Sei sulla pagina 1di 22

BTS3900 Installation Guideline V1.

BTS3900 installation guidelines V1.0

Product Name

HUAWEI BTS3900

Document name

BTS3900 Installation Guidelines V1.0

Confidentiality Level

INTERNAL

Prepared by

BELKADA Samir

Prepared date

27/09/2011

Contents
1...................................................................................... Indoor BTS Installation 2
1.1

Overview of Huawei indoor BTS3900.........................................................................................2

1.2

CPRI cables and RF cables layout.............................................................................................3

1.3

Cable routing of indoor BTS3900................................................................................................4

1.4

Cable layout on the top of cabinet..............................................................................................5

1.5

DDF installation in the existing transmission cabinet..................................................................6

1.6

E1 transmission cable connection for normal sites.....................................................................6


201612-11

Huawei Confidential

Page1, Total 22 ,

BTS3900 Installation Guideline V1.0


1.7

E1 transmission cable connection for cascaded sites................................................................6

1.8

E1 cable color sequence.............................................................................................................7

1.9

Alarm cable connection (From OTA alarm system to BTS)........................................................8

1.10

Antistatic wrist strap.................................................................................................................... 9

1.11

Power cable labels.................................................................................................................... 10

1.12

Signal cable labels.................................................................................................................... 11

1.13

BTS Power on........................................................................................................................... 14

1.14

Site cleaning............................................................................................................................. 15

2............................................................................................... BTS Integration 16


2.1

Hardware Ready for Integration................................................................................................16

2.2

Transmission Ready for Integration..........................................................................................16

2.3

Hardware and Transmission Ready for Integration...................................................................17

2.4

BTS Integration......................................................................................................................... 17

2.5

Tools and Materials for Site Engineer for BTS Integration........................................................18

2.6

Possible Problem for BTS Integration and Solution..................................................................18

2.7

BTS Integration Status Check...................................................................................................20

201612-11

Huawei Confidential

Page2, Total 22 ,

BTS3900 Installation Guideline V1.0

1. Indoor BTS Installation

1.1

Overview of Huawei indoor BTS3900

201612-11

Huawei Confidential

Page3, Total 22 ,

BTS3900 Installation Guideline V1.0

1.2

CPRI cables and RF cables layout

Respect the
color ring tape
for each cell
(red, yellow and
blue)

900M

900M &1800M
CPRI cables to down CPRI port
on the RFU (Not up CPRI port)!

Notes: Connect the CPRI and the RF cables according to the engineering design ( BTS dual
band design from CME ConnectorTool software)

201612-11

Huawei Confidential

Page4, Total 22 ,

BTS3900 Installation Guideline V1.0

1.3

Cable routing of indoor BTS3900

201612-11

Huawei Confidential

Page5, Total 22 ,

BTS3900 Installation Guideline V1.0

E1 Cable

Alarm Cable

Power Cable

201612-11

Huawei Confidential

Page6, Total 22 ,

BTS3900 Installation Guideline V1.0

1.4

Cable layout on the top of cabinet

201612-11

Huawei Confidential

Page7, Total 22 ,

BTS3900 Installation Guideline V1.0

1.5

DDF installation in the existing transmission cabinet

HUAWEI DDF

1.6

E1 transmission cable connection for normal sites


Huawei
BBU
(GTMU)

1.7

Huawei
E1 DDF
Huawei
Responsible

OTA
DDF
Huawei
Responsible

OTA
IDU
OTA
Responsible

E1 transmission cable connection for cascaded sites


Huawei
BBU
(GTMU)

201612-11

Huawei
E1 DDF
Huawei
Responsible

OTA
DDF
Huawei
Responsible

Huawei Confidential

OTA IDU to up hop


OTA IDU to next hop

OTA
Responsible

Page8, Total 22 ,

BTS3900 Installation Guideline V1.0

1.8

E1 cable color sequence


E1
No.1 E1

No.2 E1

No.3 E1

No.4 E1

201612-11

PIN
X.19
X.20
X.1
X.2
X.21
X.22
X.3
X.4
X.23
X.24
X.5
X.6
X.25
X.26
X.7
X.8

Wire Color
gray
white
blue
white
blue
red
orange
white
orange
red
green
white
green
red
brown
white

Remarks
TX+
TXRX+
RXTX+
TXRX+
RXTX+
TXRX+
RXTX+
TXRX+
RX-

Huawei Confidential

Huawei E1 DDF port


1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Page9, Total 22 ,

BTS3900 Installation Guideline V1.0

1.9

Alarm cable connection (From OTA alarm system to BTS)


Huawei
BBU
(UPEU)

Huawei
Alarm DDF
Huawei
Responsible

OTA
Alarm System
OTA
Responsible

External alarm cables in UPEU

External alarm cables in DDF

OTA alarm definition:


Port name
Ext-alm0

Ext-alm1

201612-11

RJ45 port

Alarm configuration

Rectifier alarm

Main power alarm

Door alarm

Battery alarm

Fire alarm

+30 Temperature alarm

Air Conditioner alarm

+40 Temperature alarm

Huawei Confidential

Page10, Total 22 ,

BTS3900 Installation Guideline V1.0

Alarm cable distribution in UPEU


Alarm cables to DDF

To FAN COM OUT

The alarm label should be


printed and sticked on the DDF

1.10 Antistatic wrist strap

201612-11

Huawei Confidential

Page11, Total 22 ,

BTS3900 Installation Guideline V1.0

1.11 Power cable labels

Label in the bottom of BTS

Label in OTA power cabinet

201612-11

Huawei Confidential

Page12, Total 22 ,

BTS3900 Installation Guideline V1.0

1.12 Signal cable labels


CPRI lable in BBU side:

CPRI label in GRFU/DRFU side:

E1 cable and alarm cable labels in BBU:

201612-11

Huawei Confidential

Page13, Total 22 ,

BTS3900 Installation Guideline V1.0

Alarm cable label


E1 cable label

E1 cable and alarm cable labels in DDF:

E1 cable label

Alarm cable label

201612-11

Huawei Confidential

Page14, Total 22 ,

BTS3900 Installation Guideline V1.0

201612-11

Huawei Confidential

Page15, Total 22 ,

BTS3900 Installation Guideline V1.0

1.13 BTS Power on


1. When should we power on BTS?
1.1. For new sites, the BTS should be power on after hardware installation;
1.2. For the sites which already installed, please power on the BTS when you enter
the sites for clean up/ pre-acceptance/ acceptance with OTA.
2. Measure input voltage before power on BTS and record the voltage value.
The input voltage of the indoor BTS should be between -44V DC~-57V DC;
The input voltage of the outdoor BTS should be between 180V AC~260V AC;
3. If the voltage is out of the range, please record the problem and inform
your PM to ask OTA to solve the rectifier problem.
4. Indoor BTS power on sequence:
1) Switch on the switch for 2G BTS in OTA power cabinet;
2) Switch on FAN;
3) Switch on BBU;
4) Switch on UPEU (in BBU);
5) Switch on GRFU/DRFU;
DCDU01 in BTS3900 cabinet:

5. Indoor BTS power off sequence:


1)
2)
3)
4)
5)

Switch off GRFU/DRFU;


Switch off UPEU (in BBU);
Switch off BBU;
Switch off FAN;
Switch off the switch for 2G BTS in OTA power cabinet;

201612-11

Huawei Confidential

Page16, Total 22 ,

BTS3900 Installation Guideline V1.0

1.14 Site cleaning

201612-11

Huawei Confidential

Page17, Total 22 ,

BTS3900 Installation Guideline V1.0

2 BTS Integration

2.1

Hardware Ready for Integration

BTS was installed (with GRFU/DRFU);


E1 cable was connected from BTS to OTA DDF;
BTS was power on;

2.2

Transmission Ready for Integration

BSC engineer perform the loop test with OTA to check the E1 link from Microwave
IDU to BSC

Huawei
BTS

Huawei
E1 DDF
Huawei
Responsible

OTA
DDF
Huawei
Responsible

OTA
IDU
OTA
Responsible

OTA
DDF

Huawei
DDF

Huawei
BSC
BTS Site

201612-11

Huawei Confidential

BSC

Page18, Total 22 ,

BTS3900 Installation Guideline V1.0

2.3

Hardware and Transmission Ready for Integration

1. BTS was installed (with GRFU/DRFU);


2. E1 cable was connected from BTS to OTA DDF;
3. BTS was power on;
4. E1 loop test was done by OTA&Huawei and the E1 link from IDU to BSC is OK;

2.4

BTS Integration

If the BTS is powered on and E1 connection is done without problem, the BTS can
be integrated automatically.
If the BTS cant be integrated, site engineer should visit the sites for
troubleshooting.

201612-11

Huawei Confidential

Page19, Total 22 ,

BTS3900 Installation Guideline V1.0

2.5

Tools and Materials for Site Engineer for BTS Integration

When you go to the sites, please take necessary tools and materials and try to
close the installation problem in sites. Do not just record and report the problem.
1) Key for sites;
2) PC, Ethernet cable and necessary softwares (SMT)
3) Multimeter;
4) E1 connection tool;
5) E1 cable (20 meters);
6) Key for Indoor BTS3900;
7) Key for outdoor BTS3900A;
8) Key for the outdoor transmission cabinet;
9) DC power cable and connectors (10 meters);
10) AC power cable and connectors (10 meters);

2.6

Possible Problem for BTS Integration and Solution

No

Problem

Solution

Access problem (Owner refuse)

Contact with OTA deployment engineer

Access problem (No suitable key)

Contact with OTA deployment engineer

Access problem (Lock was broken)

Use screw driver for help

BTS not powered on

Power on BTS

E1 cable is not connected from BTS to Connect E1 cable


OTA DDF

E1 cable connection mistake;

Reconnect E1 cable

GRFU/DRFU board are not installed

Record the problem and inform RPM

Transmission problem

Physical loop from Huawei DDF to BSC to


check OTA transmission from IDU to BSC;

201612-11

Huawei Confidential

Page20, Total 22 ,

BTS3900 Installation Guideline V1.0

No

Problem

Solution
(BSC engineer will check status)
Physical loop from Huawei DDF to BTS to
check the E1 cable connection;
(If the LIU0 LED light is off, the E1 cable
connection is OK)

OTA didnt connect E1 cable from IDU Contact OTA deployment engineer for
to OTA DDF
help and connect the E1 cable by ourself

10

OTA didnt remark TX/RX in OTA DDF

Contact OTA deployment engineer for


help and connect the E1 cable by ourself

11

[Outdoor] OTA didnt connect AC power Record the problem and inform OTA
cable from TGBT to the fuse (for 2G deployment engineer and Huawei RPM
BTS)

12

[Outdoor] OTA didnt provide AC power Connect the AC power cable by ourself
cable from fuse (for 2G BTS) to BTS

13

[Outdoor] OTA outdoor power doesnt Record the problem and inform OTA
work
deployment engineer and Huawei RPM

14

[Outdoor] No key for OTA outdoor Contact with OTA deployment engineer
transmission cabinet

201612-11

Huawei Confidential

Page21, Total 22 ,

BTS3900 Installation Guideline V1.0

2.7

BTS Integration Status Check


1. If the LIU0 LED light is off, that means the transmission to BTS is OK,

LIU0 light should be off

2. Also please check with BSC engineer that if he can see the BTS in BSC.
If the BTS can be monitored in BSC, the BTS is integrated successfully!
3. Check if there is any alarm of the BTS in site. All the LED lights should be off or
green. No any red light.

4. Check with BSC engineer if there is any alarm of the BTS in BSC.

201612-11

Huawei Confidential

Page22, Total 22 ,

Potrebbero piacerti anche