Mechanical Strength
RESIBLOC cast resin transformers
provide ultimate withstand to thermal
and mechanical stress associated
with overload and short circuit
conditions because of the licensed
glass fiber roving technique which
binds the coil together for maximum
mechanical strength.
Short Circuit Integrity
The RESIBLOC design components,
70% glass fiber content, epoxy
insulation system, and the licensed
combination of glass fiber radial
and cross bracing introduced during
the winding process are all
combined in the RESIBLOC cast
resin coil to achieve a virtual
winding block. The result is a
hermetically sealed coil with
exceptional mechanical strength,
high short circuit withstand
capability and extreme thermal
shock stability at both high and
low temperature levels.
Environmentally Friendly
An environmentally safe epoxy
insulation system which is highly
resistant to moisture, chemical
contamination, fire and explosion,
Core Construction
The core is manufactured from high
permeability cold-rolled, grain
oriented silicon steel. The steel is
precision cut to assure that it will
be smooth and burr-free.
RESIBLOC transformers utilize a
step-lap mitered core construction
to ensure optimum performance
and minimal sound levels. The
mitered core joints allow efficient
flux transfer along natural grain
lines between the core legs
and yoke.
The step-lap construction further
enhances the efficiency of the
joint by reducing joint fringing,
which reduces core losses and
exciting current. The core is
designed and built to provide the
lowest possible losses from the
effects of magnetic hysteresis and
eddy currents. All possible steps
are taken to prevent local
circulating currents and to avoid
built-in bending stresses.
The finished core is coated with a
corrosion resistant sealant, which
provides lamination cohesion and
environmental protection.
For rigidity and support, the upper
and lower yokes are solidly clamped
with steel support members.
Smooth outer
surfaces of the
RESIBLOC
cast resin
transformer
restricts dirt
and dust
accumulation.
Strip wound secondary and sectionalized
primary winding cutaway view.
Coil Construction
Low Voltage Windings
Indoor/Outdoor Application
NEMA1
Indoor Enclosure
NEMA 3R
Outdoor Enclosure
Typical forced air cooling increases the rated capacity of RESIBLOC transformers 33 1/3% on units
up to 3750 kVA and 25% for units 3751 kVA and larger.
Electronic Temperature
Monitor (ETM)
The ETM combines temperature
indication and fan control functions
for the transformer and accepts
input from three thermal sensors.
Features:
Digital temperature display
Hottest winding temperature is
automatically displayed
Temperature of any single
winding can be displayed
Maximum temperature can be
recalled even if the supply
power has been interrupted
Fan, alarm, and trip functions
are controlled by the hottest
winding temperature
DPDT contacts are provided
for fan, alarm, and trip functions
Contacts are dry
Alarm relay is fail-safe
Fans can be manually operated
Includes internal sonic alarm,
which can be temporarily silenced
without canceling the alarm circuit
Optional Features
Fan exerciser (programmable)
will energize fans once per week
Remote communication available
through RS-232 port.
15 kV 95 kV BIL Copper 80
kVA
Height
Width
Depth
Weight
Inches (mm)
Inches (mm)
Inches (mm)
Lbs. (kg)
300
90 (2286)
90 (2286)
60 (1524)
500
750
96 (2438)
102 (2591)
60 (1524)
60 (1524)
1000
90 (2286)
90 (2286)
90 (2286)
6000 (2724)
7500 (3405)
9000 (4086)
102 (2591)
60 (1524)
60 (1524)
10,500 (4767)
1500
102 (2591)
114 (2896)
2000
2500
3000
102 (2591)
102 (2591)
102 (2591)
102 (3048)
126 (3200)
138 (3505)
66 (1676)
66 (1676)
66 (1676)
15,500 (7037)
20,000 (9080)
23,500 (10,669)
14,500 (6583)
Values listed are typical and should not be used for construction purposes.
Quality Assurance
RESIBLOC coils have successfully passed severe thermal shock tests with no cracking.
Optional Tests:
1. Impulse Tests-full and
3.
4.
5.
6.
7.
8.
9.
Specifications
Self-Cooled
Power Rating
kVA
Primary
Voltage
kV
Primary BIL
kV
Secondary
Voltage
kV
Secondary BIL
kV
Temperature
Rise
C
112.5-25,000
Up through 35
Up to 150
Up through 15
Up to 75
80
8.
Temperature Rise
ANSI C57.12.01
ANSI C57.12.91
ANSI N45.2-1977
NRC 10CFR50 Appendix B
ISO 9001
NEMA ST20
MIL-I-45208A
kVA 3-Phase
112 1/2
FanCooled
Ventilated
Dry
150
225
300
500
400
667
750
1000
1000
SelfCooled
Secondary Voltage
Fan-Cooled
208Y/120 480Y/277
Weather
480
240
Resistant
Delta
Delta
Ventilated
X
X
X
X
X
400
X
X
kVA Correction
2400 Delta
4160Y /
2400
4160 Delta
Altitude
(FT)
RESIBLOC
(AA)
3300
4000
5000
.994
.985
6000
.975
Forced Air
(FA)
1.00
BIL
Correction
1.00
.989
1.00
.98
.95
.974
667
7000
.966
X
X
8000
1333
1000
1333
X
X
.959
.944
9000
.957
.948
.929
.914
1000
1500
1333
2000
1333
2000
X
X
X
X
X
X
.939
.930
.898
.883
.80
.77
2000
2500
3750
2666
3333
4687
2666
3333
4687
.868
.853
.838
.75
.72
.70
6250
9375
12,500
6250
9375
X
X
X
X
X
.921
.912
.903
5000
7500
X
X
10,000
11,000
12,000
13,000
14,000
15,000
.894
.823
.67
12,500
10,000
.92
.89
.86
.83
Ventilated
(Class AA
Rating)
kVA
40
45
50
0-1167
1168-1667
1668-2000
68
69
501-700
701-1000
1001-1500
1501-2000
2001-3000
3001-4000
4001-5000
55
60
62
64
65
66
68
70
71
2001-3333
3334-5000
5001-6667
6668-8333
71
73
74
75
5001-6000
6001-7500
72
75
0-9
10-50
51-150
151-300
301-500
Class FA
and AFA
Rating
67
1
S
1
1
S
1
1
S
15.0
25.0
34.5
1
1
S
1
1
2
1
2
1
S
NOTES:
S = Standard value.
1 = Optional higher levels where exposure to overvoltage occurs
and improved protective margins are required.
2 = Lower levels where protective characteristics of applied surge
arresters have been evaluated and found to provide appropriate
surge protection.
Impedance Chart
kVA
ANSI Std.
112.5-500
None Specified
501 & Larger *
5.75%
* For Units with 60 kV Primaries and below.
1
S
ABB
5.75%
5.75%
Specification Guide
The transformer shall be RESIBLOC epoxy cast resin,
dry type construction, three (3) phase, (50,60) Hz. The
epoxy cast resin design being offered must have a minimum
5 years documented field experience. Mean time to failure
analysis per ANSI C57.117-1986 must be provided as
evidence for field experience.
Each coil shall be provided with four (4) approximately 2.5% full capacity tap connections on the surface
of the coil in the high voltage winding, two (2) above
and two (2) below normal, for deenergized tap changing
made accessible by removable panels on the transformer
enclosure.
The transformer shall be mounted in a heavy gauge ventilated steel enclosure for (indoor, outdoor) use. The
enclosure shall be finished with ANSI 61 paint color. The
paint shall be applied using an electrostatically deposited
dry powder paint system. The transformer bus and enclosure shall be custom manufactured to ensure interchangeability with existing HV and LV equipment.
The transformer base shall be designed and fabricated to
permit jacking, rolling, or skidding in any direction.
ABB Inc.
Dry Type
Liquid Filled
www.abb.com/transformers