Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
electrical-engineering-portal.com/test-on-110kv-power-cable-after-installation-1
12/22/2014
Test On 110kV Power Cable After Installation Part 1 (on photo: Kyoritsu 4102A digital earth resistance tester)
Description
Remark
1/7
Check cable bends to ensure that bending radius is equal to or greater than the minimum
bending radius specified
Verify that shields are terminated as specified (through link box or directly grounded)
Verify the exact route length as per approved drawings from terminations to terminations
Check that all grounding points are securely connected to ground grid as specified
10
11
Single core cable connected between power transformer and switchgear shall be single
point earthed as switchgear side and at floating side SVL (sheath voltage limiter) should be
installed
12
Check single point or both ends, via voltage limiter as per approved design
13
14
15
16
17
Check the cable outer jacket for any physical damage during and after installation
18
Check for the cross connection of cable metallic sheath in cross bonding system
19
Check the rubber seal in cable clamps to avoid any damage to cable outer jacket
20
Check the insulating shrouds are installed at the base of the cable terminations
21
For accessories (sealing terminations, instrument panels and link boxes) check the
following:
a. Name plates installed and data is correct
b. Danger signs
c. Bolt tightness check and paint work conditions
2. Electrical Test
2/7
(Standards Reference is IEC 60840, and relevant SEC Transmission specifications 11-TMSS-02, TCS-P-104.08).
ITEM
Description
10
11
12
13
Remark
3/7
Instructions
1. The screens of all cables at one end are to be shorted and grounded.
2. The conductor of the cable under test is to be connected to the negative pole of the meter.
3. The positive pole of the meter is to be grounded.
4. Through a switch ground the other end of this conductor of the cable under test and measure the
resistance.
5. If the resistance becomes zero, the phase identification is ok and checks whether the correct color coding is
applied or not.
6. To cross check, open the switch, the meter shall read high resistance (Tending to infinity).
4/7
7. Similarly repeat the test for other phases and verify the correctness of color coding.
Reference
IEC 60228 Conductors of insulated cables
Instructions
1. The conductors are short circuited at the far end by minimum 95 mm 2 cable.
2. The other ends of the cable are connected to the bridge according to equipment instructions.
3. Note down the measured value.
4. The resistance of conductor at 20C/km is obtained by substituting the measured value in the formula.
Formula for Temperature Correction:
For Copper R20 = R/L (1 + 0.00393*(T-20)) /KM
Where,
R20 Conductor resistance at 20C *(ohm/km
R Measured resistance of one phase (ohm)
L Exact length (km)
0.00393 Temperature coefficient at 20C for copper (K)
T Temperature of conductor when measured in C
5/7
3. Capacitance Test
The capacitance shall be measured between conductor and metallic screen. According to IEC, the measured
value shall not sxceed the normal value specified by the manufacturer by more than 8%.
Reference
IEC 60840 Applies to cable voltage ratings between 30 kV and 150 kV. It includes a regular type test
sequence for cables and a separate sequence for the cable accessories.
6/7
Instructions
Connections are made as per below schematic.
Connect the instrument cable between conductors and metallic screen and take the measurements.
The capacitance is measured between each individual conductor and sheath. A capacitance bridge is used
for this measurement.
The value obtained can be converted to F/km
Formula for Capacitance:
C = Cm/L (F/km)
Where:
C Capacitance in F/k
Cm Measured Capacitance in F
L Length of Cable in km.
To be continued soon
7/7