Sei sulla pagina 1di 40

VFD

Variable Frequency Drive

nfi

Practical
Demonstration of

VFD

nfi

Delta- M Series
1.5 KW
I/P: 230V 1/3 Phase
O/P: 230 3 Phase

VFD Status Screen


Motor OFF

Command Freq. Output Freq.

nfi

Parameters

Direction

Amperes

Keypad Control
Terminals

Freq. Display

nfi

POT
Extended
Terminal Blocks

Control Terminals

Relay Feedback
Terminals

Freq. Feedback
Analog Voltage
Input

nfi

Analog Current
Input

Motor Brake
Terminals

Motor Output
Terminals

nfi

3 Phase/ 1 Phase
220 VAC

nfi

Important Parameters used in various Applications

Source of Frequency Command


Master frequency determined by digital keypad
Master frequency determined by 0 to +10 V input on
AVI terminal
Master frequency determined by 4 to 20mA input on
ACI terminal
Master Frequency Determined by Rs 485 Comm. port
Master frequency determined by potentiometer on
digital keypad

nfi

Important Parameters used in various Applications

Source of Frequency Command


Master frequency determined by digital keypad

Frequency Increment
Frequency Decrement

nfi

Important Parameters used in various Applications

Source of Frequency Command


Master frequency determined by 0 to +10 V input on
AVI terminal

nfi

Important Parameters used in various Applications

Source of Frequency Command


Master frequency determined by 4 to 20mA input on
ACI terminal

nfi

Important Parameters used in various Applications

Source of Frequency Command


Master frequency determined by Rs 485 Comm. port

nfi

Important Parameters used in various Applications

Source of Frequency Command


Master frequency determined by potentiometer on
digital keypad

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by digital keypad
Operation determined by external control terminals,
keypad STOP is effective
Operation determined by external control terminals,
keypad STOP is ineffective
Operation determined by RS 485 Comm. port,
keypad STOP is effective
Operation determined by RS 485 Comm. port,
keypad STOP is ineffective

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by digital keypad
VFD STOP

VFD RUNNING
RUN
STOP

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by external control terminals,
keypad STOP is effective

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by external control terminals,
keypad STOP is ineffective

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by external control terminals,
keypad STOP is effective

nfi

Important Parameters used in various Applications

Operation Control of VFD


2 Wire Control (1) On/Off & Direction
from Toggle Button

nfi

Important Parameters used in various Applications

Operation Control of VFD


2 Wire Control (2) On/Off & Direction
from Toggle Button

nfi

Important Parameters used in various Applications

Operation Control of VFD


3 Wire Control On/Off from Push Button &
Toggle Button for Direction Control

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by RS 485 Comm. port,
keypad STOP is effective

nfi

Important Parameters used in various Applications

Source of Operation Command


Operation determined by RS 485 Comm. port,
keypad STOP is ineffective

nfi

Important Parameters used in various Applications

STOP Method
Ramp Stop
Coast Stop

nfi

Important Parameters used in various Applications

Maximum Output Frequency Range

0 ~ 400 Hz

nfi

Important Parameters used in various Applications

Acc./ Dec.

Time

Voltage / Frequency Setting for various Applications

nfi

Important Parameters used in various Applications

Jog Frequency
To adjust the Speed of Motor at Jog Mode

Jog Acc./ Dec Time


0.1 to 600.0 sec or 0.01 to 600.0 sec

nfi

Important Parameters used in various Applications

Second Source of Frequency Command

Keypad Up/Down
AVI (0-10V)
ACI (4-20mA)
Keypad Potentiometer

Reverse Operation Inhibition


Parameter Lock
PLC Operation

Jog Acc./ Dec Time

nfi

0.1 to 600.0 sec or 0.01 to 600.0 sec

VFD
Biasing

nfi

Adjusting Voltage
by Frequency
Curves

www.nfiautomation.org

VFD Biasing

1 Volt = 5 Hz
Pr.03=50Hz--Max. output Freq.
Pr.48=0%--bias adjustment
Pr.49=0 -- bias polarity
Pr.50=100% -- pot. freq. gain
Pr.51=0 -- REV disable in negative bias

50 Hz

25 Hz

nfi
0 Hz

5V

10V

www.nfiautomation.org

VFD Biasing

1 Volt = 5 Hz
Pr.03= 50Hz--Max. output Freq.
Pr.48= 20%--bias adjustment
Pr.49= 0 -- bias polarity
Pr.50= 100% -- pot. freq. gain
Pr.51= 0 -- REV disable in negative bias

50 Hz

Bias Adjustment =
(Bias Range)/(Full range) x 100
= 10/50 x 100
= 20%

25 Hz

Bias Adjustment
10 Hz

nfi
0 Hz

5V

10V

www.nfiautomation.org

VFD Biasing
Bias Adjustment = (XV/ Full voltage Range) x 100
(Full Freq. Range Bias Freq. range) / (Full voltage range) = (Bias Freq. 0 Hz) / XV
Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100
Pot. Freq Gain
50 Hz

Pr.03= 50Hz--Max. output Freq.


Pr.48= 25%--bias adjustment
Pr.49= 0 -- bias polarity
Pr.50= 80% -- pot. freq. gain
Pr.51= 0 -- REV disable in negative bias

25 Hz

Bias Adjustment
10 Hz

nfi
0 Hz

-2.5V

5V

10V

www.nfiautomation.org

VFD Biasing
Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

50 Hz

Pot. Freq Gain


Pr.03= 50Hz--Max. output Freq.
Pr.48= 0%--bias adjustment
Pr.49= 0 -- bias polarity
Pr.50= 200% -- pot. freq. gain
Pr.51=0 -- REV disable in negative bias

25 Hz

nfi
0 Hz

5V

10V

1 Volt = 5 Hz

www.nfiautomation.org

VFD Biasing
Bias Adjustment = (XV/ Full voltage Range) x 100
(Full Freq. Range Bias Freq. range) / (Full voltage range) = (Bias Freq. 0 Hz) / XV
Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100
Pot. Freq Gain
50 Hz

Pr.03= 50Hz--Max. output Freq.


Pr.48= 42.8 %bias adjustment
Pr.49= 0 -- bias polarity
Pr.50= 70 % pot. freq. gain
Pr.51= 0 -- REV disable in negative bias

Bias Adjustment
15 Hz

nfi
4.28

5V

10V

www.nfiautomation.org

VFD Biasing
Bias Adjustment =
(Bias Voltage Range)/(Full Voltage range) x 100
= 1/10 x 100
= 10%
50 Hz

Pr.03= 50Hz--Max. output Freq.


Pr.48= 10%--bias adjustment
Pr.49= 1 -- bias polarity
Pr.50= 100% -- pot. freq. gain
Pr.51= 0 -- REV disable in negative bias

45 Hz
25 Hz

nfi
0 Hz

Bias Adjustment

5V

10V

www.nfiautomation.org

VFD Biasing

Bias Adjustment =
(Bias Voltage Range)/(Full Voltage range) x 100
= 1/10 x 100
= 10%

Pot. Freq Gain


50 Hz

Pr.03= 50Hz--Max. output Freq.


Pr.48= ____ bias adjustment
Pr.49= 1 -- bias polarity
Pr.50= ____-- pot. freq. gain
Pr.51= 0 -- REV disable in negative bias

25 Hz

nfi
0 Hz

Bias Adjustment

5V

10V

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

www.nfiautomation.org

VFD Biasing

Bias Adjustment =
(Bias Voltage Range)/(Full Voltage range) x 100
= 5/10 x 100
= 50%

50 Hz

Fwd
25 Hz

2.5V
0

0 Hz

5V
Rev

nfi

7.5V

10V

25 Hz
50 Hz

Pot. Freq Gain = (Full voltage Range)/ (Effective Voltage Range) x 100

Pr.03= 50Hz--Max. output Freq.


Pr.48= 50%--bias adjustment
Pr.49= 1 -- bias polarity
Pr.50= 200% -- pot. freq. gain
Pr.51= 1 -- REV disable in negative bias

www.nfiautomation.org

VFD Biasing

Bias Adjustment =
(Bias Voltage Range)/(Full Voltage range) x 100
= 10/10 x 100
= 100%

50 Hz

Pr.03=50Hz--Max. output Freq.


Pr.48=100%--bias adjustment
Pr.49=1 -- bias polarity
Pr.50=100% -- pot. freq. gain
Pr.51=1 -- REV disable in negative bias

25 Hz

nfi
0 Hz

5V

10V

Important Parameters used in various Applications

Analog Output Signal


Analog Frequency Meter
(0 to Maximum Output Frequency)
Analog Current Meter
(0 to 250% of the rated AC drive current)

nfi

Analog Output Gain 0 ~ 200%

Important Parameters used in various Applications

OverVoltage Stall Prevention


Over-Current Stall Prevention during Acceleration

nfi

Potrebbero piacerti anche