Sei sulla pagina 1di 13

Project:

Customer:
Engineer:
Pump Manufacturer:

Technical Data Submittal Documents


Model GPD
Diesel Engine Driven Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections
Note: The drawings included in this package are for controllers covered under our standard offering.

Actual AS BUILT drawings may differ from what is shown in this package.

August 2016

Technical Data
GPD Diesel Fire Pump Controller
Built to NFPA 20 (latest edition)
Standard,
Listings,
Approvals and
Certifications

Underwriters Laboratory (UL)

UL218 - Fire Pump Controllers


CSA C22.2 No. 14 Industrial Control Equipment

FM Global

Class 1321/1323

New York City

Accepted for use in the City of New York by the Department of Buildings

Seismic Certification

See page 5 for details

Optional

CE Mark

Enclosure

Various EN, IEC & CEE directives and standards

Protection Rating
Standard: NEMA 2 (IP31)
Optional
NEMA 12
NEMA 3
NEMA 3R
NEMA 4

NEMA 4X-304 sst painted


NEMA 4X-304 sst brushed finish
NEMA 4X-316 sst painted
NEMA 4X-316 sst brushed finish

Accessories
Bottom entry gland plate
Lifting Lugs
Keylock handle
Ambient
Temperature
Rating

Paint Specifications
Red RAL3002
Powder coating
Glossy textured finish

Standard
5C to 40C / 41F to 104F
Optional
5C to 55C / 41F to 131F
AC

General

IP54
IP55
IP65
IP66

DC
Grounding system
Battery chargers

120V / 1ph / 60hz


208V to 240V / 1ph / 50-60hz
12VDC
24VDC
Negative
Two independent fully automatic
10A continuous charge
500mA trickle charge

Battery 1 & Battery 2 voltage


Electrical Reading Battery 1 & Battery 2 charging amperage
Charging mode
Pressure Reading

Pressure and
Event Recorder

August 2016

Continuous system pressure display


Cut-in and Cut-out pressure setting
Pressure readings with date stamp
Event recording with date stamp
Under regular maintained operation, events can be stored in memory for up to 5 years
Data viewable on operator interface display screen
Downloadable by USB port to external memory device

Technical Data
GPD Diesel Fire Pump Controller

Pressure sensing

Audible Alarm

Visual & Audible


Alarms

Remote Alarm
Contacts

Pressure transducer and run test solenoid valve assembly for fresh water application
Pressure sensing connection 1/2 Female NPT
Drain connection 3/8
Rated and calibrated for 0-500psi working pressure
Externally mounted with protective cover
4 alarm bell - 85 dB at 10ft. (3m)
Visual only
Periodic test
Engine run
Main switch in HAND
Main switch AUTO
High raw water temperature
ECM warning
Pump room temperature (oF or oC)
Visual and Audible
Battery #1 & battery #2 failure
Overspeed
Charger #1 & Charger #2 failure
Low oil pressure
AC power available
High engine temperature
Low pump room temperature
Fail to start
System overpressure
High fuel level
PLD low suction pressure
ECM fault
ECM Selector switch in alternate position

Cranking Cycle
Main switch in OFF
Low raw water flow

Low fuel level


Water reservoir low
Fuel tank leak
Fail when running
Fuel injection malfunction
Low engine temperature

DPDT-8A-250V.AC
Engine run
Common controller trouble
Charger #1 & Charger #2 failure
Pressure line failure
Common engine trouble
Battery #1 & battery #2 failure
Overspeed
High engine temperature
DC failure
Fail when running
Fail to start
Fuel injection malfunction** Loss of continuity (starter) #1 and/or #2 Low oil pressure
ECM selector switch in alternate position***
Common pump room alarm (field re-assignable)*
Low suction pressure
Water reservoir low
Low fuel level
Low pump room temperature
Water reservoir empty
High fuel level
High pump room temperature
AC Failure
Fuel tank leak
H-O-A selector switch in OFF or HAND
Free (field programmable)*

Terminals for
Field Connections
for External
Devices

Low fuel level


High fuel level (re-assignable)
Fuel tank leak (re-assignable)
Remote AUTOMATIC start
Deluge valve start (re-assignable)

ViZiTouch
Operator Interface

Solid state controls


4.2 color touch screen (HMI technology)
Upgradable software
Expandable storage
Multi-language

*Except if option C13 is ordered. Tornatech reserves the right to use any of these four alarm points for special specific application requirements
**Applicable to electronic engines only.
*** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.

August 2016

Technical Data
GPD Diesel Fire Pump Controller

Operation

Selector Switch

Hand-Off-Auto
Behind lockable and breakable cover

Automatic Start

Start on pressure drop


Remote start signal from automatic device

Manual Start

Crank 1 and Crank 2 start pushbuttons


Run test pushbutton
Deluge valve start
Remote start from manual device

Crank Cycle

6 consecutive cycle attempts


3 X 15s crank from battery 1 or 2 alternatively
15s rest in between each crank attempt
Manual with Stop pushbutton
Automatic after expiration of minimum run timer ***

Stopping

Field Adjustable &


Visual Countdown

Timers
Actuation

Visual Indication

Mode
Communication
Protocol
Capability

Alarm and
shutdown
schedule

12V.DC
24V.DC

Pressure
Non-pressure
Automatic
Non-automatic

Protocol: Modbus
Connection type: Shielded female connector RJ45
Frame Format: TCP/IP
Addresses: See bulletin MOD-GPD
Automatic Start

Manual or Remote Start

Run Test or Periodic Test

High Coolant

Alarm only

Alarm only

Shutdown

Low Oil Pressure

Alarm only

Alarm only

Shutdown

Overspeed

Shutdown

Shutdown

Shutdown

Approx. shipping
dimensions in inches
(mm)

Approx. Shipping
Weight in Lbs (kg)

Approx. shipping
dimensions in inches
(mm)

Approx. Shipping
Weight in Lbs (kg)

32" l x 29" w x 16" h


(813 x 737 x 407 )

85 (39)

32 l x 29 w x 26 h
(813 x 737 x 661)

115 (52)

Wall Mount
Starting Voltage

Minimum run timer ***(off delay)


Sequential start timer (on delay)
Periodic test timer

Floor Mount

*** Automatic shutdown shall be approved by the AHJ.

August 2016

Technical Data
GPD Diesel Fire Pump Controller
Seismic
TRU Compliance, LLC
Certification
A Tobalski Watkins Affiliate
Company

Seismic
Certification

Mounting
details

Rigid wall mounting


Building
Code

Seismic
Information

TWEI Project No.: 15014

IBC
2015,
CBC
2016

Test
Seismic
Criteria Parameters
ICCES
AC156

AFLX-H ARIG-H AFLX-V ARIG-V

SDS

z/h

IP

2.0

1.0

1.5

3.20

2.40

1.33

0.53

3.2

0.0

1.5

3.20

1.28

2.13

0.85

ASCE 7-10
Chapter 13

RRS for Nonstructural Components Testing

Spectral Response Acceleration (g)

10.0

1.0

0.1
0.1

1.0

10.0

Frequency, f (Hz)
Horiz. Level 1

Vert. Level 1

Notes:
Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
OSHPD Special Seismic Certification Preapproval (OSP)

August 2016

Technical Data
GPD Diesel Fire Pump Controller
C14

Delayed automatic start on AC power failure


(factory set at 15 minutes)

C15

Low zone pump control function

C16

Middle zone pump control function

C17

High zone pump control function

C19

Lockout/interlock circuit from equipment installed inside the


pump room

D4

Pressure transducer and run test solenoid valve for fresh


water rated for 0-500psi (for factory calibration purposes only)

System overpressure alarm contact (For engines with PLD)


(Form C-SPDT)

D6

Pressure transducer and run test solenoid valve for sea


water rated for 0-500PSI

Extra controller trouble alarm contact (Form C-SPDT)

D7A

Low fuel level float switch supplied as separate item (1-1/4)

A12

Extra engine trouble alarm contact (Form C-SPDT)

D7B

Low fuel level float switch supplied as separate item (1-1/2)

Ax

Additional engine alarm contact (Form C-SPDT)


(specify function)

D8A

High fuel level float switch supplied as separate item (1-1/4)

D8B

High fuel level float switch supplied as separate item (1-1/2)

B1

Low fuel level alarm contact (Form C-SPDT)

D9A

Anti-condensation heater & thermostat

B2

Water reservoir level low alarm contact (Form C-SPDT)

D9B

Anti-condensation heater & humidistat

B3

Water reservoir empty alarm contact (Form C-SPDT)

D9C

Anti-condensation heater & thermostat & humidistat

B4

Low pump room temperature alarm contact (Form C-SPDT)

B5

High fuel level alarm contact (Form C-SPDT)

D11

Low suction pressure transducer for fresh water rated at


0-300PSI with visual indication and alarm contact

B6

Low system (discharge) pressure alarm contact


(Form C-SPDT)

D11A

Low suction pressure transducer for sea water rated at


0-300PSI with visual indication and alarm contact

B7

Low suction pressure alarm contact (Form C-SPDT)

D12

Tropicalization

B8

Pump on demand alarm contact (Form C-SPDT)

D25

Mounting stand

B9

Fuel tank leak alarm contact (Form C-SPDT)

D25A

Mounting stand SST- 304 painted

B10

Main relief valve open alarm contact (Form C-SPDT)

D25B

Mounting stand SST- 304 brushed finish

B11

Flow meter loop valve open alarm contact (Form C-SPDT)

D25C

Mounting stand SST- 316 painted

B12

Water reservoir level high alarm contact (Form C-SPDT)

D25D

Mounting stand SST- 316 brushed finish

B13

High pump room temperature alarm contact (Form C-SPDT)

D26

Combined low and high fuel level float switch (1-1/4)

Bx

Additional pump room alarm contact (Form C-SPDT)


(specify function)

D26A

Combined low and high fuel level float switch (1-1/2)

D27

Fuel level probe (2) Level indication

C5

CE Mark with factory certificate

D28

Field programmable I/O board - 8 Input / 5 output

C6

Nickel Cadmium battery chargers

D29

Field programmable I/O board - 8 Input / 10 output

C7

Engine block heater circuit (same voltage as battery charger


primary)

D30

Redundant pressure transducer for fresh water rated for


0-500PSI

C8

Foam pump application w/o pressure transducer and run


test solenoid valve

D31

Redundant pressure transducer for sea water rated for


0-500PSI

C9

Non pressure actuated controller w/o pressure transducer


and run test solenoid valve

D32

Modbus with RTU frame format and RS485 connection

D33

Window kit for operator interface

C13

Louver activation circuit (battery power specific)

A1

Periodic test alarm contact (Form C-SPDT)

A2

Overspeed alarm contact (Form C-SPDT)

A3

Low oil pressure alarm contact (Form C-SPDT)

A4

High coolant temperature alarm contact (Form C-SPDT)

A5

Failure to start alarm contacts alarm contact (Form C-SPDT)

A6

Battery 1 & 2 failure alarm contact (2 x Form C-SPDT)

A7

Charger 1 & 2 failure alarm contact (2 x Form C-SPDT)

A8

AC failure alarm contact (Form C-SPDT)

A9
A11

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

August 2016

Technical Data
GPD Diesel Fire Pump Controller
L01

Other language and English (bilingual)

L14

Russian

L02

French

L15

Turkish

L03

Spanish

L16

Swedish

L04

German

L17

Bulgarian

L05

Italian

L18

Thai

L06

Polish

L19

Indonesian

L07

Romanian

L20

Slovenian

L08

Hungarian

L21

Danish

L09

Slovak

L22

Greek

L10

Croatian

L23

Arabic

L11

Czech

L24

Hebrew

L12

Portuguese

L25

Chinese

L13

Dutch

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

August 2016

Technical Data
GPD Diesel Fire Pump Controller
ViZiTouch Operator Interface
3

PMS 295

PMS 361

Noir

10

1
12

11

13

1 - Power on LED
2 - Color touch screen
3 - Alarm LED
4 - HOME page button
5 - ALARM page button
6 - CONFIGURATION page button
7 - HISTORY page button

August 2016

14

8 - USB port
9 - CRANK 1 button
10 - CRANK 2 button
11 - Contextual navigation pad
12 - STOP button
13 - RUN TEST button
14 - HELP button

Diesel Engine Fire Pump Controller

12Vdc or 24Vdc Negative Ground


Dimensions

Model:GPD
Built to the latest edition of the NFPA 20 standard
3/8" [10] X4

27 1/8" [689]
26 1/8" [663]
23 3/4" [600]

10" [253]

22 1/4" [564]

9" [228]

See Notes

28 7/8" [734]

27 5/8" [700]
29 7/8" [760]

23 1/2" [597]

6 7/8" [174]

2 7/8" [73]

19 1/8" [486]

- Controller Standard without Mounting Stand


- Order Option D25 if Mounting Stand
Required

12 7/8" [327]

47 7/8" [1208]

22 1/2" [571]
Sensing Line Connection - 1/2 " F.NPT

13 1/2" [343]

Drain - 3/8 " M.TUBE

6 5/8" [168]

5" [127]

Notes:

7 1/8" [183]

1 1/4" [31]

- Standard NEMA: NEMA 2


- Standard Paint : Textured Red RAL 3002.
- All Dimensions are in Inches [Millimeters].
- Center of ViZiTouch Screen: 22-1/4" [565] from Bottom (No Feet).
- Bottom Conduit Entrance Through Removable Gland Plate Recommended.
- Use Watertight Conduit and Connector Only.
- Protect Equipment Against Drilling Chips.
- Door Swing Equal to Door Width.
- Seismic mounting to be rigid wall only.
Projection

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV.
NYC
Dpt of Building
Approved

2016

1
2
3

DESCRIPTION
Change Solenoid Valve Cover
Added Seismic Logo
Modified Tornatech & Seismic Logo

Drawing number

DD/MM/YY
20/11/14
21/08/15
11/04/16

GPD-DI500 /E
CDL

All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Diesel Engine Fire Pump Controller

12Vdc or 24Vdc Negative Ground


Layout

Model:GPD
Built to the latest edition of the NFPA 20 standard

Designation

Description

Filter

CB1-2

Magnetic Breaker 1 Pole 10 Amp.

BC1-BC2

Battery Charger #1 and #2

CB3-4

Magnetic Breaker 1 Pole 15 Amp.

GPDB

I/O Diesel Board

SS1

Lockable 3 Position Selector Switch

MB

ViZiTouch Main Board

IS1

Isolating Switch

BC1

MB

DANGER

CB1
CB2

CB3
CB4

BC2
F

SS1
GPDB

RATING
LABEL

Front Door Layout

Internal Layout
REV.

NYC
Dpt of Building
Approved

2016

IS1

2
3
4
5

DESCRIPTION

Change CB position

General Revision
Added Seismic logo
Modified Tornatech & Seismic logo

DD/MM/YY
09/04/15
26/06/15
21/08/15
11/04/16

Drawing number

GPD-LY600 /E

All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Diesel Engine Fire Pump Controller

12Vdc or 24Vdc Negative Ground


Wiring schematic
F
IS1
L

1L

L'

120-240 Vac
50-60Hz

N
E

N'

Built to the latest edition of the NFPA 20 standard

CB2

53

14
CB1

Filter
1N

Model:GPD

13
54

Battery Charger 1

53
54

Power Available

BATT.
+ _

63 11

Controller Trouble
(Fail Safe)
Engine Run

Main Switch in HAND or OFF


Common Engine Trouble
Common Pump Room Alarm
(Field Programmable)

14

24

11

24

12

22

14

24

11

24

12

22

14

24

11

24

12

22

14

24

11

24

12

22

14

24

11

24

12

22

14

24

11

24

12

22

B1 B2

15 16

Battery Charger 2

ALARM

BATT.
+ _

SUPPLY
L

Com NO NC

17 18

13 54

ALARM

BOOST

Com NO NC

B1 B2

83 11

19 20

21 22

SUPPLY
L

14 54

I/O Diesel Board


J36
TB1

J38
TB2

Yellow/Green

J24

Blue

SV1

J40
TB3

J16

AI5-IN

J42
TB4

J14

AI4-IN

J37
TB5

J15

AI3-IN

J39
TB6

+ Gnd
-

Brown

Analog Input
Flow / Spare Temperature

SV1

Analog Input
Fuel Level
Analog Input
Water Level / Suction Pressure

J17

AI2-IN

AI1-IN

21

Discharge Pressure
Transducer

PT1

Red

J18
Low Fuel Level

BOOST

White
Black

22

Remote Auto Start

*J1

Deluge Valve Start

**J2

* Remove Jumper J1 to Use this Feature

** Remove Jumper J2 to Use this Feature


(Re-Assignable)

23
24
25

J25

53

Vac

J44

26

Power Available

54

Vac

27

Fuel Tank Leak

28

(Re-Assignable)

Temperature
Sensor 1

29

High Fuel Level

30

(Re-Assignable)

J11

J8
P1

TM1

J6

ViZiTouch

Main Board
MP+

J35

P1

MP-

J3

P2

J16

(-)

Electronic Control Module Fault

304

304

PLD Low Suction Pressure

305

305

High Raw Water Temperature

310

310

Low Raw Water Flow

311

311

Low Engine Temperature

312

312

24V

GND

COM

DI0

COM

DI1

COM

DI2

Main Switch

B1+

J1

B1CF1
G

B2+

J107

B2CF2

Energize to Start Solenoid

J104-1

Engine Run

J104-2

Overspeed

J104-3

J19-2

64

Low Oil Pressure

J104-4

J19-1

84

High Engine Temperature

J104-5

J46-2

62

Battery 1

J104-6

J46-1

Battery 2

J104-7

J2-2

G
63

Start Contactor 1

J104-8

Start Contactor 2

10

10

J104-9

J3-2

Ground

11

11

J104-10

J3-1

83

Ground

11

11

J104-11

J45-2

82

Energize to Stop Solenoid

12

12

J104-12

J45-1

REV.
1
2
3

62
6

J2-1

NYC
Dpt of Building
Approved

2016

COM

Vext

SS1

30

J106

G
HV+

J103

AB1

J13
DI3

303

COM

303

DI4

Electronic Control Module Warning

J4

COM

302

DI5

302

COM

Fuel Injection Malfunction

DI6

301

COM

301

DI7

J14

ECM SS in Alt. Pos

Red
Black

(+)

31

15
16
17
18

Battery Charger 1

19
20
21
22

Battery Charger 2

OFF

32
AUTO
HAND

CB3

11
63
11
83
82
8

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

CB4

DESCRIPTION
Added Re-Assignable Inputs
Added Seismic Logo and IS1
Modified Tornatech & Seismic Logo

Drawing number

DD/MM/YY
08/04/15
21/08/15
11/04/16

GPD-WS602 /E
CDL

All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Diesel Engine Fire Pump Controller

12Vdc or 24Vdc Negative Ground


Louver Connections

Model:GPD
Built to the latest edition of the NFPA 20 standard

Located in Controller
Engine Run Alarm Contact
11-14

11-12

21-24

21-22

Normally Opened
Closes to alarm

Normally Closed

or

or

Opens to alarm

14
11
12

24
21
22

J38
TB2

M
Louvers Motor

Power Supply from a Reliable


External Power Source
(See NFPA20-2013 11.3.2 & A 11.3.2)

REV.
NYC
Dpt of Building
Approved

2016

0
1
2

DESCRIPTION
First Issue
Added Seismic logo
Modifed Tornatech & Seismic logo

DD/MM/YY
25/05/15
21/08/15
11/04/16

Drawing number

GPD-TD403 /E

All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Diesel Engine Fire Pump Controller

12Vdc or 24Vdc Negative Ground


Terminals Diagram

Model:GPD
Built to the latest edition of the NFPA 20 standard

Power Supply

Alarm Contacts

Terminals Wire Size:


16 - 6 AWG
2 Nm

Terminals Wire Size:


12 - 24 AWG
0.5 Nm

120-240 Vac
50-60Hz

IS1

N
G

Controller Trouble
(Fail Safe)

Engine Connections

Engine Terminal Strip

3
4
5
6
8

Energize to Start Solenoid


Engine Run
Overspeed
Low Oil Pressure
High Engine Temperature
Battery 1
Battery 2

J104-1

J104-2

J104-3

J104-4

J104-5

J104-6

J104-7

Louver Activation
Circuit

Engine Run

Main Switch in
HAND or OFF

Start Contactor 1

J104-8

10

Start Contactor 2

10

J104-9

11

J104-10

11 Ground

12

301

302
303
304
305
310
311
312

Ground
Energize to Stop Solenoid

11

J104-11

12

J104-12

301

Fuel Injection Malfunction

305

High Raw Water Temperature

J103

Low Raw Water Flow

J36 - 14
J36 - 11
J36 - 12

Normally Closed
Opens to alarm

J36 - 24

TB1

J36 - 21
J36 - 22

Normally Opened
Closes to activate

J38 - 14
J38 - 11
J38 - 12

Normally Opened
Closes to alarm

J38 - 24

TB2

J38 - 21
J38 - 22

Normally Opened
Closes to alarm

J40 - 14
J40 - 11
J40 - 12

Normally Opened
Closes to alarm

J40 - 24

TB3

J40 - 21
J40 - 22

Normally Opened
Closes to alarm

(Re-Assignable)
J42 - 14
J42 - 11
J42 - 12

Normally Opened
Closes to alarm

J42 - 24

TB4

J42 - 21
J42 - 22

Normally Opened
Closes to alarm

(Re-Assignable)
J37 - 14
J37 - 11
J37 - 12

Normally Opened
Closes to alarm

J37 - 24

TB5

J37 - 21
J37 - 22

Normally Opened
Closes to alarm

(Re-Assignable)
J39 - 14
J39 - 11
J39 - 12

Normally Opened
Closes to alarm

J39 - 24

TB6

J39 - 21
J39 - 22

All wiring between the controller and diesel engine shall be


stranded (NFPA20)
Wiring between controller and engine (terminals 301, 302, 303,
304, 305, 310, 311, 312, 2 ,3 ,4 ,5) must be #14AWG as
minimum.

I/O Diesel Board


21

Low Fuel Level

22

Remote Auto Start

*J1

Deluge Valve Start

**J2

23

Wiring between controller and engine (terminals 1, 12 [rated at


8A or 10A for 20 seconds] 9, 10 [rated at 8A or 10A for 15
seconds]) must be stranded #10AWG as minimum.

24
25
26

J25

27

Wiring between controller and engine (terminals 6, 8, 11 [rated


at 12A]) must be stranded and sized according to distance.

28
29
30

REV.
NYC
Dpt of Building
Approved

2016

I/O Diesel Board

312

Terminals Wire Size:


12 - 24 AWG
0.5 Nm

(Re-Assignable)

(Field
Programmable)

Normally Closed
Opens to alarm

Normally Closed
Opens to alarm

311

Field Connections

High Fuel Level

Normally Closed
Opens to alarm

Normally Closed
Opens to alarm

310

Low Engine Temperature

(Re-Assignable)

Normally Closed
Opens to alarm

Normally Closed
Opens to alarm

304

PLD Low Suction Pressure

Fuel Tank Leak

Normally Closed
Opens to alarm

303

Electronic Control Module Fault

** Remove Jumper J2 to Use this Feature


(Re-Assignable)

Normally Closed
Opens to alarm

Normally Closed
Opens to alarm

302

Electronic Control Module Warning

* Remove Jumper J1 to Use this Feature

Common Engine
Trouble

Common Pump
Room Trouble

I/O Diesel Board

Electronic Control Module Selector Switch in


Alternate Position

Normally Closed
Opens to activate

Normally Closed
Opens to alarm

11

Normally Opened
Closes to alarm
Normally Opened
Closes to alarm

I/O Diesel Board

(11-12-14) / 8A
(21-32-24) / 5A

2
3
4

DESCRIPTION
Added Seismic logo
Louver activation circuit added
Modifed Tornatech & Seismic logo

DD/MM/YY
21/08/15
08/12/15
11/04/16

Drawing number

GPD-TD602 /E

All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.

Potrebbero piacerti anche