Programmable Logic Controllers (PLCs) have become an integral part of the industrial environment. As a
technician involved with the processes controlled by PLCs, it is important to understand their basic
functionalities and capabilities.
Talk Page

PLC Overview
Talk Page

What is a Programmable Logic Controller?


A programmable logic controller (PLC) is a digital computer used for automation of electromechanical
processes, such as control of machinery on factory assembly lines, amusement rides, or lighting fixtures.
PLCs are used in many industries and machines. Unlike general-purpose computers, the PLC is designed
for multiple inputs and output arrangements, extended temperature ranges, immunity to electrical noise, and
resistance to vibration and impact. Programs to control machine operation are typically stored in batterybacked or non-volatile memory. A PLC is an example of a real time system since output results must be
produced in response to input conditions within a bounded time, otherwise unintended operation will result.
Figure 1 shows a graphical depiction of typical PLCs.

Figure 1: Typical PLCs

Figure 2: Examples of Hardware PLCs Control


Talk Page

History of the PLC


PLC invention was in response to the needs of the American automotive manufacturing industry where
software revision replaced the re-wiring of hard-wired relay based control panels when production models
changed.
Before the PLC, control, sequencing, and safety interlock logic for manufacturing automobiles relied on
hundreds or, in some instances, thousands of relays, cam timers, and drum sequencers and dedicated
closed-loop controllers. The process for updating such facilities for the yearly model change-over was very
time consuming and expensive, as electricians needed to individually and manually rewire each and every
relay.
In 1968 GM Hydramatic issued a request for proposal for an electronic replacement for hard-wired relay
systems. The winning proposal came from Bedford Associates of Bedford, Massachusetts. The first PLC,
designated the 084 because it was Bedford Associateseighty-fourth project, was the result. Bedford
Associates started a new company dedicated to developing, manufacturing, selling, and servicing this new
product: MODICON, which stood for MOdular DIgital CONtroller. One of the people who worked on that
project was Dick Morley, the "father" of the PLC.
In other industries, PLCs replaced relay systems used in manufacturing applications. This eliminated the
high cost of maintaining these inflexible systems. In 1970, with the innovation of the microprocessor, the
machine that was originally used as a relay replacement device only, evolved into the advanced PLC of
today.
Talk Page

Advantages of PLCs
There are six major advantages of using PLCs over relay systems as follows:
Flexibility
Ease of troubleshooting
Space efficiency
Low cost
Testing
Visual operation
Flexibility: One single PLC can easily run many machines.
Ease of Troubleshooting: Back before PLCs, wired relay-type panels required time for rewiring of panels
and devices. With PLC control any change in circuit design or sequence is as simple as retyping the logic.
Correcting errors in PLC is both fast and cost effective.
Space Efficient: Fewer components are required in a PLC system than in a conventional hardware system.
The PLC performs the functions of timers, counters, sequencers, and control relays, so these hardware
devices are not required. The only field devices that are required are those that directly interface with the
system such as switches and motor starters.
Low Cost: Prices of PLCs vary from few hundreds to few thousands. This is minimal compared to the prices
of the contact, coils, and timers that companies pay to match the same things. Using PLCs also saves on
installation cost and shipping.
Testing: A PLC program can be tested, evaluated, and validated in a lab prior to implementation in the field.
Visual observation: When running a PLC program a visual operation displays on a screen or module
mounted status lamps assist in making troubleshooting a circuit quick, easy, and relatively simple.

Talk Page

Components of a PLC
All PLCs have the same basic components. These components work together to bring information into the
PLC from the field, evaluate that information, and send information back out to various field. Without any of
these major components, the PLC will fail to function properly.
The basic components include a power supply, central processing unit (CPU or processor), co-processor
modules, input and output modules (I/O), and a peripheral device.

Figure 3: PLC Components


Talk Page

Input/Output Modules
The type of input modules used by a PLC depends on the type of input device. For example, some respond
to digital inputs, which are eitheronoroffwhile others respond to analog signals. In this case, analog signals
represent machine or process conditions as a range of voltage or current values. The PLC input circuitry
converts signals into logic signals that the CPU can use. The CPU evaluates the status of inputs, outputs,
and other variables as it executes a stored program. The CPU then sends signals to update the status of
outputs.
Output modules convert control signals from the CPU into digital or analog values that can be used to control
various output devices. The programming device is used to enter or change the PLCs program or to monitor
or change stored values. Once entered, the program and associated variables are stored in the CPU. In
addition to these basic elements, a PLC system may also incorporate an operator interface device to simplify
monitoring of the machine or process.
Talk Page

Power Supply
The function of the power supply is to provide the DC power to operate the PLC. It is supplied by singlephase 120 or 240 VAC line power that powers the PLC system. See Figure x.

Figure 4:PLC Power Supply


The Power Supply is a module located in the PLC system module rack. The DC power (voltage and current)
it provides power the other modules in the rack, such as the CPU, Co-processor Modules, and I/O Modules.
The line power provided to the PLC system also powers the I/O Field Devices. The PLC system is protected
against PLC module or field device malfunctions. The Fuse in Figure 4 provides this protection.
Talk Page

Central Processing Unit CPU


The function of the CPU is to store and run the PLC software programs. It also interfaces with the CoProcessor Modules, the I/O Modules, the peripheral device, and runs diagnostics. It is essentially the
"brains" of the PLC.
The CPU, shown in Figure X, contains a microprocessor, memory, and interface adapters.

Figure 5: CPU
The items shown inside the CPU and their basic functions are as follows:
The microprocessor codes, decodes, and computes data.
The memory (ROM, PROM/EEPROM/UVPROM, and RAM) stores both the control program and the
data from the field devices.
The I/O Interface adapter connects the Co-Processor Modules, the I/O Modules and the Peripheral
Device to the CPU.
Talk Page

Co-processor Modules
Co-Processor Modules are programmable general-purpose microcomputers that expand the capability and
functionality of a PLC system. A Co-Processor Module is controlled by the CPU, and interfaces with the CPU
as shown above.
Co-Processor Modules monitor and control peripheral systems such as the following:
Alphanumeric Displays
Video Graphics Displays
Communication Networks
Talk Page

Software
The function of Software is to provide instructions to the CPU and Co-Processor Modules. Physically,
software is a large group of logic ones and zeros stored in the memory of the CPU.
Talk Page

Peripheral Device
The function of the peripheral device is to input data and monitor the equipment operation. It may be a

personal computer, handheld programmer, or an operator touch screen.


Talk Page

Basic Operation of a PLC


The operation of a PLC is very simple. The processor makes decisions based on a "ladder logic" program
written by the user. In order to use the program properly, the PLC must communicate with the various field
devices it monitors and controls. It then compares the actual conditions of the field devices with what the
program instructs them to do, and updates the output devices accordingly.
1. Input switch is pressed
2. Input module places a "1" in the input data table
3. The ladder logic program sees the "1" and caused a "1" to be put into the output data table
4. The output data table causes the output module to energize associated point
5. The output device energizes

Figure 6: PLC Operation


Talk Page

Ladder Logic of a Hardwired System


Ladder logic is a programming language that represents a program by a graphical diagram based on the
circuit diagrams of relay-based logic hardware. It is primarily used to develop software PLCs used in
industrial control applications. The name is based on the observation that programs in this language
resemble ladders, with two vertical rails and a series of horizontal rungs between them.
Ladder logic is widely used to program PLCs, where sequential control of a process or manufacturing
operation is required. Ladder logic is useful for simple but critical control systems, or for reworking old

hardwired relay circuits. As PLCs became more sophisticated, it has also been used in very complex
automation systems. Often the ladder logic program is used in conjunction with a HMI program operating on
a computer workstation.
Manufacturers of programmable logic controllers generally also provide associated ladder logic programming
systems. Typically, the ladder logic languages from two manufacturers will not be completely compatible;
ladder logic is better thought of as a set of closely related programming languages rather than one language
(the IEC 61131-3 standard has helped to reduce unnecessary differences, but translating programs between
systems still requires significant work). Even different models of PLCs within the same family may have
different ladder notation such that programs cannot be seamlessly interchanged between models.
Ladder logic is a rule-based language rather than a procedural language. A "rung" in the ladder represents a
rule. When implemented with relays and other electromechanical devices, the various rules "execute"
simultaneously and immediately. When implemented in PLC, the rules execute sequentially by software in a
continuous loop (scan). By executing the loop fast enough, the effect of simultaneous and immediate
execution is achieved to within the tolerance of the time required to execute every rung in the "loop" (the
"scan time").
Talk Page

Simple Ladder Diagram of a Hardwired Circuit


The language itself is a set of connections between logical checkers (contacts) and actuators (coils). If a path
traced between the left side of the rung and the output, through asserted (true or closed) contacts, the rung is
true and the output coil storage bit is asserted 1. If no path is traced, then the output is false (0) and the coil
by analogy to electromechanical relays is considered de-energized.
Ladder logic has contacts that make or break circuits to control coils. Each coil or contact corresponds to the
status of a single bit in the PLCs memory. Unlike electromechanical relays, a ladder program can refer any
number of times to the status of a single bit, equivalent to a relay with an indefinitely large number of
contacts.
Contacts may refer to physical or hard inputs to the PLC from devices such as pushbuttons and limit
switches via an integrated or external input module, or may represent the status of internal storage bits,
which may be generated elsewhere in the program.
Each rung of ladder language typically has one coil at the far right. Some manufacturers may allow more
than one output coil on a rung.
( ) - Regular coil. It is energized whenever its rung is closed.
(\\) - "Not" coil. It is energized whenever its rung is open.
[ ] - Regular contact. It is closed whenever its corresponding coil or an input which controls it is
energized.
[\\] - "Not" contact. It is open whenever its corresponding coil or an input which controls it is energized.
The coil or output of a rung, may represent a physical output, which operates some device connected to the
PLC, or may represent an internal storage bit for use elsewhere in the program.

Figure 7: Simple Ladder Diagram


Ladder logic is typically read left to right and top to bottom. As each of the lines or rungs are evaluated, the
output coil of a rung may feed into the next stage of the ladder as an input. In a complex system there will be
many rungs on a ladder, which are numbered in order of evaluation.
Talk Page

PLC Operations
Talk Page

Basic Operation
The operation of a PLC is very simple. The processor makes decisions based on a ladder logic program
written by the user (see Topic I). In order to use the program properly, the PLC must communicate with the
various field devices it is tasked with monitoring and controlling. It then compares the actual conditions of the
field devices with what the program instructs them to do, and updates the output devices accordingly.
Talk Page

Operational Sequence
The operational sequence shown in Figure 6 is as follows:
1. Input switch is pressed
2. Input module places a "1" in the input data table
3. The ladder logic program sees the "1" and caused a "1" to be put into the output data table
4. The output data table causes the output module to energize associated point
5. The output device energizes

Figure 8: PLC Operational Sequence


Talk Page

The Scan Cycle


PLCs operate by continually scanning programs and repeat this process many times per second. When a
PLC starts, it runs checks on the hardware and software for faults, also called a self-test. If there are no
problems, then the PLC will start the scan cycle. The scan cycle consists of three steps: input scan,
executing program(s), and output scan. Figure 7 shows the three steps.
Input Scan: A simple way of looking at this is the PLC takes a snapshot of the inputs and solves the logic.
The PLC looks at each input card to determine if it isonoroffand saves this information in a data table for use
in the next step. This makes the process faster and avoids cases where an input changes from the start to
the end of the program.
Execute Program (or Logic Execution) : The PLC executes a program one instruction at a time using only
the memory copy of the inputs the ladder logic program. For example, the program has the first input ason,
since the PLC knows which inputs are on/off from the previous step it will be able to decide whether the first
output should be turned on.
Output Scan: When the ladder scan completes, the outputs are updated using the temporary values in
memory. The PLC updates the status of the outputs based on which inputs were on during the first step and
the results of executing a program during the second step. The PLC now restarts the process by starting a
self-check for faults.

Figure 9: PLC Scan Cycle


Talk Page

Logic Scan
Ladder logic programs are modeled after relay logic. In relay logic, each element in the ladder will switch as
quickly as possible. Program elements can only be examined one at a time in a fixed sequence. The ladder
logic graphic in Figure 8 is interpreted left-to-right, top-to-bottom. The ladder logic scan begins at the top
rung. At the end of the rung, it interprets the top output first, then the output branched below it. On the second
rung, it solves branches, before moving along the ladder logic rung.

Figure 10: PLC Logic Scan


Talk Page

PLC Hardware
Talk Page

PLC Components
PLCs have grown throughout industrial control applications because of the ease they bring to creating a
controller: ease of programming, ease of wiring, ease of installation, and ease of changing. All PLCs have the
same basic components. These components work together to bring information into the PLC from the field,
evaluate that information, and send information back out to various field. Without any of these major
components, the PLC will fail to function properly. PLCs span a wide range of sizes, but all contain six basic
components as shown in Figure 9 and Figure 10:
1. Power supply
2. Input module

3. Output module
4. Processor (CPU)
5. Rack or mounting assembly
6. Programming unit (software)

Figure 11: PLC Rack

Figure 12: PLC Components


Talk Page

Power Supply
The power supply, as shown in Figure 13, provides power for the PLC system. The power supply provides
internal DC current to operate the processor logic circuitry and input/output assemblies. Common power
levels used are 24V DC or 120 VAC.

Figure 13: Power Supply


Talk Page

Input/Output Modules
Many types of inputs and outputs can be connected to a PLC, and
they can all be divided into two large groups analog (discrete) and
digital. Digital inputs and outputs are those that operate due to a
discrete or binary change - on/off, yes/no. Analog inputs and outputs
change continuously over a variable range - pressure, temperature,
potentiometer. AC modules are always discrete. DC modules can be
either discrete or analog.
The standard PLC module types and their descriptions are as follows:
AC Input - Uses AC voltage for input field device status.
DC Input (Discrete) - Uses DC voltage for input field device status.
DC Input (Analog) - The input is a variable DC signal level.
AC Output - Controls the ON/OFF state of AC output field devices such as relays, coils, and solenoids.
DC Output (Discrete) - Discrete DC output modules control the ON/OFF states of DC output field
devices.
DC Output (Analog) - Provides a variable DC level.
I/O modules are available with various numbers of field device points, such as 4, 8, 16 and 32 point.
Optocouplers in the modules are used to electrically isolate the module from the CPU.
Talk Page

Input Modules
Input modules provide the electrical connection between field devices (pushbuttons, limit switches,
photoeyes) and internal process of the PLC. They differ in voltages and types of signals produced such
ason,offor a variable voltage. Figure 14 shows an example of a generic input module.

Figure 14: PLC Input Module


Talk Page

Input Module Wiring


During normal PLC operation, different methods of connecting the
field device wires to the I/O Modules offer no significant advantages
over each other. Field devices can be wired differently to provide
safety and protection in the event of failures in field devices, or faults
in their electrical circuits.
"Backups" are field devices required to operate properly to provide
safety in the event of a failure of another device or fault in a circuit. If
the circuit for a backup is not affected, the backup should operate
properly and continue to provide safety.
The safety of sequentially controlled systems, industrial facilities, and
even personnel frequently depends on field devices (especially the
backups) operating properly.
Sink and Source connections at a DC Input Module are defined by whether or not the field device DC power
comes from a power supply external to the PLC (see Figure 14). Neither connection has any fault protection

advantage
Talk Page

Input Indicators
Indicator lights are located on the digital input modules. These lights indicate the status of the input point on
the module. The active light indicates whether or not the module is active and communicating with the
processor.
The indicator lights are numbered in two rows, 00-7 and 10-17 (I/O addressing will be discussed later).
These numbers represent each of the input points on the module. If an input point has power applied to it, the
associated light illuminates. The lights are very useful in verifying that field devices, such as switches and
photoeyes, are properly operating.
Figure 15 shows the common layout for indicator lights on an input module. Note that these lights ONLY
show the user that power is getting to this point on the module. They do NOT indicate whether or not the
processor is actually receiving that indication.

Figure 15: Input Indicators


Talk Page

Output Module
Outputs are the devices that the PLC uses to send changes out to the world. These are the actuator the PLC
can change to adjust or control the process - motors, lights, relays, pumps, etc. Figure 16 shows an example
of an output module.

Figure 16: PLC Output Module


Talk Page

Output Module Wiring


DC Modules use "Sink" and "Source" connections. The connections are determined by the configuration of
the module being used. DC Modules are configured differently because of the DC polarity differences
required of the two connections.
Talk Page

Discrete Modules
The term refers to an Off switching output. One type of PLC module that produces discrete signals is a relay
module. It has physical relay that opens (Figure 17) or closes (Figure 18) to make or break a circuit
connected to its terminals. Relay modules have several pairs; each of which are connected to internal relay
contacts.

Figure 17: Relay Module Open Contact

Figure 18: Relay Module Closed Contact


Another type of discrete module is the sinking output
module so named because conventional current flows
into its terminal when a specific output is turned on.
Conventional current flows from a positive to negative
potential.

Figure 19: Sinking Output Module


Figure 20 and Figure 21 show the sequence sinking output module activated and not activated.

Figure 20: Output Module Activated

Figure 21: Output Module NOt Activated


Figure 22 shows a graphical depiction of events when the output is activated:
1. An NPN transistor turns on
2. The output terminal goes to LOW
3. Conventional current flows from the positive of the power supply through the field device into the
sinking terminal of the output module through the transistor to the negative of the power supply.

Figure 22: Output Activated


Talk Page

Discrete Module Wiring


The DC Output (Discrete) Module field device DC power always comes from a power supply external to the
PLC (see Figure X). For certain fault conditions, the source output connection offers additional safety and
protection.
Talk Page

Numerical Data Modules


With the integration of the microprocessor into PLC architecture in the early 1970s arrived new capabilities
for arithmetic operation and data manipulation. This expanded processing capability led to a new class of I/O
interfaces known as numerical data I/O. Numerical input interfaces allowed measured quantities to be input
from instruments and other devices that provided numerical data, while numerical output interfaces allowed
control of devices that required numerical data.
In general, numerical data I/O interfaces can be categorized into two groups: those that provide interface-tomulti-bit digital devices and those that provide interface-to-analog devices. The multi-bit interfaces are like
the discrete I/O in that the processed signals are discrete. The difference, however, is that with the discrete
I/O, only a single bit is required to read an input or control an output. Multi-bit interfaces allow a group of bits
to be input or output as a unit to accommodate devices that require the bits to be handled in parallel form or
in serial form. The numerical data I/O allows monitoring and control of analog voltages and currents, which
are compatible with many sensors, motors drives, and process instruments. With the use of multi-bit or
analog I/O, most process variables can be measured or controlled with appropriate interfacing.
Talk Page

AC/DC Input Modules

Talk Page

AC Input Modules
AC input modules detect the presence or absence of AC voltage, and convert that voltage to a low level for
input to the CPU. The AC voltage indicates the field device status. The voltage level is commonly 24, 115 or
220 VAC. Modules are available for up to 1,000 VAC. An AC Input module schematic diagram is shown in
Figure X. When the field device completes the input circuit, a path for AC exists. An LED on the front of the
module, indicates the input is present.

Figure 23: AC Input Module Schematic


A rectifier converts the AC to DC. The optocoupler isolates the input module from the CPU and effectively
drops the DC voltage level to a level safe for CPU operations.
Most AC input modules use an external AC power supply for "interrogation" of the field devices. On-board AC
power supplies increase the size of the module and require additional heat dissipation considerations.
AC inputs may use a common neutral connection for several points or there may be an "isolated" neutral for
each point for additional fault protection. The input module shown in Figure 7 uses neutral C1 for points 0007 and neutral C2 for points 10-17. Analog AC input modules are not commonly used because there are no
standardized analog AC voltage or current signals.
Talk Page

DC Input Discrete Modules


Discrete DC input modules detect the presence or absence of DC voltage, and convert that voltage to a low
level for input to the CPU. The DC voltage is used to indicate the field device status. Figure X shows a DC
Input module schematic diagram.

Figure 24: DC Input Module (Discrete)


The DC voltage may be supplied by the input module (sink input) or it may be supplied by an external power
supply (source input). Detailed explanations of "sinked" and "sourced" connections are given in this module
later under "Field Device Wiring Connections."
As with AC input modules, the input is optocoupled to the CPU for isolation and CPU protection. An LED
provides indication when the input is present (true).
Talk Page

DC Input Analog Modules


Analog DC input modules detect a DC voltage or current level, convert that variable into a proportional digital
signal and transmit that data to the CPU for processing. The modules can be configured to operate on
standard instrumentation signal ranges such as 4-20 mA, 10-50 mA, 15V, 0-1 0V.
A schematic diagram of an analog DC input module is shown in Figure 9.

Figure 25: DC Input Module (Analog)


After the module converts the analog value to digital, the PLC can turn control functions on and off at preset
analog values. For example, when the input analog value reaches 70 percent, an alarm sounds.
In special applications, an analog input can be combined with an analog output module. Through
programming, the PLC can then perform like a conventional single loop controller.
Talk Page

AC/DC Output Modules


Talk Page

AC Output Modules
AC output modules control the ON/OFF states of AC output field devices such as relays, coils, and
solenoids. They do not normally supply power to the field devices. Figure X is a schematic diagram of the
module.

Figure 26: AC Output Module


The CPU uses a low-voltage DC signal to activate an opto-coupler in the output module. The opto-coupler
gates a TRIAC or SCR that in turn completes the current path for the external power supply and field device.
As with most PLC modules, the voltage rating and the number of points are selectable and the outputs may
have common or isolated neutrals.
Talk Page

DC Output Modules Discrete


Discrete DC output modules control the on/off states of DC output field devices. Power is supplied by an
external power supply. A schematic diagram of the module is shown in Figure 27.

Figure 27: DC Output Module (Discrete)


The CPU sends a low-level DC signal to an opto-coupler that completes the external DC current path that
energizes the output field device. Field device connections may either be "sinked" or "sourced".
Talk Page

DC Output Modules Analog


Analog DC output modules convert digital data from the CPU to analog data for field device use. A Digital to
Analog (D/A) converter in the module performs the conversion. See Figure 28 for a schematic diagram of the
module.

Figure 28: DC Output Module (Analog)


Analog outputs conform to standard instrumentation signals (4-20 mA, 10-50 mA, 1-5V, 0-1 0V). An external
DC power supply is used to power the output field device and the optocoupler in the module.
Analog outputs and inputs require more computing time than discrete modules. The additional time is
needed to perform A/D and D/A conversions and to "block transfer" the additional information to and from the
CPU.
For this reason, most PLC applications use on/off control with only a small amount of analog I/O. If a large
amount of analog data requires processing, other systems (loop controllers, Digital Control Systems) are
usually used.
Talk Page

Proportional Integral and Derivative PID Processor Module


A PID module combines analog input, analog output, and a control program of a typical single loop controller.
A PID module is a smart module. This means that it has an on-board microprocessor and program.
The module carries out loop control without the use of the CPU in the PLC. These modules do communicate
with the CPU for non-routine functions such as alarm reporting and programming changes.
Talk Page

Controls and Indicators


Most processor modules have front panel lights or indications to provide the user with status indications of
PLC operation. These lights are very useful in troubleshooting. Also provided on most processor modules is
a switch used to change the module mode of operation from RUN to PROGRAM. Additional connections are
also usually provided to allow the connection of a terminal for programming the PLC and a port for
connections to external I/O.
Talk Page

Scanning
The processor module controls the PLC by executing the software program. During program execution, the
processor reads all the inputs and uses the values, in accordance with the control logic, to energize or deenergize the outputs, thus solving the ladder network. Once all the logic is solved, the processor updates all
outputs. The process of reading the inputs, executing the program, and updating the outputs is known as a
scan. The time required to make a single scan varies from 1 msec to 100 msec.
The scan is normally a continuous and sequential process of reading the status of inputs, evaluating the
control logic, and updating outputs. The common scan method of monitoring the inputs at the end of each
scan is inadequate for reading certain rapid inputs. Some PLCs provide software instructions that will allow
the interruption of the continuous program scan to immediately receive an input or update an output. These
immediate instructions are very useful when the PLC must instantaneously react to a critical input or output.
Talk Page

User Program
The user program memory is an area reserved in the application memory for the storage of the control logic.
All the PLC instructions that control the machine or process are stored here. The addresses of inputs and
outputs, whether real or internal, are specified in this section of memory.
When the processor is in the run mode and the program is executed, the processor interprets the user
program memory locations and controls the bits of the data table that correspond to real or internal outputs.
The interpretation of the user program is accomplished by the processors execution of the executive
program.
The maximum amount of available user program memory is normally a function of the processor size (i.e.,
I/O capacity). In medium and large controllers, the user program area is normally flexible by altering the size
of the data table so that it meets the minimum data storage requirements. In small processors, however, the
user program area is normally fixed.
Talk Page

Addressing and Number Systems


Talk Page

Number Systems
The earliest number or counting system known to man was developed to help determine a quantity for a
collection of possessions. As daily activities became more complex, numbers became more important in
trade, time, distance, and all other aspects of human life.
Numbers are extremely important in everyday life. As such, a more complex system was required than
counting everything on ones fingers and toes.
Ever since the necessity to count objects was discovered, man has been looking for easier ways to count
them. The abacus, developed by the Chinese, is one of the earliest known methods for counting. The simple
system of beads and wires arranged within a frame provided an early means for calculation. The apparatus
proved helpful and is still used in some parts of the world today.
As time, technology, and need progressed, so did the means and methods required for accurate calculation.
The first adding machine was invented by Blaise Pascal in 1642. Twenty years later, an Englishman, Sir
Samuel Morland, developed a more compact device that could multiply, add, and subtract. Then, Wilhelm
Liebnitz perfected a machine in 1671 that could perform all the basic operations including addition,
subtraction, multiplication, and division, as well as the extraction of the square root. The principles pioneered
by Liebnitz are still used today by modern electronic digital computers.
Computers are used wherever repeated calculations or the processing of large amounts of data is necessary.
Some of the greatest applications are found in the military, scientific, and commercial fields. These fields
have applications ranging from manufacturing processes to engineering design, to the identification and
destruction of enemy targets. The advantages of digital computers include speed, accuracy, and labor
savings. Often, computers are used to manage routine jobs, allowing personnel to perform other tasks, which

may require a human touch.


People and computers normally do not speak the same language. However, methods of translating
information into forms that are understood and used by both are necessary. Humans generally speak in
words and numbers expressed in the decimal number system, while computers only understand coded
electronic pulses that represent digital information.
In this section, you will learn about number systems, in general, and specifically learn about binary, octal,
and hexadecimal number systems. The methods for converting numbers in the binary, octal, and
hexadecimal systems to equivalent numbers in the decimal system, and vice versa, will also be discussed.
This training module will discuss the different types of number systems that can be converted easily to the
electronic pulses necessary for digital equipment and industrial communications.
Talk Page

Types of Number Systems


The decimal system is the most commonly used number system. The Roman numeral system, though
seldom used, is another well-known number system. Other number systems include binary, octal, and
hexadecimal. All number systems have a base and a number value.
Talk Page

Binary
The simplest possible number system is the binary, or base 2, system. Since the binary number system is a
base 2 system, only two symbols, 0 and 1, are used.
The binary system is also a positional notation system. While the decimal system uses powers of 10 to
determine the value of a position, the binary system uses powers of 2 to determine the value of a position. A
bar graph showing the positions and the powers of the base is shown below:

Table 1 provides a comparison of decimal and binary numbers. Notice each time the total number of binary
symbol positions increases, the binary number indicates the next higher power of 2. The table also shows
that more symbol positions are necessary in the binary system to represent equivalent values in the decimal
system.

Talk Page

Octal
The octal, or base 8, number system is a common system used with computers. Because of its relationship
with the binary system, it is useful in programming some types of computers. As with the other systems, the
base, or radix, is the number of symbols used in the system. The octal system uses eight symbols, 0 through
7. The base is indicated by the subscript 8. Table 2 compares the binary, octal, and decimal number systems
and shows that one octal digit is the equivalent value of three binary digits.

Similar to the decimal and binary systems, the octal system is a positional notation system. The octal system
uses powers of 8. The following bar graph shows the positions and the power of the base:
Here the power, orexponent, indicates the number of times the base is multiplied
by itself. The value of thismultiplicationis expressed in base 10 as shown below:
Talk Page

Decimal to Octal/Octal to Decimal Conversion


In decimal systems, each decimal place is a base of 10. For example:
In octal, numerals each place is a power with base 8. For example:
By performing the calculation above in the familiar decimal system we see why
112 in octal is equal to 64 + 8 + 2 = 74 in decimal.
Talk Page

Binary to Octal/Octal to Binary Conversion

The following example further illustrates this comparison and shows the conversion of octal 2258to binary
and back to octal:

Talk Page

Hexadecimal
The hexadecimal, or hex, number system is a more complex system in use with computers. The name is
derived from the fact that the system uses 16 symbols. It is beneficial in computer programming because of
its relationship to the binary system. Since 16 in the decimal system is the 2 to the fourth power (or 24), one
hex digit has a value equal to four binary digits. Table 2 compares the binary and hexadecimal number
systems.

As in each of the previous number systems, a unit stands for a


single object. A number in the hex system is the symbol used to
represent a unit or quantity. The Arabic numerals 0 through 9 are
used with the first six letters of the alphabet. Letters are sometimes
used in math problems to represent unknown quantities but in the
hex system, A, B, C, D, E, and F each have a definite value as
shown below:
The base, or radix, of the hex system is 16, which represents the
number of symbols used in the system. A quantity expressed in hex
is annotated by the subscript 16, as shown below:

Like the binary, octal, and decimal systems, the hex system is a
positional notation system. Powers of 16 are used for the positional
values of a number. The following bar graph shows the positions:
Multiplying the base times itself the number of times indicated by
the exponent will show the equivalent decimal value:
As seen by the positional values, usually fewer symbol positions are
required to express a number in hex than in decimal. The following
example shows this comparison:
Talk Page

Binary Coded Decimal


Computers and microprocessors both operate on a series of
electrical pulses called words. A word can be represented by a
binary number such as 101100112. The word length is described by
the number of digits or BITS in the series. A series of four digits
would be called a 4-bit word and so forth. The most common are 4-,
8-, and 16-bit words. Quite often, these words must use binarycoded decimal inputs.
Binary-coded decimal, or BCD, is a method of using binary digits to
represent the decimal digits 0 through 9. A decimal digit is
represented by four binary digits, as shown below:
You should note in the table above that the BCD coding is the
binary equivalent of the decimal digit.
Since many devices use BCD, knowing how to handle this system
is important. You must realize that BCD and binary are not the
same. For example, 4910in binary is 1100012, but 4910in BCD is
01001001BCD. Each decimal digit is converted to its binary equivalent.
Talk Page

Addressing
Addressing is the most important concept to understand when learning PLCs.
Addressing is how we make a correlation between the field devices controlled
by the PLC, and the data that is stored in the PLCs memory. If you cannot
address a point or group of points in the PLCs memory, then you cannnot
control the field device associated with that point.
The easiest way to approach understanding the addressing used in
the Allen Bradley PLC-5 is to view all addresses from the
processors point of view. By this, we mean that in order for a real
device in the field, such as a relay, to be operated by the PLC, the
PLC must first have a record of that point in its memory. That point can then be accessed by the PLC. The

Allen Bradley PLC-5 stores the information regarding all of the points it
can address in areas called Data Tables as shown in figure 29. The
data tables are divided up by function.

Figure 29: Data Table Files


Talk Page

Addressing Terminology
There are seven terms one must know in order to understand addressing as defined below.
Talk Page

Chassis
Hardware assembly (physical rack) that houses devices such as I/O modules, adapter modules, processor
modules, and power supplies. Chassis are available in six sizes: 4-, 8-, 12-, and 16-slot.
Talk Page

Group
An I/O addressing unit consisting of one input and one output word (16 bits each) of the data table.
Depending on the density of the I/O module and the addressing mode used, some of the bits in a group may
be unused. The group number is included in I/O addresses in the position represented with agin the format:
I:rrg/xx.
Talk Page

Rack
An I/O addressing unit that corresponds to eight input image table words and eight output image table words
(8 groups). A rack is a logical entity not to be confused with the physical chassis. 8 groups = 1 full rack, 6
groups = rack, 4 groups = rack, 2 groups = rack. The rack number is included in I/O addresses in the
position represented with an "rr" in the format: I:rrg/xx.
Talk Page

Slot
A location in a chassis for installing a module. The number of physical slots per group determines the
addressing mode.
Talk Page

Elements
Data files are made up of individual data blocks called "Elements" or "Structures". Each element is composed
of "words", and each word is composed of "bits". Elements are comprised of from 1 to 56 words, depending
on the instruction. Most instructions you will encounter will have from one to three words to an element.
An example of an element level address is T4:0
T4:0 indicates the first timer (0) in the default timer file (T4). Each timer is comprised of three (3) 16 bit
words. When you say T4:0, you are referring to all three of these words as a group.

Figure 30: Elements


Another example, illustrated on the right, is the address N7:15. This identifies element 15 in the integer file
N7. Since integer files have one word elements, the element number and word number will match in this
case as shown in Figure X and Figure Y.

Figure 31: Element Address


Talk Page

Words
Words are the next level of identification down from elements. Each
"word" in the PLC is comprised of 16 bits as shown in Figure 32.
When an instruction is addressed to the word level, it is looking at
all 16 bits of a particular word in an element. When an element is
comprised of more than one word, the 0 word contains status data
in bit form, and the other words contain data which must be stored
in more than one bit.
A good example is a timer file. Timers elements are comprised of
three words. The 0 word contains status information which can be
stored in individual bits. For example, the 17 bit in the 0 word is the done bit, indicating that the timer has
timed out.

The one and two words contain information which require a full word to contain. In the timer, the one word
contains the value of the preset (PRE) of the timer, and the two word contains the information about the
Accumulator (ACC). These words are addressed by their symbols, PRE and ACC. When accessing an
element to the word level, the period (.) is used to delimit instead of the slash (/).

Figure 32: Word Address


Talk Page

Bit
The smallest unit of data in a PLC is the bit. Bits make up
words, which in turn make up elements. Many instructions must
be specified down to the bit level. For example, if you want to
know the status of the Done bit on a timer, you must specify the
address down to the bit level. The address would be:
T4:0/DN
T4:0 is the element we are addressing. Since we are
addressing a single bit, we put the "/" sign as a bit delimiter, and
then specify the bit. In this case the Done bit. Figure 33 shows
the element B3:63 and the bit 15. Note that in this case, the individual bits are identified by numbers, not
names (as in the done bit in the timer). This is true of bits in all files except those having more than one word
in an element.

Figure 33: Bit Address


Talk Page

Bytes
A group of bits forming a piece of data. Usually a subset of a
word consisting of eight bits.
Talk Page

Rack Addressing Rules


Addressing to a rack is just assigning a physical slot in the
chassis to a logical word in the processor. Rack addressing
involves only data tables 0 and 1, the output and input data
tables. The type of addressing shown in figure x is called single
slot addressing, and is the most common type of addressing used in Allen Bradley PLCs. To review the
rules for rack addressing, use the following while referring to the previous figure on PLC 5 Racks.:
A rack is a logical term that defines 8 words in the processor input data table and 8 words in the
processor output data table.
These words are numbered 0-7.
Each logical rack can store 128 bits of information in its input rack and 128 bits in its output rack. (8
words per rack x 16 bits per word=128 bits of data storage)
In single slot addressing, each physical slot is addressed to one input word and also to one output
word. This makes it possible to put either an input module or an output module in any slot.
The number of logical racks determines how many points a particular model of PLC can address. This
number is fixed for any particular processor and cannot be changed.
Rack addressing is always in the format shown in Figure 34 below.

Figure 34: Rack Addressing Format


Talk Page

Addressing Examples
Each type of device has its own table in which to store data. In order to specify exactly which piece of data is
to be accessed, an addressing format is used which makes use of this data structure.
In Figure 35, addresses for input and output addresses are shown. Reading from the left to the right, the
addresses tell the following:
Which data table a point exist in
Which rack of data the point is in
Which group the point is in
The exact point
Note that a colon separates the file identifier from the rest of the address. This is constant for ALL
addresses.

Figure 35: Rack Addressing Format


Talk Page

PLC Communications
Talk Page

PLC Communication Description


PLCs communicate with other PLC stations on the Data Highway+and also communicate with their own

remote racks via the remote I/O communications channel. Some guidelines for PLC communications are as
follows:
The DH+provides communications between processors on the DH+
Each processor on the DH+MUST have its own unique address
A total of 64 (77 Octal) stations can be set up on one peer link.
If a processor has enough communications channels (like the 5/40), it can communicate on more than
one DH+peer link at a time.
DH+is simply a method for communicating from one PLC to another. It DOES NOT allow one PLC to
control another PLC. It just lets you talk from PLC to PLC. It also makes it possible to plug a terminal
into ANY PLC on the peer link and talk to any other PLC on the peer link with the terminal.
Each chassis MUST have either an Adapter module or a Processor module installed in the left most
slot.
In order for a processor to have remote chassis, one channel MUST be set up as a scanner channel.
Talk Page

PLC Communication Protocols


Today, most manufacturers of PLC systems have developed their own proprietary communication protocol,
making it difficult to combine PLC components from different manufacturers. Communication protocols set
the standards for data representation, signaling, authentication, and error detection required to send
information over a communications channel. MODBUS is currently the most common protocol used by PLC
manufacturers.
Talk Page

PLC Networking
Talk Page

Device Net
Device Net is one of the most widely supported networks. It is an open standard, so components from a
variety of manufacturers can be used together in the same control system. It is supported and promoted by
the Open Device Net Vendors Association (ODVA). This group includes members from all of the major
controls manufacturers. The network is noise-resistant and robust. One major change for the control
engineer is that the PLC chassis can be eliminated and the network can be directly connected to the sensors
and actuators. This reduces the total amount of system wiring by moving I/O points closer to the application
point. Two-way communication inputs and outputs allow diagnosis of network problems from the main
controller.
Device Net covers all seven layers of the Open Systems Interconnection (OSI) standard. The protocol has a
limited number of network addresses with very small data packets. This helps limit network traffic and
ensures responsiveness. The length of the network cables limits the maximum speed of the network. The
basic features include:
A single bus cable that delivers data and power
Up to 64 nodes on the network
A data packet size of 0-8 bytes
Cable lengths of 500m/250m/100m for speeds of 125kbps/250kbps/500kbps, respectively
Devices can be added or removed while power is on
Based on the CANbus (Controller Area Network) protocol for OSI levels 1 and 2
Addressing includes peer-to-peer, multicast, master/slave, polling, or change of state
Talk Page

Control Net

Control Net is complimentary to Device Net. The standard is designed for communication among controllers
and it permits more complex messages than Device Net. It is not suitable for communication with individual
sensors and actuators, or with devices off the factory floor. Control Net is a more complicated protocol
method than Device Net. Control Net features include:
Multiple controllers and I/O on one network
Deterministic
Data rates up to 5Mbps
Multiple topologies (bus, star, tree)
Multiple media (coax, fiber, etc.)
Up to 99 nodes with addresses; up to 48 without a repeater
Data packets up to 510 bytes
Unlimited I/O points
Maximum length examples:
1000m with coax at 5Mbps - 2 nodes
250m with coax at 5Mbps - 48 nodes
5000m with coax at 5Mbps with repeaters
3000m with fiber at 5Mbps
30Km with fiber at 5Mbps and repeaters
Five repeaters in series, 48 parallel segments
Devices individually powered (no network power)
Devices can be removed while network is active
The network is unique because it supports a real-time messaging scheme called Concurrent Time Domain
Multiple Access (CTDMA). The network has scheduled, high priority and unscheduled, low priority updates.
When collisions are detected, the system waits at least 2ms for unscheduled messages. However, scheduled
messages will be passed sooner, during a special time window.
Talk Page

Ethernet
Ethernet is the predominate networking format. The first version was released in 1980 by a consortium of
companies, and various versions of Ethernet frames were released in the subsequent years. These include
Version II and Novell Networking (IEEE 802.3). Most modern Ethernet cards support different types of
frames.
The Ethernet frame is shown in Figure 36. The first six bytes make up the destination address for the
message. If all of the bits in the bytes are set, then any computer that receives the message will read it. The
first three bytes of the address are specific to the card manufacturer, and the remaining bytes specify the
remote address. The address is common for all versions of Ethernet. The source address specifies the
message sender. The Ethernet type identifies the frame as a Version II Ethernet packet if the value is greater
than 05DChex. Other Ethernet types use these two bytes to indicate the data length. The data can be from
46 to 1,500 bytes in length. The frame concludes with a checksum that is used to verify data is correctly
transmitted. When the end of the transmission is detected, the last four bytes are used to verify the frame is
correctly received.

Talk Page

Data Highway Plus DH+


Allen-Bradley PLCs communicate with other PLC
stations on the DH+protocol and also communicate
with their own remote chassis via the remote I/O
communications channel. Some guidelines for
DH+communications include:
The DH+provides communication among
DH+processors.
Each processor on the DH+must have its own
unique address.
A total of 64 (77 Octal) stations can be set up
on one peer link.
If a processor has enough communication channels (like the 5/40), it can communicate on more than
one DH+peer link at a time.
DH+is simply a method for communicating from one PLC to another. It does not allow one PLC to
control another PLC; it just lets you talk from PLC to PLC. It also makes it possible to plug a terminal
into any PLC on the peer link and talk to any other PLC on the peer link with the terminal.
Each chassis must either have an adapter module or a processor module installed in the leftmost slot.
In order for a processor to have a remote chassis, one channel must be set up as a scanner channel.
Talk Page

PLC Terms
Talk Page

ASCII
Stands for "American Standard Code for Information Interchange." For example, when the letter "A" is
transmitted it is automatically coded as "65" by the sending equipment. The receiving equipment translates
the "65" back to the letter "A." Thus, different devices can communicate with each other as long as both use
ASCII code.
Talk Page

ASCII Module
This intelligent PLC module is used for connecting PLCs to other devices also capable of communicating
using ASCII code as a vehicle.
Talk Page

Bus Topology
This is a linear local area network (LAN) arrangement in which individual nodes are tapped into a main
communications cable at a single point and broadcast messages. These messages travel in both directions
on the bus from the point of connection until terminators at each end of the bus dissipate them.

Figure 36: Bus Network Topology


Talk Page

CPU
Stands for "central processing unit," which is that part of a computer, PLC, or other intelligent device where
arithmetic and logical operations are performed and instructions are decoded and executed.
Talk Page

Daisy Chain
This is a description of the connection of individual devices in a PLC network, where each device is
connected to the next and communications signals pass from one unit to the next in a sequential fashion.
Talk Page

Distributed Control
This is an automation concept in which portions of an automated system are controlled by separate
controllers, which are located in close proximity to their area of direct control (control is decentralized and
spread out over the system).
Talk Page

Host Computer
A computer used to transfer data to, or receive data from, a PLC in a PLC/computer network.
Talk Page

Intelligent Device
Any device equipped with its own CPU.

I/O
Abbreviation for Inputs and Outputs, which are modules that handle data to the PLC (inputs) or signals from
the PLC (outputs) to an external device.
Talk Page

Kbps

This stands for "kilobits (thousand) bits per second," a rate of measure for electronic data transfer.
Talk Page

Mbps
Abbreviation for "million bits per second."
Talk Page

Node
This term is applied to any one of the positions or stations in a network. Each node incorporates a device
that can communicate with all other devices on the network.
Talk Page

Protocol
Manner in which data is arranged and coded for transmission on a network.
Talk Page

Ring Topology
This is a LAN arrangement in which each node is connected to two other nodes, resulting in a continuous,
closed, circular path or loop for messages to circulate, usually in one direction (Figure X). Some ring
topologies have a special "loop back" feature that allows them to continue functioning even if the main cable
is severed.

Figure 37: Ring Topology

Talk Page

RS232
An IEEE standard for serial communications that describes specific wiring connections, voltage levels, and
other operating parameters for electronic data communications. There also are several other RS standards
defined.
Talk Page

Serial
Electronic data transfer scheme in which information is transmitted one bit at a time.
Talk Page

Serial Port
Communication access point, shown in Figure 38, on a device that is set up for serial communications.

Figure 38: Serial Communications Port


Talk Page

Star Topology
A LAN arrangement in which nodes are connected to one another through a central hub, which can be active
or passive (Figure 39). An active hub performs network duties such as message routing and maintenance. A
passive central hub simply passes the message along to all the nodes connected to it.

Figure 39: Star Topology


Talk Page

Topology
This relates to a specific arrangement of nodes in a LAN in relation to one another. See Figure 40 for the
most commonly used types topologies.

Figure 40: Topology


Talk Page

Transparent
This term describes automatic events or processes built into a system that require no special programming or
prompting from an operator.
Talk Page

Remote I/O Configurations


It is common in the industry to centralize PLCs in relation to the process being controlled. This cuts down on
the number and length of cabling used to transmit information to and from the PLC. In some cases, this is not
feasible or ideal because an industrial environment can be quite harsh on the sensitive electronics used in
PLCs. For this reason, remote I/O modules have come into existence. There are many advantages to using
remote I/O modules, including:
Remote I/Os eliminate expensive point-to-point wires by networking just a few, or thousands of,
process signals onto one digital communication link.
For data acquisition, remote I/O modules send signals from field-mounted sensors, transmitters,
transducers, and alarms directly to DCS, PLC, and PC-based systems.
Ability to send control signals long distances to remote valves, pumps, and motors with remote?I/O.
Unburdening of an overworked computer system by distributing signal conditioning and intelligence.
Can be used as expansion I/O to add points to a PLC system.
Convert weak sensor signals to immune digital signals to avoid damage during long-distance
transmission through a noisy industrial environment.
Remote I/O allows signals to be transmitted any distance and over any terrain with twisted-pair wires,
fiber optics, radio link, or modems.
Talk Page

Peer-to-Peer Configurations
Peer-to-peer networks, as shown in Figure 40, enhance reliability by decentralizing the control functions
without sacrificing coordinated control. In this type of network, numerous PLCs are connected to one another
in a daisy-chain fashion, and a common memory table is duplicated in the memory of each. In this way, when
any PLC writes data to this memory area, the information is automatically transferred to all other PLCs in the
network. They then can use this information in their own operating programs.
With peer-to-peer networks, each PLC in the network is responsible for its own control site and only needs to
be programmed for its own area of responsibility. This aspect of the network significantly reduces
programming and debugging complexity; because all communications occur transparently to the user,
communications programming is reduced to simple read-and-write statements.
In a peer-to-peer system, theres no master PLC. However, its possible to designate one of the PLCs as a
master for use as a type of group controller. This PLC then can be used to accept input information from an
operator input terminal, for example, sending all the necessary parameters to other PLCs and coordinating
the sequencing of various events.
Talk Page

Host Computer
PLCs also can be connected with computers or other intelligent devices. In fact, most PLCs, from the small to
the very large, can be directly connected to a computer or part of a multi-drop host computer network via
RS232C or RS422 ports. This combination of computer and controller maximizes the capabilities of the PLC,
for control and data acquisition, as well as the computer, for data processing, documentation, and operator
interface.
In a PLC/computer network, as shown in Fig. 4C, all communications are initiated by the host computer,
which is connected to all the PLCs in a daisy-chain fashion. This computer individually addresses each of its
networked PLCs and asks for specific information. The addressed PLC then sends this information to the
computer for storage and further analysis. This cycle occurs hundreds of times per second.
Host computers also can aid in programming PLCs; powerful programming and documentation software is
available for program development. Programs then can be written on the computer in relay ladder logic and
downloaded into the PLC. In this way, you can create, modify, debug, and monitor PLC programs via a
computer terminal.
In addition to host computers, PLCs often must interface with other devices, such as operator interface

terminals for large security and building management systems. Although many intelligent devices can
communicate directly with PLCs via conventional RS232C ports and serial ASCII code, some do not have the
software ability to interface with individual PLC models. Instead, they typically send and receive data in fixed
formats. It is the PLC programmers responsibility to provide the necessary software interface.
The easiest way to provide such an interface to fixed-format intelligent devices is to use an ASCII/BASIC
module on the PLC. This module is essentially a small computer that plugs into the bus of the PLC. Equipped
with RS232 ports and programmed in BASIC, the module easily can handle ASCII communications with
peripheral devices, data acquisition functions, programming sequences, "number crunching," report and
display generation, and other requirements.
Talk Page

PLC Software
Talk Page

Software vs. Firmware


The terms software and firmware both refer to digitally stored programs and data structures that are read and
written by computers. In the PLC world, software is usually reserved for computer applications that allow the
logical creation, monitoring, and troubleshooting of a PLC program. One example of PLC software is the
RSLogix program developed by Allen-Bradley for use with their controllers. Firmware can be referred to as
the actual program a PLC uses to execute logical instruction. Firmware is often stored in internal memory or
on an Electrically Erasable Programmable Read-Only Memory (EEPROM). EEPROMs can be used to store
program backups if there is a program fault or a sustained power loss to the PLC.
Talk Page

HMI Human Machine Interface


The basic purpose of an HMI is to allow convenient and intuitive graphical interface with a process and for
control systems to be more interactive and user-friendly. HMIs provide a simple display that helps an
operator determine machine conditions and make simple settings. The following are the most common uses
of HMIs:
Display of machine and process faults and status
Simple operational commands such as stop/start
Monitor of production/process counts and values
Talk Page

Ladder Logic Diagrams


The ladder logic used in PLCs today was once referred to as relay logic due to the implementation of
physical relay coils used to control processes. Relay logic is now known as ladder logic because when the
logic circuit schematic is laid out with electrical notation, it resembles a ladder with separate rungs,
perpendicular between rails, containing symbols used to represent Boolean logic expressions such as AND,
OR, and NOT.

Figure 41: Ladder Logic


The example in Figure 41 shows two rungs containing a series of relays denoted as X, Y, and Z. These are
inputs while the symbol for S is an output.
The logical expression for this circuit is S=X AND (Y OR Z). If normally open contacts X and Y are closed,
there is an output at S. Likewise, because of the OR function of Y and Z, there also is an output at S if X and
Z are closed, but Y remains open. Any combination of Boolean expressions can be used in ladder logic,
including but not limited to AND, OR, NOT, NAND, NOR, and XOR. Figure 32 shows a ladder logic circuit
with two normally closed contacts, X and Y, connected in an OR configuration with the output S. Their
equivalent Boolean logic gate symbols are also shown. Table 5 is a logic chart showing the combination of
inputs that create a logic high or low output from this circuit.

Figure 42: NAND Circuit


The two NOT gates leading into the OR gate in
Figure 42(b) represent the normally closed contacts
in Figure 42(a). The NOT gate function reverses the
logic of any incoming signal, turning a HI into a LO
and vice versa. When multiple rungs are connected to
a single output on a ladder logic diagram, an OR
function exists, as represented by the OR gate in
Figure 42(b). The combination of these three logic
gates can be shown as a single NAND gate, as in
Figure 32(c). The NAND gate functions just like an
AND gate, creating a logic HIGH output in the
presence of logic HI inputs X and Y. The only
difference is the addition of the NOT function,
reversing the output from a logic HI to a logic LO so
that two HI inputs equal a LO output. Understanding
the logic of this circuit, you can see that to turn the
lamp off, X and Y must be HI. It is common when
examining logic circuits to refer to logic levels as true
or false, with true representing logic HI and false
representing logic LO.
Talk Page

Logic Instructions
In order to use the PLC and make simple edits, it is
necessary to understand some basic commands. The
commands are all entered in ladder logic format, and many of them are based on nomenclature used in relay
logic. There are timers, counters, coils, and contacts, among other commands.
Talk Page

Relays
Talk Page

Examine If Closed XIC


This command functions as the input or storage bit (Figure 43). The command is addressed to the bit level. If
the corresponding memory bit is 1 (true), the instruction allows rung continuity and outputs are energized
(other factors may affect rung continuity). If the corresponding memory bit is 0 (false), the instruction does
not allow rung continuity (it assumes its normally open state) and outputs on the rung are de-energized
(other factors can influence rung continuity).

Figure 43: XIC Command


A simple way to look at this instruction is from the processors point of
view. The processor is looking for power on that input point to make
this statement a true statement. If a switch in the field is closed, the
processor sees power on the point and makes the XIC true. This
causes the rung to be true and enables any output that is present.
This command is similar to a normally open contact on a real world
relay. If power is not on the relay, the contact is open and continuity through the rung is not allowed. If power
is not on the PLC point, this command is false and does not allow continuity through the rung, just like the
relay contact.
If power is applied to the relay, the contact is closed and allows continuity through the rung. In the case of the
XIC, as shown in Figure 43, if power is applied to the field point, the instruction becomes true and allows
continuity in the rung, just like the real world relay.

Talk Page

Examine If Open XIO

Figure 44: XIO Command


This command is similar to the XIC, except it works in reverse, as
shown in Figure 34. If the corresponding memory bit is 0 (false), the
instruction allows rung continuity and outputs are energized (other
factors may affect rung continuity). If the corresponding memory bit is
1 (true), this instruction does not allow rung continuity and outputs on
the rung are de-energized (other factors can influence rung
continuity).
A simple way to look at this instruction is from the processors point of view. The processor is looking for no
power on that input point to make this statement a true statement. If a switch in the field is opened, the
processor sees no power on the point, and makes the XIO true. This causes the rung to be true, and enables
any output that is present.
This command is similar to a normally closed contact on a real world relay. If power is not on the relay, the
contact is closed and continuity through the rung is allowed. If power is not on the PLC point, this command
is true, and allows continuity through the rung, just like the relay contact.
If power is applied to the relay, the contact is open, and does not allow continuity through the rung. In the
case of the XIC, if power is applied to the field point, the instruction is false, and does not allow continuity in
the rung, just like the real world relay.
Talk Page

Output Energized OTE

Figure 45: OTE Command


The OTE instruction, which is shown in Figure 45, is used to control a
bit in memory. If the bit corresponds to an output module terminal, the
device wired to the terminal is energized when the instruction is
enabled and de-energized when the instruction is disabled. If the
input conditions that precede the OTE instruction are true, the
processor enables that instruction. If the input conditions are false, the
processor disables that instruction. When rung conditions are false,
the corresponding device de-energizes.
An OTE instruction is similar to a relay coil. The OTE instruction is controlled by preceding input instructions
and the relay coil is controlled by contacts in its hardwired rung.
Talk Page

Output Latched OTL

Figure 46: OTL Command


The OTL instruction in Figure 46 functions much the same as the
OTE, with the exception that once a bit is set with an OTL, it
islatchedon. Once an OTL bit has been set on (1 in the memory), it
remains on, even if the rung condition goes false. The bit must be
reset with an OTU instruction.
When the processor changes from run to program mode, or when the

processor loses power and there is battery backup, the last true OTL instruction continues to control the bit
in memory. The latched output device is energized, even though the rung conditions that control the
instruction may have gone false.
The OTL instruction is retentive. When the processor loses power, is switched to program mode or test
mode, or detects a major fault causing outputs to go off. However, the states of retentive outputs are retained
in memory. When the processor resumes operation in run mode, retentive outputs immediately return to their
previous states. Non-retentive outputs, such as OTE outputs, are reset.
Talk Page

Output Unlatched OTU

Figure 47: OTU Command


Figure 47 displays an OTU command, which is a retentive output
instruction that only turns off a bit (it cannot turn on a bit). This
instruction usually is paired with OTL instruction, with both
instructions addressing the same bit. The OTU instruction turns off the
bit that was turned on (latched) by the OTL instruction.
When the processor changes from run to program mode, or when the
processor loses power and there is battery backup, the bit is retained in the state set by the last rung of the
latch/unlatch pair that was true.
The OTU instruction tells the processor to turn off the addressed bit based on the rung condition. Thereafter,
the bit remains off, regardless of the rung condition, until it is turned on, typically by an OTL instruction in
another rung.
Talk Page

Timers
Talk Page

Timer On Delay TON

Figure 48: TON Command


The TON instruction shown in Figure 48 is used to turn an output on
or off after the timer has been on for a preset time interval. This
instruction begins timing, at either 1 second or 1-hundredth of a
second intervals, when its rung is true and continues until one of the
following happens:
The accumulated value equals the pre-set value.
The rung goes false.
The processor resets the accumulated value when the rung conditions are false, regardless of whether or not
the timer has timed out. When the rung conditions go True, the timer is on and the Enable (EN) bit is set.
When the timer reaches its preset count and times out, the Done (DN) bit is set to true.
Talk Page

Timer Off Delay TOF

Figure 49: TOF Command


The output instruction in Figure 49 begins timing, at either 1 second
or 1-hundredth of a second intervals, when its rung goesfalseand
continues timing until one of the following conditions occur:
The accumulated value equals the pre-set value.
The rung goes true.
The processor resets the accumulated value when the rung conditions are true, regardless of whether or not
the timer has timed out.
Talk Page

Retentive Timer On RTO

Figure 50: RTO command


The RTO instruction shown in Figure 50 is used to turn an output on
or off after its timer has been on for a preset time interval. The RTO
instruction lets the timer stop and start without resetting the
accumulated value.
The RTO instruction begins timing when its rung goes true. As long as
the rung remains true, the timer updates the accumulated value each
program scan, until it reaches the pre-set value. The RTO instruction retains its accumulated value even if
one of the following occurs:
The rung goes false.
There is a change to program mode.
The processor faults or loses power.
When the processor resumes operation or the rung goes true, timing continues from the retained
accumulated value. By retaining its accumulated value, retentive timers measure the cumulative period
during which its rung is true. The RTO command is reset using the RES command.
Talk Page

Counters
Talk Page

Count Up Counter CTU

Figure 51: CTU Command


The CTU instruction shown in Figure 51 counts upward over a range
of -32,768 to+32,767. Each time the rung changes from false to true,
the CTU instruction increases the accumulated value by one count.
When the accumulated value equals or exceeds the pre-set value, the
CTU sets a DN bit the ladder program can use to initiate an action,
such as controlling a storage bit or an output device. CTU instructions
are retentive and require an RES instruction to be reset. They also
reset if the counter decreases below the pre-set value.
Talk Page

Count Up Counter CTD

Figure 52: CTD Command


Figure 52 shows CTD instruction, which counts downward over a
range of+32,767 to -32,768. Each time the rung changes from false to
true, the CTD instruction decreases the accumulated value by one
count. The DN is set as long as the accumulated value is greater than
or equal to the pre-set value. When the accumulated value is less
than the pre-set value, the CTD resets a DN bit, which the ladder
program can use to initiate an action, such as controlling a storage bit
or an output device. CTD instructions are retentive and require RES instruction to be reset. They also reset if
the counter increases above the pre-set value.
Talk Page

Reset Command RES

Figure 53: RES Command


The RES instruction shown in Figure 53 is an output instruction that
resets a timer or counter. The RES executes when its rung is true.
Reset commands normally are used for counters and retentive timers,
but also may be used for TONs to reset the timers while their rungs
are still true.
Talk Page

Data Transfer Instructions

Figure 54: Data Transfer Instructions


The Move (MOV) command shown in Figure 54 is an output instruction that
copies a value from a source address to a destination. As long as the rung
remains true, the instruction moves the data during each scan. This command
makes a copy of the original and places the duplicate in a new location (Dest).
The original value remains intact and unchanged in its source location.
Talk Page

Arithmetic Commands

Figure 55: ADD Command


PLCs have a wide variety of available mathematical commands. These commands
simply perform the indicated math function on any valid instruction address data or
any number.
In the example shown in Figure 55, the user is adding the contents of N7:21 to the
contents of N7:22. The result is stored in file N7:19. Notice that the actual contents of
the register being used is shown below the register. In this case, N7:21, containing the number 20 is added to
N7:22, containing the number 5. The result is stored in N7:19 as the number 25 (20+5).
All math commands work in a similar manner.
Talk Page

Data Manipulation Instructions


Talk Page

Master Control Reset

Figure 56: MCR Command


Figure 56 shows output instruction, which is also known as zone control used to
set up areas or zones of the ladder program where all non-retentive outputs
may be simultaneously disabled for the same length of time. It is used in pairs:
one MCR to define the start of the effected ladder area and one MCR to define
the end of the area.
An input instruction is programmed on the rung of the first MCR to control rung logic continuity. When the
rung is false, all non-retentive outputs within the controlled zone are disabled. When the rung is true, all
rungs are scanned according to their normal rung conditions, disregarding the zone control instruction.
CAUTION: MCR-controlled areas must contain only two MCR instructions: one to define the start and one to
define the end. Any additional MCR orgo-to" type instructions could produce unexpected program damage or
machine operation results. DO NOT OVERLAP MCR ZONES! The MCR instruction is not a substitute for a
hardwired master control relay that provides emergency stop capability. You still should install a hardwired
master control relay to provide emergency I/O power shutdown.
Talk Page

Program Control Instructions


Talk Page

Subroutines

Subroutines are an important part of a PLC program. By using them, the programmer can make a program
much more logical and faster to execute.
Basically, a subroutine is a ladder that is only executed when it is called from the main program. File number
2 is always the first ladder in a program and, as such, is the main ladder. When the processor scans its
ladder programs, it only scans ladder number 2 unless ladder number 2 commands it to go to another
subroutine. If no other ladders are called by a JSR, then the ONLY ladder executed is file 2 . When a
JSR is encountered, the program jumps out of that ladder (in this case ladder 2), and goes to the ladder
called for in the subroutine jump command. When the end of the file is reached, the program jumps back to
the file that has the JSR, in this case file 2, and continues executing. It also returns if a Return (RET)
command is encountered in the ladder.
In order to call a subroutine, a command, such as the one shown in Figure 57, is used. It is called a JSR

(Jump To Subroutine) command. Notice that in this case, the subroutine being called is ladder file number U:
3. The "U" indicates the file is for a user. All ladder files are for users.