Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1, MARCH 2003
57
I. INTRODUCTION
58
(1)
is calculated in relation to total third-harmonic
where voltage
, recalculated in secondary circuit, induced in the
voltage
stator winding between neutral and terminals.
III. SYSTEM GROUNDING GENERATOR NEUTRAL
An analysis of the operating conditions of the ground-fault
protection of the generator stator winding was made for the
system grounding generator neutral shown in Fig. 2.
If the unit is not protected by a system excited by the zerosequence voltage component, the neutralization coefficient can
be close to unity. In this way, the level of a ground-fault current
in the arcing channel is determined by its active component
which depends mainly on the neutralizer resistive parameters
and it usually equals 5% of the capacitive component of the
ground-fault current. In units equipped with generator breakers
without additional capacitance, this current does not exceed
0.2 A.
59
where
is a value of the grounding resistance of the generator
neutral.
The value of primary grounding admittance in systems with
a grounding transformer equals
(4)
(5)
Simulation tests were run for the parameters of the third-harF,
H and for the
monic stop filter:
.
1000 resistor
D. Neutral Grounded Through Capacitive Voltage Divider
In this method of grounding the generator neutral [Fig. 2(d))],
the capacitive voltage divider performs a function of a capacitive
voltage transformer, feeding the protection system excited by
the zero-sequence voltage component, connected to the termi. Similarly as for the grounding of the
nals of capacitance
neutral through a resistor, the maximum level of ground-fault
current equals several amperes. Whereas the particular capacitances of the grounding system result from the proper operation
of the protection system excited by the zero-sequence voltage.
60
(7)
an offset coefficient of the protection excited by
the zero-sequence voltage component (assumed to
equal 0.7);
a relative length of the stator winding phase protected by the ground-fault protection excited by the
zero-sequence voltage component in relative units
(assumed to equal 0.97);
capacitance between the windings of low and high
voltage of the main transformer;
generator phase voltage.
Simulation tests were run for different values of the capacitance to ground of the generator breakers.
B. Resistor
IV. ANALYSIS OF SIMULATION RESULTS
Since it was found that the results of the simulation tests did
not differ markedly among the particular types of generators,
the results were analyzed for an 1100-MVA unit. Parameters of
unit-connected generator are: voltage 24 kV, current 26.7 kA,
capacitance to ground of main insulation of generator stator
winding phase 0.21 F, external capacitance of unit seen from
generator terminals 0.058 F, generator reactance in over transients states 0.27 p.u., and zero-sequence reactance of generator
0.13 p.u. The resultant admittance of the branch grounding the
generator neutral was calculated by applying relations (2), (3),
(5), and (6).
A. Ground-Fault Neutralizer
The third-harmonic voltage in the branch of the measuring
element versus the distance of the location of ground faults from
the neutral, for the same ratio of voltage transformers feeding
the protection system in units equipped with generator breakers
without capacitance to ground, is shown in Fig. 5(a). In these
schemes, the neutralizer does not influence significantly the
operating conditions of the ground-fault protection. The level
of the neutralization coefficient also affects slightly the thirdharmonic voltage feeding the protection measuring element in
units equipped with additional capacitance to ground [Fig. 5(b)].
As it is seen in Fig. 5(c)(d), the capacitance to ground of the
generator breakers affects the operating conditions of groundfault protection to a higher degree than does the level of the
neutralization coefficient.
Generally, it can be stated that both the neutralization coefficient and additional capacitance to ground of generator breaker
influence to a small extent the operation of the ground-fault protection excited by the voltage third harmonic.
61
V. CONCLUSIONS
1) The operating conditions of the ground-fault protection
system excited by the ratio of the third-harmonic voltages in the neutral and at the generator terminals depend
on the method of grounding the generator neutral. The
grounding system influences both the range and character
of changes in the voltage feeding the measuring element
of the protection during ground faults along the whole
length of the stator winding.
2) When the neutral is grounded through a ground-fault neutralizer, the neutralization coefficient of the capacitive
component of the ground-fault current and the value of
the additional capacitance to the ground of the generator breakers influence the operating conditions of the
ground-fault protection only to a limited degree.
3) If the grounding resistance of the generator neutral is
lower than 5 k , the grounding resistance of the generator
neutral influences significantly the voltage feeding the
measuring element of the protection system, independent
of the value of generator breaker capacitance. At resistance higher than 5 k , this influence practically decays.
4) If the generator neutral is grounded through a series
arrangement of a resistor and a third-harmonic stop filter,
the voltage feeding the measuring element of the protection system decreases as the distance of the ground-fault
location from the neutral increases. A proper choice of
stop filter parameters allows one to create conditions
under which the protection system covers practically
100 percent of the stator winding.
5) The grounding of the generator neutrals through a capacitive voltage divider, especially in units equipped with generator breakers without additional capacitance to ground,
can make impossible the protection of the part of the
stator winding close to the neutral.
6) The operating conditions of a protection system excited
by the third-harmonic voltage must be analyzed if any
62
[9] M. Zielichowski, Optimization of third harmonic ground-fault protection schemes for unit connected generators, in Proc. Int. Power Eng.
Conf., Nanyang Technology Univ., vol. 1, Singapore, 1995, pp. 323327.
, Properties of earth-fault arcs in turbogenerator stators,
[10]
Rozprawy Elektrotechniczne, vol. 23, no. 2, pp. 433446, 1977.
, Dynamic resistance of the earth-fault channel in turbogenera[11]
tors, Przeglad Elektrotechniczny, vol. 66, no. 45, pp. 7779, 1990.
[12] M. Zielichowski and M. Fulczyk, Influence of load on operating conditions of third harmonic ground-fault protection system of unit connected
generators, Proc. Inst. Elect. Eng.Generation, Transmission and Distribution, vol. 146, no. 3, pp. 241248, 1999.
Mieczyslaw Zielichowski was born in 1941. He received the M.Sc., Ph.D., and
D.Sc. degrees in electrical engineering from the Wroclaw University of Technology, Poland, in 1964, 1969, and 1989, respectively.
Currently, he is Professor with the Institute of Electrical Power Engineering
of the Wroclaw University of Technology. He was the bursar of the French Government from 1979 to 1980, and in 1979, joined the Institut National Polytechniqe de Grenoble/France. His main research interests include power systems,
control, as well as protection and power apparatus.
Marek Fulczyk was born in 1968. He received the M.Sc. and Ph.D. degrees in
electrical engineering from the Wroclaw University of Technology, Poland, in
1993 and 1997, respectively.
Currently, he is a Researcher with ABB Corporate Research in Cracow,
Poland. His special research and professional interest are in the field of power
system protection, 3-D modeling, and simulations of electric fields.