5 kV, up to 40 kA
Power Circuit Breaker
Standard Features
Dead tank design, with one self-blast interrupter per tank on a
galvanized steel frame
All tanks factory leak tested in a hard-vacuum chamber with a
helium mass spectrometer
Certified per ANSI C37.04, C37.06, and C37.09 Standards
FSA-2 motor charged spring operating mechanism
Frame mounted NEMA-3R steel control cabinet protected with
TGIC polyester powdercoat finish
Single tank-mounted gas density monitor and pressure gauge
Porcelain bushings
Continuous current ratings through 3000 A
Ships fully assembled and factory tested with 5 psig SF6 gas
Options and Accessories
Condition monitoring with the Circuit Breaker Sentinel (CBS)
Density monitor and temperature-compensated pressure gauge
directly-mounted on each tank
Extra creep and/or extra strike bushings for special applications
Silicone rubber composite bushings
Tank heaters for operation in ambient temperatures below -40C
High seismic designs
National Board certification of interrupter tanks per the ASME
Pressure Vessel and Boiler Code
FSA-2 Mechanism
The type FSA-2 spring mechanism,
mounted within the breaker control cabinet,
provides the driving force to gang-operate
the breakers self-blast interrupters.
Mechanical energy for closing is stored
in a pair of helical springs, whose charge
is maintained by a universal motor. Each
closing operation simultaneously charges a
similar pair of trip springs.
The mechanism is simple and relatively low
powered, resulting in minimal mechanical
stresses during breaker operation and
lower overall maintenance costs.
10 1/4"
(260)
96 25/32" (2459)
36 5/32"
(918.4)
33 11/16" (855)
PHASE SPACING
33 11/16" (855)
PHASE SPACING
66 27/35" (1698)
27" (688)
METAL TO METAL
21" (305)
27" (688)
29 1/2" (749)
METAL TO METAL
METAL TO METAL
19 5/16" (491)
101 7/16"
(2576)
MIN.
MONITOR
POLE 1
128"
(3251)
LIVE
PARTS
70 5/8"
(4971)
130 5/16"
(3110)
HEIGHT OF
COUNTER
POSITION
INDICATOR
AND
SPRING
POSITION
INDICATOR
83 7/32"
(2114)
109"
(2770)
93 1/16"
(2364)
HEIGHT TO
BREAKER
C/L
BOTTOM OF
CONTROL
CABINET
HEIGHT OF
LEG
GAS GAUGE/ EXTENSIONS
FILL VALVE
ASME
STAMPING
ON TANK
AND END
COVER
(AS REQUIRED)
INSTALLED
HEIGHT TO
TOP OF
BUSHING
MINIMUM
BUSHING
HEIGHT
33 5/8"
(854)
31 7/8"
(810)
RUPTURE
DISC
145 1/2"
(3696)
LOCATION OF
EXTERNAL
ELECTRICAL
69 SW.
(AS REQUIRED)
LOCATION OF
EXTERNAL ELECTRICAL
OUTLET
(AS REQUIRED)
Rated Capabilities
Circuit Breaker
Type
Rated Maximum
Voltage
(kV, rms)
Short Circuit
and Short Time
Current
(kA, rms)
Maximum
Continuous
Current
(A, rms)
Rated Interrupting
Time
(Cycles)
Full Wave
Withstand Voltage
(kV, Peak)
Power Frequency
Insulation
Withstand Voltage
(kV, rms)
2 -sec Chopped
Wave Impulse
Voltage
(kV, Peak)
Closing and
Latching Current
(kA, Peak)
38PM31-12
38
31.5
1200
200
80
258
82
38PM31-20
38
31.5
2000
200
80
258
82
38PM31-30
38
31.5
3000
200
80
258
82
38PM40-12
38
40
1200
200
80
258
104
38PM40-20
38
40
2000
200
80
258
104
38PM40-30
38
40
3000
200
80
258
104
48PM31-12
48.3
31.5
1200
250
105
322
82
48PM31-20
48.3
31.5
2000
250
105
322
82
48PM31-30
48.3
31.5
3000
250
105
322
82
48PM40-12
48.3
40
1200
250
105
322
104
48PM40-20
48.3
40
2000
250
105
322
104
48PM40-30
48.3
40
3000
250
105
322
104
72PM31-12
72.5
31.5
1200
350
160
452
82
72PM31-20
72.5
31.5
2000
350
160
452
82
72PM31-30
72.5
31.5
3000
350
160
452
82
72PM40-12
72.5
40
1200
350
160
452
104
72PM40-20
72.5
40
2000
350
160
452
104
72PM40-30
72.5
40
3000
350
160
452
104