Ordering information
T
R
Control output
Power supply
Alarm output
Size
Digit
Setting type
Item
1. It is unavailable for TC4SP, TC4Y.
2. 11pin socket(PG-11, PS-11) for TC4SP: sold separately.
100-240VAC 50/60Hz
No alarm output
Alarm1 output
SP
DIN W72H36mm
DIN W72H72mm
DIN W48H96mm
DIN W96H48mm
DIN W96H96mm
9999 (4digit)
Temperature controller
Specifications
TC4S
Series
Power
supply
AC power
AC/DC power
TC4SP
TC4Y
TC4M
TC4W
AC power
Power
consumption AC/DC power
Display method
Input type
Display 1
accuracy
RTD
7.014.6mm
11.022.0mm
7.415.0mm
9.520.0mm
9.520.0mm
RTD
H-54
TC4L
TC4H
100-240VAC 50/60Hz
Relay
SSR
Control
output
Unit weight
Approx. 97g
Approx. 84g
Approx. 127g Approx. 127g Approx. 118g Approx. 118g Approx. 172g
Connections
1
2
3
1
SOURCE:
100-240VAC
5VA 50/60Hz,
24VAC 5VA 50/60Hz,
24-48VDC 3W
AL1 OUT:
250VAC 1A 1a
AL2 OUT:
250VAC 1A 1a
Relay OUT:
250VAC 1A 1a
10
11
12
8
9
TC RTD B'
A
SENSOR
TC4Y
3
1
SENSOR
SOURCE:
100-240VAC
5VA 50/60Hz,
24VAC 5VA 50/60Hz,
24-48VDC 3W
11
SENSOR
TC4W
TC
RTD
AL1 OUT:
250VAC 1A 1a
13
Relay OUT:
250VAC 3A 1a
14
15
16
17 18
19
20
AL1 OUT:
250VAC 1A 1a
1 2 3 4 5
A
B'
RTD
TC
SENSOR
SOURCE:
100-240VAC
1 5VA 50/60Hz,
24VAC 5VA 50/60Hz,
24-48VDC 3W
21
B'
22
23
24
(G)
Connector/
Socket
(H)
Temp.
controller
(I)
SSR/
Power
controller
(J)
Counter
(K)
Timer
SSR OUT:
12VDC 2V
20mA Max.
(O)
Sensor
controller
10
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
(T)
Software
Relay OUT:
250VAC 3A 1a
(F)
Rotary
encoder
(S)
Field
network
device
AL2 OUT:
250VAC 1A 1a
6 7 8 9 10 11
SSR OUT:
12VDC 2V
20mA Max.
(E)
Pressure
sensor
(P)
Switching
mode power
supply
10
SSR OUT:
12VDC 2V
20mA Max.
AL1 OUT:
250VAC 1A 1a
4
B' RTD TC
(D)
Proximity
sensor
(N)
Display
unit
Relay OUT:
250VAC 3A 1a
(C)
Door/Area
sensor
(M)
Tacho/
Speed/ Pulse
meter
TC4SP
SSR OUT:
12VDC 2V
20mA Max.
(B)
Fiber
optic
sensor
(L)
Panel
meter
TC4 Series has selectable control output; Relay output, and SSRP output. AC/DC power type has Relay output and
SSR output and it is selectable.
TC4S
(A)
Photo
electric
sensor
(U)
Other
11
12
SOURCE:
100-240VAC
5VA 50/60Hz,
24VAC 5VA 50/60Hz,
24-48VDC 3W
H-55
TC Series
TC4M
TC4H/L
SSR OUT:
12VDC 2V
20mA Max.
10
11
12
5
6
1
SOURCE:
100-240VAC
5VA 50/60Hz,
24VAC 5VA 50/60Hz,
24-48VDC 3W
AL1 OUT:
250VAC
1A 1a
Relay OUT:
250VAC 3A 1a
13
15
16
17
8
9
18
13
14
15
16
17
18
14
AL2 OUT:
250VAC
1A 1a
SSR OUT:
12VDC 2V
20mA Max.
B' RTD TC
AL1 OUT:
250VAC
1A 1a
7
8
AL2 OUT:
250VAC
1A 1a
B
A
SENSOR
1
SOURCE:
100-240VAC
5VA 50/60Hz,
24VAC 5VA 50/60Hz,
24-48VDC 3W
10
11
Relay OUT:
250VAC 1A 1a
12
19
20
21
B' RTD TC
22
23
24
SENSOR
Dimensions
TC4S
<Bracket>
(unit: mm)
6
48
Panel cut-out
11
64.5
Min. 65
Min. 65
56
Panel cut-out
72.2
48
58.5
Min. 65
Min. 65
56
Panel cut-out
87
Min. 91
77
TC4M
72
Panel cut-out
64.5
68 +0.70
Min. 90
Terminal
cover
H-56
Min. 90
77.5
68 +0.7
0
<Bracket>
30
36
72
Min. 40
TC4Y
45 +0.6
0
31.5 +0.5
0
<Bracket>
45 +0.6
0
45 +0.6
0
TC4SP
45 +0.6
0
Terminal
cover
68 +0.7
0
TC4W
<Bracket>
(A)
Photo
electric
sensor
Panel cut-out
Min. 115
44.8
Min. 65
45 +0.6
0
64.5
48
96
(B)
Fiber
optic
sensor
(C)
Door/Area
sensor
92 +0.8
0
(D)
Proximity
sensor
TC4H
48
<Bracket>
64.5
Panel cut-out
(E)
Pressure
sensor
Min. 65
(F)
Rotary
encoder
96
101.5
Min. 115
92 +0.8
0
Terminal
cover
(G)
Connector/
Socket
45+0.6
0
(H)
Temp.
controller
96
TC4L
64.5
Panel cut-out
Terminal
cover
(J)
Counter
Min. 115
101.5
Min. 115
92
+0.8
0
<Bracket>
(I)
SSR/
Power
controller
(K)
Timer
(L)
Panel
meter
92+0.8
0
(M)
Tacho/
Speed/ Pulse
meter
(N)
Display
unit
13
68.5
48.4
70
22
RLA-COVER
(4896mm)
2
47.
13
(9696mm)
94
13
(O)
Sensor
controller
(P)
Switching
mode power
supply
91.5
RMA-COVER
(7272mm)
91.5
RSA-COVER
(4848mm)
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
Product mounting
TC4S/SP(4848mm) Series
TC4Y(7236mm) Series
(S)
Field
network
device
Other Series
(T)
Software
(U)
Other
Mount the product on the panel, fasten bracket by pushing with tools as shown above.
(In case of TC4Y, fasten bolts for bracket.)
H-57
TC Series
Parts description
1
1
3
2
4
5
8
PV deviation temp.
Over 2
Below 2
Under -2
Deviation display
lamp on
lamp on
lamp on
7, 8
key
Used when entering into parameter setting group,
returning to RUN mode, moving parameter, and saving
setting values.
7. Adjustment
Used when entering into set value change mode, digit
moving and digit up/down.
8. FUNCTION key
Press + keys for 3 sec. to operate function(RUN/STOP,
alarm output cancel) set in inner parameter [DI-K].
Press + keys at the same time in set value
operation to move digit. (only for TC4Y Series)
Thermocouple
L(IC)
DPt100
RTD
Cu50
Display
Input range ()
Input range ()
KCA
JIC
LIC
DPtH
DPtL
CUsH
CUsL
-50 to 1200
-58 to 2192
-30 to 500
-22 to 932
-40 to 800
-40 to 1472
-100 to 400
-148 to 752
-100.0 to 400.0
-148.0 to 752.0
-50 to 200
-58 to 392
-50.0 to 200.0
-58.0 to 392.0
Factory default
SV setting
Parameter
-
Parameter 2 group
Factory default
Parameter 1 group
Parameter
AL1
AL2
AT
P
I
D
REST
HYS
H-58
Factory default
1250
OFF
01)0
0000
05)0
002
Parameter
IN-T
UNIT
IN-B
MAvF
L-SV
H-SV
O-FT
C-MD
OUT
SSrM
Factory default
KCA
?C
0000
00)1
-050
1200
HEAT
PID
RLY
STND
Parameter
Factory default
02)0
AL-1
AMiA
AL-2
AHYS
LBaT
LBaB
DI-K
ErMV
LOC
AM@A
0001
0000
002
STOP
00)0
OFF
AC/DC power type has no SSR drive output method selection [ SSrM] function and
supports only ON/OFF output when selecting SSR in control output setting function [ OUT].
(A)
Photo
electric
sensor
(B)
Fiber
optic
sensor
(C)
Door/Area
sensor
,
Finish the setup.
(D)
Proximity
sensor
(E)
Pressure
sensor
(F)
Rotary
encoder
Check SV
(G)
Connector/
Socket
Run mode
2 sec.
SV setting
AL1
AL2
AT
P
I
D
RSET
HYS
(I)
SSR/
Power
controller
3 sec.
4 sec.
3 sec.
(H)
Temp.
controller
key over
IN-T
UNIT
IN-B
MAvF
L-SV
H-SV
O-FT
C-MD
OUT
SSrM
T
AL-1
AL-2
AHYS
LBaT
LBaB
DI-K
ErMV
LOC
(J)
Counter
Input sensor
(K)
Timer
Temperature unit
(L)
Panel
meter
Input correction
Input digital filter
(M)
Tacho/
Speed/ Pulse
meter
SV low-limit value
SV high-limit value
(N)
Display
unit
(O)
Sensor
controller
(P)
Switching
mode power
supply
Control cycle
AL1 alarm operation mode
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
(S)
Field
network
device
(T)
Software
Parameter setup
Parameter 2 group Parameter 1 group
(U)
Other
SV setting
Set parameter as the above considering parameter relation of each setting group.
Check parameter set value after change parameter of setting group 2.
Indicator type displays shaded parameter(
) of setting group 2.
AL-1, AL-2 parameter of setting group2 is decided whether to display according by alarm output type.
If alarm operation mode[ AL-1, AL-2] of setting group2 is set to AM)_/ SBa / LBa, AHYS parameter is not displayed.
H-59
TC Series
Parameter 1 group
Run mode
2 sec.
3 sec.
PAR1
S 1
AL1
1250
Set range: Deviation alarm(-[F.S] to [F.S], Absolute value alarm(temperature range)
In case alarm operation mode [ AL-1, AL-2], AM)_/ SBa / LBa of setting group 2 is
set to [ AL-1, AL-2], no parameters is displayed.
AL2
1250
Auto-tuning
AT
Proportional band
P
Integral time
1
Derivation time
D
Manual reset
REST
Hysteresis
OFF
0000
0000
05)0
002
Parameter 2 group
Run mode
3 sec.
4 sec.
PAR2
CUsL
Input type
IN-T
S 1
01)0
HYS
ON
CUsH
KCA
DPtL
JIC
DPtH
LIC
Temperature unit
UNIT
Input correction
IN-B
Input digital filter
MAvF
H-60
?C
000
)1
?F
Front temperature unit indicator will flash when selecting the unit.
L-SV
SV high-limit value
H-SV
(A)
Photo
electric
sensor
-050
1200
Control type
C-MD
Control output type
OUT
HEAT
COOL
PID
ONOF
(E)
Pressure
sensor
(F)
Rotary
encoder
(G)
Connector/
Socket
RLY
SSR
STND
CYCL
SSrM
Control cycle
(H)
Temp.
controller
(I)
SSR/
Power
controller
PHAS
(J)
Counter
02)0
AL-1
AMiA
LBaA
AM!A
AMiB
Alarm option
Press
key to convert alarm
operation mode into alarm option.
Refer to H-62 page.
AM@A
AHYS
LBA monitoring time
LBaT
LBA detection band
LBaB
DI-K
00I
002
STOP
ErMV
Lock
LOC
00)0
OFF
AlRE
LOC2
LOC3
(O)
Sensor
controller
(P)
Switching
mode power
supply
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
(S)
Field
network
device
(T)
Software
LOC1
(L)
Panel
meter
(N)
Display
unit
(K)
Timer
(M)
Tacho/
Speed/ Pulse
meter
AL-2
(C)
Door/Area
sensor
(D)
Proximity
sensor
O-FT
(B)
Fiber
optic
sensor
H-61
(U)
Other
TC Series
Functions
Alarm [ AL-1 / AL-2 ]
Alarm
operation
AM!A
There are two alarms which operate individually. You can set
combined alarm operation and alarm option. Use digital input
key(set as AlRE) or turn OFF power and re-start this unit to
release alarm operation.
Alarm
option
Alarm operation
Mode
Name
AM)_ AM!
AM@
AM#
AM$
Deviation
high-limit
alarm
Deviation
low-limit
alarm
Deviation
high/low-limit
alarm
Deviation
high/low-limit
reserve alarm
Alarm operation
Description
No alarm output
SV
100
ON
SBa
LBa
PV
110
ON
PV
90
SV
100
OFF
PV
90
ON
SV
100
SV
100
OFF
PV
110
ON
OFF
PV
90
SV
100
ON
PV
120
ON
PV
90
SV
100
OFF
PV
120
Absolute
value high
limit alarm
OFF
ON
PV
90
SV
100
Absolute-value Alarm:
Set as 90
ON
AM^
OFF
ON
OFF
AM%
OFF
Absolute
value low
limit alarm
PV
90
SV
100
Absolute-value Alarm:
Set as 90
ON
PV
110
Absolute-value Alarm:
Set as 110
OFF
SV
100
ON
SV
100
OFF
PV
110
Absolute-value Alarm:
Set as 110
Alarm option
Mode
AM .A
AM .B
AM .C
AM .D
AM .E
AM .F
Name
Standard alarm
Description
If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
Alarm latch
Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set
temperature, alarm temperature[ AL1, AL2] or alarm operation[ AL-1, AL-2], switching STOP mode to RUN mode.
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature
controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between
standard alarm [ SBaA], or alarm latch [ SBaB].
H-62
LBA
Temperature monitoring time
SV
PV
Control
output
MV
LBA
invalid
100%
0%
Loop break
alarm(LBA)
(D)
Proximity
sensor
LBA detection
band
LBA
invalid
(E)
Pressure
sensor
LBA
invalid
(F)
Rotary
encoder
Time
(G)
Connector/
Socket
Start control to
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB] during LBA monitoring
time [ LBaT]
to
to
When control output MV is 0% and PV is not decreased below than LBA detection band [ LBaB] during LBA monitoring
time [ LBa] loop break alarm (LBA) turns ON after LBA monitoring time.
to
Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.
to
to
When control output MV is 100% and PV is not increased over than LBA detection band [ LBaT] during LBA monitoring
time [ LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
to
When control output MV is 100% and PV is increased over than LBA detection band [ LBaB] during LBA monitoring
time [ LBaT] loop break alarm (LBA) turns OFF after LBA monitoring time.
to
(I)
SSR/
Power
controller
(K)
Timer
(L)
Panel
meter
(M)
Tacho/
Speed/ Pulse
meter
(N)
Display
unit
(O)
Sensor
controller
(P)
Switching
mode power
supply
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
SSR Module
Load
INPUT
(H)
Temp.
controller
(J)
Counter
When executing auto-tuning, LBA detection band[ LBaB] and LBA monitoring time are automatically set based on auto
tuning value. When alarm operation mode [ AL-1, AL-2] is set as loop break alarm(LBA)[ LBa ], LBA detection band
[ LBaB] and LBA monitoring time [ LBaT] parameter is displayed.
Temperature controller
(TC4 Series)
SSR voltage output
(12VDC)
(B)
Fiber
optic
sensor
(C)
Door/Area
sensor
LBA detection
band
LBA detection
band
LBA detection
band
LBA
LBA
monitoring time monitoring time
(A)
Photo
electric
sensor
(S)
Field
network
device
LOAD
(T)
Software
Power
100-240VAC
50/60Hz
(U)
Other
When selecting phase or cycle control mode, the power supply for load and temperature controller must be the same.
In case of selecting PID control type and phase [ PHAS] / cycle [ CYCL] control output modes, control cycle [ T] is not
allowed to set.
For AC/DC power model (TC4 - 2R), this parameter is not displayed and it is available only standard control by relay
or SSR.
H-63
TC Series
Standard ON/OFF control mode [ STND]
A mode to control the load in the same way as Relay
output type.
(ON: output level 100%, OFF: output level 0%)
AC
OUT
ON
OFF
ON
OFF
50Cycle
50Cycle
50%
80%
10%
50%
H-64
Hysteresis [ HYS]
Set control output ON / OFF interval in ON / OFF control
mode.
Heating operation
Control
output
ON
OFF
Hysteresis
[ HYS]
SV
Temperature
SV
Offset
PV
3sec.) [ DI-K]
Press
+
keys for 3 sec. at the same time and it
operates RUN/STOP function[ STOP] which is set at DI-K
or alarm clear function[ AlRE].
Run mode
ON
RUN
STOP
RUN
Lock off
OFF
Lock parameter group 2
LOC1
Lock parameter group 1, 2
LOC2
Lock parameter group 1, 2, SV setting
LOC3
OFF, LOC1 are available only for indicator(TC4 -N N).
Troubleshooting
(D)
Proximity
sensor
(E)
Pressure
sensor
(F)
Rotary
encoder
(G)
Connector/
Socket
(H)
Temp.
controller
(K)
Timer
(L)
Panel
meter
(M)
Tacho/
Speed/ Pulse
meter
(N)
Display
unit
(O)
Sensor
controller
(P)
Switching
mode power
supply
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
Error
OPEN
(C)
Door/Area
sensor
(J)
Counter
Display Description
(B)
Fiber
optic
sensor
(I)
SSR/
Power
controller
Display
(A)
Photo
electric
sensor
H-65
(S)
Field
network
device
(T)
Software
(U)
Other
TC Series
Output connections
See H-139 page for output.
TC Series
Heater
Voltage
output
terminal
Power
Condenser
0.1
630V
SSR
I
N
P
U
T
L
O
A
D
Power
Load power
Magnet or
Relay contact
Proper usage
Simple "error" diagnosis
When the load (Heater etc) is not operated
Please check operation of the OUT lamp located in front
panel of the unit.
If the OUT lamp does not operate, please check the
parameter of all programmed mode.
If lamp is operating, please check the output(Relay, SSR
drive voltage) after separating output line from the unit.
Max. 5.8mm
Max. 5.8mm
H-66