Sei sulla pagina 1di 15

KNPC M20 Substation Project

HVAC Equipment BOQ


Date:01st Dec 2015
S. No.

Description of item

Unit

Unit Price

Quantity

(A) General Items

Installation and Procurement of Twin Screw Compresser Chilled Water Type Chiller of 238 TR
(each) factory assembled and tested outdoor air cooled liquid chillers consisting of
compressors, condenser, evaporator, thermal expansion valve, subcooler, oil separator,
1 lubrication system refrigeration accessories, and control panel, complete with factory-filled
Nos.
Refrigerant (R134-a) & field installed refrigerant piping with all other accessories and fittings
required to complete the system as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 12.2,
Datasheet No.035.85-60-2.44-0003-E and DWG No. 035.085-60-2.44-0016-B

3
(2W+1S)

Installation and Procurement of Centrifugal -Singe stage Horizontal Split casing constant
speed continuous duty Pump of 585 GPM @ 15m Head (each) with inertia base, spring
isolators, having class F insulated TEFC motors, water filter, thermal insulation and aluminium
2 protection, main disconnect switch, safe 24V control circuit, pump control valves with all other Nos.
accessories and fittings required to complete the system as per HVAC Spec. 035.085-60.2.440001-E Cl. 12.3, Datasheet No.035.085-60-2.44-0004-E and DWG No. 035.085-60-2.44-0016B.

3
(2W+1S)

Installation and Procurement of Air Separator with valves and all other Accessories as per
No.
DWG No. 035.085-60-2.44-0016-B.

Installation and Procurement of High Pressure Membrane type /Open type Expansion tank of
4 SS 304 with valves and other accessories as per HVAC Spec 035.085-60.2.44-0001-E Cl.
No.
14.8 and DWG No. 035.085-60-2.44-0016-B.

Installation and Procurement of Chemical dosing pot with valves and other accessories as
No.
per DWG No. 035.085-60-2.44-0016-B

Total Quantity
Price

Remarks

Installation and Procurement of Gate Valve with matching flange as per HVAC Spec.
035.085-60.2.44-0001-E Cl.14.5 and DWG No. 035.085-60-2.44-0016-B

Nos.

Drain valve with matching flange as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 14.5 and
DWG No. 035.085-60-2.44-0016-B

Nos.

Installation and Procurement of Butterfly valve with matching flange as per HVAC Spec.
035.085-60.2.44-0001-E Cl.14.5.2 and DWG No. 035.085-60-2.44-0016-B

Nos.

30

Installation and Procurement of Motorized Butterfly valve with matching flange as per
HVAC Spec. 035.085-60.2.44-0001-E Cl.14.5.2 and DWG No. 035.085-60-2.44-0016-B

Nos.

10

Installation and Procurement of Check Valve with matching flange as per HVAC Spec.
035.085-60.2.44-0001-E Cl.14.5 and DWG No. 035.085-60-2.44-0016-B

Nos.

11

Installation and Procurement of Globe Valve with matching flange as per HVAC Spec.
035.085-60.2.44-0001-E Cl.14.5.3 and DWG No. 035.085-60-2.44-0016-B

Nos.

13

12

Installation and Procurement of Ball valve with matching flange as per HVAC Spec.
035.085-60.2.44-0001-E Cl.14.5 and DWG No. 035.085-60-2.44-0016-B

Nos.

13

Installation and Procurement of 3 Way Modulating Control Valve with matching flange as
per HVAC Spec. 035.085-60.2.44-0001-E Cl.14.5.1 and DWG No. 035.085-60-2.44-0016-B

Nos.

14

Installation and Procurement of Y-strainer with matching flanges as per HVAC Spec.
035.085-60.2.44-0001-E Cl.14.6 and DWG No. 035.085-60-2.44-0016-B

Nos.

10

Installation and Procurement of Pressure gauge of 4 1/2" dial with brass cocks on their
15 inlet and mounting accessories as per HVAC Scope of work 035.085-60-2.44-0028-E Cl.
7.3(2) and DWG No. 035.085-60-2.44-0016-B

Nos.

20

Nos.

12

16

Installation and Procurement of Insertion type Temperature Gauge with a vertical clearly
readable scale of at least 6 inches height, or a round scale of at least 4 1/2" diameter. Range
20-140F with mounting accessories as per HVAC Scope of work 035.085-60-2.44-0028-E
Cl. 7.3(1) and DWG No. 035.085-60-2.44-0016-B

17

Installation and Procurement of Circuit setter / Adjustable flow limiting Valve with
matching flange as per DWG No. 035.085-60-2.44-0016-B

Nos.

18

Installation and Procurement of Flow meter with mounting accessories as per DWG No.
035.085-60-2.44-0016-B

Nos.

19

Installation and Procurement of Pressure Safety valve with matching flange as per DWG
No. 035.085-60-2.44-0016-B

No.

20

Installation and Procurement of Non-Return Valve with matching flange as per HVAC Spec.
Nos.
035.085-60.2.44-0001-E Cl.14.5.4 and DWG No. 035.085-60-2.44-0016-B

21

Installation and Procurement of Blast resistance Sleeve as per DWG No. 035.085-602.44-0016-B

Nos.

22

Installation and Procurement of Pipe with flanges, nuts, bolts and gasket as per HVAC
Spec. 035.085-60.2.44-0001-E Cl. 14 and DWG No. 035.085-60-2.44-0016-B

Lot

23

Installation and Procurement of Pipe Flexible connector as per HVAC Spec. 035.08560.2.44-0001-E Cl. 14 and DWG No. 035.085-60-2.44-0016-B

Lot

24

Installation and Procurement of Pipe insulation as per HVAC Spec. 035.085-60.2.44-0001Lot


E Cl. 15

25

Installation and Procurement of HVAC Duct as per HVAC Spec. 035.085-60.2.44-0001-E


Cl. 16 and DWG No. 035.085-60-2.44-0021-B and 035.085-60-2.49-0001-B

Lot

26

Installation and Procurement of Duct flexible connector as per DWG No. 035.085-602.44-0021-B and 035.085-60-2.49-0001-B

Lot

27

Installation and Procurement of Duct Insulation (polyurethane) as per HVAC Spec.


035.085-60.2.44-0001-E

Lot

(B) Substation Building

Installation and Procurement of Floor Mounted completely factory assembled, wired, charged,
tested Air Handling Unit of 60000 CFM (each) with double skin aluminum construction,
insulation in panels & Thermal break between inner & outer surfaces and fitted with access
1 doors or removable panels, mixing box, metallic cleanable pre-filter, bag-filter, Cooling coil, 2 Nos.
Nos. 37 kw centrifugal fan with back draft damper and finned tubular electric heater with all
other accessories as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 12.1, Datasheet
No.035.085-60-2.44-0002-E and DWG No. 035.085-60-2.49-0001-B.

4
(2W+2S)

Installation and Procurement of Deep Bed Scrubber with pre-filter, chemical media bed,
final filter, 3 Magnetic filter gauges, scrubber housing of SS316, base frame, lifting lugs,
permanent stainless steel name plate showing the scrubber type, order number and serial
2
Nos.
number and 2 Nos. 5.5 kw centrifugal fan with back draft damper as per HVAC Spec. 035.08560.2.44-0001-E Cl. 12.6, Datasheet No.035.085-60-2.44-0002-E and DWG No. 035.085-602.49-0001-B

Installation and Procurement of Duct mounted Electrical Humidifier with immersed electrode,
stainless steel distributer and steam dispersion system complete with vapor hose, condensate
Nos.
drains tubes and all other accessories as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 12.1(g)
and DWG No. 035.085-60-2.49-0001-B.

Installation and Procurement of DWDI type, Centrifugal with Backward Inclined Bladed
4 Impeller Bleed Fan of SS-304 with back draft dampers of 0.25 KW as per HVAC Spec.
035.085-60.2.44-0001-E Cl. 19.2 and DWG No. 035.085-60-2.49-0001-B

Nos.

Installation and Procurement of Explosion Proof Fan with back draft damper of 0.4 KW as
Nos.
per DWG No. 035.085-60-2.49-0001-B

Installation and Procurement of Exhaust Purging fan with back draft damper of 3.5 KW as
Nos.
per HVAC Spec. 035.085-60.2.44-0001-E Cl. 1.5 and DWG No. 035.085-60-2.49-0001-B

Installation and Procurement of Sound Attenuator with self-noise generation below NC 30


Nos.
as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 18.2 and DWG No. 035.085-60-2.49-0001-B

Installation and Procurement of Factory-fabricated, & assembled Inertia Sand Separator


consisting of housing, a bleed air manifold, cell bodies, blade packs, bullnoses, and inlet
screen with a top coat of enamel paint as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 19.1
and DWG No. 035.085-60-2.49-0001-B

No.

Installation and Procurement of Blast Protection valve of type F(or Equiv) of Temet/Luwa
9 make as per HVAC Spec. 035.085-60.2.44-0001-E Cl. 1.5(q) and DWG No. 035.085-60-2.49- Nos.
0001-B

10

Installation and Procurement of Motorized Damper ON/OFF Type as per HVAC Spec.
035.085-60.2.44-0001-E Cl. 16.8.2 and DWG No. 035.085-60-2.49-0001-B

Nos.

22

11

Installation and Procurement of Motorized Damper Modulating type as per HVAC Spec.
035.085-60.2.44-0001-E Cl. 16.8.2 and DWG No. 035.085-60-2.49-0001-B

Nos.

12

Installation and Procurement of Fire Smoke Damper as per HVAC Spec. 035.085-60.2.44Nos.
0001-E Cl. 16.8.4 and DWG No. 035.085-60-2.49-0001-B

29

13

Installation and Procurement of Volume control Damper as per HVAC Spec. 035.08560.2.44-0001-E Cl. 16.8.1 and DWG No. 035.085-60-2.49-0001-B

25

14

Installation and Procurement of Exhaust Air Louver for Battery room exhaust as per DWG
No.
No. 035.085-60-2.49-0001-B

15

Installation and Procurement of Differential Pressure Switch as per HVAC Spec. 035.085Nos.
60.2.44-0001-E Cl. 21.3 and DWG No. 035.085-60-2.49-0001-B

18

16

Installation and Procurement of Air Pressure Switch as per HVAC Spec. 035.085-60.2.44Nos.
0001-E Cl. 21.3 and DWG No. 035.085-60-2.49-0001-B

(C) Capacitor Building

Nos.

Installation and Procurement of Roof Mounted completely factory assembled, wired, charged,
tested Air Handling Unit of 10000 CFM (each) with double skin aluminum construction,
insulation in panels, Thermal break between inner & outer surfaces, fitted with access doors or
1 removable panels, mixing box, metallic cleanable pre-filter, bag-filter, Cooling coil, 2 Nos. 10
Nos.
kw DIDW airfoil backward curved, multi-vane impeller centrifugal belt driven using TEFC (IP55) with back draft damper and finned tubular electric heater with all other accessories as per
HVAC Spec. 035.85-60-2.44-0024-E Cl. 12.1 and DWG No. 035.085-60-2.44-0021-B

2
(both
working)

Installation and Procurement of Deep Bed Scrubber with pre-filter, chemical media bed,
final filter, 3 Magnetic filter gauges, scrubber housing of SS316, base frame, lifting lugs,
2 permanent stainless steel name plate showing the scrubber type, order number and serial
No.
number and 2 Nos. 1 kw centrifugal fan with back draft damper as per HVAC Spec. 035.85-602.44-0024-E Cl. 13 and DWG No. 035.085-60-2.44-0021-B

Installation and Procurement of DWDI type, Centrifugal with Backward Inclined Bladed
3 Impeller Bleed Fan of SS-304 with back draft dampers 0.1 KW as per HVAC Spec. 035.85-60- Nos.
2.44-0024-E Cl. 20.2 and DWG No. 035.085-60-2.44-0021-B

Installation and Procurement of Exhaust Purging fan with back draft damper 0.5 KW as
per HVAC Spec. 035.85-60-2.44-0024-E Cl. 1.5 (n) and DWG No. 035.085-60-2.44-0021-B

Installation and Procurement of Sound Attenuator with self-noise generation below NC 30


Nos.
as per HVAC Spec. 035.85-60-2.44-0024-E Cl. 19.2 and DWG No. 035.085-60-2.44-0021-B

Installation and Procurement of Factory-fabricated, & assembled Inertia Sand Separator


consisting of housing, a bleed air manifold, cell bodies, blade packs, bullnoses, and inlet
screen with a top coat of enamel paint as per HVAC Spec. 035.85-60-2.44-0024-E Cl. 20.1
and DWG No. 035.085-60-2.44-0021-B

No.

Installation and Procurement of Motorized Damper ON/OFF Type as per HVAC Spec.
035.85-60-2.44-0024-E Cl. 17.8.2 and DWG No. 035.085-60-2.44-0021-B

Nos.

11

Installation and Procurement of Motorized Damper Modulating type as per HVAC Spec.
035.85-60-2.44-0024-E Cl. 17.8.2 and DWG No. 035.085-60-2.44-0021-B

Nos.

Installation and Procurement of Fire Smoke Damper as per HVAC Spec. 035.85-60-2.440024-E Cl. 17.8.4 and DWG No. 035.085-60-2.44-0021-B

Nos.

10

10

Volume control Damper as per HVAC Spec. 035.85-60-2.44-0024-E Cl. 17.8.1 and DWG No.
Nos.
035.085-60-2.44-0021-B

11

Installation and Procurement of Differential Pressure Switch as per HVAC Spec. 035.85Nos.
60-2.44-0024-E Cl. 21.3 and DWG No. 035.085-60-2.44-0021-B

No.

12

Installation and Procurement of Air Pressure Switch as per HVAC Spec. 035.85-60-2.440024-E Cl. 21.3 and DWG No. 035.085-60-2.44-0021-B

13

Installation and Procurement of HVAC Control panel as per HVAC Spec. 035.85-60-2.44-0024E Cl. 21.3

Nos.

Note: The quantity mentioned above is as per the FEED Dwg./Doc. mentioned with description. Actual quantity may vary during detail engineering

S. No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14

Description of item
HVAC load calculations including calculations for pressurization and chilled water
calculations using software mentioned in the ITB document
Power consumption data of all HVAC equipments
HVAC Equipment schedule showing all details like total capacity Static pressure,
oncoil temperature, off coil temperature etc
MR and TBE for all HVAC equipments
HVAC air flow diagrams
HVAC chilled water Diagrams
HVAC duct layouts
Chilled water piping layouts
Drainage piping layout
Pluming piping layout
HVAC control system line diagrams
Equipment data sheets
Riser and schematic drawings
HVAC Specifications

Unit

Unit Price

Quantity

Total Quantity
Price

Remarks

S. No.
1
2

Description of item
MECHANICAL
Testing & SAT (Site Acceptance Test) of HVAC System
ALL OTHER WORKS NOT COVERED ABOVE
Vendors Representative (during Precommissioning)
Contractor's Field Staff (during Precommissioning)
Final As-built documentation for all disciplines

Unit

Unit Price

Quantity

Total Quantity
Price

Remarks

Potrebbero piacerti anche