Systems Operation
EMCP4.3/4.4
Media Number -UENR1210-04
i03883596
Annunciator Module
SMCS - 4490
CAN Annunciator
Illustration 1
g02278719
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 2 of 39
The EMCP CAN annunciator serves to display system alarm conditions and status indications.
The CAN annunciator has been designed for use on the EMCP 4 accessory CAN data link. The
annunciator may be used in either local or remote applications, providing customers with
enhanced site flexibility.
In local application, the CAN annunciator may be mounted on the package generator set with the
EMCP 4 to provide a complete package-mounted monitoring solution.
The annunciator may also be mounted locally on the package generator set or remotely up to 800
feet on the Accessory CAN data link.
A maximum of four CAN annunciators can be mounted locally or remotely and connected to the
accessory CAN 2 data link.
Features
Sixteen (16) LED pairs for annunciation of up to 32 system events
An additional pair of LEDs provides status indication of the CAN data link connection
Can annunciate alarm conditions received from any module on the CAN data link
Alarm horn with lamp test and alarm acknowledge pushbuttons
Can be mounted either locally on the package generator set or remotely (up to 244 m
(800 ft)) on the accessory CAN data link
Specifications
Electrical Specifications
Control power 12 VDC and 24 VDC nominal (9 32 VDC acceptable)
Over voltage capability is 80 VDC for 2 minutes at 70 C (158 F)
Reverse voltage capability is 32 VDC for 1 hour at 70 C (158 F)
Single, 6-pin connector provides both power and communication
Environmental Specifications
Operating Temperature 40 C (40 F) to 70 C (158 F).
Relative humidity 90%, non-condensing, 30 C (86 F) to 60 C (140 F).
Failure point of 85 C (185 F). If the ambient temperature exceeds 85 C (185 F), the
device would not be expected to return to proper operation.
Network Communication Interface
Incorporates a communications port, able to operate on the EMCP 4 accessory CAN data
link
Node address is auto configurable
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 3 of 39
Wiring
The back of the CAN annunciator module contains an 8-terminal screw terminal block. Attached
to the block is a 6-pin deutsche adapter. The pin outs for both are shown in Illustration 2,
Illustration 3 and Table 1.
Illustration 2
g02279433
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 4 of 39
Illustration 3
g02280193
Table 1
Annunciator Terminal Block Pin Configuration
Terminal #
Function
Description
PWR-
- Battery Input
PWR+
N/C
Not Connected
CAN 2 High
CAN Datalink HI
CAN 2 Low
Lamp Test
Lamp Test
Alarm Acknowledge
Alarm Acknowledge
Horn Driver
LED Colors
Each pair of LEDs on the annunciator consists of two of the following three colors: green, amber,
and red, which allows for custom configuration of status, warning and shutdown conditions. The
available colors and combinations are listed in Table 2:
Table 2
LED Colors
Row
LED 1
LED 2
Red
Amber
Red
Amber
Red
Amber
Red
Amber
Red
Amber
Red
Green
Red
Amber
Red
Amber
Red
Amber
10
Red
Amber
11
Red
Amber
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 5 of 39
12
Red
Amber
13
Green
Amber
14
Green
Amber
15
Red
Green
16
Red
Amber
Illustration 4
g02279673
Table 3
Behavior
Explanation
Red solid
CAN 2 data link diagnostic. For example: the module is wired wrong (data
link), wrong cable, or no terminating resistor.
Green solid
Green flashing
Red/Green
alternating
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 6 of 39
Global Acknowledge
The CAN annunciator may be configured to both initiate and respond to an event acknowledge
message over the CAN accessory data link. If this setpoint is enabled events may be acknowledge
in the following manner:
Locally on the CAN annunciator by pressing the alarm acknowledge button
Remotely by pressing the alarm acknowledge button on the EMCP 4
By pressing the acknowledge button on another CAN annunciator configured for global
acknowledge that is on the same data link.
The default setting for this setpoint is disabled, but the default may be enabled from the
configuration tool within Cat ET.
Acknowledging events also silences the horn.
Illustration 5
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 7 of 39
Illustration 6
g02279793
3. Double click "ECU Instance Number" to enter a new ECU instance number.
Refer to Illustration 6.
Illustration 7
g02279794
4. Double click "Annunciator Data Link Global Acknowledge Enable Status" to change this
value from the drop-down menu.
Refer to Illustration 7.
Illustration 8
g02279795
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 8 of 39
Illustration 9
Illustration 10
Illustration 11
8. Select the "Trigger Condition" for the pair in the drop-down menu.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... Page 9 of 39
Illustration 12
9. Select the "Severity Level" for the pair in the drop-down menu.
Refer to Illustration 12.
Illustration 13
10. Select the "Suspect Parameter Number" for the pair in the drop-down menu.
Refer to Illustration 13.
11. The "Failure Mode Identifier" does not normally require programming since the "Severity
Level" typically has this information embedded.
To configure the behavior of the LED pairs, enter the "LED Pair Configuration" screen by
selecting "Service a LED Pair Configuration".
There are four parameters associated with each LED pair. Each parameter is dependent on
the preceding parameters (to the left) first "Trigger Condition", next "Severity Level", then
"Suspect Parameter Number", and finally "Failure Mode Identifier" (if required).
Table 4
Annunciator Supported SPNs
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 10 of 39
SPN Description
SPN
52
82
95
Fuel Level
96
98
99
100
Crankcase Pressure
101
107
Altitude
108
110
111
158
167
Battery Voltage
168
171
172
Exhaust Temperature
173
175
Engine Speed
190
625
639
Auxiliary I/O #1
701
Auxiliary I/O #2
702
Auxiliary I/O #3
703
Auxiliary I/O #4
704
Auxiliary I/O #5
705
Auxiliary I/O #6
706
Auxiliary I/O #7
707
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 11 of 39
Auxiliary I/O #8
708
Auxiliary I/O #9
709
710
711
712
970
1122
1123
1124
1125
1126
1231
1237
Fuel Leak
1239
1664
2433
2434
Generator Frequency
2436
Generator AC Voltage
2440
Generator AC Current
2448
2452
2456
2648
3543
3677
4003
4007
4009
4011
4015
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 12 of 39
Loss of Utility
4017
4024
4025
Earth Fault
4028
Earth Leakage
4029
Trigger Condition
Illustration 14
Severity Level
Severity level defines which types of events the LED pair will react to. Selections that begin with
condition exists will respond to CAN event messages for Failure Mode Identifier (FMI) 31
condition exists.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 13 of 39
For example, LED pair #2 is configured for "Condition Exists, Red On, Other Not Used, Horn
On" with SPN 190 (Emergency Stop Active). This means that when the annunciator received a
CAN message indicating emergency stop with FMI 31, the red LED will turn on and the horn will
also turn on.
"Other Not Used" indicates that the other LED color in the pair is never used.
"Green Off" (for example) indicates that the green LED lights when the condition chosen for this
LED pair is not active.
Most severity level selections imply CAN Failure Mode Identifier (FMI) codes:
Condition exists that is equivalent to FMI 31
High warning can be FMI 15 or FMI 16
Low warning can be FMI 17 or FMI 18
High shutdown is equivalent to FMI 0
Low shutdown is equivalent to FMI 1
High or low shutdown is equivalent to FMI 0 or FMI 1
Since the FMI codes are implied by this column, the FMI column is grayed out for any of these
selections.
The only option that will allow an FMI to be configured is specific diagnostic. Table 5 shows all
available FMIs.
Table 5
Failure Mode Identifier (FMI) Codes
FMI
Description
Short
Description
High Shutdown
Low Shutdown
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 14 of 39
10
N/A
11
N/A
12
N/A
13
Out of Calibration
N/A
14
Special Instructions
N/A
15
High Warning
16
High Warning
17
Low Warning
18
Low Warning
19
31
N/A
Status
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 15 of 39
Illustration 15
Additional modules may be added in parallel to remote annunciators. In order to operate properly,
the device to be added in parallel to the annunciator must not have cable drop lengths greater than
2.7 m (8.8 ft). Refer to Illustration 16.
Illustration 16
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 16 of 39
RS-485 Annunciator
Illustration 17
g02280913
The EMCP RS-485 annunciator serves to display system alarm conditions and status indications.
The RS-485 annunciator has been designed for use on a dedicated EMCP 4 fully isolated two wire
RS-485 SCADA data link (half duplex), and may be used in either local or remote applications,
providing customers with enhanced site flexibility. The RS-485 annunciator uses a custom masterslave communication protocol. The EMCP 4 controller will be the master, and the RS-485
annunciators will be the slaves. Configuration takes place within the EMCP 4.
In local application, the RS-485 annunciator may be mounted on the package generator set with
the EMCP 4 to provide a complete package-mounted monitoring solution.
The RS-485 annunciator may also be mounted separately from the generator set to provide remote
indication of system operating and alarm conditions.
The number of RS-485 annunciators is limited by the RS-485 standard.
Features
16 LED pairs for annunciation of up to 32 system events
An additional pair of LEDs provides status indication of the dedicated RS-485 annunciator
network communication connection
Ability to annunciate alarm conditions sent from the EMCP 4 within preconfigured alarm
groups
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 17 of 39
Specifications
Electrical Specifications
Control Power 12 VDC and 24 VDC nominal (9 32 VDC acceptable)
Reverse voltage capability is -32 VDC for 1 hour @ 70C
Over voltage capability is 80 VDC for 2 minutes @ 70C
Single, 8-pin connector provides both power and communication
Environmental Specifications
Operating Temperature 40 C (40 F) to 70 C (158 F).
Relative humidity 90%, non-condensing, 30 C (86 F) to 60 C (140 F).
Failure point of 85 C (185 F). If the ambient temperature exceeds 85 C (185 F), the
device would not be expected to return to proper operation.
Network Communications Interface
EMCP 4 provides a dedicated, fully isolated RS-485 SCADA data link (half duplex)
separate from the RS-485 (MODBUS) port used on the EMCP 4
Operates at 19200 bits per second
Configuration is accomplished with Cat ET
Wiring
The back of the RS-485 annunciator module contains an 8-terminal screw terminal block.
Attached to the block is an 3E-3388 Connector Receptacle As. The mating plug is a 155-2264
Connector Plug As. The pin outs for both the receptacle and terminal block are shown in
Illustration 18, Illustration 19, Table 6 and Table 7.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 18 of 39
Illustration 18
g02280253
(1) PWR +
(2) PWR (3) Not Used
(4) RS-485 +
(5) RS-485 (6) RS-485 REF
(7) Not Used
(8) Not Used
Illustration 19
g02280254
Table 6
RS-485 Annunciator Deutsche Connector Pin Configuration
Terminal #
Function
Description
BATT +
+ Battery input
BATT -
- Battery input
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 19 of 39
NA
NA
RS-485 B (+)
RS-485 A (-)
RS-485 R
RS-485 Reference
NA
NA
NA
NA
Table 7
Function
Description
BATT -
- Battery input
BATT +
+ Battery input
RS-485 R
RS-485 Reference
RS-485 B (+)
RS-485 A (-)
Lamp Test SW
Lamp Test
Alarm ACK
Alarm Acknowledge
Horn Drive
LED Colors
Each pair of LEDs on the RS-485 annunciator consists of two of the following three colors: green,
amber, and red, which allows for custom configuration of status, warning and shutdown
conditions. The available colors and combinations are listed in Table 8.
Table 8
LED Colors
Row
LED 1
LED 2
Red
Amber
Red
Amber
Red
Amber
Red
Amber
Red
Amber
Red
Green
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 20 of 39
Red
Amber
Red
Amber
Red
Amber
10
Red
Amber
11
Red
Amber
12
Red
Amber
13
Green
Amber
14
Green
Amber
15
Red
Green
16
Red
Amber
Illustration 20
g02280375
Table 9
Behavior
Explanation
Red solid
Datalink diagnostic. For example: the module is wired wrong (data link),
or no terminating resistor.
Green solid
Green flashing
Loss of communication
Red/Green
alternating
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 21 of 39
one second while the right column is off. Then the right column of LED's will be lit for one
second, while the left column is off. The test cycle will occur twice. During the second run of this
test mode (during the first cycle only), the horn will be on.
The second test mode is an individual LED test mode. In this mode, the LED's will light one at a
time, starting from the top left LED, down to the left-hand module status LED, then over to the
right-hand module status LED, then up to the top right LED. Each LED will be lit for 1/2 second,
after which the LED will turn off and the next LED will be lit. At the completion of this test mode,
the cycle will restart with the first test mode. However, on subsequent runs of the first test mode,
the horn will not turn on.
The RS-485 annunciator returns to normal operation once the lamp test button is released.
Alarm Acknowledge
The RS-485 annunciator supports an acknowledge event/silence horn function from a button press
on the RS-485 annunciator or from the EMCP 4. Both cases have different behavior and are
outlined below.
When an active event is received from the EMCP 4 and is acknowledged locally with a button
press on the RS-485 annunciator module, any flashing LED tied to that event will stop flashing
and maintain a steady illumination and the horn will be silenced.
Note: Note: Only the local RS-485 annunciator module that acknowledges the active event will
change the state of its flashing LEDs and silence the horn. The acknowledge signal sent out by the
RS-485 is not broadcast to any other units on the RS-485 annunciator data link.
When an active event is received from the EMCP 4 and is acknowledged globally with a button
press on the EMCP 4 controller,the active event is transmitted to the RS-485 Annunciator module.
Any flashing LED tied to that event will stop flashing and maintain a steady illumination and the
horn will be silenced.
Note: In this case, the EMCP 4 may acknowledge active events on multiple RS-485 annunciators
simultaneously.
The horn silence / acknowledge function will cause the local horn to be silenced until another
event causes an LED to be activated.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 22 of 39
Entering AGSM
The RS-485 annunciator shall enter AGSM by depressing the two buttons on the front panel of the
RS-485 annunciator (lamp test and alarm acknowledge) for 3 seconds. The RS-485 annunciator
shall acknowledge entrance of AGSM by flashing the top 4 rows of LED's 4 times at a 1 second
rate.
After the 3 second period has timed out, the row representing the currently assigned alarm group
address will be powered on, the remaining 11 rows of LED's will not be powered on. Refer to
Table 10.
Table 10
Row
Column 1
Column 2
Off
Off
Off
Off
Off
Off
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 23 of 39
Off
Off
Off
Off
10
Off
Off
11
Off
Off
12
Off
Off
13
Off
Off
14
Off
Off
15
Off
Off
16
Off
Off
Exiting AGSM
The annunciator will exit AGSM under two possible conditions:
A time-out period without any button presses
Pressing and holding the two buttons (alarm acknowledge and horn buttons) for 3 seconds
After a period of 15 seconds without any button presses, the RS-485 annunciator will
automatically exit AGSM and disregard any changes made to the alarm group selection and
remain configured to the alarm group prior to entering AGSM.
When an alarm group selection has been made and the two buttons are pressed (lamp test and
alarm acknowledge) and held in continuously for 3 seconds, the RS-485 annunciator will update
the current configured alarm group to the current selected alarm group and then exit AGSM.
After exiting AGSM under either one of the two exit conditions listed, the RS-485 annunciator
will flash all 16 rows of LED's for 3 seconds at which time the RS-485 annunciator will enter
regular annunciation mode.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 24 of 39
Severity Level
Severity level defines which types of events the LED pair will react to. Selections that begin with
condition exists will respond to can event messages for Failure Mode Identifier (FMI) 31
condition exists.
For example, LED pair #1 is configured for "Condition Exists, Red On, Other Not Used, Horn
On" with SPN 190 (emergency stop active). This condition means that when the RS-485
annunciator receives a data from the EMCP 4 over the RS-485 annunciator data link indicating
emergency stop with FMI 31, the red LED will turn on and the horn will also turn on.
Other not used indicates that the other LED color in the pair is never used.
Green off (for example) indicates that the green LED lights when the condition chosen for this
LED pair is not active.
Most severity level selections imply Failure Mode Identifier (FMI) codes:
Condition exists that is equivalent to FMI 31
High warning can be FMI 15 or FMI 16
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 25 of 39
Engine Running
When configuring the RS-485 annunciator for engine running, special consideration must be taken
to trigger the event. The SPN shall be configured for "Auxiliary I/O #1" (SPN 701) and it shall
have a severity level configured for any one of the condition met setpoints. Digital input #1 shall
be physically wired to the active status signal that is to be used to trigger this programmed LED. If
it is only to be based upon the status of the generator set controlled by the EMCP, then an output
such as relay output #2, fuel control relay, or engine start initiated for common engine interface
generator sets on the EMCP 4 can be used. The fuel control relay or engine start initiated active
status signal is continually active only while the engine is in running.
Alarm Group #3 has LED #15 pre-configured for "Auxiliary I/O #1" and requires the actions
above to trigger an engine running event on the RS-485 annunciator.
Alarm Groups
The RS-485 annunciator may be configured for four alarm groups. Two of these alarm groups are
fixed, two are configurable groups. Selection of which alarm group is used shall be accomplished
by using the front panel of the RS-485 annunciator module as explained above in Alarm Group
Selection Mode (AGSM). Details of the preconfigured events for each of the alarm groups are
outlined below:
Alarm Group # 1 (Custom Configurable 1) - Film # 1 (refer to Table 11) and custom film
Alarm Group # 2 (Custom Configurable 2) - Film # 1 (refer to Table 11) and custom film
Alarm Group # 3 (Fixed) - Film # 1 (refer to Table 11)
Alarm Group # 4 (Fixed) - Film # 2, or Film # 3 (refer to Table 12 and Table 13)
Note: Alarm Groups # 1 and # 2 are blank until configured.
Table 11
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 26 of 39
Alarm Group 01 & 02 default film and Alarm Group 03 film assignments. NFPA 99/110
events. Includes Fuel Level, Engine Running, and Tier 4 SCR events
Row
LED Colors
Horn
Red
E-Stop Shutdown
Amber
Not Used
NA
Red
Overcrank
Amber
Not Used
NA
Red
Amber
Red
Not Used
NA
Amber
Red
Amber
Red
Overspeed Shutdown
Green
Not Used
NA
Red
Amber
Red
Amber
Red
Not Used
NA
Amber
Red
Amber
Red
Not Used
NA
Amber
Red
Not Used
NA
Amber
Green
Not Used
NA
Amber
Green
Not Used
NA
Amber
10
11
12
13
14
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 27 of 39
15
16
Red
Not Used
NA
Green
Engine Running
Red
SCR Tier 4
Amber
SCR Tier 4
Table 12
Film #3. Alarm Group 04 film assignments. NFPA 99/110 events. Includes Fuel Level and
Air Damper Shutdown. Does not include Tier 4 SCR
Row
LED Colors
Horn
Red
E-Stop Shutdown
Amber
Not Used
NA
Red
Overcrank
Amber
Not Used
NA
Red
Amber
Red
Not Used
NA
Amber
Red
Amber
Red
Overspeed Shutdown
Green
Not Used
NA
Red
Amber
Red
Amber
Red
Not Used
NA
Amber
Red
Amber
Red
Not Used
NA
Amber
Red
Not Used
NA
10
11
12
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 28 of 39
Amber
Green
Not Used
NA
Amber
Green
Not Used
NA
Amber
Red
Green
Not Used
NA
Red
SCR Tier 4
Amber
SCR Tier 4
13
14
15
16
Table 13
Alarm Group #4 Assignments excluding Tier4
Row
LED Colors
Horn
Red
E-Stop Shutdown
Amber
Not Used
NA
Red
Overcrank
Amber
Not Used
NA
Red
Amber
Red
Not Used
NA
Amber
Red
Amber
Red
Overspeed Shutdown
Green
Not Used
NA
Red
Amber
Red
Amber
Red
Not Used
NA
Amber
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 29 of 39
10
11
12
13
14
15
16
Red
Amber
Red
Not Used
NA
Amber
Red
Not Used
NA
Amber
Green
Not Used
NA
Amber
Green
Not Used
NA
Amber
Red
Green
Not Used
NA
Red
Not Used
NA
Amber
Not Used
NA
Illustration 21
g02309975
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 30 of 39
Illustration 22
Illustration 23
g02281117
4. Select the "Alarm Group" for the annunciator by choosing from the drop-down menu.
Refer to Illustration 23.
5. Double click on an LED pair to configure the pair.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 31 of 39
Illustration 24
Illustration 25
6. Select the "Trigger Condition" for the pair in the drop-down menu.
Refer to Illustration 24 and Refer to Illustration 25.
Illustration 26
7. Select the "Severity Level" for the pair in the drop-down menu.
Refer to Illustration 26.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 32 of 39
For a complete list of choices for "Severity Level", refer to the Tables below.
Illustration 27
8. Select the "Suspect Parameter Number" for the pair in the drop-down menu.
Refer to Illustration 27.
For a complete list of choices for "Suspect Parameter Number", see the Tables below.
9. The failure mode identifier does not normally require programming since the severity level
typically has this information embedded. Refer to the information below for a diagnostic
SPN.
If the "LED Trigger Condition" is configured as "General Event", the "Severity Level" can be
configured according to Table 14.
Table 14
Allowed for LED Pairs
Trigger Condition Severity Level
1-5, 7-12, 16 13-14
Low Warning
Low Shutdown
High Warning
High Shutdown
6, 15
X
X
X
X
X
X
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 33 of 39
If the LED "Trigger Condition" is configured as "Specific Event", the "Severity Level" can be
configured according to Table 15.
Table 15
Allowed for LED Pairs
Trigger Condition Severity Level
1-5, 7-12,
16
1314
Low Warning
Low Shutdown
High Warning
High Shutdown
Specific Diagnostic
X
X
X
X
X
X
X
X
X
X
6,
15
X
X
X
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 34 of 39
X
X
X
Condition Does Not Exist, Red On, Other Not Used, Horn On
Condition Does Not Exist, Amber On, Other Not Used, Horn
On
Condition Does Not Exist, Green On, Other Not Used, Horn On
X
X
X
X
For trigger condition severity level listed in the table above from "Low Warning" to "Specific
Diagnostic" the following suspect parameter number options can be used:
Table 16
Suspect Parameter Number Text
Value
38
Aftercooler Temperature
52
82
95
96
98
99
100
Crankcase Pressure
101
107
Barometric Pressure
108
110
111
158
167
Battery Voltage
168
171
172
Exhaust Temperature
173
175
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 35 of 39
Engine Speed
190
Long Distance Annunciator Data Link Fault (Root Cause Not Known)
625
639
970
1083
1084
1122
1123
1124
1125
1126
1231
1383
2433
2434
Generator Frequency
2436
Generator AC Voltage
2440
Generator AC Current
2448
2452
2456
2529
2530
3543
3581
4004
4013
4015
4157
4158
Cranking Voltage
4256
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 36 of 39
For the trigger condition severity levels listed in the table above from "Condition Exists, Red On,
other Not Used" to "Condition Does Not Exists, Green On, other Not used, Horn On" the
following suspect parameter number options can be used:
Table 17
Suspect Parameter Number Text
Value
701
702
703
704
705
706
707
708
3920
3921
3922
3923
970
1237
1239
1664
2648
3677
3829
4000
4001
4002
4003
4004
4005
Engine in Cooldown
4006
4007
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 37 of 39
4009
4011
4013
Loss of Utility
4017
4018
4019
4024
4025
Earth Fault
4028
Earth Leakage
4029
If the "Trigger Condition Severity Level" is programmed for "Diagnostic", then the failure mode
identifier for any pair of LEDs can be configured as any of the following:
Table 18
Data Erratic, Intermittent, or Incorrect
Out Of Calibration
Special Instructions
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 38 of 39
Illustration 28
Illustration 29
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasear... Page 39 of 39
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch... 11/08/2016