Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Document # 996-0356
Copyright (C) American Power Conversion Corporation 1991. All rights reserved.
ii
Revision Record
iii
Table of Contents
REVISION RECORD -------------------------------------------------------------------------------- III
TABLE OF CONTENTS -----------------------------------------------------------------------------IV
1.0
INTRODUCTION ----------------------------------------------------------------------------- 1
2.0
SAFETY PRECAUTIONS ------------------------------------------------------------------ 2
3.0
TOOLS AND EQUIPMENT --------------------------------------------------------------- 3
4.0
PRINCIPLES OF OPERATIONS -------------------------------------------------------- 4
5.0
PROCEDURES FOR THE BACK-UPS PRO 280S/ 420S/ 650S DUET &
SMART-UPS 420/ 620 NET -------------------------------------------------------------------------- 7
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
5.14
6.0
iv
1.0 Introduction
This manual provides information required for servicing American Power Conversion
Corporation Back-UPS Pro 280S/ 420S/ 650S Duet and Smart-UPS 420/620 Net. This
guide is divided into the following sections:
Computer interface port description The Back-UPS Pro 280S/ 420S/ 650S and
Smart-UPS 420/ 620 have a communications port that may be connected to a host
computer system using a special optional interface kit. This port allows the computer to
monitor the status of the UPS and in some cases control the operation of the UPS. Below
is a detailed description of each of the serial port's pins:
Pin 1 - Shutdown Input - The UPS will shut down when +5 VDC or a HI RS232 level, sustained for 4.5 seconds, is applied to pin 1. The UPS will respond to
the signal only when operating On-Battery. If the UPS is shut down via this
utility, the UPS will turn On when the voltage is restored to within normal limits.
Pin 2 - Transfer To On-Battery Signal Output - The UPS will generate a LO to
HI RS-232 level transition upon transfer from On-Line to On-Battery operation
(utility failure). The pin is normally at a LO RS-232 level.
Pin 3 - Normally Open On-Battery Signal - This pin is the open collector of a
transistor that turns On when the UPS transfer from On-Line to On-Battery
operation (utility failure). The transistor is capable of driving ground reference
TTL inputs or loads up to 50 ma at 40 VDC, non-inductive. If used to drive
relays, the relay coil must be clamped with a "catch" diode.
Pin 4 - Common - This pin is used as common for input and output signaling.
Pin 4 is separated from chassis ground with a 20 ohm resistor.
Pin 5 - Normally Open Low Battery Signal - This pin is the open collector of a
transistor that turns On when the UPS detects a low battery condition. The
transistor is capable of driving ground referenced TTL inputs or loads up to 25 ma
at 40 VDC, non-inductive. If used to drive relays, the relay coil must be clamped
with a "catch" diode.
Pin 6 - Normally Closed On-Battery Signal - This pin is the open collector of a
transistor that turns Off when the UPS transfer from On-Line to On-Battery
operation (utility failure). The transistor is capable of driving ground reference
TTL inputs or loads of up to 25 ma at 40 VDC, non-inductive. If used to drive
relays the relay coil must be clamped with a "catch" diode.
Pin 7 Turn On/ Low turn Off.
Pin 8 This pin has no connection.
Pin 9 Common - This pin is used as common for input and output signaling.
Pin 9 is separated from chassis ground with a 20 ohm resistor.
5.0 Procedures for the Back-UPS Pro 280S/ 420S/ 650S Duet
& Smart-UPS 420/ 620 Net
Warning: Before disassembling and changing batteries, or servicing the Back-UPS Pro
Duet and Smart-UPS, make sure that mains supply and DC-supply have been switched
Off. Make sure that ALL power has been removed. Be aware that the capacitors in these
units will store energy well after all sources have been disconnected from the unit and
remember to follow ESD guidelines.
3. Turn the unit right side up and from the rear of the unit, grab the sides of the
cover and slide the cover back and away from the chassis. Keep the cover
horizontal at all times. (Fig 5.1.1).
4. Remove the LED display PCB from the bezel being careful not to allow the
exposed display PCB to short out any of its contacts to the chassis. The bezel
is now free from the unit.
3. Swing the battery door open and gently slide the battery out of the UPS. The
white battery label can be used to pull the batteries out (Fig 5.5.1).
4. Remove the units black wire from the negative battery terminal (figure 5.5.1).
5. Remove the units red wire from the positive battery terminal (figure 5.5.1).
6. To discharge the unit, press the On button several times.
7. The battery is now free from the unit.
10
d. Disconnect the secondary side violet wire from the PCBs J10 tab.
e. Disconnect the secondary side brown wire from the PCBs J5 tab.
f. Disconnect the secondary side blue wire from the PCBs J4 tab.
4. Remove the two (2) screws that connect the front of the PCB to the bezel side
of the chassis (figure 5.7.1).
5. Remove the PCBs black wire from the circuit breaker.
6. Remove the inlets white wire (power cords white wire for domestic unit)
from the PCBs tab J13 (Wht In).
7. Remove the power outlets white wire from the PCBs tab J16 (Wht Out).
8. Remove the power outlets black wire from the PCBs tab J15 (Blk Out).
9. Remove the Red battery wire from the PCBs tab J6 (Positive batt. wire).
10. Remove the Black battery wire from the PCBs tab J7 (Negative batt. wire).
11. Remove the four (4) screws that secure the rear of the PCB to the rear panel.
12. Remove the screw on the rear panel that holds the PCB to chassis (hypot
screw).
13. Lift the PCB up and away from the chassis.
14. Remove the display PCB from the bezel and now the PCB is free from its
chassis.
11
12
13
Note: Although the rear panel does not need to be removed during the Output
Transformer removal, it is recommended to ease access to the transformer.
4. Remove rear panel by removing the two screws on each side that secure the
rear panel to the bottom of the chassis (figure 5.9.1).
5. Remove the transformer from the chassis.
14
4. Remove the wires connected to the outlet and remove the outlet.
15
16
6.1
1. Plug the variac into the AC line and set the variac output for 120 VAC [230
VAC].
2. Plug the UPS into the variac and turn the UPS On.
3. Connect a true RMS voltmeter and an oscilloscope to the output of the UPS.
4. Turn off the variac. The UPS should immediately transfer to backup power
(while On-Battery the UPS's output is a stepped approximation to a sine wave
with the correct peak and rms values).
5. Using a voltmeter and oscilloscope, monitor the UPS's output voltage and
frequency.
6. Turn on the variac and observe the transfer from power inverter (stepped
wave) to utility line (sine wave) on the scope. The stepped wave should lock
into the sine wave and maintain phase synchronization. Repeat this test a few
times to clearly observe the phase lock in action.
7. If phase lock does not occur, the PCB should be replaced.
6.2
1. Plug the variac into the AC line and set the variac output for 120 VAC [230
VAC].
2. Plug the UPS into the variac and turn the UPS On. The UPS will perform a
self-test for approximately 8-10 seconds and return to the On-Line state.
3. Connect a true RMS voltmeter and an oscilloscope to the output of the UPS.
4. Turn off the variac. The UPS should immediately transfer to backup power
(while On-Battery the UPS's output is a stepped approximation to a sine wave
with the correct peak and rms values).
17
5. Using a voltmeter and oscilloscope, monitor the UPS's output voltage and
frequency.
6. The UPS should output a pure sine wave at approximately 117+5% VAC
[225+5% VAC].
7. If the sine wave is heavily distorted or the output voltage is inaccurate, the
UPS should be serviced.
6.3
1. Prior to performing this test, the unit should be charged up. Time to charge
will vary depending on the current state of the batteries.
2. Plug the variac into the AC line and set the variac output for 120 VAC [230
VAC].
3. Plug the UPS into the variac and turn the UPS On. The UPS will perform a
self-test for approximately 8-10 seconds and return to the On-Line state.
4. Apply the correct size load to the UPS. Refer to table 6.3 for proper load size.
Model
BP280S
BP420S
BP650S
SmartUPS420
SmartUPS620
Load (VA/Watt)
280VA/180W
420VA/260W
650VA/410W
420VA/260W
620VA/390W
Table 6.3
5. Using a voltmeter, monitor the UPSs output voltage. The UPS should remain
powered and it should output approximately 120+5% VAC [230+5% VAC].
6. Remove the AC line input so that the UPS operates On-Battery. The UPS
should remain powered and the output should remain the same as step 6
above. While the UPS is operating off of the utility voltage, increase the load
by approximately 75 Watts. Plugging a light bulb into the UPS can do this.
After 4 seconds, the overload light should come On and the unit should emit a
constant tone until the overload is removed.
7. If the UPS fails to support the load or recognize the overload, then it should be
serviced.
18
6.4
1. Prior to performing this test, the unit should be charged up. Time to charge
will vary depending on the current state of the batteries.
2. Plug the variac into the AC line and set the variac output for 120 VAC [230
VAC].
3. Plug the UPS into the variac and turn the UPS On. The UPS will perform a
self-test for approximately 8-10 seconds and return to the On-Line state.
4. Connect a true RMS voltmeter to the output of the UPS.
5. Apply the correct size load to the UPS. Refer to table 6.3 for proper load size.
6. Using a voltmeter, monitor the UPSs output voltage. The UPS should remain
powered and it should output approximately 120+5% VAC [230+5% VAC].
7. Remove the AC line input so that the UPS operates On-Battery. The UPS
should remain powered and the output should remain the same as step 6
above.
8. Using a stopwatch, time how long the UPS maintains power to the load. The
UPS should beep every 30 seconds, and when only 2 or 3 minutes of runtime
remain, the UPS will beep every 5 seconds. If the UPS fails to support the
load for the expected runtime, the batteries may need to be replaced. If the
batteries are new and have drained prematurely during normal operations it
may be an indication that there may be a problem with the charging circuit
and the UPS should be serviced.
9. Plug the UPS into the wall and allow it to charge for at least 6 hours before
storing or using the UPS.
6.5
1. Plug the variac into the AC line and set the variac output for 120 VAC [230
VAC].
2. Plug the UPS into the variac and turn the UPS On. The UPS will perform a
self-test for approximately 8-10 seconds and return to the On-Line state.
3. Connect a true RMS voltmeter and an oscilloscope to the output of the UPS.
4. Slowly turn down the variac and monitor the UPS's input voltage. The UPS
should transfer to SmartBoost when the voltage drops to 103+5% VAC
[196+5% VAC]. Repeat this procedure several times to ensure accurate
results.
5. While the UPS is on SmartBoost, slowly turn the variac down until the UPS
transfers to battery. The UPS should transfer to battery at approximately
92+5% VAC [174+5% VAC].
19
6. If the UPS does not transfer properly, then the calibration of the unit is
recommended. Otherwise, the UPS should be serviced.
7. Turn the variac back up so that the UPS goes back to On-Line operation.
8. Slowly turn up the variac and monitor the UPSs input voltage. The UPS
should transfer to SmartTrim when the voltage increases to 132+5% VAC
[258+5% VAC]. Repeat this procedure several times to ensure accurate
results.
9. While the UPS is on SmartTrim, slowly turn the variac up until the UPS
transfers to battery. The UPS should transfer to battery at approximately
147+5% VAC [296+5% VAC].
10. If the UPS does not transfer properly, then the calibration of the unit is
recommended. Otherwise, the UPS should be serviced.
6.6
1. Plug the variac into the AC line and set the variac output for 120 VAC [230
VAC].
2. Plug the UPS into the variac and turn the UPS On. The UPS will perform a
self-test for approximately 8-10 seconds and return to the On-Line state.
3. Place the unit on its side and remove the two (2) screws that secure the battery
door to the chassis at the bottom of the unit (figure 5.5.1).
4. Swing the battery door open and gently slide the battery out of the UPS. The
white battery label can be used to pull the batteries out (Fig 5.5.1).
5. Remove the units black wire from the negative battery terminal (figure 5.5.1).
6. Remove the units red wire from the positive battery terminal (figure 5.5.1).
7. Remove the battery.
8. Measure the DC battery charger voltage between the PCB's black battery wire
and the PCB's red battery wire.
9. The DC voltage should be at 13.6VDC+/- 3%.
10. Should the battery charger voltage fail to meet the provided range then the
unit should be serviced.
11. Connect the red wire from the unit to the positive battery terminal (figure
5.5.1).
12. Connect the black wire from the unit to the negative battery terminal (figure
5.5.1).
13. Gently slide battery into chassis.
14. Swing battery door closed and replace the two (2) screws that secure the
battery door to the chassis (figure 5.5.1).
20
6.7
The Duet and the Smart-UPS are equipped with a rear panel interface port to
allow for communication between the UPS and a host computer. A detailed
description of the port can be found in section 4.0. The following steps should be
performed to ensure the interface port is working properly.
1. Plug the variac into the AC line and set the variac output for 120 VAC
[230VAC].
2. Plug the UPS into the variac and turn the UPS On. The UPS will perform a
self-test for approximately 8-10 seconds and return to the On-Line state.
3. Using a multimeter, measure the voltage between the interface port's pin 2 and
9. The voltage should be LO RS-232 signal (-3 to -15 VDC).
4. Unplug the UPS from the variac so that the UPS operates On-Battery. The
DC voltage between pins 2 and 9 should now be a HI RS-232 level (+3 - +15
VDC).
5. While the UPS is operating On-Battery, apply a HI RS-232 signal to pin 1.
Shorting pin 1 to pin 2 can do this. A metal paper clip can be used to short the
two pins. The UPS should emit a tone and then shutdown.
6. Remove the short between pin 1 and pin 2. Plug the UPS back into the variac.
Now, the UPS should power back up.
7. Connect a 10 k ( 0.5 k) resistor between a 5 volt DC source and the
UPS's pin 3. Using a multimeter, measure the DC voltage drop across the
resistor. The voltage drop should be greater than 3.5 VDC.
8. The resistor should still be connected between a 5 volt DC source and the
UPS's pin 3. Unplug the UPS from the utility line. Using a multimeter,
measure the DC voltage drop across the resistor. The voltage should be less
than 0.6 VDC.
9. Connect a 10 k ( 0.5 k) resistor between a 5 volt DC source and the
UPS's pin 6. Using a multimeter, measure the DC voltage drop across the
resistor. The voltage drop should be less than 0.6 VDC.
10. The resistor should still be connected between a 5 volt DC source and the
UPS's pin 6. Unplug the UPS from the utility line. Using a multimeter,
measure the DC voltage drop across the resistor. The voltage should be
greater than 3.5 VDC.
11. If the UPS fails any of the above tests, the PCB should be replaced.
21
Likely caus e:
Batteries not
connected.
Bad batteries.
Probable solution:
Connect batteries.
Additional comments:
Replace batteries.
Faulty I.C.
Transistor failure.
Will not go
On-Line:
Flashing
LEDs:
(continued
on next
page).
No input at power
cord.
Program wrong
setting.
MOV blown.
Bad IC
Over clenching.
Replace PCB.
Burned trace.
Bad IC.
Bad relay.
Replace relay.
22
Overload:
Likely cause:
Circuit breaker bad.
Probable solution:
Replace circuit breaker.
Resistor out of
tolerance.
Overload condition
present.
Clamp fets or
Power fets blown.
Tel./Net.
Jack fail:
Clicking
sound:
Battery
LED On:
Bad transistor.
Will not
charge:
Bad crystal.
Bad capacitor.
Replace C60.
Bad I.C.
Replace U8.
Bad Fets.
Bad diode.
L.E.D.
failure:
Power
calibration
failed:
Bad L.E.D.
Bad diode.
Additional comments:
23
24