Sei sulla pagina 1di 45

403 2

1
265

2
3

55
26

M8

105
.5
R5

R8

20

R10

70

18

1250 5

10

27.5

4
1713 5

Inner terminal
(Thimble) for
Stranded cable

Shed Details

305

2293 5

6 Test tap
30

125

205

125 2

COMPUTER ORIGINAL

1 HV Terminal

14

5
Technical Data

20

Rated Voltage
Phase to Ground Voltage
Dry Lightning Impulse 1,2/50us
Wet power frequency AC
Routine test 1min dry 50Hz
Rated Current

100BCT 60

165

8
9
10

160

140

100
70
34
335
290
12 mounting
holes 16

M12

Test tap

10

End shield

Al alloy

Painted

Oil end insulator

Porcelain

Brown

Mounting plate

Al alloy

Painted

Rating plate

Al

Engraved
-

Test tap

Condenser core

OIP

Air end insulator

Porcelain

Brown

Oil level indicator

Glass

Top chamber

Al alloy

Painted

HV Terminal

Copper

Silver plated

Material

Finish

1
Pos
AGN

170
kV
145
kV
650 kV
275 kV
300 kV
800
A
3625 mm
1450 mm
100 mm
118 kg
14 lt
40 kA for 2 sec
1250 mm
IS:2099/IEC:60137-2003
3380 N

Creepage Distance Protected


Bushing CT
Mass
Oil Quantity
STC Rating
Arcing distance
Ref. Standard
Catilever load

30

580 5

32

Qty

Description

RH

RH

Cat.No.: LF 123 192

WITH OIL LEVEL GAUGE

GOB 650 1250-100 BCT


G.A.DRG.DRAW LEAD TYPE

2751369-217
A

2004.06.09

B
C

2004.06.19
2004.07.01

D
E

2004.09.16
2005.03.22

F 2006.02.23 H 2006.10.01
G 2006.07.27

STANDARD DRAWING

1HYT400292 R1

1:1
E
7
2

125

30
170

350 2

125 2

COMPUTER ORIGINAL

6 Test tap

1 HV Terminal

2
3

Shed Details
55
26

680 5

M8
27.5

1100 5

Solid Stem

240

300 BCT
585 5

95
86
22
46

40

50

25

105

60

15

10

2 Holes
of 14

M12

185

6 mounting
holes 16

Technical Data

225
96

Test tap

Rated Voltage
Phase to Ground Voltage
Dry Lightning Impulse 1.2/50us
Wet power frequency AC
Power frequency withstand voltage
Rated Current

10

End shield

Al alloy

Painted

Oil end insulator

Epoxy

Brown

Mounting plate

Al alloy

Painted

Rating plate

Al

Engraved
-

Test tap

Condenser core

OIP

Air end insulator

Porcelain

Brown

Oil level indicator

Glass

Top chamber

Al alloy

Painted

HV Terminal

Copper

Silver plated

Material

Finish

Pos
AGN

RH

2751369-189
A

2004.04.22

B
C

2005.01.05
2005.05.04

D
E

2006.03.01
2006.10.01

100
kV
72.5 kV
380 kV
150
kV
162
kV
800
A
1815
mm
730 mm
300 mm
38 kg
4
lt
20 kA for 2 sec
680 mm
IS:2099/IEC:60137-2003
1800 N

Creepage Distance Protected


Bushing CT
Mass
Oil Quantity
STC Rating
Arcing distance
Ref. Standard
Catilever load

1
RH

1660

With bottom terminal


suitable for bolting
the Transformer Lead

70

16

R8

6
7

.5
R5

1683 5

R10

70

10

18

20

Qty

Description

Cat.No.: LF 123 185

WITH OIL LEVEL GAUGE

GOB 380 800-300 BCT

1:1

G.A.DRG.SOLID STEM TYPE

STANDARD DRAWING

1HYT400104 R2

5
3

CROMPTON GREAVES LTD., AURANGABAD.

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
1.
Name of the Manufacturer
: Transformers & Rectifiers (India) Ltd
2.

Normal continuous rating

: 30/50MVA

3.

Normal ratio of transformation

: 132/33kV

4.

Phase Connections
a)
HV Winding
b)
LV Winding
c)
Vector group reference

: Star
: Star
: YNyno

Maximum Temperature Rise


a)
Of oil by Thermometer
b)
Of Winding by resistance
c)
By Hot spot temperature Indicator
d)
Ambient Temperature adopted

:
:
:
:

5.

50C
55C
65C
50C

6.

Limit for Hot spot temperature for which the


transformer is designed

: 140C

7.

Temperature gradient between windings


and oil.

: 22C (approx)

8.

Voltage to earth for which the star point


will be insulated.

: 95kVp / 38kVrms

9.

Type of cooling.

: ONAN/ONAF

10.

Maximum Flux Density in Iron at Normal


Voltage, Frequency and ratio
a)
Core
}
b)
Yoke
}

: } 1.6 T
: } 1.6 T

Maximum current density in winding at CMR


a)
HV Winding
Amps/sq.cm
b)
LV Winding
Amps/sq.cm

: 300 A/cm at rated tap


: 300 A/cm at rated tap

11.

12.

Magnetizing Current (HV) at normal voltage


and ratio (Amps)

: 0.5% FLRC (Approx)

13.

Power Factor of Magnetizing current at normal : 0.08 (Approx)


voltage and frequency

14.

a)

Guaranteed no load loss at normal ratio : 20.0kW


rated voltage and frequency (Max.)

b)

Guaranteed load loss at normal ratio,

: 140.0kW

Page 1 of 7

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
rated output, rated voltage, rated
frequency and 75C average winding
temperature including auxiliary losses,
if any (Max.)
15.

Guaranteed total losses at rated output, rated : At Nor Tap=160.0kW (MAX)


voltage, rated frequency and 75C average
:At Max tap=159.0kW (Approx)
winding temperature including auxiliary losses :At Min tap= 180.0kW (Approx)
if any (Max.)

16.

Total losses at rated output, rated voltage,


rated frequency and maximum attainable
temperature at site including auxiliary losses
if any. (Max.)

: 172.0 kW

17.

Auxiliary losses, if any, at rated load (Max)

: 2.0 kW

18.

Efficiencies at normal ratio, rated voltage, rated: At u.p.f


frequency and 75C average winding
temperature for the outputs of.
a) Full load
: 99.68
b) Full load
: 99.74
c) Full load
: 99.78
d) Full load
: 99.77

At 0.8pf lag

99.61
99.68
99.73
99.71

19.

Resistance per phase of (at normal tap) at 75C


a)
HV Winding (Ohms)
: 0.48 (Approx) (dc resistance)
b)
LV Winding (Ohms)
: 0.027 (Approx) (dc resistance)

20.

Reactance per phase of (at normal tap)


a)
HV Winding (Ohms)
b)
LV Winding (Ohms)

: 45.70 (Approx)
: 2.86 (Approx)

21.

Resistance Voltage drop at 75C average


winding temperature expressed as percent of
rated voltage.

: 0.2 8% (Approx)

22.

Reactance voltage drop expressed as percent


of rated voltage.

: 12.49% (Approx.)

23.

Impedance voltage at normal and 75C average : At Normal


winding temperature expressed as percent of
Tap
rated voltage.
a)
Between HV and LV winding
: 12.5%
b)
Positive sequence HV
: 12.5%
c)
Positive sequence LV
: 12.5%

24.

Regulation at full load at 75C.

Page 2 of 7

At Lowest
Tap

At Highest
Tap

11.2% (approx) 13.0%(approx)


11.2% (approx) 13.0%(approx)
11.2% (approx) 13.0%(approx)

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
a)
Unity Power Factor
: 1.06%
b)
0.8 Power Factor (Lagging)
: 8.20%
25.

Type of transformer

: Core

26.

Width of track gauge

27.

Core:
a)
Material of Core lamination
b)
Thickness of Core Plates
c)
Whether Core Plates are grain
oriented cold rolled
d)
Insulation of core lamination
e)
Insulation of core bolts
f)
Insulation of core bolt washers
g)
Insulation of core and plates
h)
Details of oil ducts in cores
i)
Whether in the plane and at right angle
to the plane of winding
ii)
Across the plane of laminations

28.

1676

: CRGO Silicon steel


: 0.3mm OR less (Nominal)
: Yes
:
:
:
:
:
:
:

Carlite
No core bolts are used
NA
Press Board
As per our design practice
Yes
No

Windings:
a)
Type of Winding
i)
HV Winding
ii)
LV Winding
b)
Insulation of HV winding
c)
Insulation of LV winding
d)
Insulation between HV & IV winding
e)
Power frequency High Voltage Tests

:
: Partially Interleaved/Intershield disc
: Helical/Continuous disc
: } Class A Kraft paper
:}
: Press Board, Oil Ducts

i)

Test Voltage for 1 minute withstand


test on High voltage windings (Induced)

: 230kVrms (line end)

ii)

Test Voltage for one minute withstand


test on Low voltage windings
Test Voltage for one minute withstand
test on Neutral end of high voltage
winding
Impulse test on High Voltage Winding
1/50 full wave withstand
Impulse test on Intermediary voltage
winding 1/50 full wave withstand
Wave form for impulse test
Inter turn insulation HV / LV
Extent of extreme and turns
Reinforcement.
Extent of end turns reinforcement
Extent of turns adjacent to tapping
reinforced.
Test Voltage for ten seconds, 50 cycles

: 70kVrms

iii)

iv)
v)
vi)
g)
i)
ii)
iii)
iv)

: 38kVrms

: 550kVp
: 170kVp
: 1.2 / 50 micro sec
: } No turns reinforcement provided
}
:}
:}
}
:}

Page 3 of 7

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
inter turn insulation test on (i).
} Dielectric tests as per IS:2026
v)
Test Voltage for ten seconds 50 cycles : }
inter turn insulation test on (ii).
}
vi)
Test Voltage for ten seconds 50 cycles : }
inter turn insulation test on (iii)
}
vii)
Test Voltage for ten seconds 50 cycles
}
inter turn insulation test on main body of }
the winding
}
h)
Type of Axial coil supports:
i)
High Voltage Winding
:} Axial spacers of Press Board
ii)
Low Voltage Winding
:}
i)
Type of radial coil supports
i)
High Voltage Winding
: } Radial ducts of Press Board
ii)
Low Voltage Winding
:}
j)
Whether HV windings are inter leaved
: Yes
k)
Details of special if any, made to improve : HV winding is Partially interleaved/Intershield
stress conditions
l)
Size of cooling ducts
: Adequate
m)
Drawings to scale indicating flow of oil in : Will be furnished later on.
the radial and axial ducts of each limb
and winding.
29.

Maximum out of balance force in winding on


short circuit at the terminals

: Negative as separate regulating winding provided

30.

Thickness of Transformer tank plate


a)
Sides
(mm)
b)
Bottom
(mm)
c)
Radiator Plate
(mm)

: 8
: 12
: 1.0

31.

Type and details of winding hot spot


temperature detector

: Thermal Image Type


150mm Dial

32.

Power requirement of heater in conservator

: Not applicable

33.

Buchholz relay description, data, range of


settings schematic diagram etc.

: Double Float Type (GOR-III)

34.

Bushings:
a)
Type
b)
Dry flash over voltage
c)
Wet flash over voltage
d)
Dry 60s withstand voltage
e)
Wet 60s withstand voltage
f)
Full wave withstand test voltage with
1.2/50 micro seconds wave
(+) Positive
(-) Negative

HV
HVN
LV
LVN
: OIP Condenser ---------Porcelain ----------: } -------- Not specified in standards ---------: } --------- Not specified in standards ---------: } 275
140
70
70
:}

: } 650
:}

Page 4 of 7

325

170

170

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
g)
Creepage distance in air
: 3625
1812.5
900
h)
Recommended gap setting (mm)
: 700
350
220
i)
Weight of assembled bushing (Kgs)
: 120
60
13
j)
Quantity of oil (ltrs.)
: 10 ltrs
5 ltrs
-35.

Free space required at top for removal of


bushings (mm)

: 3000

2000

2000

36.

Total volume of conservator (liters)

37.

Volume of conservator between the Highest and : 7.5% of total oil Quantity
lowest levels liters

38.

Cooling system:
a)
Type and make of Fan motors for forced
air cooling equipment
b)
Rating and speed of Motors
c)
Efficiency of motors at full load
d)
Temperature rise of motors at full load
e)
Number of fan motors

900
220
13 (approx)
-- (approx)
2000

: 10% of total oil volume

: Marathon Electric(Alstom) / Khaitan, Equiv make


Industrial Type
: 0.24kW/fan, 700rpm
: As per manufacturer standard
: As Per class B insulation
: 8 + 2 SB

39.

Period of continuous working at full load without : 10 min


fans.

40.

Continuous kVA rating without fans

: 30MVA

41.

Calculated time constants


a) Natural cooling
b) Forced air cooling

: 4Hrs (Approx.)
: 3Hrs (Approx.)

42.

Details of on load tap changing gear


a)
Make
: E-MR / CTR/EQUI
b)
Type
: High speed transition type
c)
Rating:
:
i)
Rated voltage
: 60kV
ii)
Rated current
: 350A
iii)
Step voltage
: 953V
iv)
Number of steps
: 24
d)
Approximate overall weight
: }
e)
Approximate overall dimensions (HxWxD) : } OLTC mounted inside tank
f)
Approximate overall quantity of oil (litres) : }

43.

Weight of copper required to complete the


transformer (Kgs.)

: 11000 (Approx.)

44.

Weight of steel required to complete the


transformer (Kgs.)

: 25500 (Approx.)

45.

Weight of fittings and parts detached for


transport (Kgs.)

:6500 (Approx.)

Page 5 of 7

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
46.

Weight of core and windings (Kgs)

: 42000 (Approx)

47.

Weight of complete transformer with all fittings


and oil (Kgs.)

:76500 (Approx)

48.

Weight of complete transformer arranged for


transport of the heaviest package, if broken
down (Kgs.)

: 68000 (Approx)
(Oil filled)

49.

Weight of oil in the transformer (Kgs.)

: 17250(Approx)

50.

Dimensions of the transformers in meters


a)
Maximum height to top of bushings
b)
Overall length
c)
Overall breadth
d)
Heaviest package for transport

:
:
:
:

51.

Taps

: +5% to -25%@1.25% neutral end of 132 KV

52.

Fault levels for which the transformer is designed : As per IS : 2026

53.

List of accessories and fittings being provided


for transformer

54.

Whether the materials covered by this Bid have : No


been fully type tested and if so, whether the
copies of the type test certificates enclosed to the
bid offer.

55.

Whether oil temperature indicator provided.

: Yes

56.

Type and size of oil temperature indicator and


whether supervisory alarm contacts provided

: Dial type, 150mm dial


Yes alarm contacts provided, (2 Contacts)-

57.

Type of oil level indicator and whether


: Magnetic Type, Yes
supervisory alarm contact for low oil level provided

58.

Type and size of Gas operated relay and


whether supervisory alarm and trip contacts
provided and their sizes and Nos.

: Double float, Gas operated, GOR-III


Yes, 2Nos

59.

Whether winding temperature indicator with


supervisory alarm indicator and trip contacts
provided and their sizes and Nos.

: Yes , 150mm Dial


04Nos

60.

Ratio and type of C.T. used for winding


temperature indicator

: HV = 292/2A
LV = 875/2A
Ring Type

REFER DRG PM0400052/01/01

: As per specification

Page 6 of 7

TARIL_PM0400052_ORANGE_50_MVA_GTP_R0
Dt : 21.09.2015
GUARANTEED TECHNICAL PARTICULARS
FOR POWER TRANSFORMERS
Sl. Description
50MVA, 132/33kV
No.
61.
Type and size of Thermostat used
: Stem type, 230V, 1Ph, AC, 0-100C 62.
No. of Breathers provided
: 02Nos
63.

Type of dehydrating agent used for Breathers

: Silica Gel

64.

Capacity of Conservator vessel (litres)

: 10% of total oil volume

65.

Valve sizes and Numbers required/fitted

: As per spec

66.

Size of Rail gauge for installation in yard

: 1676 mm

67.

Wheel base

: skid type

68.

a)
b)
c)

Type and make of pressure relief device : Spring operated, Sukrut, Atvus or Equiv -No. of each type of devices per
: 01 / Unit
transformer unit (Nos.)
Minimum pressure at which the device : 0.49kG / cm
operates (kPa)

--------------------------------------------------------------------------------------------------------------------------------------THE FIRM

Transformers & Rectifiers (India) Ltd

SIGNATURE OF BIDDER :
DESIGNATION & SEAL

DATE

Page 7 of 7