Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Control Valve
Area
Steam
Turbine
Mechanical
Power
( = Steam Flow)
Speed
Deviation
Governor Control
and
Steam Valve
Control
Valve
Position
Mechanical
Power
Steam
Flow
Steam Turbine
Steam Pressure at Control Valve
(Throttle Pressure)
A model that incorporates this effect, and allows for modeling of the effects of boiler dynamics on throttle
pressure, is the PSS/E TGOV5 model [2]. A block diagram of this model is shown in Figure 3. The governor
model is similar to the IEEEG1 model. Proper selection of the time constants and gains allows the modeling of
the reheater and intermediate and low-pressure turbine effects. It can be used for tandem and cross-compound
units. The valve has rate (velocity) limits as well as position (area) limits. However, steam flow is proportional
to the product of throttle pressure and valve area rather than just proportional to valve position as in the standard
governor models. The variables of the governor that interface with the other portions of the model are Po (load
reference of the governor), PT (throttle pressure) and ms (steam flow). The additional boiler controls will handle
practically any mode of control including conventional (boiler-follow), turbine-follow, coordinated optimal, and
variable pressure. The control mode is selected by the proper choice of constants.
K(1 + sT2)
SPEEDHP
1 + sT 1
UO
1
T3
1
s
Demand
Desired
MW
C2
+
K13
+
-
+
-
1
1 + sT7
+
+
K8
+
+
PMECHLP
PM2
PO
K14
S
RMIN
LMIN
KL
PE (pressure error)
Deadband
.
ms
PE
PE
+
C3
PM1
K7
K6
PMECHLP
LMAX
RMAX
PSP
K4
+
+
K12
+
1
1 + sT6
K2
1 + sTMW
K5
KMW
1 + sT5
PELEC
K3
.
ms
1 + sT4
PT
VMIN
MW
UC
Po
+
K1
VMAX
+
-
Po
CMIN
Controller
KI(1 + sT I)(1 + sT R)
s(1 + sTR1)
PE
PSP
+
-
CMIN
+
x
PT
PD
Fuel Dynamics
+
K11
K10
-sTD
(1 + sT F) (1 + sT W)
Desired
MW
K9
1
CBs
+
C1
+
.
ms
.
ms
The load reference of the governor, Po is fixed based on the initial loading of the unit (it could be adjusted based
on external signals such as modeling of AGC pulsing). Drum pressure, PD , is proportional to the integral of
steam generation less steam flow out of the boiler, ms. Throttle pressure, PT , is equal to drum pressure less a
pressure drop across superheaters and steam leads. This pressure drop varies as square of steam flow and also
with density of steam. [4,5]
Steam generation is controlled by the inputs to the boiler (fuel and air) which are driven by a three-mode
controller. In conventional control, the fuel is controlled to correct the pressure error, the difference between
throttle pressure and the pressure setpoint (rated pressure or 1.0 per unit). The three-mode controller includes
controller limits and can be adjusted to model manual or two mode control. Time delay in the fuel system is
modeled as it can be very significant, especially for coal-fired units.
2. Turbine-Follow. The turbine follow mode involves use of the turbine control valves to regulate boiler
pressure. This method can be done with practically no time delay so that boiler pressure suffers virtually no
transient deviations. Stored energy in the boiler is not used. Steam flow through the turbine and, therefore,
turbine power follows closely the amount of steam generation, i.e., the input to the boiler. The response of
turbine power is considerably slower than conventional control.
Implementation of turbine follow control using the TGOV5 model is shown in Figure 5. Fuel is no longer
controlled by pressure error but by a desired MW signal. A MW demand signal (fixed based on the initial
loading of the unit unless adjusted based on external signals such as modeling of AGC pulsing) is modified by a
frequency deviation bias, B, usually matching the units governor droop, 1/K, to form the desired MW signal.
As well as being the input to the fuel controls this desired MW signal is summed with a pressure error signal and
the power reference to form a MW error which is integrated to move the load reference Po, modeling the turbine
speed changer.
3. Coordinated Optimal. The coordinated optimal mode recognizes the advantages and disadvantages of the
conventional and turbine follow modes and the need for varying degrees of compromise between the desire for
fast response to load changes and the desire for boiler safety and good quality of control of steam conditions.
The implementation of this approach using the TGOV5 model structure is shown in Figure 6.
The MW demand signal is modified by a frequency deviation bias matching the units governor droop
characteristic to develop the desired MW. Comparison with the units actual output develops the MW error. The
desired MW signal may be sent to the boiler controls. Turbine-speed changer position is directed to reduce a
combination of MW error and pressure error to zero while the boiler controls are directed to reduce the pressure
error to zero. Depending on the cross-coupling strength between pressure and MW loops, the load response can
be adjusted to any degree between that of the conventional and turbine follow modes.
4. Variable Pressure. In the variable pressure (or often called sliding pressure) control mode, the pressure set
point is proportional to MW demand. The pressure error between set point and actual throttle pressure drives
steam generation through the fuel controls. The amount of coupling, if any, that occurs between the demand
signal and the turbine control valve position is selected based on the plants control philosophy. One
implementation of variable pressure control using the TGOV5 model structure is shown in Figure 7.
Thus the TGOV5 model can simulate each of these control strategies by judicious setting of the model gains.
Actual plant controls could be variants of the standard control philosophies or combinations of them. The
documentation further describing the above model in reference 2 gives data for typical boiler control methods
such a boiler-follow, turbine-follow, coordinated, and variable pressure for gas/oil and coal fired units.
Availability of Data
The data necessary to model the boiler and controls is rarely available. However, it is usually known under
which control mode a unit operates, e.g., boiler-follow. It is often preferable, in such cases, to represent boiler
response with typical data rather than ignore an important effect due to lack of data. Also, a number of key
parameters, such as boiler storage time constant (CB) and pressure drop coefficient C1 can often be estimated
from on-line measurements of unit response during system disturbances, or from staged tests.
.
m
Governor
Valve
PMECH
Turbine
+
PT
Po
PELEC
REF
MW
Demand
Governor
Valve
.
ms
MW
C2
PMECH
LMAX
RMAX
Desired
1
S
K14
RMIN
PO
LMIN
Turbine
PE (pressure error)
PT
Po
Deadband
.
ms
P
E
PE
.
ms
PSP
PT
P
E
CMIN
Controller
KI(1 + sT I)(1 + sT R)
s(1 + sTR1)
PSP
+
-
PE
-sTD
(1 + sTF) (1 + sT W )
C1
.
ms
Valve
(1 + sTF) (1 + sTW)
K1
1
PMECH
Turbine
.
ms
Governor
PT
Po
.
ms
Desired MW
.
ms
-sTD
1
CBs
Fuel Dynamics
Governor
CBs
Fuel Dynamics
+
PD
C1
CMIN
+
PD
PT
Valve
PMECH
Turbine
+
PT
Po
PELEC
f
KMW
MW
1 + sTMW
Desired
MW
Demand
C2
LMAX
RMAX
K14
MW
PO
RMIN
MW
C2
LMIN
Desired
Demand
x
+
PE (pressure error)
K12
PE
PE
Deadband
.
ms
K13
PE (pressure error)
Deadband
PSP
.
ms
PE
Po
CMIN
PSP
Controller
CMIN
PT
PE
C1
-sTD
K9
PD
+
CBs
CBs
C1
Fuel Dynamics
Fuel Dynamics
.
ms
(1 + sTF) (1 + sTW)
Figure 6.
PT
CMIN
PD
s(1 + sTR1)
PE
CMIN
s(1 + sTR1)
PSP
Controller
-sTD
.
ms
(1 + sTF) (1 + sTW )
Simulation Examples
To illustrate these points, loss of generation using a small example case was simulated. A single unit in the
system is tripped when carrying about 7% of the total system generation; all remaining units are assumed to be
steam units. Of these units, one is at about half-load, while the others are near full load but still with some MW
reserve to respond to frequency disturbances. Frequency dependence of network parameters is modeled.
Frequency dependence of loads and underfrequency load shedding are not, to more clearly show the effects of
the boiler controls. (Normally these would be modeled in actual studies).
In the first simulation, all steam governor/turbines were modeled using the "standard" IEEEG1 model; thus all
units are at 100% boiler pressure regardless of load, and throttle pressure will remain constant regardless of
steam flow. In the second simulation, the TGOV5 model was used for all units to allow for variations in throttle
pressure, and control constants were chosen to represent "boiler-follow" control. In this control method, the
steam valve position changes to increase steam flow and turbine power to arrest machine speed deviations
without concern for the effects of the increased steam flow on boiler pressure. It is up the boiler controls to
adjust fuel input to maintain pressure, and thus the boiler "follows" the change in turbine power. Thus, in the
second simulation, the control strategy for moving the valve is the same as in the first, but the difference is that
boiler pressure will not be constant. In the third simulation, all units were modeled in a turbine-follow control
mode as discussed above. In the fourth and final simulation, the partially loaded unit is modeled with TGOV5
using the "variable pressure" control constants; at partial load the pressure is assumed to be lower than at full
load (70% versus 100%), thus the steam valve must be open much more to achieve the same steam flow; other
units are modeled with boiler-follow controls. The frequency deviation at a system bus for the various
simulations is shown in Figure 8.
60.2
60
Frequency (Hz)
59.8
59.6
59.4
Boiler-follow
59.2
Turbine-follow
59
58.8
58.6
58.4
58.2
0
30
60
90
120
150
180
210
240
270
300
Tim e (seconds)
FIGURE 8: Effect of Boiler Modeling on Frequency for Example System with 7% Loss of Generation
The minimum frequency and maximum frequency deviation for each simulation are given in the table below:
Boiler Control Mode
Without Boiler Model
Boiler-follow
Turbine-follow
Variable pressure (one unit)
Minimum Frequency
59.34 Hz
59.20 Hz
59.20 Hz
58.35 Hz
Note that there is a difference in the lowest frequency reached with and without the boiler models. For the
boiler-follow and turbine-follow controls, this is primarily due to throttle pressure drop due to the increase in
steam flow as shown in Figure 9 below. This has an effect similar to a reduction in governor gain and is
overcome only as the boiler controls respond to restore pressure. Also, note that the response of the system
frequency is much slower when all units are under turbine-follow control when compared with boiler-follow.
The second dip in frequency seen in Figure 8 when boiler effects are modeled is often seen in recordings of
actual disturbances resulting from significant generation/load imbalances, and is usually due to this pressure drop
effect on the steam units.
1.05
1
0.95
0.9
Without
Boiler
Model
0.85
0.8
0.75
Turbinefollow
Boilerfollow
Variable
pressure
0.7
0.65
0
30
60
90
120
150
180
210
240
270
300
Tim e (seconds)
0.95
Valve Movement
with Boiler-follow
0.85
0.75
Valve Movement
with Variable
pressure
0.65
30
60
90
120
150
180
210
240
270
300
Tim e (seconds)
FIGURE 10: Comparison of Valve Movement and Mechanical Power for Part-Loaded Unit
for Boiler-Follow and Variable Pressure Control
One final simulation shows the effect of load limiting under boiler-follow control. Under load limiting, a units
controls do not allow excessive movement of the units control valve under governor control. This is often
necessary because rapid, large variations in valve position can lead to transients in the boiler which may make
operation difficult and could even lead to boiler trip. In this simulation, valve limits are set to be 10% above the
initial operating point (subject to a ultimate limit of 0.9 p.u. on machine MVA base) to model this effect. Figure
11 compares the system frequency transient for the loss of generation under three control assumptions: using a
standard IEEE governor model (boiler is not modeled and assumed to provide constant pressure at 100%),
boiler-follow, and finally boiler-follow with load limiting. In this example, only the two units with the largest
MW reserve were affected by load limiting as the other units were already near their maximum valve opening.
The figure illustrates the importance of modeling load limiting at steam plants as its effect on a units response in
providing MW reserve can be very significant.
60.2
Frequency (Hz)
60
59.8
59.6
Boiler-follow
59.4
59.2
Boiler-follow
with load limiting
59
58.8
0
30
60
90
120
150
180
210
240
270
300
Tim e (seconds)
Appendix I
Parameters:
K
T1 & T2
T3
Uo
Uc
VMAX
VMIN
T4
T5, T6, & T7
K1, K3, K5, & K7
K2, K4, K6, & K8
K9
K10
K11
K12
K13
K14
RMAX
RMIN
LMAX
LMIN
C1
C2
C3
B
CB
KI
TI
TR
TR1
CMAX
CMIN
TD
TF
TW
Psp
TMW
KL
KMW
DPe
References:
1.
IEEE Committee Report Dynamic Models for Steam and Hydro Turbines in Power Systems, IEEE
Transactions on Power Apparatus and Systems, Vol. PAS-92, pp. 1904-1915, 1973.
2.
PSS/E Program Application Guide, Power Technologies, Inc., Vol. II, pp. 22-12 - 22-18, 1998
3.
"MW Response of Fossil-Fueled Steam Units," IEEE Working Group on Power Plant Response to Load
Changes, F.P. de Mello (Chairman), Joint Power Generation Conference, IEEE Transactions on Power
Apparatus and Systems, Vol. PAS-92, No. 2, March/April 1973, pp. 455-463.
4.
"Dynamic Models for Fossil Fueled Steam Units in Power System Studies", Working Group on Prime
Mover and Energy Supply Models for System Dynamic Performance Studies, F.P. de Mello (Chairman),
IEEE Transactions on Power Systems, Vol. 6, No. 2, May 1991, p. 753.
5.
F. P. de Mello, "Boiler Models for System Dynamic Performance Studies," IEEE Transactions on Power
Systems, Vol. 6, No. 1, February 1991, pp. 66-74.