCRETE
2-3.02. Preliminary Review. Reports covering the source and quality of concrete
materials and the concrete proportions proposed for the work shall be submitted to
ENGINEER for review before performing the required trial mixture designs and before
concrete work is started. The reports required shall be as indicated in Tables 2A and
28. Review of these reports will be for general acceptability only, and continued
compliance with all contract provisions will be required.
2-3.02-01. Aqqregate Reports.
listed in Tables 2A and 2B.
2-3.02.02. Mixture Design Report. Design quantities and test results on each mixture
shall be submitted for review and shall be accepted before concrete work is started.
The report on each tentative concrete mixture and on the proposed concrete mixture
shall contain the information in Tables 2A and 26, and shall be submitted to
ENGINEER.
2-3.02.03. Mixture Design Testinq. As stipulated in the Quality Control section, all tests
and reports required for preliminary review shall both be made by an independent
testing laboratory at the expense of CONTRACTOR specifically for this project. All
materials shall be tested in accordance with the specified test methods and reports for
these tests shall be prepared specifically for this project. If the source of any concrete
materials is changed during the contract, the materials and the new mixture design shall
be tested in accordance with the specified preliminary review requirements and reports
shall be submitted for review.
Aggregates shall be sampled and tested in accordance with ASTM C33. In addition, the
bulk specific gravity of each aggregate shall be determined in accordance with ASTM
C127 and ASTM C128.
Concrete test specimens shall be made, cured, and stored in accordance with ASTM
C192 and tested in accordance with ASTM C39.
Slump shall be determined in accordance with ASTM C143. Total air content shall be
determined in accordance with ASTM C231 and verified in accordance with
ASTM C138.
Concrete temperature shall be determined in accordance with
ASTM C1064 and unit weight (mass) shall be determined in accordance with
ASTM C138- Water-soluble chloride ion shall be determined in accordance with ASTM
C1218.
Initial set tests shall be made at ambient temperatures of 70F and 90'F to determine
compliance with the specified time for initial set. The test at 70'F shall be made using
concrete containing the specified normal set/water-reducing admixture and, when
required, air-entraining admixture. The test at 90'F shall be made using concrete
03300-11
CAST-IN-PLACE
CONCRETE
03300-12
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. EN09021.01
CAST-IN-PLACE
CONCRETE
2-5.01. Consistency. The consistency of concrete shall be suitable for the placement
conditions. Aggregates shall float uniformly throughout the mass, and the concrete
shall flow sluggishly when vibrated or spaded. The slump shall be kept uniform.
2-5.02. Delivery Tickets. A delivery ticket shall be prepared for each load of
ready-mixed concrete and a copy of the ticket shall be handed to ENGINEER by the
truck operator at the time of delivery. Tickets shall indicate the name and location of
CONTRACTOR, the project name, the mixture identification, the quantity of concrete
delivered, the quantity of each material in the batch, the outdoor temperature in the
shade, the time at which the cement was added, and the numerical sequence of the
delivery.
PART 3 - EXECUTION
3-1. CONTRACTOR'S ON GOING MATERIAL CONTROL TESTING. The following
tests and the test reports are required during the progress of the work and shall be
made at the expense of CONTRACTOR. The frequency specified herein for each field
control test is approximate and subject to change as determined by ENGINEER.
03300-13
CAST-IN-PLACE
CONCRETE
3-1.01. Aqqreqate Gradation. Each 200 tons of fine aggregate and each 400 tons of
coarse aggregate and at least once every 6 months, aggregates shall be sampled and
tested in accordance with ASTM D75 and C1363-1.02. Sand Equivalent. The sand equivalent test shall be conducted each time the
sand gradation tests are conducted.
3-1.03. Fly Ash. Each 400 tons of fly ash shall be sampled and tested in accordance
with ASTM C618 and C311. CONTRACTOR shall supply ENGINEER with certified
copies of supplier's (source) test reports showing chemical composition and physical
analysis for each shipment delivered to CONTRACTOR and certifying that the fly ash
complies with the specifications. The certificate shall be signed by both the fly ash
supplier and CONTRACTOR.
3-1.04. Cement. CONTRACTOR shall supply ENGINEER with certified copies of
supplier's (source) test reports showing chemical composition and physical analysis for
each shipment delivered to CONTRACTOR, and certifying that the cement complies
with ASTM C150 and these specifications. The certificate shall be signed by both the
cement manufacturer and CONTRACTOR.
3-2. OWNER'S FIELD CONTROL TESTING. Field control tests, including aggregate
gradation (if needed), slump, air content, and making compression test cylinders, shall
be performed by ENGINEER or testing laboratory personnel. CONTRACTOR shall
provide all facilities and the services of one or more employees as necessary to assist
with the field control testing.
As stipulated in the quality control section, tests required during the progress of the
work shall be made at the expense of AGENCY.
The frequency specified herein for each field control test is approximate and subject to
change as determined by ENGINEER.
ENGINEER may require field testing prior to the addition of superplasticizer at the site
to determine compliance with the specifications. Field testing after the addition of
superplasticizer shall be conducted as specified and as needed to determine that the
concrete is in compliance with the specifications. Air tests shall be conducted whenever
field tests are conducted.
3-2.01. Slump. A slump test shall be made for each 50 cubic yards of concrete. Slump
shall be determined in accordance with ASTM C143.
3-2.02. Air Content. An air content test shall be made on concrete from one of the first
three batches mixed each day and on concrete from each batch of concrete from which
03300-14
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. EN09021.01
CAST-IN-PLACE
CONCRETE
accordance with ASTM C231 and verified in accordance with ASTM C138.
3-2.03. Unit Weight. A unit weight test shall be made on concrete from each batch of
concrete from which concrete compression test cylinders are made. Unit weight shall
be determined in accordance with ASTM C138.
3-2.04. Concrete Temperature. A concrete temperature test shall be made on concrete
from the first batch of concrete mixed each day and on concrete from each batch of
concrete from which concrete compression test cylinders are made.
Concrete
temperature shall be determined in accordance with ASTM C1064.
3-2.05- Water-Soluble Chloride Ion. Water-soluble chloride ion testing shall be
performed once for each 1,000 cubic yards of concrete in accordance with ASTM
C1218.
3-2.06. Compression Tests. One set of four concrete compression test cylinders shall
be made each day when 25 to 50 cubic yards of concrete is placed. One additional set
of test cylinders shall be made from each additional 50 cubic yards, or major fraction
thereof, placed in any one day. Two cylinders of each set shall be tested at an age of
7 days and the remaining cylinders shall be tested at an age of 28 days.
*
Test cylinders shall be 6 inches in diameter by 12 inches high and shall be made, cured,
stored, and delivered to the laboratory in accordance with ASTM C31 and tested in
accordance with ASTM C39.
Each set of compression test cylinders shall be marked or tagged with the date and time
of day the cylinders were made, the location in the work where the concrete
represented by the cylinders was placed, the number of the delivery truck or batch, the
air content, the slump, the unit weight, and the concrete temperature.
3-2.07. Shrinkage Tests. Concrete shrinkage tests shall be performed once for each
1,000 cubic yards of concrete with controlled shrinkage that is placed and shall be made
on concrete from a batch of concrete from which concrete compression test cylinders
are made. Shrinkage testing shall be conducted as specified for the preliminary trial
mixes.
The average drying shrinkage of each set of test specimens cast in the field from
concrete delivered to the site as measured at the 21 days' drying age shall not exceed
the values indicated in Tables 1A and 1B.
3-2.08. Test Reports. Five copies of each test report shall be prepared and distributed
by the testing laboratory to the Resident Project Representative (two copies),
ENGINEER, and CONTRACTOR, in accordance with the quality control section.
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. ENO9021-01
03300-15
CAST-IN-PLACE
CONCRETE
Concrete
1.
Classification .
Concrete Class
Al
A3
A2
A4
A5
Size,
C33
---
489
---
440
464
---
1/2")
B
536
---
514
---
460
489
514
Size
564
--
526
---
480
514
526
584
601
555
--
500
526
555
No.
67
(3/4")
03300-16
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. EN09021.01
CAST-IN-PLACE
CONCRETE
Concrete Class
Al
A2
A3
A4
A5
601
636
564
---
520
Fine
--
---
750
Aggregate,
555
564
--
--
(Sand)
2.
Field, 7 days;
3,375
3,000
3,000
3,000
3,000
3,000
3,000
Field, 28 days;
fic
Laboratory,
28
4,500
4,000
4,000
4,000
4,000
4,000
4,000
5,200
5,200
5,200
5,200
5,200
5,200
5,200
days; T'cr
3.
Maximum watercementitious
material ratio
0.42
0.45
0.45
0.45
0.45
0.48
0.45
4.
Maximum
coarse
aggregate size.
1/2
1-1/2
Sand
1-1/2
1-1/2
5.
ASTM
C33
Yes
Yes
maximum
nominal
aggregate
gradation
required.
Yes
Yes
size
"18-8" combined
--
Yes
Yes
---
Yes
----------
gradation
required.
6.
Slump
before
super-plasticizer
added
03300-17
CAST-IN-PLACE
CONCRETE
Concrete Class
Al
A2
A3
A4
A5
Slump
after
adding
superplasticizer
7.
Air entrainment, 6
percent,
(1
percent)
8.
25
25
9.
Testing limits
Sand equivalent,
min. percent
75
Chloride
ion, 0.10
25
22
30
25
25'
75
75
75
75
75
75
0.10
0.15
0.10
0.30
0.15
0.10
max. percent
C
0.036
0.036
0.048
--
---
0.048
0.048
Field
0.048
0.048
0.064
---
--
0.064
0.064
Coarse
Aggregate: Clay
and
shale
combined
particles shall not
exceed,
max.
percent
10
Temperature at
time of delivery,
max.
85
85
90
85
90
95
85
Temperature at 85
time
of
placement, max.
85
90
85
90
95
85
03300-18
CAST-IN-PLACE
CONCRETE
1.
Concrete
Classification
Concrete Class
D1
D2
D3
D4
D5
D6
D7
Size,
C33
aggregate
Size
No.
467
---
600*
480
--
--
---
380
(1-1/2")
B
460
620*
500
--
---
536
400
Size
480
640*
520
--
---
564
420
No.
67
(3/4")
500
660*
555
900
584
584
440
520
680*
---
900
601
601
460
2.
Field, 7 days;
3,000
3,000
3,000
3,000
1,500
4,000
4,000
4,000
4,000
2,000
2,250
3,000
*
2,000
B
Field,
28
days;
3,000
4,000
2,500
03300-19
CAST-IN-PLACE
CONCRETE
Concrete
Classification
Concrete Class
D1
D2
D3
D4
DS
D6
D7
Laboratory,
days; f'cr
3,200
5,200
4,800
4,400
5,200
5,200
2,000
28
2,800
3.
Maximum watercementitious
material ratio
0.65
0.45
0.50
0.40
0.45
0.403
0.45
0.75
4.
Maximum
coarse
aggregate
inches.
1"
11/2"
11/2"
1/2"
1/2"
1"
11/2"
Yes
Yes
Yes
Yes
Yes
--
--
size;
5.
ASTM
maximum
nominal
aggregate
gradation
required.
C33
Yes
Yes
size
"18-8" combined
--
--
aggregate
gradation
required.
6.
Slump
before
superplasticizer
added
Slump
after
adding
superplasticizer
10
7.
Air entrainment,
--
--
---
percent
percent)
(1
03300-20
CAST-IN-PLACE
CONCRETE
D1
D2
D3
D4
D5
D6
D7
8.
30
25
30
30
35
25
30
9.
Testing limits
Sand equivalent,
--
75
75
75
75
75
--
0.30
0.30
0.30
--
0.15
0.15
0.30
--
0.048
--
min.
B
Chloride
ion,
max. percent
C
--
0-048
Field
---
0.064
--
--
---
0.064
---
10
--
Coarse
Aggregate: Clay
and
shale
combined
particles shall not
exceed,
max.
percent
10
Temperature at 95
time of delivery
95
90
90
85
85
95
Temperature
time
placement
95
90
90
85
85
95
at 95
of
NOTES:
# "D2" (Underwater concrete) - Limit aggregate to 3/4" for reinforced concrete, up to
1-1/2" for unreinforced concrete.
*
"D2" (Underwater concrete).- Reduce cement content 100 lbs per cubic yard for
each aggregate size listed for 2,500 psi.
a
"D5" Wash water trough top edge water-cement ratio, 100 percent sand passing
No. 8 sieve.
03300-21
CAST-IN-PLACE
CONCRETE
Concrete Class
Al
A2
A3
A4
A5
Gradation
Deleterious materials
Fineness modulus
Alkali-aggregate reactivity
Sand equivalent
Gradation
Deleterious materials
Abrasion loss
Soundness test
Alkali-aggregate reactivity
---
Fine aggregate
Coarse aggregate
"18-8" requirement
--
---
---
---
---
---
--- _X
03300-22
RP-4 ODOR CONTROL
BACKUP BLOWER
PROJECT NO. EN09021.01
CAST-IN-PLACE
CONCRETE
Al
A2
A3
A4
A5
Slump
Water content
Water-cementitious
materials ratio
X
X
X
X
Specific gravity
aggregate
of
each
Ratio of fine
aggregates
to
total
Air content
---
Temperature
Unit weight
X
X
---
---
---
---
---
D2
D3
D4
D5
D6
D7_
Water-soluble
report
Shrinkage, report
Field
chloride
compression
ion,
test
CoceeIls
Aggregate reports
D1
03300-23
CAST-IN-PLACE
CONCRETE
D1
D2
D3
D4
D5
D6
D7
---
--
Gradation.
---
---
Deleterious materials
--
---
Fineness modulus
---
---
--
Alkali-aggregate reactivity
---
X.
Fine aggregate
Sand equivalent
B
Coarse aggregate
Source and type
Gradation
Deleterious materials
---
Abrasion loss
---
---
---
Soundness test
--
---
Alkali-aggregate reactivity
---
---
---
---
---
---
Admixtures,
---
---
X-
---
---
---
---
---
---
---
03300-24
CAST-IN-PLACE
CONCRETE
Concrete Class
D1
D2
D3
D4
D5
D6
D7
Slump
---
---
Water content
---
Water-cementitious
materials ratio
---
--
Specific gravity
aggregate
of
each
Ratio
to
total
---
-----
---
Air content
---
---
Temperature
Unit weight
---
---
--
--
--
---
--
---
---
---
---
of
fine
aggregates
Shrinkage
Field
Compression
Test
END OF SECTION
03300-25
CAST-IN-PLACE
CONCRETE
---