Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
EN ISO 9001
Presented by:
L I C A T
I O N
G U
I D
E L I N
E S
PPLICATION
GUIDELINE
O V E RV O LTA G E P R O T E C T I O N
Dimensioning,
testing and application
of metal oxide
surge arresters
in medium voltage
networks
Foreword
ts
in s
time interval
in V
Uc
in V
maximum continuous operating voltage of the arrester (mainly given in kV, rms)
UE
in V
maximum overvoltage at the end of an open line (mainly given in kV, peak value)
UK
in V
Um
in V
Up
in V
Ur
in V
Uref
in V
UT
in V
UTOV
in V
u(t)
in V
in m/s
in
ZK
in
1
S
The silicon technology, which is used in medium voltage by ABB High Voltage Technologies Ltd, and the
further developing of the metal oxide material opens new application spheres. All these are taken into
account in the new edition.
We hope, that you as a reader will be satisfied with our new revised edition and you will find it useful for your
purpose. We welcome amendments and suggestions in order to meet all possible customer needs.
26
1
S
Contents
in m
conductor length
BIL
in kV
in m
conductor length
in F
Ce
d
in m
in J
Ec
in J
in A
Introduction
8.3
8.4
2.1
8.5
8.6
4.1
8.7
4.2
4.3
9.1
4.4
9.2
9.3
9.4
10
10.1
10.2
10.3
10.4
In
in A
IK
in A
Iref
in A
5.1
in A
peak current of the stroke current (mainly given in kA, peak value)
5.2
i(t)
in A
5.3
Mechanical stability
5.4
Air pollution
K
L
in H
5.5
in m
protective distance
LK
in m
cable length
6.1
6.2
10.5
6.3
Temporary overvoltages
10.6
Tests
10.7
7.1
Type tests
10.8
7.2
Routine tests
10.9
7.3
Acceptance tests
7.4
Special tests
11
12
8.1
13
Conclusions
MCOV
in V
in W
p.u.
in W
heat flow from the active arrester parts to the external environment (cooling)
in V /s
S(t)
in V / s
So
in V / s
steepness of the lightning overvoltage at the point of the stroke (mainly given in kV / s)
SK
in Var
in C
temperature
in s
time
8.2
25
Bibliography
1 Introduction
Avoiding
1 p.u. = 2 x Um / 3 ,
the Um means the maximum r.m.s voltage value between the
phases in an undisturbed network operation [1].
Three types of overvoltages are essentially distinguished [2]:
Bibliography
[1] IEC Publication 99-5, First edition 1996-02 : Surge arresters Part 5 : Selection and
application recommendations.
[2] R. Rudolph und A. Mayer: berspannungsschutz von Mittelspannungskabeln. Bull.
SEV/VSE 76 (1985) 4, S. 204-208.
[3] R. Rudolph: Bemessung, Prfung und Einsatz von Metalloxid-Ableitern. Bull.
SEV/VSE 75 (1984) 23, S. 1407-1412.
[4] A. Mayer und R. Rudolph: Funkenstreckenlose berspannungsableiter ermglichen
optimalen berspannungsschutz. Brown Boveri Technik 72(1985) 12, S. 576-585.
[5] W. Schmidt: Metalloxid, ein fast idealer berspannungsableiter. Bull.
SEV/VSE 7 / 1998, S. 13-20.
[6] IEC Publication 60099-4, Edition 1.1, 1998-08: Surge arresters Part 4: Metal-oxide
surge arresters without gaps for a.c. systems.
[7] ANSI/IEEE Publication C62.11 1993: IEEE Standard for Metal-Oxide Surge Arresters
for Alternating Current Power Circuits.
[8] R. Rudolph: ZnO-Ableiter. Eine Alternative zu konventionellen Ableitern. Elektrotechnik
und Maschinenbau 5 (1983), S. 195-200.
[9] IEC Publication 71-1 (1993-12): Insulation coordination - Part 1: Definitions, principles
and rules.
[10] IEC Publication 71-2 (1996-12): Insulation coordination Part 2: Application guide.
[11] G. Balzer und K.H. Weck: Isolationskoordination von gasisolierten Schaltanlagen.
ETG - Fachbericht 32 (1990), S. 71-89.
[12] VDEW Strungs- und Schadensstatistik 1990. Verlags- und Wirtschaftsgesellschaft
der Elektrizittswerke m.b.H.
[13] A.J. Eriksson et al.: Guide to procedures for estimating the lightning performance of
transmission lines. Report of WG 01 of CIGRE Study Committee 33, Oct. 1991.
[14] K. Berger: Methoden und Resultate der Blitzforschung auf dem Monte San Salvatore bei
Lugano in den Jahren 1963 bis 1971. Bull. SEV/VSE 63 (1972) 24, S. 1403-1422.
[15] Surge arrester application guide. IEC 37 (Sec) 85, Jan 1992.
[16] R.B. Anderson and A.J. Eriksson: Lightning parameters for engineering application.
Electra, 69 (1980), S. 65-102.
[17] A.J. Eriksson et al.: A study of lightning stresses on metal oxide surge arresters.
Cigre paper 33-08 (1986).
[18] M. Christoffel: Der Einfluss von Kabelstrecken auf die berspannungsvorgnge in
bertragungssystemen mittlerer und hoher Spannungen. Brown Boveri Mitt. 51 (1964)
6, S. 369-376.
[19] A. Braun: Schirmspannungen und Schirmverluste bei Mittelspannungs-VPE-Kabeln.
Elektrizittswirtschaft 88 (1989) 26, S. 1898-1906.
[20] M. Darveniza und D.R. Mercer: Lightning protection of pole mounted transformers.
IEEE Transactions on Power Delivery, Vol. 4, No. 2, April 1989, S. 1087-1093.
[21] G. Balzer: Schaltvorgnge in Mittelspannungsnetzen und deren Bercksichtigung bei
der Planung. Brown Boveri Technik, 73 (1983) 5, S. 270-278.
[22] Non-linear metal-oxide resistor polymeric housed surge arresters without sparkgaps.
IEC 37 / 154 / CD; March 1996
[23] W.Schmidt: Die neuen POLIM -berspannungsableiter mit Silikonisolation fr
Mittelspannungsnetze. ABB Revue 2/96
24
All the parallel MO-columns of the MO-arresters without sparkgaps conduct current at the same time. The energy of the
overvoltage is in this way distributed on all the parallel arresters, so
that the energy capacity as a limiting parameter disappears.
MO-arresters can be used both with 50 Hz and with 16 2/3 Hz
because they do not conduct any follow current. On the other
hand in the spark-gap arresters the follow current flows with
16 2/3 Hz three times longer than with 50 Hz. As a result the sparkgaps and the SiC resistors are loaded with a corresponding higher
energy. In order to prevent this it is necessary to reduce the peak
value of the follow current. This asks for spark-gap arresters
with a higher nominal voltage, which however makes a considerable increasing of the protection level necessary. For the
better understanding of the facts it is necessary to add that the MOarrester may be used with d.c. voltage, the arrester with plate
spark-gaps however cannot resist this strain.
Up = 4 p.u
Diameter of blocks in mm
38
47
62
75
250
550
1000
1350
3.6
5.5
9.0
13.3
MO
SiC
0
10-4
10-2
2 x Uc
200A
5.66
[kV]
13
In = 10 kA
10
Table 1
Correlation between typical MO-resistors and the line discharge
classes acc. to IEC. Line discharge class 5 is important only in
high-voltage systems above 420 kV, and not mentioned here.
20
10 2
current wave 8 / 20 ms
10 4 [A]
1 m for Um < 24 kV
Figure 1
If this is not possible, the cross arms on the last 3 poles before the
substation or the electrical equipment must be earthed or another
set of arresters must be installed one pole in front of the
substation. In this case the upper limit for the earth connection is 2
m. The connection lines to the arrester in the case of a cable must
be as short as possible.
23
Figure 2
MO-resistors (collection) produced by ABB
Arrester type
In
kA
POLIM-DN
3.33
65
2.6
150
2000
POLIM-D
10
3.5
100
3.6
250
2000
POLIM-DA
10
3.33
100
3.5
350
2000
MWK / MWD
10
3.07
100
5.5
550
2000
POLIM-I
10
3.07
100
5.5
550
2000
POLIM-S
10
3.00
100
9.0
1000
2000
POLIM-H
20
3.19
100
13.3
1350
2000
Table 2
Electrical main data of the MV-surge arresters from ABB
(most common types). E / Uc as tested in the operating duty test.
If, for a certain arrester type, the reactive power of the parallel
capacitor bank exeeds the limiting values in Table 9, an arrester
with better energy qualities must be selected. For networks not
operating under standard voltages, the limiting values in the
column with the lower standard voltage apply for SK. If the reactive
power is very large, arresters connected parallel must be chosen.
In such a case the arrester supplier must be informed in order to
take measures to guarantee a sufficiently good current distribution
in the parallel arresters. The supplier should also be consulted
when arresters with Uc < Um are to be used.
with resin, which makes up the whole into a rigid body. The
insulating polymeric housing is then thrust over the resin block or
shrunk on it. This costruction has the disadvantage that it forcible
breaks apart when the MO-blocks are overloaded. Another
disadvantage is the fact that there are different insulating
materials, which also means that there are more boundary layers.
Therefore it is necessary to take special measures for
sealing.
Figure 3
MO-surge arresters with silicone housing. (POLIM-family)
reinforced loops or bands. The silicon is directly put on the MOresistors. This direct moulding has the advantage that no gas
volume stays in the arrester. Sealing problems and inner partial
discharges are in this way out of question. There are no interfaces
between polymeric materials where humidity can go in. An
explosion or a shattering of the housing is not possible.
13. Conclusions
11 Arresters for D.C. Voltage
Lightning overvoltages are a hazard for all the electrical equipment
in a MV network. However, surge arresters assure reliable protection against excessive overvoltage stresses. The closer the arrester
to the electrical equipment, the better the protection.
Figure 3a
MO-surge arresters with silicone housing
left: MWK for outdoor application
right: MWD for indoor application
22
SK
Ec = ----------- x [3 - (Uc / Um)2]
Assuming that the arrester must carry out this process 3 times
with no cool down phase, it follows with Uc > Um that
Ec
---Uc
6 x SK
------------ x Um
>
If the bank remains disconnected from the network after a shutdown, the arresters discharge the voltage to zero, not merely to
2 x Uc. Below 2 x Ucthe discharge current through the arrester
is very small, so that the remaining discharge takes a long time.
During this time the arrester can cool down. It releases more heat
than it receives during the remaining discharge. Therefore it was
justified in the above calculation of Ec to take into account only the
energy taken up by the arrester, up to the discharge at 2 x Uc.
Arrester type
Uc > Um
POLIM-D
MWK
MWD
POLIM-I
POLIM-S
POLIM-H
E/Uc [kJ/kV]
3.6
5.5
9.0
13.3
Um [kV]
SK[MVA]
SK[MVA]
SK[MVA]
3.6
0.67
1.03
1.69
2.50
7.2
1.35
2.07
3.39
5.01
12
2.26
3.45
5.65
8.35
17.5
3.29
5.03
8.24
12.18
24
4.52
6.90
11.30
16.70
36
6.78
10.36
16.95
25.05
SK[MVA]
Table 9
Arrester parellel to capacitor bank. Maximum allowable reactive
power SK of the bank for the indicated arrester types. Three
discharges without a cool down phase are allowed for the
arresters.
E/Uc: The arrester energy absorbtion capability in relation to Uc.
21
Due to the simple construction of the active part without sparkgaps, which means a very high stability from the mechanical point
of view, and also due to the simple construction generally
speaking, such arresters can also undertake the support insulator
function and are not in danger of exploding in case of an overload.
Silicone is the best insulating material concerning dirt, and that is
why the arresters which are insulated with silicone behave
favourable especially with high pollution.
U
[p.u.]
1.0
4/10ms
1/5ms
8/20ms
30/60ms
2000ms
0.5
I [A]
Figure 4
Normalised current-voltage ( U-I)
characteristic of a MO-surge arrester with In = 10 kA
0%=^ 7
HC Hydrophobicity
5
4
3
2
^1
100%=
Arrester type
2000
test time
3000
4000
5000
Figure 5
Change of hydrophobicity of EPDM (black) and silicone (white)
in the accelerated ageing test acc. to IEC 1109.
The short-time tests acc. to IEC 507 provide the basis for the
dimensions of the insulator. In certain cases, the insulator behaviour may deviate under actual field conditions as a result of
other parameters (eg, due to the shape of the sheds). However, it is
generally true for silicone as well as for the ceramic insulators that
extreme pollution calls for a longer creepage path.
The mentioned temporary reduction in hydrophobicity was taken
into account in the design of the POLIM arresters, and the specific
creepage path was not reduced. All of the discussed surge
arresters with silicone insulation have been designed with a
specific creepage path of at least 25 mm per kV, providing a more
than adequate safety margin. Whenever possible, all the pollution
and lifetime tests were carried out on complete MO arresters. The
tests were performed to the various standards (eg, the 1,000-hour
humidity room test to IEC 1109, the 5,000-hour aging cycle test
and the salt-fog test to IEC 507) and showed that the silicone
insulation performs better after ten years in service that the other
types of insulation.
kJ/kV Uc
POLIM-DN
0.4
0.33
0.26
65
2.6
POLIM-D
0.4
0.33
10
0.55
100
3.6
POLIM-DA
0.4
0.33
10
0.53
100
3.5
MWK, MWD
POLIM-I
0.4
0.33
10
0.48
100
3.4
POLIM-S
0.4
0.33
10
0.47
100
3.3
POLIM-H
0.4
0.33
20
1.0
100
3.2
3
2
1
2.5
0
kA kJ/kV Uc kA kJ/kV Uc
kJ/kV Uc
5
4
High current
4/10 ms
Table 3
Energy load of arresters in MV-networks
8
cm/kVrms
Creapage
4 5
7 10
15 20
salt content of water
30 40
kg/m3 80
Figure 5a
Comparison of the specific creapage distance of porcelain (black)
and silicone insulators (white), depending on the salt content in the
salt fog test acc. to IEC 507
uL x Um
Uc > ---------------T
T = 1.26
(from Figure 8)
1.4 x 14 kV
Uc > ------------------- = 15.56 kV
1.26
The arrester type needed is called MWK 16. Its Uc is 16 kV and the
protection level at In = 10 kA is 49.1 kV.
For
1.4 x 14 kV
Uc > ------------------ = 14.96 kV
1.31
uL = 1.4
20
wooden poles
earthed crossarms
30
60
30
60
Um [kV]
a [m]
a [m]
a [m]
a [m]
3.6
300
300
500
500
7.2
43
37
53
53
12
20
14
20
14
17.5
17
10
16
10
24
19
12
19
12
36
16
11
20
11
UK
F
A1
UT
MV
LV
A2
Figure 17
ZK []
Uc > 0.24 x IK x LK in kV
Arrester type
arc furnace
big capacitor batteries
very long cable sections
expensive rotating machines
Vertical
Load
N
POLIM-DN
250
50
625
POLIM-D
250
50
625
POLIM-DA
350
50
1000
MWK, MWD
350
68
1200
POLIM-I
2500
100
2000
POLIM-S
4000
100
3000
POLIM-H
6000
100
4000
Table 4
Mechanical data of MV-surge arresters, produced by ABB
Figure 6
Repelling water on silicone surface (hydrophobicity-effect)
P,Q
when Um < 24 kV
b < 0.6 m
when Um > 24 kV
Arrester with
Up = 3.8 p.u. for MO
Up = 4 p.u. for SiC
and In = 10 kA
Type of Line
Arrester Type
Um
ZK
[kV]
[]
30
3.6
60
30
7.2
60
30
12
60
30
17.5
60
30
24
60
30
36
60
The necessary measures for this are relatively simple: the cross
arms of the last three poles before the station are to be earthed. The
overvoltage which runs into the station from the modified lines
now have the same form as if it came from a line with continuous
earthed crossarms. The disadvantage of this solution is that
additional lightning overvoltages cause flashovers between the
conductor and the earth owing to the reduced insulation level of the
line. A more efficient method than the earthing the cross arms
would be to install another set of arresters one pole in front of the
substation. The effect is a very strong reduction in the amplitude of
the incoming overvoltage. This in turn leads to a protective
behaviour of the arrester at the equipment which is better than that
of earthed cross arms.
stable
operating point
Figure 7
Power loss P of the MO discs and heat flow Q from the active
arrester parts to the exterior as a function of the MO
temperature T at the continuous operating voltage Uc
9
Wooden pole
MO
LK
[m]
SiC
LK
[m]
64
45
40
30
25
21
28
23
22
20
30
20
15
11
6
4
6
5
1
1
earthed
Wooden pole
crossarms
MO
SiC MO
SiC
LK
LK
LK
LK
[m] [m] [m] [m]
6
7
3
3
64
28
9
9
50
19
4
4
40
14
7
9
32
10
3
4
26
5
4
6
4
22
2
3
28
5
5
10
4
24
3
5
22
1
1
8
1
20
1
4
LK
earthed
crossarms
MO
SiC
LK
LK
[m] [m]
17
17
10
10
14
22
11
13
19
9
7
14
15
4
3
13
17
4
3
15
1
15
1
14
thermal runaway
critical point
LK
Table 7
Maximum allowable length LK of cable sections with one-sided
arrester protection. The cable is connected to a lightning
endangered line.
Lightning overvoltage and momentary value of system voltage
having different polarities.
8 8
b<1m
8 8
8 8
8 8
18
U=660 kV
C=0
20
A
C=0,5nF
10
L (m)
C=2nF
2
1
UT
30
b (m)
1: poor
2: good
3: excellent
S=800 kV / ms
F:
U:
A:
T:
C:
1.4
7 Tests
1.35
T 1.3
Figure 15
1.25
Figure 14b
1.2
1.15
1.1
14a):
14b):
Uc
1.05
1.0
1
UTOV
10
100
1000
10'000
t (s)
Figure 8
Strength T=UTOV / Uc with respect to temporary overvoltages UTOV
as a function of their duration t at an ambient temperature (air
temperature outside the arrester) of 45C. The curve a applies to
an arrester without preload, the curve b to an arrester, preloaded
with the guaranteed energy E. t is the time duration of the
overvoltage with power frequency.
The curves apply for the MO-surge arrester type MWK.
Figure 16
MO-surge arrester type POLIM-D 12 N with disconnector,
installed on a distribution transformer
1.4 mA
1.4 mA
1.6 mA
2.2 mA
3.6 mA
5.0 mA
10
for POLIM-DN
for POLIM-D, MVK
for POLIM-DA
for MWK, MWD, POLIM-I, POLIM-C
for POLIM-S
for POLIM-H
Rated voltage Ur
This is the highest permissible r.m.s. value of the power frequency
voltage for which the arrester is dimensioned in order to operate
correctly under temporary overvoltage conditions as established
in the operating duty tests
Figure 9
MO-surge arrester type MWK after overload test with
20kA (0,2 sec) short circuit current.
Partial discharge test: this test serves to prove that the arrester is
free of partial discharge. The measurement takes place at a voltage
of 1.05 x Uc on the entire arrester. According to IEC [6] a partial
dischage level of < 50 pC is permissible. ABB arresters are tested
more strictly though and must be kept within the 5 pC limit.
(2)
Equation (2) is defined for the time interval 0 < t < 2 x U/S. U = 660
kV is assumed for lines with earthed cross arms. This is
approximately the flashover voltage of a 20 kV line insulator when
there are chopped voltage impulses with a steepness of 800 kV / s
and negative polarity.
If one puts the values U and S into equation (2), then it becomes
clear that the temporal rise in overvoltage u(t) runs about the same
for both types of line. Because the arrester limits the voltage to well
below U, the higher value S in wooden pole lines has no effect
regarding the protective distance of the arrester. Nevertheless, the
protective distances for both of these line types are different. The
reason lies in the difference in height U of the incoming
overvoltage wave. The lightning current i that passes through the
arrester reaches the approximately peak value.
2 x U - Up
i = ----------------Z
UT
T
b
A
Up
Overvoltage at transformer T
U: incoming overvoltage wave
v: propagation velocity of U
S: maximum steepness of U
A: arrester
Up: protection level of A
(3)
Figure 13
These values apply to both MO and spark-gap arresters. The
influence of capacitance C of the electrical equipment on the length
of L is clearly seen. The protective distance of the arrester for the
network operating levels of Um = 17.5 kV and 24 kV are described
in Figure 14. Here it is also clear how L decreases with the
increasing capacitance of the electrical equipment.
S=1550 kV / ms
U=3000 kV
30
C=0
10
L (m)
b (m)
C=0,5nF
5
3
C=2nF
2
1
Figure 14a
16
20
UT
0,5
b (m) 1
1,5
Z x di / dt
S=
2
u(t) =
i(t)
i/2
i/2
Z x i(t)
2
t
u(t)
overhead Line
surge impedance of F
time
total stroke current as a function of time
maximum steepness of i(t)
lightning overvoltage as a function of time
maximum steepness of u(T)
Figure 12
In 10% of all lightnings, the maximum stroke current change di/dt
is higher than 32 kA/s. When Z = 450 , every 10th lightning
stroke will cause a maximum voltage steepness S > 7200 kV/s. A
steepness of this order is to be expected in the substation only if
the lightning strikes neareby. The probability of this happening is
relatively small. As an example, a lightning stroke with a current
rate of rise of over 32 kA/s striking within 25 m of a station would
occur on the average once every 5000 years.
Substantially smaller voltage rates of rise are to be expected at the
station when the lightning stroke occurs far from the substation.
Due to corona damping, the front of the overvoltage wave flattens
out as it proceeds from the point of the stroke towards the station.
If So is the steepness at the location of the stroke, the steepness
along the length d of the line decreases to the value
1
S = ----------------1/So + K x d
20 kV network with
earthed cross arms
Time interval
ts [years]
1
S[kV/ms]
2
S[kV/ms]
1
S[kV/ms]
2
S[kV/ms]
600
1940
1850
1060
820
400
1630
1530
920
730
300
1450
1350
820
660
200
1200
1100
700
580
100
820
660
520
440
Table 6
Expected steepness S from lightning overvoltages in MV substations: The shown values of S will, on the average, be exceeded
once in the time interval ts.
1 in the case of single phase lightning strikes
2 in the case of three phase lightning strikes
Overhead line
15
Wooden poles
Earthed cross
arms
U [kV]
3000
660
S [kV/s]
1550
800
For the arrester to meet the needs of the network system, two
conditons are necessary to be fulfilled in the selection of the
maximum continuous operating voltage Uc:
Uc must be higher than the constant power frequency voltage at
the arrester terminal.
Overload test: this test shows the behaviour of the arrester under
overload. During the test the arrester is loaded deliberately with
increasing voltage up to destruction and up to the appearance of
the system short current. Because of the special construction
(completely moulded) and the chosen insulation material
(silicone) the ABB MV-arresters are safe from explosion and
destruction up to the highest tested currents. Silicone is a self
extinguishing material. Fire is not caused by downfalling burning
insulation-material.
UTOV
Uc > ---------T(t)
Weather-aging test: the test shows the long time behaviour of the
insulation material and the construction in case of cyclical
environmental situations like warmth, humidity, rain, saltfog and
UV rays during the continuous voltage applied. The test extends on
a totally duration of 5000 hours.
Uc >
Um
Um
Uc > ------ for the arrester between transformer neutral and earth
3
12
U c > Um
1.1 x Um
1.05 x Um
Uc > ------------- = 0.83 Um
T
8.3. Networks with Solidly Earthed Neutral Systems (Ce < 1.4)
1.4 x Um
Uc > 0.667 x U m
Uc > U m
Um
Uc > ----------for arresters between phase and earth.
T
Generally speaking, the earth fault monitoring would switch off the
earth fault quickly (t < 3 s ): therefore T = 1.28.
Under extremely poor earthing conditions, e.g. in desert regions,
only a slight fault current flows in the case of a remote earth fault. If
this is not caught by monitoring, switching off will not take place.
The arresters in the vicinity of the earth fault are then loaded for a
long period of time with Um. In such cases it is advisable to choose
Uc > Um.
Uc > U m
a)
A1
A2
A3
b)
A4
Uc > 0,667 x Um
transformer
protection with 6 arresters
neptun design
four identical arresters with Uc > 0.667 x Um
b
A
Overvoltage at the line end E
3.6
7.2
12
17.5
24
36
BIL
kV
40
60
75
95
125
170
Up
kV
12
24
40
58.3
79.9
119.9
3.33
2.5
1.88
1.63
1.56
1.42
BIL / Up
Up
Figure 11
2 x S x (a + b)
UE = UP + -------------------- v = 300 m/s
v
Experience has shown that a safety factor of 1.2 is sufficient
between the BIL of the electrical equipment and the lightning
overvoltage UE at the electrical equipment.
BIL
2 x S x (a + b)
------ > UE = Up + -------------------1.2
v
Table 5
Withstand voltage (BIL) acc. IEC [9] and protection level of modern
surge arresters with Up = 4p.u.
The factor 1.4 is generously calculated because it is to be taken into
account that the overvoltage can exceed UP in the electrical
equipment. Reflection effects cause increasing overvoltage at the
electrical equipment with increasing distance from the arrester.
After a certain distance the arrester protection is insufficient. The
protective distance L is understood to be the maximum distance
between the arrester and the electrical equipment allowing
sufficient protection.
Figure 10
13
UE
The more the Basic Insulation Level (BIL) exceeds the protection
level UP of the arrester, the better the electrical equipment is
protected against lightning overvoltages. Modern arresters with
UP = 3.33 x UC and under this value, maintain UP < 4 p.u. even
when placed in a system with high-ohmic insulated neutral. For
electrical equipment which is subject to lightning overvoltages ,
the [9] recommends the indicated BIL values given in Table 5. In
addition, the IEC [10] recommends for MV networks BIL > 1.4 x
UP. As can be seen in Table 5, modern arresters fulfill this
requirement.
kV
Um
14
U c > Um
1.1 x Um
1.05 x Um
Uc > ------------- = 0.83 Um
T
8.3. Networks with Solidly Earthed Neutral Systems (Ce < 1.4)
1.4 x Um
Uc > 0.667 x U m
Uc > U m
Um
Uc > ----------for arresters between phase and earth.
T
Generally speaking, the earth fault monitoring would switch off the
earth fault quickly (t < 3 s ): therefore T = 1.28.
Under extremely poor earthing conditions, e.g. in desert regions,
only a slight fault current flows in the case of a remote earth fault. If
this is not caught by monitoring, switching off will not take place.
The arresters in the vicinity of the earth fault are then loaded for a
long period of time with Um. In such cases it is advisable to choose
Uc > Um.
Uc > U m
a)
A1
A2
A3
b)
A4
Uc > 0,667 x Um
transformer
protection with 6 arresters
neptun design
four identical arresters with Uc > 0.667 x Um
b
A
Overvoltage at the line end E
3.6
7.2
12
17.5
24
36
BIL
kV
40
60
75
95
125
170
Up
kV
12
24
40
58.3
79.9
119.9
3.33
2.5
1.88
1.63
1.56
1.42
BIL / Up
Up
Figure 11
2 x S x (a + b)
UE = UP + -------------------- v = 300 m/s
v
Experience has shown that a safety factor of 1.2 is sufficient
between the BIL of the electrical equipment and the lightning
overvoltage UE at the electrical equipment.
BIL
2 x S x (a + b)
------ > UE = Up + -------------------1.2
v
Table 5
Withstand voltage (BIL) acc. IEC [9] and protection level of modern
surge arresters with Up = 4p.u.
The factor 1.4 is generously calculated because it is to be taken into
account that the overvoltage can exceed UP in the electrical
equipment. Reflection effects cause increasing overvoltage at the
electrical equipment with increasing distance from the arrester.
After a certain distance the arrester protection is insufficient. The
protective distance L is understood to be the maximum distance
between the arrester and the electrical equipment allowing
sufficient protection.
Figure 10
13
UE
The more the Basic Insulation Level (BIL) exceeds the protection
level UP of the arrester, the better the electrical equipment is
protected against lightning overvoltages. Modern arresters with
UP = 3.33 x UC and under this value, maintain UP < 4 p.u. even
when placed in a system with high-ohmic insulated neutral. For
electrical equipment which is subject to lightning overvoltages ,
the [9] recommends the indicated BIL values given in Table 5. In
addition, the IEC [10] recommends for MV networks BIL > 1.4 x
UP. As can be seen in Table 5, modern arresters fulfill this
requirement.
kV
Um
14
Z x di / dt
S=
2
u(t) =
i(t)
i/2
i/2
Z x i(t)
2
t
u(t)
overhead Line
surge impedance of F
time
total stroke current as a function of time
maximum steepness of i(t)
lightning overvoltage as a function of time
maximum steepness of u(T)
Figure 12
In 10% of all lightnings, the maximum stroke current change di/dt
is higher than 32 kA/s. When Z = 450 , every 10th lightning
stroke will cause a maximum voltage steepness S > 7200 kV/s. A
steepness of this order is to be expected in the substation only if
the lightning strikes neareby. The probability of this happening is
relatively small. As an example, a lightning stroke with a current
rate of rise of over 32 kA/s striking within 25 m of a station would
occur on the average once every 5000 years.
Substantially smaller voltage rates of rise are to be expected at the
station when the lightning stroke occurs far from the substation.
Due to corona damping, the front of the overvoltage wave flattens
out as it proceeds from the point of the stroke towards the station.
If So is the steepness at the location of the stroke, the steepness
along the length d of the line decreases to the value
1
S = ----------------1/So + K x d
20 kV network with
earthed cross arms
Time interval
ts [years]
1
S[kV/ms]
2
S[kV/ms]
1
S[kV/ms]
2
S[kV/ms]
600
1940
1850
1060
820
400
1630
1530
920
730
300
1450
1350
820
660
200
1200
1100
700
580
100
820
660
520
440
Table 6
Expected steepness S from lightning overvoltages in MV substations: The shown values of S will, on the average, be exceeded
once in the time interval ts.
1 in the case of single phase lightning strikes
2 in the case of three phase lightning strikes
Overhead line
15
Wooden poles
Earthed cross
arms
U [kV]
3000
660
S [kV/s]
1550
800
For the arrester to meet the needs of the network system, two
conditons are necessary to be fulfilled in the selection of the
maximum continuous operating voltage Uc:
Uc must be higher than the constant power frequency voltage at
the arrester terminal.
Overload test: this test shows the behaviour of the arrester under
overload. During the test the arrester is loaded deliberately with
increasing voltage up to destruction and up to the appearance of
the system short current. Because of the special construction
(completely moulded) and the chosen insulation material
(silicone) the ABB MV-arresters are safe from explosion and
destruction up to the highest tested currents. Silicone is a self
extinguishing material. Fire is not caused by downfalling burning
insulation-material.
UTOV
Uc > ---------T(t)
Weather-aging test: the test shows the long time behaviour of the
insulation material and the construction in case of cyclical
environmental situations like warmth, humidity, rain, saltfog and
UV rays during the continuous voltage applied. The test extends on
a totally duration of 5000 hours.
Uc >
Um
Um
Uc > ------ for the arrester between transformer neutral and earth
3
12
Rated voltage Ur
This is the highest permissible r.m.s. value of the power frequency
voltage for which the arrester is dimensioned in order to operate
correctly under temporary overvoltage conditions as established
in the operating duty tests
Figure 9
MO-surge arrester type MWK after overload test with
20kA (0,2 sec) short circuit current.
Partial discharge test: this test serves to prove that the arrester is
free of partial discharge. The measurement takes place at a voltage
of 1.05 x Uc on the entire arrester. According to IEC [6] a partial
dischage level of < 50 pC is permissible. ABB arresters are tested
more strictly though and must be kept within the 5 pC limit.
(2)
Equation (2) is defined for the time interval 0 < t < 2 x U/S. U = 660
kV is assumed for lines with earthed cross arms. This is
approximately the flashover voltage of a 20 kV line insulator when
there are chopped voltage impulses with a steepness of 800 kV / s
and negative polarity.
If one puts the values U and S into equation (2), then it becomes
clear that the temporal rise in overvoltage u(t) runs about the same
for both types of line. Because the arrester limits the voltage to well
below U, the higher value S in wooden pole lines has no effect
regarding the protective distance of the arrester. Nevertheless, the
protective distances for both of these line types are different. The
reason lies in the difference in height U of the incoming
overvoltage wave. The lightning current i that passes through the
arrester reaches the approximately peak value.
2 x U - Up
i = ----------------Z
UT
T
b
A
Up
Overvoltage at transformer T
U: incoming overvoltage wave
v: propagation velocity of U
S: maximum steepness of U
A: arrester
Up: protection level of A
(3)
Figure 13
These values apply to both MO and spark-gap arresters. The
influence of capacitance C of the electrical equipment on the length
of L is clearly seen. The protective distance of the arrester for the
network operating levels of Um = 17.5 kV and 24 kV are described
in Figure 14. Here it is also clear how L decreases with the
increasing capacitance of the electrical equipment.
S=1550 kV / ms
U=3000 kV
30
C=0
10
L (m)
b (m)
C=0,5nF
5
3
C=2nF
2
1
Figure 14a
16
20
UT
0,5
b (m) 1
1,5
U=660 kV
C=0
20
A
C=0,5nF
10
L (m)
C=2nF
2
1
UT
30
b (m)
1: poor
2: good
3: excellent
S=800 kV / ms
F:
U:
A:
T:
C:
1.4
7 Tests
1.35
T 1.3
Figure 15
1.25
Figure 14b
1.2
1.15
1.1
14a):
14b):
Uc
1.05
1.0
1
UTOV
10
100
1000
10'000
t (s)
Figure 8
Strength T=UTOV / Uc with respect to temporary overvoltages UTOV
as a function of their duration t at an ambient temperature (air
temperature outside the arrester) of 45C. The curve a applies to
an arrester without preload, the curve b to an arrester, preloaded
with the guaranteed energy E. t is the time duration of the
overvoltage with power frequency.
The curves apply for the MO-surge arrester type MWK.
Figure 16
MO-surge arrester type POLIM-D 12 N with disconnector,
installed on a distribution transformer
1.4 mA
1.4 mA
1.6 mA
2.2 mA
3.6 mA
5.0 mA
10
for POLIM-DN
for POLIM-D, MVK
for POLIM-DA
for MWK, MWD, POLIM-I, POLIM-C
for POLIM-S
for POLIM-H
Figure 6
Repelling water on silicone surface (hydrophobicity-effect)
P,Q
when Um < 24 kV
b < 0.6 m
when Um > 24 kV
Arrester with
Up = 3.8 p.u. for MO
Up = 4 p.u. for SiC
and In = 10 kA
Type of Line
Arrester Type
Um
ZK
[kV]
[]
30
3.6
60
30
7.2
60
30
12
60
30
17.5
60
30
24
60
30
36
60
The necessary measures for this are relatively simple: the cross
arms of the last three poles before the station are to be earthed. The
overvoltage which runs into the station from the modified lines
now have the same form as if it came from a line with continuous
earthed crossarms. The disadvantage of this solution is that
additional lightning overvoltages cause flashovers between the
conductor and the earth owing to the reduced insulation level of the
line. A more efficient method than the earthing the cross arms
would be to install another set of arresters one pole in front of the
substation. The effect is a very strong reduction in the amplitude of
the incoming overvoltage. This in turn leads to a protective
behaviour of the arrester at the equipment which is better than that
of earthed cross arms.
stable
operating point
Figure 7
Power loss P of the MO discs and heat flow Q from the active
arrester parts to the exterior as a function of the MO
temperature T at the continuous operating voltage Uc
9
Wooden pole
MO
LK
[m]
SiC
LK
[m]
64
45
40
30
25
21
28
23
22
20
30
20
15
11
6
4
6
5
1
1
earthed
Wooden pole
crossarms
MO
SiC MO
SiC
LK
LK
LK
LK
[m] [m] [m] [m]
6
7
3
3
64
28
9
9
50
19
4
4
40
14
7
9
32
10
3
4
26
5
4
6
4
22
2
3
28
5
5
10
4
24
3
5
22
1
1
8
1
20
1
4
LK
earthed
crossarms
MO
SiC
LK
LK
[m] [m]
17
17
10
10
14
22
11
13
19
9
7
14
15
4
3
13
17
4
3
15
1
15
1
14
thermal runaway
critical point
LK
Table 7
Maximum allowable length LK of cable sections with one-sided
arrester protection. The cable is connected to a lightning
endangered line.
Lightning overvoltage and momentary value of system voltage
having different polarities.
8 8
b<1m
8 8
8 8
8 8
18
wooden poles
earthed crossarms
30
60
30
60
Um [kV]
a [m]
a [m]
a [m]
a [m]
3.6
300
300
500
500
7.2
43
37
53
53
12
20
14
20
14
17.5
17
10
16
10
24
19
12
19
12
36
16
11
20
11
UK
F
A1
UT
MV
LV
A2
Figure 17
ZK []
Uc > 0.24 x IK x LK in kV
Arrester type
arc furnace
big capacitor batteries
very long cable sections
expensive rotating machines
Vertical
Load
N
POLIM-DN
250
50
625
POLIM-D
250
50
625
POLIM-DA
350
50
1000
MWK, MWD
350
68
1200
POLIM-I
2500
100
2000
POLIM-S
4000
100
3000
POLIM-H
6000
100
4000
Table 4
Mechanical data of MV-surge arresters, produced by ABB
0%=^ 7
HC Hydrophobicity
5
4
3
2
^1
100%=
Arrester type
2000
test time
3000
4000
5000
Figure 5
Change of hydrophobicity of EPDM (black) and silicone (white)
in the accelerated ageing test acc. to IEC 1109.
The short-time tests acc. to IEC 507 provide the basis for the
dimensions of the insulator. In certain cases, the insulator behaviour may deviate under actual field conditions as a result of
other parameters (eg, due to the shape of the sheds). However, it is
generally true for silicone as well as for the ceramic insulators that
extreme pollution calls for a longer creepage path.
The mentioned temporary reduction in hydrophobicity was taken
into account in the design of the POLIM arresters, and the specific
creepage path was not reduced. All of the discussed surge
arresters with silicone insulation have been designed with a
specific creepage path of at least 25 mm per kV, providing a more
than adequate safety margin. Whenever possible, all the pollution
and lifetime tests were carried out on complete MO arresters. The
tests were performed to the various standards (eg, the 1,000-hour
humidity room test to IEC 1109, the 5,000-hour aging cycle test
and the salt-fog test to IEC 507) and showed that the silicone
insulation performs better after ten years in service that the other
types of insulation.
kJ/kV Uc
POLIM-DN
0.4
0.33
0.26
65
2.6
POLIM-D
0.4
0.33
10
0.55
100
3.6
POLIM-DA
0.4
0.33
10
0.53
100
3.5
MWK, MWD
POLIM-I
0.4
0.33
10
0.48
100
3.4
POLIM-S
0.4
0.33
10
0.47
100
3.3
POLIM-H
0.4
0.33
20
1.0
100
3.2
3
2
1
2.5
0
kA kJ/kV Uc kA kJ/kV Uc
kJ/kV Uc
5
4
High current
4/10 ms
Table 3
Energy load of arresters in MV-networks
8
cm/kVrms
Creapage
4 5
7 10
15 20
salt content of water
30 40
kg/m3 80
Figure 5a
Comparison of the specific creapage distance of porcelain (black)
and silicone insulators (white), depending on the salt content in the
salt fog test acc. to IEC 507
uL x Um
Uc > ---------------T
T = 1.26
(from Figure 8)
1.4 x 14 kV
Uc > ------------------- = 15.56 kV
1.26
The arrester type needed is called MWK 16. Its Uc is 16 kV and the
protection level at In = 10 kA is 49.1 kV.
For
1.4 x 14 kV
Uc > ------------------ = 14.96 kV
1.31
uL = 1.4
20
SK
Ec = ----------- x [3 - (Uc / Um)2]
Assuming that the arrester must carry out this process 3 times
with no cool down phase, it follows with Uc > Um that
Ec
---Uc
6 x SK
------------ x Um
>
If the bank remains disconnected from the network after a shutdown, the arresters discharge the voltage to zero, not merely to
2 x Uc. Below 2 x Ucthe discharge current through the arrester
is very small, so that the remaining discharge takes a long time.
During this time the arrester can cool down. It releases more heat
than it receives during the remaining discharge. Therefore it was
justified in the above calculation of Ec to take into account only the
energy taken up by the arrester, up to the discharge at 2 x Uc.
Arrester type
Uc > Um
POLIM-D
MWK
MWD
POLIM-I
POLIM-S
POLIM-H
E/Uc [kJ/kV]
3.6
5.5
9.0
13.3
Um [kV]
SK[MVA]
SK[MVA]
SK[MVA]
3.6
0.67
1.03
1.69
2.50
7.2
1.35
2.07
3.39
5.01
12
2.26
3.45
5.65
8.35
17.5
3.29
5.03
8.24
12.18
24
4.52
6.90
11.30
16.70
36
6.78
10.36
16.95
25.05
SK[MVA]
Table 9
Arrester parellel to capacitor bank. Maximum allowable reactive
power SK of the bank for the indicated arrester types. Three
discharges without a cool down phase are allowed for the
arresters.
E/Uc: The arrester energy absorbtion capability in relation to Uc.
21
Due to the simple construction of the active part without sparkgaps, which means a very high stability from the mechanical point
of view, and also due to the simple construction generally
speaking, such arresters can also undertake the support insulator
function and are not in danger of exploding in case of an overload.
Silicone is the best insulating material concerning dirt, and that is
why the arresters which are insulated with silicone behave
favourable especially with high pollution.
U
[p.u.]
1.0
4/10ms
1/5ms
8/20ms
30/60ms
2000ms
0.5
I [A]
Figure 4
Normalised current-voltage ( U-I)
characteristic of a MO-surge arrester with In = 10 kA
Arrester type
In
kA
POLIM-DN
3.33
65
2.6
150
2000
POLIM-D
10
3.5
100
3.6
250
2000
POLIM-DA
10
3.33
100
3.5
350
2000
MWK / MWD
10
3.07
100
5.5
550
2000
POLIM-I
10
3.07
100
5.5
550
2000
POLIM-S
10
3.00
100
9.0
1000
2000
POLIM-H
20
3.19
100
13.3
1350
2000
Table 2
Electrical main data of the MV-surge arresters from ABB
(most common types). E / Uc as tested in the operating duty test.
If, for a certain arrester type, the reactive power of the parallel
capacitor bank exeeds the limiting values in Table 9, an arrester
with better energy qualities must be selected. For networks not
operating under standard voltages, the limiting values in the
column with the lower standard voltage apply for SK. If the reactive
power is very large, arresters connected parallel must be chosen.
In such a case the arrester supplier must be informed in order to
take measures to guarantee a sufficiently good current distribution
in the parallel arresters. The supplier should also be consulted
when arresters with Uc < Um are to be used.
with resin, which makes up the whole into a rigid body. The
insulating polymeric housing is then thrust over the resin block or
shrunk on it. This costruction has the disadvantage that it forcible
breaks apart when the MO-blocks are overloaded. Another
disadvantage is the fact that there are different insulating
materials, which also means that there are more boundary layers.
Therefore it is necessary to take special measures for
sealing.
Figure 3
MO-surge arresters with silicone housing. (POLIM-family)
reinforced loops or bands. The silicon is directly put on the MOresistors. This direct moulding has the advantage that no gas
volume stays in the arrester. Sealing problems and inner partial
discharges are in this way out of question. There are no interfaces
between polymeric materials where humidity can go in. An
explosion or a shattering of the housing is not possible.
13. Conclusions
11 Arresters for D.C. Voltage
Lightning overvoltages are a hazard for all the electrical equipment
in a MV network. However, surge arresters assure reliable protection against excessive overvoltage stresses. The closer the arrester
to the electrical equipment, the better the protection.
Figure 3a
MO-surge arresters with silicone housing
left: MWK for outdoor application
right: MWD for indoor application
22
All the parallel MO-columns of the MO-arresters without sparkgaps conduct current at the same time. The energy of the
overvoltage is in this way distributed on all the parallel arresters, so
that the energy capacity as a limiting parameter disappears.
MO-arresters can be used both with 50 Hz and with 16 2/3 Hz
because they do not conduct any follow current. On the other
hand in the spark-gap arresters the follow current flows with
16 2/3 Hz three times longer than with 50 Hz. As a result the sparkgaps and the SiC resistors are loaded with a corresponding higher
energy. In order to prevent this it is necessary to reduce the peak
value of the follow current. This asks for spark-gap arresters
with a higher nominal voltage, which however makes a considerable increasing of the protection level necessary. For the
better understanding of the facts it is necessary to add that the MOarrester may be used with d.c. voltage, the arrester with plate
spark-gaps however cannot resist this strain.
Up = 4 p.u
Diameter of blocks in mm
38
47
62
75
250
550
1000
1350
3.6
5.5
9.0
13.3
MO
SiC
0
10-4
10-2
2 x Uc
200A
5.66
[kV]
13
In = 10 kA
10
Table 1
Correlation between typical MO-resistors and the line discharge
classes acc. to IEC. Line discharge class 5 is important only in
high-voltage systems above 420 kV, and not mentioned here.
20
10 2
current wave 8 / 20 ms
10 4 [A]
1 m for Um < 24 kV
Figure 1
If this is not possible, the cross arms on the last 3 poles before the
substation or the electrical equipment must be earthed or another
set of arresters must be installed one pole in front of the
substation. In this case the upper limit for the earth connection is 2
m. The connection lines to the arrester in the case of a cable must
be as short as possible.
23
Figure 2
MO-resistors (collection) produced by ABB
1 Introduction
Avoiding
1 p.u. = 2 x Um / 3 ,
the Um means the maximum r.m.s voltage value between the
phases in an undisturbed network operation [1].
Three types of overvoltages are essentially distinguished [2]:
Bibliography
[1] IEC Publication 99-5, First edition 1996-02 : Surge arresters Part 5 : Selection and
application recommendations.
[2] R. Rudolph und A. Mayer: berspannungsschutz von Mittelspannungskabeln. Bull.
SEV/VSE 76 (1985) 4, S. 204-208.
[3] R. Rudolph: Bemessung, Prfung und Einsatz von Metalloxid-Ableitern. Bull.
SEV/VSE 75 (1984) 23, S. 1407-1412.
[4] A. Mayer und R. Rudolph: Funkenstreckenlose berspannungsableiter ermglichen
optimalen berspannungsschutz. Brown Boveri Technik 72(1985) 12, S. 576-585.
[5] W. Schmidt: Metalloxid, ein fast idealer berspannungsableiter. Bull.
SEV/VSE 7 / 1998, S. 13-20.
[6] IEC Publication 60099-4, Edition 1.1, 1998-08: Surge arresters Part 4: Metal-oxide
surge arresters without gaps for a.c. systems.
[7] ANSI/IEEE Publication C62.11 1993: IEEE Standard for Metal-Oxide Surge Arresters
for Alternating Current Power Circuits.
[8] R. Rudolph: ZnO-Ableiter. Eine Alternative zu konventionellen Ableitern. Elektrotechnik
und Maschinenbau 5 (1983), S. 195-200.
[9] IEC Publication 71-1 (1993-12): Insulation coordination - Part 1: Definitions, principles
and rules.
[10] IEC Publication 71-2 (1996-12): Insulation coordination Part 2: Application guide.
[11] G. Balzer und K.H. Weck: Isolationskoordination von gasisolierten Schaltanlagen.
ETG - Fachbericht 32 (1990), S. 71-89.
[12] VDEW Strungs- und Schadensstatistik 1990. Verlags- und Wirtschaftsgesellschaft
der Elektrizittswerke m.b.H.
[13] A.J. Eriksson et al.: Guide to procedures for estimating the lightning performance of
transmission lines. Report of WG 01 of CIGRE Study Committee 33, Oct. 1991.
[14] K. Berger: Methoden und Resultate der Blitzforschung auf dem Monte San Salvatore bei
Lugano in den Jahren 1963 bis 1971. Bull. SEV/VSE 63 (1972) 24, S. 1403-1422.
[15] Surge arrester application guide. IEC 37 (Sec) 85, Jan 1992.
[16] R.B. Anderson and A.J. Eriksson: Lightning parameters for engineering application.
Electra, 69 (1980), S. 65-102.
[17] A.J. Eriksson et al.: A study of lightning stresses on metal oxide surge arresters.
Cigre paper 33-08 (1986).
[18] M. Christoffel: Der Einfluss von Kabelstrecken auf die berspannungsvorgnge in
bertragungssystemen mittlerer und hoher Spannungen. Brown Boveri Mitt. 51 (1964)
6, S. 369-376.
[19] A. Braun: Schirmspannungen und Schirmverluste bei Mittelspannungs-VPE-Kabeln.
Elektrizittswirtschaft 88 (1989) 26, S. 1898-1906.
[20] M. Darveniza und D.R. Mercer: Lightning protection of pole mounted transformers.
IEEE Transactions on Power Delivery, Vol. 4, No. 2, April 1989, S. 1087-1093.
[21] G. Balzer: Schaltvorgnge in Mittelspannungsnetzen und deren Bercksichtigung bei
der Planung. Brown Boveri Technik, 73 (1983) 5, S. 270-278.
[22] Non-linear metal-oxide resistor polymeric housed surge arresters without sparkgaps.
IEC 37 / 154 / CD; March 1996
[23] W.Schmidt: Die neuen POLIM -berspannungsableiter mit Silikonisolation fr
Mittelspannungsnetze. ABB Revue 2/96
24
Contents
in m
conductor length
BIL
in kV
in m
conductor length
in F
Ce
d
in m
in J
Ec
in J
in A
Introduction
8.3
8.4
2.1
8.5
8.6
4.1
8.7
4.2
4.3
9.1
4.4
9.2
9.3
9.4
10
10.1
10.2
10.3
10.4
In
in A
IK
in A
Iref
in A
5.1
in A
peak current of the stroke current (mainly given in kA, peak value)
5.2
i(t)
in A
5.3
Mechanical stability
5.4
Air pollution
K
L
in H
5.5
in m
protective distance
LK
in m
cable length
6.1
6.2
10.5
6.3
Temporary overvoltages
10.6
Tests
10.7
7.1
Type tests
10.8
7.2
Routine tests
10.9
7.3
Acceptance tests
7.4
Special tests
11
12
8.1
13
Conclusions
MCOV
in V
in W
p.u.
in W
heat flow from the active arrester parts to the external environment (cooling)
in V /s
S(t)
in V / s
So
in V / s
steepness of the lightning overvoltage at the point of the stroke (mainly given in kV / s)
SK
in Var
in C
temperature
in s
time
8.2
25
Bibliography
Foreword
ts
in s
time interval
in V
Uc
in V
maximum continuous operating voltage of the arrester (mainly given in kV, rms)
UE
in V
maximum overvoltage at the end of an open line (mainly given in kV, peak value)
UK
in V
Um
in V
Up
in V
Ur
in V
Uref
in V
UT
in V
UTOV
in V
u(t)
in V
in m/s
in
ZK
in
1
S
The silicon technology, which is used in medium voltage by ABB High Voltage Technologies Ltd, and the
further developing of the metal oxide material opens new application spheres. All these are taken into
account in the new edition.
We hope, that you as a reader will be satisfied with our new revised edition and you will find it useful for your
purpose. We welcome amendments and suggestions in order to meet all possible customer needs.
26
1
S
EN ISO 9001
Presented by:
L I C A T
I O N
G U
I D
E L I N
E S
PPLICATION
GUIDELINE
O V E RV O LTA G E P R O T E C T I O N
Dimensioning,
testing and application
of metal oxide
surge arresters
in medium voltage
networks