Field Suppression Equipment with
DC-Breaker and Electronic
Switching-on of the Discharge Resistor
4. Objective of Field Suppression
A fast de-excitation of the synchronous machine is
necessary in order to limit the damage in case of
intemal faults which cannot be switched off by
tripping the generator breaker. It is therefore im-
portant to rapidly eliminate the source voltage which
Grives the fault current. The result is a forced
suppression of the air-gap flux of the generator and
of the field current (Fig.1)..
Figure 1
By controlling the power converter from rectifier to
inverter operation, the excitation equipment has
also the facility of quick de-excitation. However, the
field suppression must also be guaranteed in case
of failure ofthe thyristor fring pulses andthe power
converter. Therefore, a completely independent
field suppression equipment has to be provided for
each generator.
The most severe intemal fault condition results
froma S-phase short circuit a the generator termi-
nals (a). The physical consequences of this faut
determine the layout of the entire fied suppression
‘equipment. In order to avoid iron burning, al insu-
lation failures of the stator winding must initiate an
10
DC-Breaker Converter
Discharge
Circuit
immediate field suppression as well (b). A simple
‘ground fault of the rotor winding which is usually
fully insulated from ground does not cause a fault
current, But a very severe disturbance on the rotor
side e.g. a short circuit atthe slip rings, calls for a
uick separation of the voltage source (0). Also
certain excitation failures (d) call for immediate
separation.
Physically field suppression with the usual equip-
‘ment is a conversion of the magnetic field energy to
heat. This happens partly within the field winding,
parily in a separate field discharge resistor. At the
same time, the excitation source must be inter-
rupted by a breaker.
HIER 94 833 E 1ABB
2. Methods of Field Suppression
There are various de-excitation circuits with ditfe-
rent configurations, which areinpartclosely related
to rotating exciters used in the past. For static
excitation systems, the field suppression by means
ofa parallaldischarge resistor as shown in Fig. 1 is
generally in use today.
Basically, the field suppression comprises two
‘functions:
- The switching-on of the discharge resistor
~The disconnecting ofthe field-winding from the
power converter
It a conventional fieldbreaker is used, both func-
tions are performed by the same apparatus. The
‘experience gained with fieldbreakers in the past
was good. However, afieldbreakeris a very special
device and an increasing number of manufacturers
have meanwhile stopped their production, particu-
larly for breakers with rated currents above 2000
Ampére.
‘A very reliable alternative is the application of a
normal DC-breaker to open the field-circuit and a
controlled thyristor to connect the field discharge
resistor. The advantage ofthis solution is the use of
a breaker which has proved its reliability in other
applications (e.g. on traction vehicles).
In both cases, the breaker rating is determined by
the maximum field current, the dielectric strength of
the rotor winding and the type and rating of the
discharge resistor.
The field de-excitation is initiated by the tripping
‘command: The discharge resistor Ris connected
first whereby the voltage of the field winding U,
appears across its terminals. The breaker starts to
open immediately. The field current |is compelled
to commutate to the field discharge circuit. Since
the current decreases only slowly, the voltage
across the field discharge resistanceincreases first
tothe value Upe = I” Re. The inductance of the field
winding acts here as driving source, whereby the
2 HIER 94 833 E
induced voltage E, is added to the source voltage
U,
‘These two voltages appear across the main pole of,
the breaker during breaking and give rise to arcing.
‘The maximum arc voltage U,,.. which can be
sustained by the contact, is therefore a defining
‘magnitude for the breaker and for the rating of the
field discharge resistor Rena
After the extinguishing of the arc the current flows
over the field discharge resistor. Inthe caseol linear
field discharge resistor (1) the current decays with
the time constant
4
Re,
By using a non-linear field discharge resistor (2),
the de-excitation is realized faster.
Asatast decay of he flux is required, itis important
to realize that the flux decay can be forced only in.
the direct axis. The time constants inthe quadrature
axis cannot be influenced by the excitation system.
Ma suppression resistor R, = R, field resistance) is
connected in series, the effective time constants at
no-load (T,,) and with load (T.,) are reduced to halt,
The armature time constant T, and the one of the
quadrature axis T,, remain unchanged.
With an undisturbed excitation system, the de-
excitation is initiated by controling the thyristor-
bridge in the inverter mode before tripping the
breaker. Thestrainon the breakeris reducedas the
voltage across the main contact is much smaller
when the breaker opens. However, because of
possible excitation failures the design of the brea-
ker and the discharge resistor must be based upon
‘maximum output voltage (ceiling).
e910Figure 2
3. Components of Field Suppression Equipment
‘The main components of the field discharge circuit ciated firing electronics and current measuring as
are the DC-breaker, the thyristor circuit with asso- well as the discharge resistor (Fig.3).
0c-Brekee Fring Unit Thyritors
®
weet
I Puse |
tt 1 Ampifcaion |
3 0 Suopy |
21] (et wenitorng |
2 ea Current a
2 ts] wonitorng I i
5 J Pose -
tt mpitecion
ig sae Supy | j
<—{_Weontoring
te curent | 7
S21 wentoring | fl
° a ate
teoletor Pulse Pulse Current Discharge
Switch Control Unit Transformer Measuring Resistor
Figure 3
e410 HIER 94 833 EABB
3.1 DC-Breaker
Generally the DC-breaker has to interupt a direct
current in a circuit with resistance and inductance.
‘At rather low voltage and current this is only possi-
ble with the aid of the inverse voltage created
across a well defined aro.
More recent manufactured breakers are equipped
with limiting means such as auxiliary arc gaps,
limiting resistors and above all the feature of divi-
ing the arc into a muttitude of series arcs. The
result is a more controlled and rather constant arc
voltage.
‘The most important criterion of a breaker is its
interrupting capacity. It is determined by the follo-
wing factors:
- maximum are voltage
~ maximum interrupting current
- maximum are energy
The arc voltage mainly depends on the geometric
dimensions of the arc chamber. For the current
interruption, dynamic forces and the arc quenching
capability are important.
‘Apart from their breaking capacity, DC-breakers
are characterized by their rated current and rated
voltage.
Contrary to field breakers, DC-breakers are provi-
ded with an electronic overcurrent release. It limits
the fault current in case of a DC-short circuit, thus
protecting converter thyristors and fuses from
damage.
3.2 Field Suppression Resistor
Apart of the field energy is converted to heat within
the field suppression resistor. Its size is also deter-
‘mined by the heat storing capacity. Another impor-
{ant factor is the rigidity of conductors, terminals
and the resistor itself to withstand the dynamic
forces of peak currents. For field suppression,
4 HIER 94 633 E
linear and non-linear (voltage dependent) resistors
are used,
The field current decreases according to the well-
known exponential function. For generators, the
‘maximum intial value of the field current appears in
case of a 3-phase stator terminal short circuit. The
field voltage is proportional to the current. Its initial
value U,, = j,, “ Re must be smaller than the rotor
insulation test voltage. On the other hand, the field
breaker can commutate the current onto the sup-
pression resistor only if its arcing voltage is higher
than the sum of maximum field voltage U,, and the
ceiling voltage U, of the excitation source.
‘The energy to be absorbed is given by the following
integral:
We= Re F (ot
To speed up the field suppression mainly for large
machines, voltage dependant resistors made of
silicon-carbide are used. With decreasing voltage
this material shows a remarkable rise of its specific
resistance. The initial resistance value is the same
as fora linear suppression resistor, being limited by
the maximum admissible voltage. As a result of the
increase in resistance, the voltage decreases slow-
ly, however, the current very rapidly. The effective
time costant becomes a function of the momentary
voltage.
3.3 The Thyristor-Crowbar circuit
‘The thyristor-crowbar circuit consists basically of
the following functional blocks:
- One thyristor each for the positive and the ne-
gative current direction
- Firing electronics close to thyristors including
covervoltage detection
- Thyristor current measuring
- Control electronics
‘The thyristors are selected based on the thermal
stress during the field suppression and the maxi-
mum are voltage of the DC-breaker. The thyristors
e010ABB
‘are mounted in a suitable press-unit and are natu-
rally cooled
‘The functional safety ofthe thyristor-crowbarcircuit
is treated with spacial care. Consequently, the fring
of the discharge-thyristor (positive current direc-
tion) is assured by multiple measures.
~ Simultaneously with the breaker OFF-command,
the discharge thyristor is fired continiously by
two independent firing circuits.
~ Should this controled fring fail, the DC current
builds up a sufficiently high voltage to fire the
thyristors by overvokage. Two independent BOD's
(BOD = Break-over Diodes) break over at apre-
determined voltage level fre thereby the thyri-
stors.
‘The thyristor itself serves as a last protection
‘measure. Its peak inverse voltages selectedto
bbe lower than the arcing voltage of the breaker.
‘Should both described firing circuits fail, the
thyristor is fired by itself by overvoltage. In this
case the thyristor might be injured, however, fur-
ther damage to the field winding is prevented.
Overvottages resulting from induced negative field
‘currents should, with a safety margin, always remain
below the insulation level of the rotor winding, ie.
below the test voltage, as well as below the peak
reverse voltage (PIV) of the converter thyristors.
Under all circumstances to avoid an insulation fault
or thyristor failure by overvottage - asynchronous
running for instance - an additional thyristor for the
negative current direction is provided. For its firing,
a BOD is used as well.
‘current in the discharge circuit is measured, also
with respect to its direction, and further processed.
Measuring and processing circuits are redundant.
(On each field-discharge the unilormity of two
‘measurings aremonitored. Analarm-signalisinitia-
ted upon failure.
4. Advantages of the DC-breaker solution
The application of a DC-breaker instead of a con-
ventional fieldbreaker offers the advantages listed
below:
= Commercially available and also used for other
applications. It is worldwide manufactured by
several companies.
Insensitive to vibration and shock due to simple
‘mechanical construction and application on
traction vehicle .
= High arcing voltage resulting in shorter dischar-
ge time,
+ Automatic overcurrent release limits the fault
‘current in case of DC-short circuits.
- No movable parts in the discharge cicuit
High insulating level
In comparison to the conventional fieldbreaker,
following features are to be considered:
~ Inordertoachieve a suitable arcing voltage, field
breakers are often equipped with two or more
main contacts with arc chambers which are
connected in series. It was evident to separate
these contacts on the positive and the negative
pole, thus achieving a galvanic separation bet-
‘ween the field winding and the voltage source.
However, with respect to fault clearance, a double
pole breaking is not necessary. There are no
faults which could only be cleared by double
pole interruption.
~ Should existing safety regulation ask for double
pole separation between field winding and con-
verter, e.g. for maintenance work, an additonal
isolator-switch will be mounted in the negative
pole.
HIER 94 833 E 5ABB
~ In case of the fieldbreaker, the discharge con-
tacts are operated by a mechanical link on of
shortly before the opening of the main contacts.
‘A mechanical failure of the discharge contact
canon theotherhand prevent the maincontacts
‘rom opening, Such a serious fault is not possi-
ble with the DC-breaker solution.
5. Mechanical construction of the Thyristor-Crowbar circuit
‘The crowbar circuit is built as follows:
Base plate
UNS 4014’a. for § kV Test Voltage
UNS 4024 a for 10 kV Test Voltage
Var. 1 for |,, < 4000 A
Var. 2 for |, > 4000 A
‘The base plate contains, apart from the two pulse
transformers, the redundant current measuring and.
the RC-circuits for the thyristors.
Thyristor press-unit
For 2" and 3” disc thyristors:
UNS 4012a, Var. for thyristor CS 1000-18
Var.2 for thyristor YST 36-22
Var.3 for thyristor CS 1702-44
For 4" disc thyristors:
UNS 4022a, Var. for thyristor YST 60-22
Var.2 for thyristor CS 2402-44
Firing unit
UNC 4610a
The firing unit comprises of the two redundant fring,
circuits for the positive thyristor. Each firing circuit
consists of a coupling diode to the pulse transfor-
mer and an emergency firing by means of a break
over diode.
For the negative thyristor, a simple overvoltage
firing by means of another break over diode is
Provided,
6 HIER 94 833 E
Control unit
UNC 46114
‘The control unit contains two independent chan-
nels. Each one is equipped with
Pulse amplifier for the firing pulses of the
positive thyristor
Monitoring of the external supply voltages
415 Vand +48 V
Evaluation of the current measuring.