Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Like2 1
Previous
Next
The relays used in power system protection are of different types.
Among them differential relay is very commonly used relay for
protecting transformers and generators from localised
faults.Differential relays are very sensitive to the faults occurred
within the zone of protection but they are least sensitive to the
faults that occur outside the protected zone. Most of the relays
operate when any quantity exceeds beyond a predetermined value
for example over current relay operates when current through it
exceeds predetermined value. But the principle of differential relay
is somewhat different. It operates depending upon the difference
between two or more similar electrical quantities.
these CTs opposes each other. From the circuit is clear that only if
any nonzero difference is created between this to secondary
currents, then only this differential current will flow through the
operating coil of the relay. If this difference is more than the peak
up value of the relay, it will operate to open the circuit breakers to
isolate the protected equipment from the system. The relaying
element used in differential relay is attracted armature type
instantaneously relay since differential scheme is only adapted for
clearing the fault inside the protected equipment in other words
differential relay should clear only internal fault of the equipment
hence the protected equipment should be isolated as soon as any
fault occurred inside the equipment itself. They need not be any
time delay for coordination with other relays in the system.
This simple thumb rule is that the current transformers on any star
winding should be connected in delta and the current transformers
on any delta winding should be connected in star. This is so done to
eliminate zero sequence current in the relay circuit.
If the CTs are connected in star, the CT ratio will be In/1 or 5 A CTs
to be connected in delta, the CT ratio will be In/0.5775 or 50.5775
A
approximately 90o. In this way fluxes acting on the disk are in phase
and hence no torque is exerted in the relay disc.
Differential Protection of
Transformer | Differential Relays
Like6 1
Previous
Next
Generally Differential protection is provided in the electrical
power transformer rated more than 5MVA. The Differential
Protection of Transformer has many advantages over other
schemes of protection.
1.
The faults occur in the transformer inside the insulating oil can
be detected by Buchholz relay. But if any fault occurs in the
transformer but not in oil then it can not be detected by Buchholz
relay. Any flash over at the bushings are not adequately covered
by Buchholz relay. Differential relays can detect such type of
faults. Moreover Buchholz relay is provided in transformer for
detecting any internal fault in the transformer but Differential
Protection scheme detects the same in more faster way.
2.
The differential relays normally response to those faults which
occur in side the differential protection zone of transformer.
Previous
Next
During study of electrical protective relays, some special terms are
frequently used. For proper understanding, the functions of different
protective relays, the definition of such terms must be understood
properly. Such terms are,
1.
Pick up current.
2.
Current setting.
3.
Plug setting multiplier (PSM).
4.
Time setting multiplier (TSM).
force, in the coil also changes. That means if active turns of the
relay coil is reduced, then proportionately more current is required
to produce desired relay actuating force. Similarly if active turns of
the relay coil is increased, then proportionately reduced current is
required to produce same desired deflecting force. Practically same
model relays may be used in different systems. As per these
systems requirement the pick up current of relay is adjusted. This is
known as current setting of relay. This is achieved by providing
required number of tapping in the coil. These taps are brought out
to a plug bridge. The number of active turns in the coil can be
changed by inserting plug in different points in the bridge. The
current setting of relay is expressed in percentage ratio of relay
pick up current to rated secondary current of CT.
That means,
For
example, suppose, you want that, an over current relay should
operate when the system current just crosses 125% of rated
current. If the relay is rated with 1 A, the normal pick up current of
the relay is 1 A and it should be equal to secondary rated current of
current transformer connected to the relay. Then, the relay will be
operated when the current of CT secondary becomes more than or
equal 1.25 A. As per definition,
The current setting is
sometimes referred as current plug setting. The current setting of
over current relay is generally ranged from 50 % to 200 %, in steps
of 25 %. For earth fault relay it is from 10% to 70% in steps of
10%.
Suppose we have
calculate PSM for the specified faulty current level. For that, we
have to first divide primary faulty current by CT ratio to get relay
faulty current. Say the faulty current level is 1500 A, in the CT
primary, hence secondary equivalent of faulty current is 1500/
(100/1) = 15 A
Step-4
Now, after calculating PSM, we have to find out the total time of
operation of the relay from Time / PSM curve. From the curve, say
we found the time of operation of relay is 3 second for PSM = 10.
Step-5 Finally that operating time of relay would be multiplied with
time setting multiplier, in order to get actual time of operation of
relay. Hence say time setting of the relay is 0.1. Therefore actual
time of operation of the relay for PSM 10, is 3 0.1 = 0.3 sec or
300 ms.
Distance Relay or Impedance Relay Working Principle Types
Like1 1
Previous
Next
There is one type of relay which functions depending upon the
distance of fault in the line. More specifically, the relay operates
depending upon the impedance between the point of fault and the
point where relay is installed. These relays are known as distance
relay or impedance relay.
Working Principle of Distance or Impedance Relay
relay,
Next
Restricted Earth Fault Protection of Transformer
An external fault in the star side will result in current flowing in the
line current transformer of the affected phase and at the same time
a balancing current flows in the neutral current transformer, hence
the resultant current in the relay is therefore zero. So this REF relay
will not be actuated for external earth fault. But during internal fault
the neutral current transformer only carries the unbalance fault
current and operation of Restricted Earth Fault Relay takes place.
This scheme of restricted earth fault protection is very sensitive
for internal earth fault of electrical power transformer. The
protection scheme is comparatively cheaper than differential
power transformer.
Previous
Next
Any internal fault inside the stator winding is cleared by mainly
differential protection scheme of the generator or
alternator.The differential protection is provided in the generator by
using longitudinal differential relay.
Generally
instantaneous attracted armature type relays are used for this
purpose because all they have high speed operation and also they
are free from being affected by any AC transient of the power
circuit.
There are two sets of current transformers one CT is connected to
the line side of the generator and other is connected to the neutral
side of the generator in each phase. It is needless to say that the
characteristics of all current transformers installed against each
phase must be matched. If there is any major mismatched in the
current transformers characteristics of both sides of the generator,
there may be high chance of malfunctioning of differential relay
during the fault external to the stator winding and also may be
during normal operating conditions of the generator.
To ensure that the relay does not operate for the faults external to
the operated zone of the protection scheme, a stabilizing resistor is
fitted in series with the relay operating oil. It also ensures that if
one set of CT has been saturated, there will be no possibility of
malfunctioning of the differential relay.
It is always
preferable to use dedicated current transformers for differential
protection purpose because common current transformers may
cause unequal secondary loading for other functionalities imposed
on them. It is also always preferable to use all current transformers
for differential protection of generators or alternators should be
of same characteristics. But practically there may be some
difference in characteristics of the current transformers installed at
line side to those installed in neutral side of the generator. These
mismatches cause spill current to flow through the relay operating
coil. To avoid the effect of spill current, percentage biasing is
introduced in differential relay.
The percentage
biased differential relay comprises two restraint coils and one
operating coil per phase. In the relay, the torque produced by
operating coil tends to close the relay contacts for instantaneous
tripping of circuit breakers but at the same time the torque
Inter-winding faults //
Similar to bus protections, transformers are protected by differential relays .
Inter-winding faults (short circuits) and ground faults within power transformers can
be detected by this protection scheme.
Failure to detect these faults and quickly isolate the transformer may cause serious damage
to the device.
1. A transformer has a turns ratio so the current in is not really equal to the current
out. The current transformers are not likely exactly matched to the transformer turns
ratio so there will always be an unbalance currentin the operating coil of a transformer
differential relay.
2. Transformers require magnetising current. There will be a small current flow in the
transformer primary even if the secondary is open circuited.
Figure 1
Transformer Differential Protection
Referring again to Figure 1, you will notice that when the transformer is first
energized, there will not be any current flowing in CT2. The CT1 secondary
current I1s flows through both the restraint and operate coils and prevents operation
unless the current is very high.
The restraint coils also prevent relay operation due to tap-changes, where the ratio
of transformer input to output current can continuously vary.
One other item included in transformer differential relays, but not shown in the diagram, is
second harmonic restraint.
When transformers are first energized there is over-fluxing (saturation) of the core and
the large inrush energizing current has a distorted waveform. This waveform is
described as having high second harmonic content.
The transformer differential relays make use of this known fact and add in extra
restraint when it detects this second harmonic. This extra feature prevents the
transformer from tripping due to magnetizing current when being energized, but does
not add any time delay.
Because the differential relay will not operate with load current or faults outside the
protected zones (through faults), it can be set to operate at a low value of current
thereby giving rapid operation when a fault occurs. There is no need to time delay the
operation of the relay and therefore a fast acting type of relay can be used.
Resource: Science and Reactor Fundamentals Electrical CNSC Technical
Training Group
Differential relays take a variety of forms, depending on the equipment they protect.
The definition of such a relay is one that operates when the vector difference of two
or more similar electrical quantities exceeds a predetermined amount. It will be seen
later that almost any type of relay, when connected in a certain way, can be made to
operate as a differential relay. In other words, it is not so much the relay
construction as the way the relay is connected in a circuit that makes it a differential
relay.
Most differential-relay applications are of the current-differential type. The simplest
example of such an arrangement is shown in Fig. 14. The dashed portion of the circuit
of Fig. 14 represents the system element that is protected by the differential relay. This
system element might be a length of circuit, a winding of a generator, a portion of a
bus, etc.
A current transformer (CT) is shown in each connection to the system element. The
secondaries of the CTs are interconnected, and the coil of an overcurrent relay is
connected across the CT secondary circuit.
This relay could be any of the a-c types that we have considered.
Now, suppose that current flows through the primary circuit either to a load or to a
short circuit located at X. The conditions will be as in Fig. 15. If the two current
transformers have the same ratio, and are properly connected, their secondary
currents will merely circulate between the two CTs as shown by the arrows, and no
current will flow through the differential relay.
Fig. 15.
Conditions for an external load or fault
But, should a short circuit develop anywhere between the two CTs, the conditions of
Fig. 16 will then exist. If current flows to the short circuit from both sides as shown,
the sum of the CT secondary currents will flow through the differential relay. It is not
necessary that short-circuit current flow to the fault from both sides to cause
secondary current to flow through the differential relay. A flow on one side only, or
even some current flowing out of one side while a larger current enters the other side,
will cause a differential current.
In other words, the differential-relay current will be proportional to the vector difference
between the currents entering and leaving the protected circuit; and, if the differential
current exceeds the relays pickup value, the relay will operate.
It is only necessary, as before, that all the CTs have the same ratio, and that they be
connected so that the relay receives no current when the total current leaving the
circuit element is equal vectorially to the total current entering the circuit element.
The principle can still be applied where a power transformer is involved, but, in this
case, the ratios and connections of the CTs on opposite sides of the power
transformer must be such as to compensate for the magnitude and phase-angle
change between the power transformer currents on either side. This subject will be
treated in detail when we consider the subject of power-transformer protection.
A most extensively used form of differential relay is the percentage-differential type.
This is essentially the same as the overcurrent type of current-balance relay that was
described earlier, but it is connected in a differential circuit, as shown in Fig. 18.
The differential current required to operate this relay is a variable quantity, owing to
the effect of the restraining coil. The differential current in the operating coil is
proportional to I1 I2, and the equivalent current in the restraining coil is proportional
to (I1 + I2)/2, since the operating coil is connected to the midpoint of the restraining
coil; in other words, if we let N be the number of turns on the restraining coil, the total
ampere-turns are I1N/2 + I2N/2, which is the same as if (I1 + I2)/2 were to flow through
the whole coil.
The operating characteristic of such a relay is shown in Fig. 19. Thus, except for the
slight effect of the control spring at low currents, the ratio of the differential operating
current to the average restraining current is a fixed percentage, which explains the
name of this relay. The term through current is often used to designate I2, which is
the portion of the total current that flows through the circuit from one end to the other,
and the operating characteristics may be plotted using I2 instead of (I1 + I2)/2, to
conform with the ASA definition for a percentage differential relay.
The advantage of this relay is that it is less likely to operate incorrectly than a
differentially connected overcurrent relay when a short circuit occurs external to the
protected zone.
Current transformers of the types normally used do not transform their primary
currents so accurately under transient conditions as for a short time after a short
circuit occurs.
This is particularly true when the shortcircuit current is offset. Under such conditions,
supposedly identical current transformers may not have identical secondary currents,
owing to slight differences in magnetic properties or to their having different amounts
of residual magnetism, and the difference current may be greater, the larger the
magnitude of short-circuit current. Even if the short-circuit current to an external fault
is not offset, the CT secondary currents may differ owing to differences in the CT types
or loadings, particularly in power-transformer protection. Since the percentagedifferential relay has a rising pickup characteristic as the magnitude of through current
increases, the relay is restrained against operating improperly.
Figure 20 shows the comparison of a simple overcurrent relay with a percentagedifferential relay under such conditions. An overcurrent relay having the same
minimum pickup as a percentage-differential relay would operate undesirably when
the differential current barely exceeded the value X, whereas there would be no
tendency for the percentage-differential relay to operate.
Transformer differential
protection (ANSI 87T)
P OST ED SE P 5 20 12 BY E DVA RD I N PR OT E CT IO N , T RA N SF OR ME RS W IT H 11 C OMM EN TS
The transformer inrush currents. The operating speed required means that
a time delay longer than the duration of this current cannot be used (several tenths
of a second);
2.
The action of the on-load tap changer causes a differential current.
The characteristics of transformer differential protection are related to
the transformer specifications:
1.
Transformation ratio between the current entering Iin and the current
leaving Iout ;
2.
Primary and secondary coupling method;
3.
Inrush current;
4.
Permanent magnetizing current.
The block diagram is shown in Figure 1 below.
Figure 2
Transformer differential protection tripping curve
Transformer switching causes a very high transient current (from 8 to 15 In), which
only flows through the primary winding and lasts several tenths of a second.
It is thus detected by the protection as a differential current and it lasts far longer than
the protection operating time (30 ms). Detection based only on the difference between
the transformer primary and secondary currents would cause the protection to be
activated. Therefore, the protection must be able to distinguish between a differential
current due to a fault and a differential inrush current.
Experience has shown that the inrush current wave contains at least 20% of second
harmonic components (current at a frequency of 100 Hz), while this percentage is
never higher than 5% upon occurrence of an overcurrent due to a fault inside the
transformer.
The protection must therefore simply be locked when the percentage of second
harmonic component in relation to the fundamental harmonic component (current at
50 Hz) is higher than 15%, i.e. I2/I1 > 15%.
Introduction
Differential protection is a unit-type protection for a specified zone or piece of
equipment. It is based on the fact that it is only in the case of faults internal to the
zone that the differential current (difference between input and output currents) will
be high.
However, the differential current can sometimes be substantial even without an
internal fault.
This is due to certain characteristics of current transformers (different saturation levels,
nonlinearities) measuring the input and output currents, and of the power transformer being
protected.
With the exception of the inrush and overexcitation currents, most of the other
problems, can be solved by means of the percent differential relay, which adds to the
normal differential relay two restraining coils fed by the zone-through current, by
proper choice of the resulting percent differential characteristic, and by proper
connection of the current transformers on each side of the power transformer.
Percentage restraint differential protective relays have been in service for many
years. Figure 1 shows a typical differential relay connection diagram. Differential
elements compare an operating current with a restraining current.
The operating current (also called differential current), Id, can be obtained from
the phasor sum of the currents entering the protected element:
Figure 1 Simple
diagram connection for differential power transformer protection
Id is proportional to the fault current for internal faults and approaches zero for any
other operating (ideal) conditions.
There are different alternatives for obtaining the restraining current, IRT. The most
common ones include the following:
Title:
Overcurrent Protection of
Transformer (NEC 450.3)
P OST ED OC T 8 20 12 BY J IG UPA RM AR IN T RA NS FO RM ER S WI TH 22 CO MME NT S
Content
Introduction
Overcurrent protection of transformers >600V (NEC450.3A)
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
Introduction
The overcurrent protection required for transformers is consider for Protection of
Transformer only. Such overcurrent protection will not necessarily protect the primary
or secondary conductors or equipment connected on the secondary side of the
transformer.
When voltage is switched on to energize a transformer, the transformer core normally
saturates.
This results in a large inrush current which is greatest during the first half cycle
(approximately 0.01 second) and becomes progressively less severe over the next
several cycles (approximately 1 second) until the transformer reaches its normal
magnetizing current. To accommodate this inrush current, fuses are often selected
which have time-current withstand values of at least 12 times transformer primary
rated current for 0.1 second and 25 times for 0.01 second. Some small dry-type
transformers may have substantially greater inrush currents.
To avoid using over sized conductors, overcurrent devices should be selected at
about 110 to 125 percent of the transformer full-load current rating. And when using
such smaller overcurrent protection, devices should be of the time-delay type (on the
primary side) to compensate for inrush currents which reach 8 to 10 times the full-load
primary current of the transformer for about 0.1 s when energized initially.
Protection of secondary conductors has to be provided completely separately
from any primary-side protection.
A supervised location is a location where conditions of maintenance and supervision
ensure that only qualified persons will monitor and service the transformer
installation. Overcurrent protection for a transformer on the primary side is typically a
circuit breaker. In some instances where there is not a high voltage panel, there is a
fused disconnect instead.
It is important to note that the overcurrent device on the primary side must be
sized based on the transformer KVA rating and not sized based on the
secondary load to the transformer.
Go to Content
Unsupervised
Location of Transformer (Impedance <6%)
Rating of Pri. Circuit Breaker at Point A= 600% of Pri. Full Load Current or Next
higher Standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 125% of Sec. Full Load
Current or Next higher Standard size.
Rating of Sec. Fuse at Point B= 250% of Sec. Full Load Current or Next higher
Standard size. or
Rating of Sec. Circuit Breaker at Point B= 300% of Sec. Full Load Current.
Example: 750KVA, 11KV/415V 3Phase Transformer having Impedance of
Transformer 5%
Go to Content
Unsupervised
Location of Transformer (Impedance 6% to 10%)
Rating of Pri. Circuit Breaker at Point A= 400% of Primary Full Load Current or
Next higher Standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 125% of Sec. Full Load
Current or Next higher Standard size.
Rating of Sec. Fuse at Point B= 225% of Sec. Full Load Current or Next higher
Standard size.
Rating of Sec. Circuit Breaker at Point B= 250% of Sec. Full Load Current or
Next higher Standard size.
Example: 10MVA, 66KV/11KV 3Phase Transformer, Impedance of Transformer is
8%
Rating of Pri. Fuse = 3X87A = 262A, so next standard size of Fuse = 300A.
Go to Content
Rating of Pri. Circuit Breaker at Point A= 300% of Primary Full Load Current or
Next higher Standard size.
Go to Content
Supervised Location of
Transformer (Impedance Up to 6%)
Rating of Pri. Circuit Breaker at Point A= 600% of Pri. full load current or next
lower standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 250% of Sec. Full Load
Current or Next higher Standard size.
Rating of Sec. Fuse at Point B= 250% of Sec. Full Load Current or Next Lower
Standard size.
Rating of Sec. Circuit Breaker at Point B= 300% of Sec. Full Load Current or
Next Lower Standard size.
Example: 750KVA, 11KV/415V 3Phase Transformer having Impedance of
Transformer 5%
Rating of Primary Fuse = 3X39A = 118A, so next lower standard size of fuse =
110A.
Supervised Location of
Transformer (Impedance 6% to 10%)
Rating of Pri. Circuit Breaker at Point A= 400% of Pri. full load current or next
lower standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 250% of Sec. full load current
or next higher standard size.
Rating of Sec. Fuse at Point B= 225% of Sec. full load current or next lower
standard size.
Rating of Sec. Circuit Breaker at Point B= 250% of Sec. full load current or next
lower standard size.
Example: 750KVA, 11KV/415V 3Phase Transformer having Impedance of
Transformer 8%
Rating of Primary Fuse = 3X39A = 118A, so next lower standard size of Fuse =
110A.
Here we see two notable conditions while we select Fuse / Circuit Breaker in
Supervised Location and Unsupervised Location.
First notable condition is Primary Overcurrent Protection. In unsupervised location
fuse in primary side is 300% of primary current or Next Higher Standard size and in
supervised location is 300% of primary current or Next Lower Standard size. Here
primary overcurrent protection is same in both conditions (300%), but selecting size of
Fuse/Circuit Breaker is different.
Lets us Check with the Example for 750KVA, 11KV/415V 3Phase Transformer.
Any
location
Supervised
locations
only
Secondary Protection
More than 600V
C. B.
Fuse
Rating
Less than
6%
600%
(NH)
300%
(NH)
6% To 10%
400%
(NH)
300%
(NH)
Any
300%
(NH)
250%
(NH)
Not
required
Not
required
Not
required
Less than
6%
600%
300%
300%
250%
250%
6% To 10%
400%
300%
250%
225%
250%
C. B.
Fuse
Rating
Less than
600V
C.B or
Fuse
Rating of Primary Fuse = 1.25X18A= 23A, so next higher standard size of Fuse
= 25A.
Go to Content
Primary and
Secondary side Protection of Transformer
Rating of Primary Fuse = 1.67X8A= 13A, So Next Lower Standard Size of Fuse
=9A.
Rating of Pri. Fuse / C.B at Point A= 125% of Pri. Full Load Current or Higher
Standard size.
Primary Protection
More than 2A to 9A Less than
9A
2A
Secondary Protection
More than
9A
Less than
9A
Primary only
protection
125%
(NH)
167%
300%
Not required
Not
required
Primary and
secondary
protection
250%
250%
250%
125%(NH)
167%
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
Recloser
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
ANSI
37 Phase undercurrent
48/51LR/14 Locked rotor / excessive starting time
66 Starts per hour
50V/51V Voltage-restrained overcurrent
26/63 Thermostat, Buchholz, gas, pressure, temperature detection
38/49T Temperature monitoring by RTD
ANSI index
Recloser
ANSI 79
Automation device used to limit down time after tripping due to transient or
semipermanent faults on overhead lines. The recloser orders automatic reclosing of
the breaking device after the time delay required to restore the insulation has elapsed.
Recloser operation is easy to adapt for different operating modes by parameter
setting.
ANSI index
ANSI index
against generators running like motors when the generators consume active
power
against motors running like generators when the motors supply active power
reactive overpower protection for motors which consume more reactive power with
field loss
reverse reactive overpower protection for generators which consume reactive power
with field loss.
ANSI index
excessive motor starting time due to overloads (e.g. conveyor) or insufficient supply
voltage. The reacceleration of a motor that is not shut down, indicated by a logic input,
may be considered as starting.
directly upon starting, before the detection of excessive starting time, with
detection of locked rotor by a zero speed detector connected to a logic input, or
by the underspeed function.
too frequent starts: motor energizing is inhibited when the maximum allowable number
of starts is reached, after counting of:
consecutive motor hot or cold starts (reacceleration of a motor that is not shut
down, indicated by a logic input, may be counted as a start)
starts too close together in time: motor re-energizing after a shutdown is only allowed
after an adjustable waiting time.
ANSI index
ANSI 27 UNDERVOLTAGE
Protection of motors against voltage sags or detection of abnormally low network
voltage to trigger automatic load shedding or source transfer. Works with phase-tophase voltage.
ANSI 59 OVERVOLTAGE
Detection of abnormally high network voltage or checking for sufficient voltage to
enable source transfer. Works with phase-to-phase or phase-to-neutral voltage, each
voltage being monitored separately.
Load shedding The rate of change of frequency protection function is used for load
shedding in combination with the underfrequency protection to:
Example
Decide Size of circuit breaker (overcurrent protection device) is required on the primary side
to protect a 75kva 440v-230v 3 transformer.
Example
Decide size of circuit breaker (overcurrent protection device) is required on
the secondary side to protect a 75kva 440v-230v 3 transformer. We have Calculate
the secondary overcurrent protection based on the size of the transformer, not the
total connected load.
75kva x 1,000 = 75,000va
75,000va / (230V x 3) = 188.27 amps. (Note: 230V 3 is calculated)
The current (amps) is more than 9 amps so use 125% rating.
188.27 amps x 1.25 = 235.34 amps
Therefore: Use 300amp 3-pole circuit breaker (per NEC 240.6).
Previous
Next
Over Current and Earth Fault Protection of Transformer
relay 20 to 80 %.
Another range of setting on earth fault relay is also available and
may be selected where the earth fault current is restricted due to
insertion of impedance in the neutral grounding. In the case of
transformer winding with neutral earthed, unrestricted earth fault
protection is obtained by connecting an ordinary earth fault relay
across a neutral current transformer. The unrestricted over current
and earth fault relays should have proper time lag to co-ordinate
with the protective relays of other circuit to avoid indiscriminate
tripping.