Electrical auxiliaries

100-250AF

Functions
and characteristics

AX - AL - AXAL - ALV

Plug-in location: AX - AL - AXAL - ALV

EZC100

EZC100-2P. EZC100-3P.

EZC100-4P.

EZC250

EZC100.

EZC250-3P. EZC250-4P.

EZCV250

EZCV250-3P. EZCV250-4P.

AXAL and AX electrical auxiliaries on EZC100.

Indication contacts

Provide remote circuit breaker status information.


They can be used for indications, electrical locking, relaying, etc.
Common-point changeover contacts.
Auxiliary switch (ON/OFF)
AX indicates the position of the circuit breaker contacts.
Alarm switch (trip indication)
bb AL indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v operation of a voltage release.
bb ALV indicates that the circuit breaker has tripped due to an of earth-leakage fault.
They return to de-energised state when the circuit breaker is reset.
AXAL electrical auxiliaries on EZC250.

Characteristics
Contacts

Rated thermal current (A)


Minimum load
Utilisation category (IEC 60947-5-1)
Operational current (A) 24 V
48 V
125 V
250 V

5
10 mA at 24 V
AC12
AC15
5
5
5
5
5
3
3
2

DC12
4
2.5
0.4
0.2

Connections
Connection wire length
Cross-section

AXAL, AX and ALV electrical auxiliaries on EZCV250.

A-14

450 mm
EZC100: 1 mm2,
EZC250/EZCV250: 1.5 mm2

DC14
3
1
0.4
0.2

Auxiliary switch (AX)


EZAUX10.

Auxiliary switch (AX)


EZEAX.

All EasyPact EZC


electrical auxiliaires
are snapped in place

Earth-leakage alarm switch


(ALV).

Designation
Auxiliary switch (AX)
Alarm switch (AL)
Auxiliary/Alarm switch (AXAL)
Earth-leakage alarm switch (ALV)
(1) Only EZCV250.

Cat. no.
EZC100
EZAUX10
EZAUX01
EZAUX11
-

EZC250/EZCV250
EZEAX
EZEAL
EZEAXAL
EZEALV (1)

A-15

Electrical auxiliaries
100-250AF

Functions
and characteristics

SHT - UVR - UVRN

Plug-in location : SHT - UVR - UVRN

EZC100

EZC100-2P. EZC100-3P.

EZC100-4P.

EZC250

EZC250.

EZC250-3P. EZC250-4P.

EZCV250

EZCV250-3P. EZCV250-4P.

SHT and UVR releases on EZC100.

Remote tripping

Shunt Trip (SHT) or Under Voltage Release (UVR/UVRN).

Shunt Trip (SHT)


bb This release trips the circuit breaker when the control voltage rises above 0.7 x Un
bb Control signals can be of the impulse type (u 20 ms) or maintained.
Under Voltage Release (UVR/UVRN)
bb This release trips the circuit breaker when the control voltage drops below a
tripping threshold
bb Tripping threshold between 0.35 and 0.7 times the rated voltage
bb Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.

SHT and UVR releases on EZC250.

Operation
When the circuit breaker has been tripped by an SHT or UVR/UVRN release, it must
be reset locally:
bb SHT or UVR/UVRN tripping takes priority over manual closing
bb in the presence of a standing trip order, closing of the contacts, even temporary, is
not possible.
Circuit breaker tripping by an SHT/UVR/UVRN release meets the requirements of
standard IEC60947-2.

Characteristics
Mechanical

Mechanical endurance

Electrical
SHT
UVR
UVRN
UVRN release on EZCV250.

Connections
SHT
UVR
UVRN

A-16

pick-up consumption
response time
seal-in consumption
response time
seal-in consumption
response time

10 % of MCCB mechnical endurance

EZC100

EZC250/EZCV250

AC/DC
< 30 VA
< 50 ms
< 5 VA
< 50 ms
< 5 VA
< 50 ms

AC
< 30 VA
< 50 ms
< 5 VA
< 50 ms
< 5 VA
< 50 ms

DC
< 35 W
< 100 ms
< 10 W
< 100 ms
< 10 W
< 100 ms

EZC100

EZC250/EZCV250

pre-wired (1 mm2)
pre-wired (1 mm2)
pre-wired (1 mm2)

pre-wired (0.5 mm2)


screws (< 2 mm2)
pre-wired (0.5 mm2)

Installation
bb EZC100 SHT and UVR: internal mounting
bb EZC250/EZCV250:
v SHT: internal mounting
v UVR: external mounting
v UVRN: internal mounting
Designation

Shunt Trip EZASHT.

Cat. no.

Shunt Trip EZESHT.


SHT
Shunt trip
release

DC

AC

UVRN
Under voltage
release
(only EZC250-4P
and EZCV250
3/4P)
DC

Under Voltage Release


EZEUVRN.

UVR
Under voltage
release

AC

Under Voltage Release


EZAUVR.

AC

DC

100-130 V

200-277 V

380-480 V

24 V
48 V
110-130 V
200-240 V
277 V
380-415 V
440-480 V
24 V
48 V
125 V
110-130 V
200-240 V
277 V
380-415 V
440-480 V
24 V
48 V
125 V

EZC100
EZASHT100AC

EZASHT200AC

EZASHT380AC

EZASHT024DC
EZASHT048DC
EZAUVR110AC
EZAUVR200AC
EZAUVR277AC
EZAUVR380AC
EZAUVR440AC
EZAUVR024DC
EZAUVR048DC
EZAUVR125DC

110-120 V
120-130 V
200-240 V
277 V
380-440 V
440-480 V

EZC250/EZCV250
EZESHT100AC
EZESHT120AC
EZESHT200AC
EZESHT277AC
EZESHT400AC
EZESHT440AC
EZESHT024DC
EZESHT048DC
EZEUVRN110AC
EZEUVRN200AC
EZEUVRN277AC
EZEUVRN400AC
EZEUVRN440AC
EZEUVRN024DC
EZEUVRN048DC
EZEUVRN125DC
EZEUVR110AC
EZEUVR200AC
EZEUVR277AC
EZEUVR400AC
EZEUVR440AC
EZEUVR024DC
EZEUVR048DC
EZEUVR125DC

Under Voltage Release


EZEUVR.

A-17

Direct rotary handle


100-250AF

Functions
and characteristics

Direct rotary handle

Suitable for Motor Control Centre (MCC) switchboards.


bb Degree of protection IP40 or IP54, IK07 (IP54 with gasket supplied).
bb The direct rotary handle maintains:
v suitability for isolation
v indication of the three positions O (OFF), I (ON) and tripped
v circuit breaker locking capability in the OFF position by one to three padlocks,
(padlock not supplied) shackle diameter 5 for EZC100, 8 for EZC250/EZCV250
v door opening disabled when the circuit breaker is ON
v circuit breaker closing is disabled if the door is open.
Direct rotary handle (black) for EZC100.

IP40 or IP54

Direct rotary handle (red/yellow) for EZC100.

EZC100.

Direct rotary handle (black) for EZC250/EZCV250.


EZC250/EZCV250.

Padlocking

EZC100.

Designation
Direct rotary handle (red/yellow) for EZC250/EZCV250.
Direct rotary handle (black)
Direct rotary handle (red/yellow)

A-18

EZC250/EZCV250.

Cat. no.
EZC100
EZAROTDS
EZAROTDSRY

EZC250/EZCV250
EZEROTDS
EZEROTDSRY

Extended rotary handle


100-250AF
Extended rotary handle

The extended rotary handle is used to control, from the front face of the
switchboard, a device installed at the back of the switchboard.
bb Degree of protection IP40 or IP54, IK08 (IP54 with gasket supplied).
bb The extended rotary handle maintains:
v suitability for isolation
v indication of the three positions O (OFF), I (ON) and tripped
v circuit breaker locking capability in the OFF position by one to three padlocks,
(padlock not supplied) shackle diameter: 5 for EZC100, 8 for EZC250/EZCV250
v door opening disabled when the circuit breaker is ON.
bb The extended rotary handle is made up of:
v a unit on the front cover of the circuit breaker (secured by screws)
v an assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally
v an extension shaft that must be adjusted to the distance between back of circuit
breaker and door.

Extended rotary handle (black) for EZC100.

IP40 or IP54

Extended rotary handle (red/yellow) for EZC100.

EZC100.

Extended rotary handle (black) for EZC250/EZCV250.

EZC250/EZCV250.

Padlocking

EZC100.
Extended rotary handle (red/yellow) for EZC250/EZCV250.

Designation
Extended rotary handle (black)
Extended rotary handle (red/yellow)

EZC250/EZCV250.

Cat. no.
EZC100
EZAROTE
EZAROTERY

EZC250/EZCV250
EZEROTE
EZEROTERY

A-19

Functions
and characteristics

Plug-in

The plug-in allows you to connect, disconnect from the


circuit breaker rapidity.

Plug-in

100 A

The plug-in base is equipped with terminals which, depending on their orientation,
serve for front and rear connection. Degree of protection IP20.

BF
EZC

BFN

NH

EZC

100

100
BFN
EZC

100

EasyPact EZC100H 100A


TM

~~
~
~~

NEMA-AB1
240
277/480Y

~
~

TH11126

Ui=690V~ Uimp=6kV Cat.A


50/60Hz 40/50C
JIS C8201-2-1
Icu/Ics(kA)
100/50
30/15
30/8
20/5
10/3
10/5

IEC 60947-2
Ue(V)
220/240
380/400
415
440
550
250

HIC (kAmps)
100
18

Front connection.

Fixation on rail DIN.

Fixation on rear plate.

Connection accessories
All accessories for fixed devices (bars, lugs) may be used with the plug-in base.

y7

y8.5

y9

y17

y17

Tightening torque

ReferencesPlug-in

y7
y9
EZAPLUG3L
EZAPLUG3H
EZAFSHB3 - set of 3
EZAPCON1L
-y17
set of 2
y17
EZAPCON1H

100 A

Kit, plug-in base 3P 15 A-50 A


Kit, plug-in base 3P 60 A-100 A
Fishbone connectors
Plug-in connectors 15 A-50 A
Plug-in connectors 60 A-100 A

EZAPCON1H

EZAPCON1L

y8.5

EZAFSHB3

Fishbone
TM

HIC (kAmps)
100
18

EasyPact

JIS C8201-2-1
Icu/Ics(kA)
100/50
30/15
30/8
20/5
10/3
10/5

~~
~~
~

~
~
NEMA-AB1
240
277/480Y

EZC100H 100A

IEC 60947-2
Ue(V)
220/240
380/400
415
440
550
250

TM

EasyPact

A-20

Ui=690V~ Uimp=6kV Cat.A


50/60Hz 40/50C

HIC (kAmps)
100
18

JIS C8201-2-1
Icu/Ics(kA)
100/50
30/15
30/8
20/5
10/3
10/5

~
~

~~
~~
~

Fishbone.

TH11126

NEMA-AB1
240
277/480Y

IEC 60947-2
Ue(V)
220/240
380/400
415
440
550
250

Ui=690V~ Uimp=6kV Cat.A


50/60Hz 40/50C

TH11126

EZC100H 100A

The fishbone, designed for vertical installation, saves space and reduces
cabling time.

Insulation of live parts

Terminal shields

Short terminal shield only.

Insulating accessories used for protection against direct contact with power circuits.
They provide IP40 degree of protection and IK07 mechanical impact protection.
Terminal-shield types
Easypact EZC 100 to 250:
bb short terminal shields
Short terminal shields
They are used with:
bb plug-in in all connection configurations
bb fixed versions with rear connection.
Terminal shields and pitch
Combination possibilities are shown below.

EasyPact EZC100H 100A


TM

NEMA-AB1
240
277/480Y

~
~

HIC (kAmps)
100
18

~~
~
~~

TH11126

Ui=690V~ Uimp=6kV Cat.A


50/60Hz 40/50C
JIS C8201-2-1
Icu/Ics(kA)
100/50
30/15
30/8
20/5
10/3
10/5

IEC 60947-2
Ue(V)
220/240
380/400
415
440
550
250

Circuit breaker Easypact EZC

100/160/250
35

Pitch (mm)

Interphase barriers

Safety accessories for maximum insulation at the power-connection points:


bb they clip easily onto the circuit breaker
bb single version for fixed devices and adapters on plug-in bases
bb not compatible with terminal shields
bb the adapter for the plug-in base is required for mounting on plug-in and
withdrawable versions.

A-21

Functions
and characteristics

Plug-in

The plug-in allows you to connect, disconnect from the


circuit breaker rapidity.

Plug-in

250 A

The plug-in base is equipped with terminals which, depending on their orientation,
serve for front and rear connection. Degree of protection IP20.

Front connection.

Fixation on rail DIN.

Fixation on rear plate.

Connection accessories
All accessories for fixed devices (bars, lugs).

LV429241

y6

y10

= =

= =

y25

y25

Tightening torque

References Plug-in

EZEPLUG3L - 60 mm breaker
EZEPLUG3H - 68 mm breaker
EZEPLUG4 - 68 mm breaker
EZEPCON1 - set of 2
EZEPCON1

A-22

250 A
Kit, plug-in base 3P 100 A - 250 A
Kit, plug-in base 3P 100 A - 250 A
Kit, plug-in base 4P 100 A - 250 A
Kit, plug-in connectors 100 A - 250 A

Insulation of live parts

Short terminal shield only

Terminal shields

Insulating accessories used for protection against direct contact with power circuits.
They provide IP40 degree of protection and IK07 mechanical impact protection.
Terminal-shield types
Easypact EZC 100 to 250:
bb short terminal shields.
Short terminal shields
They are used with:
bb plug-in in all connection configurations
bb fixed versions with rear connection.

EasyPact

TM

Terminal shields and pitch


Combination possibilities are shown below.
Circuit breaker Easypact

100/160/250

Short terminal shields

35

Pitch (mm)

Interphase barriers

Safety accessories for maximum insulation at the power-connection points:


bb they clip easily onto the circuit breaker
bb single version for fixed devices and adapters on plug-in bases
bb not compatible with terminal shields
bb the adapter for the plug-in base is required for mounting on plug-in and
withdrawable versions.

Interphase barriers.

Rear insulating screens

Safety accessories providing insulation at the rear of the device.


Their use is mandatory for devices with spreaders, installed on backplates, when
terminal shields are not used.
The available screen dimensions are shown below.
Circuit breaker Easypact
100/160/250
3P
4P

W x H x thickness (mm)
W x H x thickness (mm)

140 x 105 x 1
175 x 105 x 1

Rear insulating screens.

A-23

Power connections and cable


lugs 100-250AF

Functions
and characteristics

Standard circuit breaker terminals

All EasyPact EZC circuit breakers are supplied with terminal screws
Screw M5

EZC100 60 to 100 A

Screw M8

EZC250/EZCV250 63 to 250 A

Screw M8

EZC100 15 to 50 A

Connection of insulated bars or cables with lugs

EZC100
L (mm)
h (mm)
d (mm)
e (mm)

Bars

(mm)

Crimp lugs

y 50 A
> 50 A

L (mm)
d (mm)

(mm)
Tightening torque

y 50 A
> 50 A

y 50 A
> 50 A

y 17
d + 10
y7
y6
5.5
8.5

EZC250/
EZCV250
y 25
d + 10
y8
y6
9

y 17
y9
5.5
8.5
2 N.m
5.5 N.m

y 25
y8
9
13 N.m

Cable lugs

Cable lugs directly screwed on standard circuit breaker terminals.

Cables from 2.5 to 16 mm.

u 100 A (EZC250/EZCV250)

> 50 A (EZC100)

y 50 A (EZC100)

Cables from 10 to 50 mm.

Designation
Cable lug up to 50 A (set of 2)
Cable lug up to 50 A (set of 3)
Cable lug from 60 A up to 100 A (set of 2)
Cable lug from 60 A up to 100 A (set of 3)
Cable lug from 100 A up to 250 A (set of 3)
Cable lug from 100 A up to 250 A (set of 4)

Cables from 42.2 to 150mm.

Cat. no.
EZC100
EZALUG0502 (1)
EZALUG0503 (1)
EZALUG1002 (2)
EZALUG1003 (2)
-

EZC250/EZCV250
EZELUG2503
EZELUG2504

Important:
(1) EZALUG0502 and EZALUG0503 can be use with maximum rating of 50 A.
(2) EZALUG1002 and EZALUG1003 can be use with maximum rating of 100 A.

A-24

Power connections and


insulation of live parts
100-250AF

Spreaders

Increase the pitch of the circuit breaker terminals:


bb EZC100 from 25 mm to 35 mm
bb EZC250/EZCV250 from 35 mm to 45 mm.

Spreader.

Terminal extensions

Additional terminal extensions are available for EZC250/EZCV250 at 35 mm pitch.

Terminal extensions.

Designation

Cat. no.

EZC100
EZASPDR3P
EZASPDR4P
-

Spreaders for 3-pole breaker (set of 3)


Spreaders for 4-pole breaker (set of 4)
Terminal extension for 3-pole breaker (set of 3)
Terminal extension for 4-pole breaker (set of 4)

EZC250/EZCV250
EZESPDR3P
EZESPDR4P
EZETEX
EZETEX4P

Phase barriers

bb Safety accessories for maximum insulation at the power connection points.


bb Usable with all other connection accessories, except terminal shields.
bb Each breaker is delivered with a set of phase barriers
(1 for 2 poles, 2 for 3 poles and 3 for 4 poles breaker).
bb Additional set of phase barriers available for insulation between outgoings or
between 2 side by side mounted breakers.

Phase barriers for EZC100.

Designation
Phase barriers for EZC250/
EZCV250.

Phase barriers for 60 mm depht (set of 2)


Phase barriers for 68 mm depht (set of 3)

EZC100
EZAFASB2
-

EZC250/EZCV250
EZEFASB2
EZEFASB3N

Terminal shields

Cat. no.

bb Insulating accessory used for protection against direct contacts with power circuit
connections. It provides a degree of protection of IP20 and a mechanical resistance
of IK07.
bb The long terminal shield is used with front cable or isolated busbar connections.
bb Designed for 3-pole EZC100, 3, 4-pole EZC250/EZCV250.

Terminal shield for EZC100.

Terminal shield
for EZC250/EZCV250.

Designation
Terminal shield 3P, 60 mm depth (set of 2)
Terminal shield 3P, 68 mm depth (set of 2)
Terminal shield 4P, 60 mm depth (set of 2)
Terminal shield 4P, 68 mm depth (set of 2)

Cat. no.

EZC100
EZATSHD3P
EZATSHD4P
-

EZC250/EZCV250
EZETSHD3P
EZETSHD3PN
EZETSHD4PN

A-25

DIN rail adaptor, padlocking,


sealing screws 100-250AF

Functions
and characteristics

DIN rail adaptor

Breaker mounting on a DIN rail is possible by using special adaptator (EZC100 only).
Number of adaptators:
bb one for two 1P, or one 2P or one 3P
bb two for one 4P.

Mounting on DIN rail (optional).

Designation

Cat. no.
EZC100
EZADINR

Din rail adaptor

EZC250/EZCV250
-

Padlocking system

Locking in the OFF position guarantees isolation as per IEC 60947-2.


Padlocking system can receive:
bb up to 2 padlocks 5 mm (padlocks not supplied) for EZC100
bb up to 3 padlocks 8 mm for EZC250/EZCV250 (padlocks not supplied).

Padlocking device for


EZC100.

Padlocking device for


EZC250/EZCV250.
Toggle locking using a removable device:
for EZC100

Designation
Padlocking system
Padlocking system for EZC250-3P
Padlocking system for EZC250-4P and
EZCV250-3/4P

A-26

for EZC250/EZCV250

Cat. no.
EZC100
EZALOCK
-

EZC250/EZCV250
EZELOCK
EZELOCKN

Sealing screws

Designation
Sealing screws (set of 2)

Cat. no.
EZC100
EZASSCR

EZC250/EZCV250
-

A-27

Electrical auxiliaries 400AF

Functions
and characteristics

AX - AL

DB119648

Plug-In location: AX - AL

EZC400-3P.
EasyPact

TM

EZC 400N

EZC400-4P.

Indication contacts

Provide remote circuit breaker status information.


They can be used for indications, electrical locking, relaying, etc.
Common-point changeover contacts.

Auxiliary switch (ON/OFF)


AX indicates the position of the circuit breaker contacts.
Alarm switch (trip indication)
AL indicates that the circuit breaker has tripped due to:
bb an overload
bb a short-circuit
bb operation of a voltage release.
It returns to de-energised state when the circuit breaker is reset.
Functions (AL or AX) is determined by the mounting location of the auxiliary
EasyPact

TM

Characteristics

EZC 400N

Contacts

Rated thermal current (A)


Minimum load
Utilisation category (IEC 60947-5-1)
Operational current (A) 24 V

AX and 2 AL.

48 V
125 V
250 V

5
10 mA at 24 V
AC12
AC15
5
5

DC12
4

DC14
3

5
5
3

2.5
0.4
0.2

1
0.4
0.2

5
3
2

Connections
450 mm
1.5 mm2

Connection wire length


Cross-section

Signalling switch (AX or AL).

All EasyPact EZC


electrical auxiliaires
are snapped in place

Double signalling switch


(2 AX or 2 AL).

Designation
Signalling switch (AX or AL)
Double signalling switch (2 AX or 2 AL)

A-28

Cat. no.
EZ4AUX
EZ4AUX2

SHT - UVR

Plug-In location: SHT - UVR

EZC400-3P.
EasyPact

TM

EZC400-4P.

EZC 400N

Remote tripping

Shunt Trip (SHT) or Under Voltage Release (UVR).


Shunt Trip (SHT)
bb This release trips the circuit breaker when the control voltage rises above 0.7 x Un
bb Control signals can be of the impulse type (u 20 ms) or maintained.

Under Voltage Release (UVR)


bb This release trips the circuit breaker when the control voltage drops below a
tripping threshold
bb Tripping threshold between 0.35 and 0.7 times the rated voltage
bb Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.

EasyPact

TM

Operation
When the circuit breaker has been tripped by an SHT or UVR release, it must be
reset locally:
bb SHT or UVR tripping takes priority over manual closing
bb in the presence of a standing trip order, closing of the contacts, even temporary, is
not possible.
Circuit breaker tripping by an SHT or UVR release meets the requirements of
standard IEC60947-2.

EZC 400N

Characteristics

SHT or UVR voltage release.

Mechanical

Mechanical endurance

10 % of MCCB mechanical endurance

Electrical
AC
SHT
UVR

pick-up consumption
response time
seal-in consumption
response time

< 30 VA
< 50 ms
< 5 VA
< 50 ms

DC
< 35 W
< 100 ms
< 10 W
< 100 ms

Connections
Connection wire length
Cross-section
Shunt Trip SHT.

450 mm
1.5 mm2

Shunt Trip UVR.

Installation
SHT and UVR: internal mounting
Designation
SHT
Shunt Trip
Release

AC

DC
UVR
Under Voltage
Release

AC

DC

Cat. no.
24-48 V
100-240 V
277 V
380-480 V
24-48 V
100-220 V
24 V
48 V
100-110 V
120-130 V
200-240 V
277 V
380-480 V
24 V
48 V
125 V

EZ4SHT048ACDC
EZ4SHT200ACDC
EZ4SHT277AC
EZ4SHT400AC
EZ4SHT048ACDC
EZ4SHT200ACDC
EZ4UVR024ACDC
EZ4UVR048ACDC
EZ4UVR110ACDC
EZ4UVR130ACDC
EZ4UVR200AC
EZ4UVR277AC
EZ4UVR400AC
EZ4UVR024ACDC
EZ4UVR048ACDC
EZ4UVR130ACDC

A-29

Direct rotary handle 400AF

Functions
and characteristics

Direct rotary handle


Suitable for Motor Control Centre (MCC) switchboards
bb Degree of protection IP50, IK07.
bb The direct rotary handle maintains:
v suitability for isolation
v indication of the three positions O (OFF), I (ON) and tripped
v circuit breaker locking capability in the OFF position by one to three padlocks,
(padlock not supplied) shackle diameter 8
v door opening disabled when the circuit breaker is ON
v circuit breaker closing is disabled if the door is open.

IP50

Padlocking

Designation
Direct rotary handle

A-30

Cat. no.
EZ4ROTDS

Extended rotary handle 400AF

Extended rotary handle

The extended rotary handle is used to control, from the front face of the
switchboard, a device installed at the back of the switchboard.
bb Degree of protection IP54, IK08 (IP54 with integrated seal).
bb The extended rotary handle maintains:
v suitability for isolation
v indication of the three positions O (OFF), I (ON) and tripped
v circuit breaker locking capability in the OFF position by one to three padlocks,
(padlock not supplied) shackle diameter: 8
v door opening disabled when the circuit breaker is ON.
bb The extended rotary handle is made up of:
v a unit on the front cover of the circuit breaker (secured by screws)
v an assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally
v an extension shaft that must be adjusted to the distance between of circuit breaker
and door.

IP54

Padlocking

Designation
Extended rotary handle

Cat. no.
EZ4ROTE

A-31

Power connections, cable lugs,


spreaders and extensions
400AF

Functions
and characteristics

Standard circuit breaker terminals


All EasyPact EZC circuit breakers are supplied with terminal screws
Screw M10

EZC400 250 to 400 A

Connection of insulated bars or cables with lugs


L (mm)
h (mm)
d (mm)
e (mm)
(mm)

y 32
d + 10
y 10
y 10
10

Crimp lugs

L (mm)
d (mm)
(mm)

y 32
y 10
10
30 N.m

Bars

Tightening torque

Cable lugs
Cable lugs directly screwed on standard circuit breaker terminals,
for cables from 35 to 300 mm.

Designation

Cable lug up to 400 A (set of 3)


Cable lug up to 400 A (set of 4)

Cat. no.

EZ4LUG4003
EZ4LUG4004

Terminal extensions

Extend power connection of the EZC400 at 44 mm pitch.


Designation

Extend power connection for 3-pole breaker (set of 3)


Extend power connection for 4-pole breaker (set of 4)

Cat. no.

EZ4TEX3P
EZ4TEX3P

Spreaders

Increases the pitch of the circuit breaker terminals to 70 mm.


Designation

Spreaders 70 mm for 3-pole breaker (set of 3)


Spreaders 70 mm for 4-pole breaker (set of 4)

A-32

Cat. no.

EZ4SPDR73P
EZ4SPDR74P

Insulation of live parts


and padlocking 400AF

Phase barriers

bb Safety accessories for maximum insulation at the power connection points.


bb Usable with all other connection accessories, except terminal shields.
bb Each breaker is delivered with a set of phase barriers
( 2 for 3 poles and 3 for 4 poles breaker).
bb Additional set of phase barriers available for insulation between outgoings or
between 2 side by side mounted breakers.

Designation
Phase barriers for 3-pole breaker (set of 2)
Phase barriers for 4-pole breaker (set of 3)

Cat. no.
EZ4FASB2
EZ4FASB3

Terminal shields

bb Insulating accessory used for protection against direct contacts with power circuit
connections. It provides a degree of protection of IP20 and a mechanical resistance
of IK07.
bb The long terminal shield is used with front cable or isolated busbar connections.
bb Designed for 3, 4-pole EZC400.

Designation
Terminal shield for 3P (set of 2 parts)
Terminal shield for 4P (set of 2 parts)

Cat. no.
EZ4TSHD3P
EZ4TSHD4P

Padlocking system

Locking in the OFF position guarantees isolation as per IEC 60947-2.


Padlocking system can receive up to 3 padlocks 8 mm (padlocks not supplied).

Designation
Padlocking system

Cat. no.
EZ4LOCK

A-33

A-34