Sei sulla pagina 1di 2

TA

OIL PUMP TYPE TA


GEAR SIZES 2-3-4-5

TA - 11 - Ed 11 - September 2014

This is a general specification leaflet ; for specific applications not


covered herein, contact Suntec.
The SUNTEC TA oil pump is specially designed for industrial heating applications
using light or heavy oils. It is fitted with a preheater location to render cold starting
easier.

PUMP
IDENTIFICATION
(Not all model combinations are available
Consult your Suntec representative)

APPLICATIONS
- Light oil, B10 heating oil/biofuel blend (as defined in DIN V51603-6) and
kerosene.
- One or two-pipe system.

TA : Pressure regulation

Gear set capacity


(see pump capacity curves)

PUMP OPERATING PRINCIPLE


The gear set draws oil from the tank and transfers it to the valve regulating the oil
pressure to the nozzle line. All oil which does not go through the nozzle line will be
dumped through the valve back to the return line in two pipe installation or, if it is
a one-pipe installation, back to the gear-set.
Bleed :
The plug of the pressure gauge port must be loosened until the air is evacuated from
the system.
Note :
All TA models are delivered for two-pipe system (by-pass plug fitted in vacuum
gauge port).
For one-pipe system, the by-pass plug must be removed and the return port sealed
by steel plug and washer.

Shaft rotation
(seen from shaft end)
A : clockwise rotation
C : anti clockwise rotation

TA

40 10

Pressure range :
30 : 7 - 30 bars
40 : 7 - 40 bars

PREHEATING FACILITY
Care should be taken to avoid starting pump with high viscosity cold oil leading to
pump and coupling damage. For this reason, the TA pump body includes a cavity
to accept an electric preheater. This cavity has been located to give maximum heat
transfer from the heater to the oil in the pump without direct contact between the
heater cartridge and the oil.
Heaters should be connected for a period of time prior to starting the pump. When
the right temperature is reached, they can be switched off or left permanently
switched on to maintain fluid oil in the pump during the periodic burner shut-downs.
The oil supply, pipes and filters must be separately heated.

Preheater facility

Revision number

Oil under suction


Oil under pressure
By-passed oil
returned to tank,
or to suction

Vacuum or
inlet pressure
gauge port

Vacuum or
inlet pressure
gauge port

Pressure
gauge port

Intake
from Tank

To
nozzle

By-pass
plug
inserted

Pressure
gauge port

Intake
from Tank

To
nozzle

By-pass
plug
removed
Pressure
adjustment

Pressure
adjustment

Return

TWO PIPE
INSTALLATION

ONE PIPE
INSTALLATION

Return
plugged

SUNTEC INDUSTRIES FRANCE - 1, rue Lavoisier - CS 60102 - F-21603 LONGVIC Cedex - Tel. 33 (0)3 80 70 60 70 - Fax 33 (0)3 80 70 61 11- www.suntec.fr

Pump capacity

TECHNICAL DATA

Mounting

Flange mounting

Connection threads
Inlet and return
Nozzle outlet
Pressure gauge port
Vacuum gauge port

Cylindrical according to ISO 228/1


G 1/2
G 1/2
G 1/4
G 1/4

Shaft

12 mm

By-pass plug

Inserted in vacuum gauge port


for 2 pipe system;
to be removed with a 3/16" Allen key
for 1 pipe system
5,4 kg (TA2)
5,7 kg (TA3)
6 kg (TA4)
6,4 kg (TA5)

Weight

Hydraulic data

Nozzle pressure ranges 30 : 7 - 30 bars


40 : 7 - 40 bars
Delivery pressure
setting
30 bars

Oil temperature

0 - 150C in the pump

2400

Inlet pressure

light oil :

2200

heavy oil :

0,45 bars max. vacuum to prevent


air separation from oil
5 bars max.

light oil :
heavy oil :

5 bars max.
5 bars max.

1600

3600 rpm max.

Torque (@ 40 rpm)

0,3 N.m

15

20

25

75 cSt
20 cSt
5 cSt -

30

35
40
45
Pressure (bars)

Rated speed = 2850 rpm

Data shown are for new pumps, with no allowance for wear.

Power (W)

Rated speed

10

Viscosity =

Operating viscosity
2 - 75 mm/s (cSt)
(Higher viscosity oil can be used by feeding the pump
and by heating the oil to lower its viscosity under 75 cSt.
For kerosene applications, contact SUNTEC)

Return pressure

Ref : SK 220,221,290; 23/01/06

Capacity (L/h)
1600
1500
1400 TA5
1300
1200
1100
TA4
1000
900
800 TA3
700
600
500 TA2
400
300
200
100
0

General

Power consumption
2600

2000
1800

TA5

1400

TA5
TA4
TA3
TA2

1200
1000
800
600

Choice of heater

TA4
TA3
TA2

400
200

Cartridge

12 mm

Fitting

according to EN 50262

Rating

80-100 W

0
0

10

15

20

25

30

35

40

45

Pressure (bars)
Viscosity =

75 cSt
5 cSt -

Rated speed = 2850 rpm

Data shown are for new pumps, with no allowance for wear.

PUMP DIMENSIONS

Example shows pump with "C" rotation and serial number

TA2 TA3 TA4 TA5


(mm)

50

54

58

500 000. - Reverse all pump connections for "A" rotation.

125

66

64

101

36

22,5

22,5

n
B
54

130

11

19 min
M16x1,5

85

4
12
13,5

B-B
36

n Suction

o Nozzle outlet

102

1,5 max
8 min
12 min

Return

Pressure
gauge port

We reserve the right to change specifications without prior notice.

12,1 min

66

or inlet pressure gauge port


r Vacuum
and internal by-pass plug

11

71,5 min

Pressure
adjustment

t Preheater
cavity

TA - 11 - Ed 11 - Sept. 2014