UL Listing Category
Product Description
Reliable Models F1FR Series Sprinklers are quick response sprinklers which combine the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler.
The Models F1FR Series Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers
have demonstrated response times in laboratory tests
which are five to ten times faster than standard response
sprinklers. This quick response enables the Model F1FR
Series sprinklers to apply water to a fire much faster than
standard sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled
amount of special fluid hermetically sealed inside a precisely manufactured glass capsule. This glass bulb is
specially constructed to provide fast thermal response.
The balance of parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase
can be seen as a small bubble. As heat is applied, the
liquid expands, forcing the bubble smaller and smaller as
the liquid pressure increases. Continued heating forces
the liquid to push out against the bulb, causing the glass
to shatter, opening the waterway and allowing the deflector to distribute the discharging water.
Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and standard response sprinklers should not be intermixed.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 156
Rev. B
Bulletin 156
Rev. B
UL Listing Category
Sprinklers, Automatic &Open
Quick Response Sprinklers
UL Guide Number
VNIV
Pendent
Product Description
Reliable Models F1FR 300 QR Upright, Pendent and
Recessed Pendent Sprinklers are high pressure rated
automatic sprinklers which can handle a maximum
service pressure of 300 psi (20,7 bar).
These automatic sprinklers are quick response
sprinklers which utilize a 3.0mm frangible glass bulb.
They have demonstrated response times in laboratory
tests which are five times faster than standard response
sprinklers. This quick response enables Model F1FR-300
sprinklers to apply water to a fire much faster than
standard response sprinklers of the same temperature
rating.
The glass bulb contains an accurately controlled
amount of special fluid hermetically sealed inside. The
other sprinkler parts are made of brass, copper or
beryllium nickel.
At normal temperatures, the glass bulb contains fluid
in both the liquid and vapor phases. The vapor phase
can be seen as a small bubble. As heat is applied, the
liquid expands, forcing the bubble smaller and smaller as
the liquid pressure increases. Continued heating forces
the liquid to push out against the bulb, causing the glass
to shatter, opening the waterway and allowing the
deflector to distribute the discharging water.
The temperature rating of the sprinkler is identified by
the color of the glass bulb.
Recessed Pendent
Application
The most common applications for Model F1FR-300
Quick Response Sprinklers will be in fire protection
systems for high rise buildings where a quick response
rating is required and the pressure entering the sprinkler
system is in excess of 175 psi (12 bar). The use of these
sprinklers will provide opportunity to reduce or eliminate
the need for pressure reducing valves.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Upright
Pendent
Nominal
Orifice Size
"
(15mm)
17 "
32
(20mm)
"
(15mm)
17 "
32
(20mm)
Nominal K Factor
Thread Size
US
Metric
5.6
80
8.0
115
5.6
80
8.0
115
Sprinkler Height
2.2"
(56mm)
2.4"
(61mm)
2.2"
(56mm)
2.4"
(61mm)
Approval
Organizations
Sprinkler
Identification
Number (SIN)
1, 2, 3
R5625
1, 2, 3
R5622
1, 2, 3
R5615
1, 2, 3
R5612
Pendent
Upright
"
(15mm)
17 "
32
(20mm)
Thread Size
Nominal K Factor
US
Metric
5.6
80
8.0
115
Sprinkler
Height
2.2"
(56mm)
2.4"
(61mm)
Escutcheon Data
Escutcheon Approvals Adjustment (1)
Model
F1
(1)
1, 2, 3
" (19mm)
Face of Fitting to
Ceiling Dimension
3 " 15
16 - 16 "
(5mm - 24mm)
2.
Approval
Organizations
1, 2, 3
R5615
1, 2, 3
R5612
(1)
Installation
Finishes
Standard Finishes:
Sprinkler
Escutcheon
Brass
Bronze
Chrome
Chrome
White Polyester Coated
White Painted
Special Application Finishes:
Sprinkler
Escutcheon
Bright Brass
Bright Brass
Black Plated
Black Plated
Black Paint
Black Paint
Off White
Off White
Satin Chrome
Satin Chrome
(1)
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Finish (where applicable)
Maintenance
Model F1FR-300 Sprinklers should be inspected
quarterly and the sprinkler system maintained in
accordance with NFPA 25. Do not clean sprinklers with
soap and water, ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming.
Remove any sprinkler that has been painted (other than
factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should be maintained in the original
cartons and packaging until used to minimize the
potential for damage to sprinklers that would cause
improper operation or non-operation.
Sprinkler
Temperature
F
Ordinary
Ordinary
Intermediate
Intermediate
High(1)
(1)
135
155
175
200
286
C
57
68
79
93
141
Maximum Ambient
Temp.
Bulb Color
F
C
Orange
38
100
Red
38
100
Yellow
66
150
Green
66
150
Blue
107
225
Sprinkler Types
Standard Upright
Standard Pendent
Recessed Pendent
3.
Automatic sprinklers
Deluge valves
Check valves
Sprinkler wrenches
Open sprinklers
Spray nozzles
Sight drains
Alarm valves
Retard chambers
Air compressors
Pressure gauges
Identification signs
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Recycled
Paper
UL Listing Category
Design Criteria
UL Guide Number
VNIV
Product Description
The Reliable Model VELO-ECOH Extended Coverage Sprinkler has a very extra large orifice, Nominal
K=14.0 (200). It can provide Ordinary Hazard protection to 400 ft2 (37.2 m2 ) at lower pressures than an XLO
which has a K=11.2 (160.2).
The Model GFR VELO-ECOH Sprinklers provide protection in Ordinary Hazard Group 1 and 2 Occupancies
to 400 ft2 (37.2m2) per sprinkler when the system is designed to NFPA 13 hydraulic density requirements.
Model GFR VELO-ECOH Upright Sprinklers are to be
installed according to the design criteria shown in this
bulletin. The use of ECOH sprinklers can provide opportunities for lower system installation costs by requiring fewer sprinklers, less piping and reduced labor.
Model GFR VELO-ECOH Sprinklers use a levered
fusible alloy solder link.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Technical Data
Sprinkler
Model
GFR VELOECOH
Upright (1)
(1)
Thread
Size
Orifice
Size
NPT
(R)
0.70
(18mm)
Temperature
Rating
Max. Ambient
Temp.
165
74
100
38
212
100
150
66
Maximum
Sprinkler
Spacing
Maximum
Coverage
Area
20 ft.
(6.1 m)
400 ft.2
(37.2 m2)
Approvals
Sprinkler
Identification Number
(SIN)
1,2
R6553
20 ft. x 20 ft.
(6.1m x 6.1m)
(1)
Coverage
Area
400 ft.
2
(37.2m )
0.15 gpm/ft2
2
(6.1L/min/m )
Density
0.16 gpm/ft2
2
(8.1 L/min/m )
Density
(6.5 L/min/m )
Density
0.19 gpm/ft2
2
(7.7 L/min/m )
Density
Ordinary Hazard 3
0.21 gpm/ft2
2
Nominal
K Factor
(8.25 L/min/m )
Density
Flow
Pressure
Flow
Pressure
Flow
Pressure
Flow
Pressure
Flow
Pressure
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
gpm
(L/min)
psi
(bar)
60.0
(227)
18.4
(1,3)
80.0
(302)
32.7
(2,3)
64.0
(242)
20.9
(1,5)
76.0
(287)
29.5
(2,1)
84.0
(318)
36.0
(2,5)
US
Metric
14
200
For spacing and coverage areas less than 20 ft. x 20 ft. (6.1m x 6.1m) and 400 ft2, the flows and
pressures for the 20 ft. x 20 ft. (6.1m x 6.1m) spacing and 400 ft2 (37.2m2) area must be used.
Maintenance
Model GFR VELO-ECOH Upright Extended Coverage Sprinklers should be inspected quarterly and the
sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any
sprinkler that has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper operation or non-operation.
Ordering Information
Specify:
1. Sprinkler Model
2. Temperature Rating
3. Sprinkler Finish
Finishes(1)
Standard Finishes
Bronze
Chrome Plated
(1)
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Recycled
Paper
Sales Offices
Sales Fax
Corporate Offices
Internet Address
P/N 9999970181
Thread
Size
Nominal K Factor
US
Metric
Sprinkler
Height
Approval
Organization
Pendent
NPT(R)
5.6
80
2.25 (57mm)
1, 2, 3, 4
RA1425 (1)
NPT(R)
5.6
80
57mm
3, 4
RA1475
Conventional
Pendent
Upright
(1)
K Factor
Nominal
Orifice
Thread
Size
US
Metric
Sprinkler
Height
(15mm)
NPT(R)
5.6
80
2.25 (57mm)
RA1414
2.
Nominal
Orifice
US
(15mm)
Temp. Rating
Metric
Thread
Size
Model
5.6
80
NPT
(15mm)
5.6
80
(15mm)
5.6
(15mm)
5.6
(1)
Bulb
Color
Approvals
Sprinkler
Identification
Number(SIN)
1, 2
RA1414
Sprinkler
Cover
F1FR
135F/57C
135F/57C
100F/38C
Orange
NPT
F1FR
155F/68C
135F/57C
100F/38C
Red
80
NPT
F1FR
175F/79C
165F/74C
100F/38C
80
NPT
F1FR
200F/93C
165F/74C
100F/38C
1, 2, 4
RA1414
Yellow
1, 2
RA1414
Green
1, 2
RA1414
(1)
Figure 2
Figure 1
Installation Aid
Sprinkler with a threaded Model CCP cup which is factory attached to the sprinkler. The assembly is completed by the installation of the attractive, low profile, 135F
(57C) or 165F (74C) rated Model CCP push on cover
plate assembly. The cover plate and sprinkler cup assemblies are joined using a cover plate skirt with flexible
tabs for threaded engagement. A choice of two cover
plate assemblies provide either (13mm) or 5/16 (8mm)
of cover adjustment.
Do not install these sprinklers in ceiling which have
positive pressure in the space above.
After a 25/8 (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model RC1
Wrench. A Teflon* based thread sealant should be
applied to the sprinkler threads only. The Model RC1
Wrench is then used to engage the sprinkler wrenching
surfaces and to install the sprinkler in the fitting. When
inserting or removing the wrench from the sprinkler/cup
assembly, care should be taken to prevent damage to
the sprinkler. DO NOT WRENCH ON ANY OTHER PART
OF THE SPRINKLER. The cover plate is then pushed
onto the cup. Final adjustment is made by hand turning
the cover plate until the skirt flange makes full contact
with the ceiling. Cover plate removal requires turning in
the counter clockwise direction.
Installation
Temperature Ratings
Sprinkler
Max. Ambient
Classification Temperature
Bulb Color
Temp.
C
F
Ordinary
Ordinary
Intermediate
Intermediate
High (1)
(1)
57
68
79
93
141
135
155
175
200
286
100F (38C)
100F (38C)
150F (66C)
150F (66C)
225F (107C)
Orange
Red
Yellow
Green
Blue
Escutcheon Data
Escutcheon
Approvals
Model
F1
1, 3, 4
F2
1, 2, 3, 4,
FP Push-on/
Thread-off
1, 4
Adjustment
A
Dimension
Max Recess
Min Recess
Max Recess
Min Recess
Max Recessed
Min Recessed
1 (38.1mm)
34
/ (19.1mm)
1 (38.1mm)
1 (25mm)
7 16
/ (11mm)
15 16
/ (24mm)
Face of Fitting
to Ceiling or
Wall Dimension
3 16
/ - 15/16
(5mm - 24mm)
3 16
/ - 11/16
(5mm - 17mm)
11/2 (38.1mm)
1 (25.4mm)
Maintenance
The Models F1FR 56 and F1FR 56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle
vacuuming. Remove any sprinkler which has been painted
(other than factory applied) or damaged in any way. A stock
of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Finishes (1)
Sprinkler
Bronze
Chrome Plated
White Polyester
Coated (4)(5)
Standard Finishes
Escutcheon
Brass
Chrome
Plated
White Painted
Cover plate
Chrome
White
(2)
(3)
(4)
(5)
Bright Brass
Black Plated
Black Paint
Off White
Satin Chrome
Bright Brass
Satin
Off White
Black Paint
Black Plated
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where
9. Cover plate Model
10. Cover plate Thread size
11. Cover plate Temperature
12. Cover plate Adjustment
13. Cover plate Finish
applicable)
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Productsmanufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A 12/09