Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
INSTRUCTIONS
GEH-2O57
CONTENTS
PAGE
DESCRIPTION
APPLICATION
RATINGS
CHARACTERISTICS
BURDENS
CONSTRUCTION
11
ACCEPTANCE TESTS
12
INSTALLATION PROCEDURE
13
ADJUSTMENTS
17
CALCULATION OF SETTINGS
18
OPERATING PRINCIPLES
25
MAINTENANCE
25
26
RENEWAL PARTS
29
GEH2057
GEII2057
Since the relay burden is likely to be small compared to the lead burden, in
creasing the CT ratio tends to improve the relative performance of the CTs as a result
of reducing the maximum secondary fault current and increasing the accuracy of the CTs.
The CT secondary current should not exceed the continuous thermal rating of the CT
secondary winding.
The relay current corresponding to maximum KVA (on a forcedcooled basis)
should
not exceed twice tap value, the thermal rating of the relay.
The CT ratios should be high enough that the secondary currents will not damage
the relay under maximum internal fault conditions (refer to RATINGS).
The relay current corresponding to rated KVA of the power transformer (on a selfcooled basis) should not exceed the relay tap value selected (magnetizing inrush might
operate the instantaneous overcurrent unit).
If the transformer under consideration
does not have a self-cooled rating, the transformer manufacturer should be consulted
for the equivalent selfcooled rating; that is, the rating of a self-cooled
trans
former that would have the same magnetizing inrush characteristics as the transformer
being considered.
The current transformer tap chosen must be able to supply the relay
with eight
times rated relay tap current with an error of less than 20 percent of total current.
If the current transformers produce an error of greater than 20 percent at less
than
eight times tap value, the harmonic content of the secondary current may be suffici
ent
to cause false restraint on internal faults.
The CT ratios should be selected to provide balanced secondary current on external
faults.
Since it is rarely possible to match the secondary currents exactly by
selection of current transformer ratios, ratio-matching taps are provided on
the relay.
Currents may usually be matched within five percent using these taps.
When the
protected transformer is equipped with load ratio control, it is obvious that a
close
match cannot be obtained at all points of the ratio-changing range. In this case
the
secondary currents are matched at the middle of the range, and the percentage-di
fferen
tial characteristic of the relay is relied upon to prevent relay operation on
the
unbalanced current which flows when the load-ratio control is at the end of the range.
In some applications, the power transformer will be connected to the high voltage
or low voltage system through two breakers, as shown in Figure 9; for example,
a ring
bus arrangement. In this case, the CT ratios must be selected so that the secondary
windings will not be thermally overloaded on load current flowing around the
ring in
addition to the transformer load current. It is recommended that CTs on each of the two
low voltage (or high voltage) breakers be connected to a separate restraining winding
to assure restraint on heavy through-fault current flowing around the ring bus.
Two parallel transformer banks should not be protected with one set of differen
tial protection, since the sensitivity of the protection will be reduced. In addition,
if the banks can be switched separately, there is a possibility of flash operation
on
magnetizing inrush to one transformer bank causing a sympathetic inrush into the bank
already energized.
In this case, the harmonics tend to flow between the banks, with
the possibility that there will be insufficient harmonics in the relay current to
restrain the relay.
GEII-2057
t
2
r
where:
I
t
48,400
current in amperes
time in seconds
GEH-2057
CHARACTER 1ST I Cs
PICKUP AND OPERATING TIME
The operating characteristic is shown in Figures 4 and 4A. The
curve for various
percentage slopes shows the percent slope versus the through-curre
nt flowing in the
transformer.
The percentage slope is a figure given to a particular percen
t slope
tap setting, and indicates approximate slope characteristic.
Pickup
at
zero
restraint is approximately 30 percent of tap value (see Table
I). Figure 4A is the
same curve, except it is expanded from five to zero amperes.
Curves of the operating time of the main unit and of the instant
aneous unit are
shown plotted against differential current in Figure 5. The main
unit time given is
the total time, and includes main unit operating time and auxilia
ry unit operating
time.
OVERCURRENT UNIT PICKUP
The overcurrent unit is adjusted to pick up when the differe
ntial current
transformer ampere-turns are eight times the ampere-turns produc
ed by rated tap
current flowing in that tap.
For example, when only one CT supplies current, and
the tap plug for the CT is in the five ampere tap, 40 ampere are
s
required for
pickup.
This pickup value is based on the AC component of current transfo
rmer
output only, since the differential current transformer in the relay
produces only a
half cycle of any DC (offset) component present.
If ratio matching taps are chosen so that rated CT current is not
greater than
the tap rating on a selfcooled basis, the overcurrent unit will
not pick up on
magnetizing inrush.
If CT currents are greater than tap rating, there is danger
that the unit may pick up, especially on small transformer banks.
If this happens,
then the CT ratio or relay tap setting should be increased, rather
than increasing
the pickup of the overcurrent unit. If the overcurrent unit setting
must be raised,
the requirements on CT error will be more stringent, in accord
ance with the
following equation:
E
where:
E
P
=
=
20
(?.5)(P8)
GEH- 2057
nbalanced
tha I the secondary Cu rrents become u
unbalanced
currents
the
GEH- 2057
BURDENS
Note that burdens and minimum pickup values are substantially independent of the
The
percent slope settings, and are all approximately 100 percent power factor.
amperes.
5.0
at
current
transformer
figures given are the burdens imposed on each
TABLE I
RELAY
1D
1)D
ILL)DDiJL)
lLuDDLuu
TAP
SETTING
AMPS
ZERO
RESTRAINT
PICKUP****
AMPS
2.9
3.2
3.5
38
4.2
4.6
5.0
8.7
OPERATING CIRCUIT**
60 HERTZ RELAYS***
IMPEDANCE
BURDEN
OHMS
VA
3.2
2.7
2.4
2.0
1.9
1.6
1.5
0.7
0.87
0.96
1.05
1.14
1.26
1.38
1.50
2.61
0.128
0.108
0.096
0.080
0.076
0.064
0.060
0.028
RESTRAINT CIRCUIT
60 HERTZ RELAYS***
IMPEDANCE
BURDEN
OHMS
VA
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.5
0.052
0.048
0.044
0.040
0.036
0.032
0.028
0.020
GEH2057
special
transformers is completed through a
ided
The primary circuit of each of these
prov
are
ns
itio
pos
tap
Two or three horizontal rows of
ghthrou
tap block arrangement.
each
for
row
one
),
16B
Type BDD15B or BDD
is
a
y
rela
the
her
whet
is
on
ng
mer
endi
(dep
t transfor
A tap on the differential curren
by
ings
wind
current transformer winding.
of the through-current restraint
connected to a corresponding tap
inserting tap plugs in the tap blocks.
in Figure
four-circuit applications, as shown
When the BUD16B relay is used on
connected
ally
norm
er
jump
ected to stud 7, and the
ted at
nnec
9, the fourth circuit CT is conn
disco
be
ld
shou
le,
of the relay crad
rear
the
at
1,
and
6
s
inal
term
block (above
between
nnected to the upper row in the tap
reco
be
ld
shou
It
end.
6
inal
term
differential
the
which connects it directly to the
should be
the row marked winding number 1),
The terminal on the movable lead
y.
movable
the
in
current transformer in the BOD rela
t
s the best match for the curren
placed under the tap screw that give
end.
currents.
line current transformer secondary
The taps permit matching of unequal
ts, and a tap
that when matching secondary curren
ged
arran
so
are
ns
ectio
conn
tap
sponding taps
The
another in a horizontal row, the corre
ghcurrent
plug is moved from one position to
throu
transformer winding, and one of the
-current
ugh
on both the differential current
thro
ent
y selected, so that the perc
transformer windings are simultaneousl
restraint remains constant.
THROUGH-CURRENT RESTRAINT CIRCUIT
of each
ives the output of the secondary
of all
A full wave bridge rectifier rece
uts
outp
In the BDD16B relay, the DC
mer.
stor
resi
ed
throughcurrent restraint transfor
tapp
a
The total output is fed to
l.
three units are connected in paralle e at the front of the relay.
A 15, 25 or 40
plat
(R3) through the percent slope tap
Resistor taps are
cted by means of three taps.
sele
be
may
nt
stme
adju
e
slop
percent
the 40 percent
to
ds
spon
corre
The right tap
es.
slop
n
give
for
set
pre
and
le
stab
adju
ied to the restraint coil of the
The output is rectified and appl
slope setting.
polarized unit.
DIFFERENTIAL CURRENT CIRCUIT
plies the
er secondary output directly sup
form
trans
t
ren
cur
tial
eren
diff
The
a series tuned
coils of the polarized unit through
ating
oper
the
t,
uni
The
us
neo
anta
inst
nant trap.
t circuit through a parallel reso
r
ifie
rect
e
circuit, and the harmonic restrain
each passed through a full wave bridg
operating and restraint currents are
unit coils.
before passing through the polarized
or (Cl) and a
e up of a five niicrofarad capacit
mad
is
uit
circ
ant
reson
es
seri
The
ency, and
currents of the fundamental system frequ ected in
pass
to
d
tune
are
h
whic
(Li)
tor
reac
is conn
ts of other frequencies. Resistor Ri
to offer high impedance to curren
to give the
sted
adju
be
can
and
r,
ifie
operate rect
ied to the
parallel on the DC side of the
appl
The output of the rectifier is
desired amount of operate current.
t.
operating coil of the polarized uni
(C2) and a
e up of a 15 microfarad capacitor
mad
is
trap
ant
reson
l
alle
par
The
e allowing
fundamental frequency currents whil
k
bloc
to
d
tune
are
h
whic
(L2)
Resistor
reactor
e.
pass with relatively little impedanc
to
s
encie
frequ
onic
harm
of
ts
r, and
ren
ifie
cur
AC side of the harmonic restraint rect
R2 is connected in parallel on the
can be
GEH2057
adjusted to give the desired amount of harmonic restraint. The output of the rectifier
is paralleled with the through-current restraint currents and applied to the restraint
coil of the polarized unit.
It is evident that if the differential current applied to the Type BOO relay has
sinusoidal wave form and system frequency, it will flow mostly in the operating coil
circuit, and will cause the relay to operate. If on the other hand, the differential
current contains more than a certain percentage of harmonics, the relay will be re
strained from operating by the harmonic currents flowing in the restraint coil.
A Thyrite resistor connected across the secondary of the differential current
transformer limits any momentary high voltage peaks which may occur, thus protecting
the rectifiers and capacitors from damage, without materially affecting the character
istics of the relay.
OVERCURRENT UNIT
The instantaneous unit is a hinged armature relay with a selfcontained target
indicator.
On extremely heavy internal fault currents, this unit will pick up and
complete the trip circuit. The instantaneous target will be exposed to indicate that
tripping was through the instantaneous unit.
Because of saturation of the CTs and relay transformers at high fault currents,
it is possible that less operating current will be provided from the differential
current transformer than the percentage slope tap would imply, and more harmonic
restraint will be provided than the actual harmonic content of the fault current would
supply. As a result, the main unit may be falsely restrained under conditions of a high
internal fault current. However, tripping is assured by the overcurrent unit opera
tion.
Pickup is set above the level of differential current produced by maximum
magnetizing inrush current. Figure 5 shows the relative levels of pickup and speed of
operation of the main unit and overcurrent unit.
MAIN OPERATING UNIT
The main operating unit of Type BOO relays is a sensitive polarized unit with
components as shown within the large circuit of the internal connection diagrams,
Figures 10 and 11.
The unit has one operating and one restraining coil, and its
contacts are identified as DHR (differential harmonic restraint) on the diagrams of the
external connections diagrams, Figures 7, 8 and 9.
The relay is a high-speed, low
energy device, and its contacts are provided with an auxiliary unit whose contacts are
brought out to studs for connection in an external circuit.
The polarized unit is mounted on an eightprong base, which fits a standard octal
radio socket, and is protected by a removable dust cover.
It is mounted behind the
nameplate of the BOO relay, and should require no further adjustment after the relay is
shipped from the factory.
The auxiliary unit carries an indicating target, and is located on the lefthand
side (front view) of the relay. The coil of this unit is not connected in the main
circuit as a sealin coil, but is connected to the OC control bus through an open
contact of the polarized relay, and through a series resistor. A tap block is provided
on the nameplate for selecting either of two DC control voltages.
Registered Trademark of the General Electric Co.
10
GEN- 2057
11
G[H-2057
If the relays are not to be installed immediately, they should be stored in their
original cartons in a place that is free from moisture, dust and metallic particles.
Foreign flatter collected on the outside of the case may find its way to the inside of
the case when the cover is removed, creating the possiblity of relay misoperation.
ACCEPTANCE TESTS
Immediately upon receipt of the relay, an inspection and acceptance test should be
made to insure that no damage has been sustained in shipment, and that the relay
calibrations have not been disturbed.
VISUAL INSPECTION
Check the nameplate stamping to insure that the model number, rating and
calibration range of the relay agree with the requisition. Remove the relay from its
case and check that there are no broken or cracked molded parts or other signs of
physical damage, and that all screws are tight.
MECHANICAL INSPECTION
Check the operation of the auxiliary and instantaneous overcurrent units manually
to see that they operate smoothly without noticeable friction or binding in the
rotating structure of the units.
ELECTRICAL TESTS:
The following electrical tests are recommended upon receipt of the relay:
o
o
o
o
of main
of the
test on
test on
operating unit
instantaneous overcurrent unit
the harmonic restraint characteristic
the slope characteristic curve for the approximate
TEST FACILITIES
The following test equipment will facilitate tests:
o
o
o
o
o
o
Check the pickup of the main unit using the connections shown in Figure 12.
During this test, the selector switches (52 and S4) are open, and current passes
through the differential circuit only.
For example, on a relay set with 25 percent
slope and a 2.9 ampere ratio matching tap, the main unit should pick up at 30
percent of tap rating, plus or minus ten percent; or the pickup should be between
0.78 and 0.96 ampere.
To check that the main unit has picked up, a source of DC
power
at
rated
12
GEH- 2057
vide a
The indicating lamp will pro
current flowing
pickup at 1.5 amperes with
the
set
t,
tes
up
pick
nal
and 25 percent slope
For an additio
tap plugs in the five ampere
the
e
plac
and
6,
and
5
s
very low energy level,
in terminal
s a polarized unit with a
use
ay
rel
I3DD
If the
the
ce
Sin
us ten percent.
tap position.
y as much as plus or min
var
may
pickup
g
d
tin
set
eate
Rep
up
pick
be made.
the minimum
eres, no adjustment should
amp
5
have
1.6
may
and
5
ch
1.3
whi
een
ts,
betw
tes
pickup is
memory of previous
c
neti
mag
the
l
se
wil
era
which
operations in succession
ault will produce an effect relay has
h-f
oug
thr
ere
sev
A
affected the first tests.
The pickup of the BDD
ed to pick up the relay.
the relay design
increase the current requir
tive relays, but due to
tec
pro
st
mo
than
ons
iati
ditions, even during
wider permissible var
ly adequate under all con
ire
ent
is
cy
ura
acc
ay
rel
and application,
s.
sh or severe fault condition
transformer magnetizing inru
the harmonic current
in the A position, check
S2,
h,
itc
sw
or
ect
sel
the
With
INSTALLATION PROCEDURE.
restraint as described in
high current
be checked by passing a
uld
sho
t
uni
nt
rre
Check
rcu
rating.
The instantaneous ove
about eight times tap
be
uld
sho
kup
Pic
s.
nal
through the 56 termi
CEDURE.
described in INSTALLATION PRO
as
int
tra
res
ent
urr
h-c
oug
thr
t with the selector
plete, check relay dropou
com
are
ts
tes
er
oth
the polarized operating
After the
s test is to insure that
thi
of
e
pos
pur
can leave
The
n.
ope
switches(es)
al fault current, which
ern
int
vy
hea
a
er
aft
amperes to
element will reset properly
Apply a current of 30
re.
ctu
stru
c
neti
mag
its
position, and
excessive residual flux in
dings in the 2.9 ampere tap
win
all
for
gs
plu
tap
h
This will cause the
terminals 5 and 6 wit
t slope position.
cen
per
25
the
in
g
plu
reduced, rapidly at
the percent slope tap
The current should then be
y.
rpl
sha
up
pick
to
Dropout current should be
auxiliary relay
ry relay drops out.
ilia
aux
the
il
unt
ly
slow
, the polarized unit
first, and then
t is other than as specified
ren
cur
t
pou
dro
If
re.
mo
0.1 ampere or
replaced.
is defective, and should be
INSTALLATION PROCEDURE
TESTS
d
ibration that will be use
vice, check the relay cal
ser
in
ay
e.
rel
pos
pur
the
s
thi
ing
plac
Before
outlined for
following test procedure is
to insure it is correct. The
Ri, R2 and R3.
by adjusting resistors
hed
plis
om
acc
is
n
atio
the other two
CAUTION: The relay calibr
e resistors will affect
thes
of
one
any
in
e
nged, the pickup,
Changes mad
event one setting is cha
the
In
gs.
tin
set
ent procedures should
resistors
urrent restraint adjustm
h-c
oug
thr
and
int
tra
res
ation is noted. The
harmonic
iation from proper calibr
dev
r
the
fur
no
il
unt
d
eate
be rep
restraint adjustment is
when the through-current
d
aine
obt
are
s
ult
res
t
bes
tings are correct.
made after the other two set
PlC KU P
13
GEH-2057
The condition of the magnetic circuit is influenced by the manner in which pickup
current is removed after a test.
For this reason, pickup readings will be slightly
lower if the current in the differential circuit is reduced gradually, than if the
current is abruptly reduced or interrupted.
Energy is stored in the series tuned
circuit when the current is applied.
This energy is dissipated in the harmonic
restraint circuit, the path of least impedance, when the current is abruptly reduced or
removed. The restraint coil of the polarized unit, having approximately three times as
many turns as the operating coil, receives a greater saturating effect than the opera
ting coil. The net effect is as though a restraint saturating current were applied to
the relay.
Since the BDD relays use a polarized unit with very low energy level, the minimum
pickup may vary as much as plus or minus ten percent.
If the pickup is found to be
anywhere within this range, 1.351.65 amperes, the setting should not be disturbed.
With DC control voltage applied to the proper studs of the relay, the pickup of
the auxiliary unit can be used as an indication of operation of the polarized relay
unit. This voltage may be applied as shown in Figure 14, and the indicating lamp will
indicate that the main unit has operated.
If the pickup is found to be out of adjustment, adjust the position of the band on
resistor Ri, which is connected in parallel with the operating coil of the polarized
unit. Resistor Ri is located at the top of the relay, and is the left-hand adjustable
resistor (see Figure 2).
HARMONIC CURRENT RESTRAINT
The harmonic restraint is adjusted by means of a test rectifier, used in conjunc
tion with suitable ammeters and load boxes.
The test is shown in Figure 14, with S2
closed to position A. Tests should be made on the 5.0 ampere and 25 percent slope taps.
The analysis of a single-phase, half wave rectified current shows the presence
of fixed percentages of DC, fundamental and second harmonic components, as well as
negligible percentages of all higher even harmonics.
This closely approximates a
typical transformer inrush current, as seen at the relay terminals, inasmuch as its
principal
components are DC, fundamental and second harmonic.
Although the percent second
harmonic is fixed, the overall percentage may be varied by providing a path for a
controlled amount of by-passed current of fundamental frequency.
The by-passed
current is added in phase with the fundamental component of half wave rectified
current, thus providing a means of varying the ratio of the second harmonic to
fundamental current.
The following expression shows the relationship between the percent second har
monic, the DC component, and the bypass current:
14
GEH2057
% Second harmonic
0.212 x DC
0.45 x Ii + 0.5 x DC
x 100
15
GEH-2057
NOTE:
BAND ON
RESISTOR R3
13
Right
Middle
Left
30
30
30
AMPERES
TRUE SLOPE
(11/13 X 100)
1j
12.0
7.5
4.8
13.2
8.3
5.0
40.0
25.0
15.0
44.0
27.5
16.5
The percent slope tolerance is ten percent of nominal, all in the plus
direction.
This is to insure that the slope characteristic never falls
below tap value.
check
the
dropout
of
the
main
unit
as
LOCATION
The location should be clean and dry,
lighted to facilitate inspection and testing.
vibration,
and well
MOUNTING
The relay should be mounted on a vertical surface.
drawings are shown in Figure 18.
CONNECTIONS
The internal connection diagrams are shown in Figures 10 and 11.
Typical wiring
diagrams for different applications are shown in Figures 7, 8 arid 9. Any through
16
GEl-I- 2057
17
GEH2057
I (Unbalance).
0.2]) x Tap
The unbalance percentage equals 100 times the unbalance current, divided by the
For a three winding bank, this unbalance must be checked
measured tap current.
with load on at least two pairs of windings in order to insure that the connections are
correct.
The curves in Figure 16 show the approximate voltages across terminals 8 and 9
required to operate the relay for various percent slope tap settings and through
currents, expressed as percentages of tap. To insure a margin of safety against false
operation, the unbalance voltage should not exceed 75 percent of that voltage required
to operate the relay for any given through-current and percent slope tap setting. This
extent of unbalance may result from the relatively high error currents of low ratio
These curves represent the BUD relay
bushing CTs at low multiples of tap current.
A voltage measurement across studs 8 and 9 of 15 percent or less of
characteristic.
the value given on the curve does not necessarily indicate that the relay will operate
This is especially true when very high through
at higher through-current values.
faults may cause CT saturation.
Small rectifier-type AC voltmeters are suitable for measurement of unbalance. The
voltmeter should not be permanently connected, since the shunt current it draws reduces
the relay sensitivity.
PERCENT SLOPE SETTING
Taps for 15, 25 and 40 percent slope settings are provided in both BDD15B and
It is common practice to use the 25 percent setting unless special
BDD16B relays.
See the PERCENT SLOPE SETTING
connections make it advisable to use one of the others.
instruction book for further
section
of
this
OF
SETTINGS
heading in the CALCULATION
details.
CALCULATION OF SETTINGS
METHOD
The calculations required for determining the proper relay and current transformer
taps are outlined below. Connections for a sample calculation for the transformer are
shown in Figure 17.
CURRENT TRANSFORMER CONNECTIONS
Current Transformer Connections
o Wye-delta
0 Deltawye
0 Wye-wye
o Delta-delta
o Deltadelta
Delta-wye
Wye-delta
Delta-delta
Wye-wye
Delta-zigzag
o with zero degrees phase shift
between primary and secondary
18
G[H-2057
1.
2.
3.
where:
4.
19
GEH- 2057
Check that the sum of relay currents that will he applied to the relay for a fault
at the terminals of the power transformer is less than 220 amperes RMS for one
second.
If the period during which a fault current flows in the relay can
definitely be limited to a shorter time, a higher current can be accommodated in
accordance with the equation:
2 x seconds
(Amperes)
48,400
Also check that the sum of the multiples of tap current on an internal or external
fault does not exceed 150.
CURRENT TRANSFORMER RATIO ERROR
The current transformer ratio error must be less than 20 percent at eight times
relay rated tap current.
This is based on the instantaneous unit being set at its
normal setting, which is eight times tap rating. If the instantaneous unit pickup is
raised above this value, the 20 percent figure must be reduced as described in
CHARACTERISTICS.
As far as CT performance is concerned, the calculations listed below are for the
worst fault condition, which is an internal ground fault between the CT and the
transformer winding, with none of the fault current supplied through the neutral of the
protected transformer.
1.
Ne
+ 2.50f
1000
2.27R ohms
NOTE:
B
N
e
f
R
=
=
=
=
=
2B
Ne
2.50f
1000
+
2.27R ohms
The multipliers used on the f and R terms include factors to cover two
leads instead of one, increase of resistance due to temperature rise,
and resistance of longest CT leads.
20
GEH- 2057
TABLE III
TOTAL BURDEN FOR 60 HERTZ RELAYS
DD TAP
(AMPS)
2.9
3.2
3.5
3.8
4.2
4.6
5.0
8.7
2.
8 TIMES
TAP (AMPS)
BURDEN (B)
(OHMS)
23.2
25.6
28.0
30.4
33.5
36.8
40.0
69.6
0.180
0.156
0.140
0.120
0.112
0.096
0.088
0.048
MINIMUM
PICKUP (AMPS)
0.87
0.96
1.04
1.14
1.26
1.38
1.50
2.61
NOTE:
3.
Esec
IZ
4.
transformer being
the particular tap of current
of
ve
cur
ion
itat
exc
the
From
ondary voltage,
t, iE corresponding to the sec
used, determine excitation curren
Esec
5.
each CT
Determine the percent error in
Percent error
IE
x 100
If it does, choose a
t of any set of CTs.
This should not exceed 20 percen
selection of
and repeat the calculations on
higher tap on that set of CTs,
cent ratio error.
relay taps, mismatch error and per
PERCENT SLOPE SETTING
rmined by the sum of:
A proper percent slope is dete
, or automatic tap
taps and the load-ratio control
o The maximum range of manual
changing means in percent.
of the relay taps.
o The maximum percent of mismatch
21
GEH2057
Thu percentage slope tap selec Lcd should he grea ter than the ratio of ma xi mum
total error current to the smallest of the throughcurrents.
In general, if the
total error current does not exceed 20 percent, the 25 percent tap is used.
If it
exceeds 20 percent, but not 35 percent, the 40 percent tap is used.
If the movable lead is used (as in Figure 9, for example), the percent slope
Lap chosen should he twice as high, since the movable lead provides no restraint.
DEiERM1NATION OF CT TURNS AND ODD RELAY TAP SETTINGS
Transformer and Line
MAX Ip = 3750/f(]ine kV)
A
19.7
15.7
20
0.98
0.79
Delta
1 .37
100% Ip
= 3000/ /3
(line kV)
CT turns
MAX sec (less than 5 amps)
100% sec
CT connections
Relay Current for 100% sec
Assume
B
49.5
39.6
20
2.47
1.98
Wye
1.98
C
157
125
60
2.62
2.08
Delta
3.60
Select a relay tap for one of the line currents and calculate
what the currents in other lines would be if they were increased
by the same ratio.
If any current is greater than the square
root of three times any other line, the 8.7 tap should be chosen
for it, and new, ideal, relay taps calculated for the other
lines.
A
C
B
Ideal relay taps (set C
8.7)
3.31
4.78
8.7
3.2
4.6
8.7
4.6
3.2
Ratio of secondary
lines currents:
1.98
1.37
Mismatch:
1.44
8.7
4.6
1.43
1 4
1.43
1.43
-
1.89
22
0 7%
1.89
3.60
1.98
Mismatch:
1.82
1.82
1.82
-
3.8Z
GEB- 2057
8.7
Ratio of secondary
linescurrents:
3.60
1.37
2 72
2.72
Mismatch:
2 63
2.63
2.63
-
4Q/
Line B:
0.312
0.096
0.205
0.568
(20 x 2.5)
1.085
(2.50 x 35)
2.27(0.25)
0.568
1000
0.096 0.138
Line C:
2(0.048)
0.568
(60 x 2.3)
0.096 0.169
0.80
(2.5 x 12.4)
0.568
1000
+
0.568
A
0.085
25.6
27.8
1.00
Impedance, ohms
Eight times tap, amperes
E CT voltage required (Ii)
curve
IE required, from excitation
Percent Ratio Error
3.4%
0.833
B
0.8
36.8
29.4
50
136%
C
0.833
69.6
50.8
0.5
0.8%
er tap on CT to improve
Exciting curve on line B is too high, try high
CT performance.
23
GEH 2057
REPEAT:
100% I
Try CT turns: (necessary to
change C also for proper match)
100% sec
Relay current
Ideal relay taps (set C
8.7)
Use taps:
15.7
39.6
20
0.79
1.37
4.40
4.6
40
0.99
0.99
3.19
3.2
80
1.56
2.70
8.7
8.7
0.912
25.6
23.4
0.25
1.0%
0.879
69.6
61
0.17
0.3%
C
125
Burdens on CT5:
Line A:
0.192
0.205
0.568
0.965
Line B:
0.156
0.188
0.568
0.912
Line C:
0.096
0.215
0.568
0.879
A
Impedance, ohms
Eight times tap, amperes
Esec CT voltage required (IZ)
IE required, from excitation curve
Percent of ratio error
0.965
36.8
35.6
1.1
3.1%
Percent error is less than 20 percent, so CT and relay taps are satisfactory.
PERCENT SLOPE SETTING
Assume load ratio control, maximum range
Relay tap mismatch, from above (lines A-B)
10.0
4.6%
14.6%
24
-._
GEH-2O57
OPERATING PRINCIPLES
TARGETS
liary relay and the instantaneous
Targets are provided for both the auxi
nal fault, one or both of these units will
overcurrent unit. In the event of an inter
e. This will produce a target indication on
operate, depending upon the fault magnitud
it
does not function as a sealin since
the unit that operates. The auxiliary relay
ld
shou
t
targe
the
r a fault is cleared,
does not carry breaker tripping current. Afte
.
relay
the
of
er
lower left hand corn
be reset by the reset slide, located at the
DISABLING TYPE BDD RELAYS
the BDD relay must be disabled to
When bypassing a breaker during maintenance,
val
by a remote switch rather than by remo
prevent false tripping. If disabling is done
autions must be taken:
of the relay connection plug, the following prec
open the trip circuit at stud 1. The
Short circuit studs 8 and 9 of the relay, or
use the series resistors in the auxiliary
trip circuit should be opened at stud 1 beca
rated control voltage, in the event that
relay circuit cannot withstand continuously
the polarized relay operates.
part of the disabling procedure, the
If the CT secondaries are short-circuited as
ted
and studs 8 and 9 should be shortcircui
trip circuit should be opened at stud 1,
CT
the
g
uitin
t-circ
ted. Do not rely on shor
before the CT secondaries are shortcircui
ing.
tripp
false
e
caus
in shorting time may
secondaries only, because any difference
MAINTENANCE
CONTACT CLEANING
cleaning fine silver contacts. This
A flexible burnishing tool should be used for
d-roughened surface, which in effect
is a flexible strip of metal with an etche
no
action of this file is so delicate that
resembles a superfine file. The polishing
and
y
it cleans off any corrosion thoroughl
scratches are left on the contacts, yet
ing of the actual points of
The flexibility of the tool insures the clean
rapidly.
contact.
with knives, files, or abrasive paper
Fine silver contacts should not be cleaned
ion
ches which increase arcing and deteriorat
or cloth. Knives or files may leave scrat
g
latin
insu
of
cles
parti
te
minu
Abrasive paper or cloth may leave
of the contacts.
prevent closing.
abrasive material in the contacts and thus
be obtained from the factory.
The burnishing tool described above can
25
GEH- 2057
An operation Lest and inspection of the relay and its connections should be
Tests may he performed as described in
made at least once every six months.
INSTALLATION TESTS, or they made he made on the service taps as described in this
section.
When inserting or withdrawing a U-shaped test plug throughjumper to complete
the trip circuit through the test plug, similar throughjumpers should also be used
If not,
on studs C and 9 to maintain the connections from the relay to the case.
false tripping upon insertion or removal of the test plug nay occur.
PICKUP
When checking pickup on a particular service tap, the expected plus or minus
ten percent variation still applies, with the following acceptable as found values
Ii
EXAMPLE:
3.5 amperes
winding 1 Lap
to
0.90 x 0.30 x 3.5
1.16
amperes
to
0.94
Ii
3.5 amperes
tap
0.80 x 3.5 = 2.8 amperes
to 1.10 x 3.5
x 3.5
to 3.85 amperes
2.25 x 2.8
26
6.30 amperes
12 (Ac)
if the
2.25 x 2 (DC)
rectifier back
GEII2057
THROUGH-CURRENT RESTRAINT
test current values indicated
In order to check the service tap slope setting, thein tap setting into account.
in Table II must be modified to take differences
be set up so that the lead from
Furthermore, the test circuit shown in Figure 14 must
onding to the winding with
corresp
ammeter 13 to the test plug is connected to the stud
stud corresponding to the
the
to
ted
the lowest tap setting. The common lead is connec
winding with the highest tap setting.
the following equation:
For any combination of taps, the percent slope Is given by
=
Percent slope
where:
Ti
12
Ii
13
=
=
=
=
[fl
12
J!
13
1)
1} x 100
13
I1(min)
ii(max)
=
=
=
21.0 amperes
21.0 amperes
22.2 amperes
27
GEH2057
TABLE IV
TAPS
TI
15
1.
2.9
15
25
40
15
3.5
25
3.8
40
25
15
17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
4.6
25
40
15
5.0
25
40
15
8.7
25 40
4.3
7.0
4.6
6.7
8.8 12.0
2.9 4.8
7.7
5.0
9.4 12.8
19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 19.2 12.8 12.8 12.8
(mln)
1
I
2.9
4.8
7.7
4.9
7.0 10.2
(max)
1
3.2
5.3
8.5 5.3
7.8 11.0
7.4
9.8 12.3 16.1 12.5 15.3 19.4 15.3 18.3 22.8 27.5 31.0 36.2
21.0 21.0 21.0 31.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 21.0 14.0 14.0 14.0
3.1
5.2
&4
5.2
7.5 10.9
B.O 10.5 14.3 10.7 13.5 17.8 13.5 16.5 21.0 28.3 29.8 35.0
3.5
5.8 9.3
5.6
8.1 11.8
8.4 11.2 15.3 11.2 14.2 18.8 14.0 17.3 22.2 26.9 30.7 36.5
22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8 22.8 15.2 15.2 15.2
(mln)
1
3.4
5.7
(max)
1
3.8
6.3 10.0
13
9.1
8.7 12.5
6.2
25.2 25.2 25.2 25.2 25.2 25.2 25.2 25.2 25.2 16.8 16.8 16.8
(mln)
1
3.8
6.3 10.1
6.5
9.3 13.4
(max)
1
4.2
7.0 11.1
(mln)
1
4.1
6.9 11.0
6.9
(max)
1
4.8
7.6 12.2
13
5.0
15
(max)
1
4.6
4.2
25 40
6.6 9.5
(max)
1
4.2
4Q 15
2.6
13
3.8
3.2
40
(mtn)
1
13
3.2
2.9
25
(min)
1
4.5
(xnax)
1
8.7
(mai)
1
28
5.5
9.0 14.2
6.1
9.9 15.7
GEH2057
RENEWAL PARTS
for the prompt
parts should be kept in stock
l
ewa
ren
of
ties
nti
qua
Sufficient
n, broken or damaged.
replacement of any that are wor
of the General
ress the nearest Sales Office
When ordering renewal parts, addthe part wanted, quantity required, and complete
e of
Electric Company. Specify the nam number, of the relay.
ial
ser
the
ng
udi
incl
nameplate data,
RENT RESTRAINT
n changed in the THROUGHCUR
bee
has
n
atio
equ
the
n,
tio
edi
Since the last
section on p.27.
29
GEH2057
INSTANTANEOUS
OVERCURRENT
UNTIDOC)
AUXLIARY
UN
SERIES TUNINT
CAPACITOR
IC.
PCACENTAGEt
CALIBRATING
RESISTORIRSI
PERCENT
SLOPE TAP
PLATE
uG CONROL
VOLTAGE TAP
PLA1E
DIFFERENTIAL
CURRENT
TNTt10CT
RECTWIEN
TERMINAL
BOARD
RATIO
MATCH PIG
TAPS
ThROUGH
CURRENT
RESTRAINT
TRANSFORMER
I TC TI
L
Figure 1(8031389) Type SOD Relay, Out of Case, Front Right View
HARMONIC RESTRAINT
ADJUSTING
RESIST
IRZI
PICKUP ADJUSTING
NEASTCR IRS
I
SERIES
TUNING
PARALLEL
TUNING
INDUCTOR ILZI
TI-ITRITE
RESISToR
-t
PRINTED CIRCUIT
RECTIFIER BOARD
SENSITIVE
POLARIZED UNIT
I OHRI
0
PARALLEL
TUNING
CAPACITOR
IC2I
Figure 2 (8031391) Type SOD Relay, Out of Case, Rear Left View
30
_i
GEH-2057
!Jvvvvvvvvvvvvv
T AVE
TYP:CAL OFFT FAULT CURREN
TYPCAL TRANSFORMER
NRUSH CURRENT WAVE
MAGNET.ZNG
t andMagnetizing
Figure 3 (6209195-0) FaultCurren
s
eform
Inrush Current Wav
31
GEH2057
80
NOTE:
70
6
zs
::::::0
:::::::::
50-----
Ui
0
CI)
Ui
C)
Ui
4
8
10
6
THROUGH CURRENT IN MULTIPLES OF TAP
12
32
14
16
U,
I)
C,
LI)
rI
C-,
-s
3-
CD
+10
U,
(D
70
10
30
50
T
S
I
0 40
P
E
C
E
I 1 iiJI1IJiI
l\
III{IjlI
1fff
iIItliII4
EDN E!I1 1
il .11.
III
I1f1ii ihL
.LLI
11I
P 60
80
90
O0
H
i
IILjIJHIii
ZBDDI6B(-)A
rf 1 1
i
f.
I
l- .{.
.LLJ
-..
iH
::
NOMINAL SLO
I: I
OUGH
ER RELAYS THR
NDING TRANSFORM LER OF THE TWO
NOTE: FOR TWO WI
AL
AS THE SM
CURRENT IS TAKEN
SFORMERS,
E WINDING TRAN
CURRENT. FOR THRE
NG OR
OMI
E
INC
TH
OF
E SUM
IT IS TAKEN AS TH
SMALLER.
IS
ER
EV
ICH
WH
TS
OUTGOING CURREN
AS A MULTIPLE
BE EXPRESSED
EACH CURRENT TO
OF TAP.
THROUGH CURREN
ACTERISTICS
OPERATING CHT AR
VS PERCENT SLOPE
IZBDDISB(-)A
a,
m
GEH2057
U)
U)
0
(F)
-J
C-)
>C)
Lii
C:,
34
GEH-2057
CONNECTING PLUG
MAIN
BRUSH
AUXILIARY
CONNECTING
BLOCK
TERMINAL
SHORTING BAR
BRUSH
35
GEIJ2057
at
.4
a
I..
Lu
La-
Lu
a
a
u-a
Lu
-.
a-)
a
wa
La-a
a
Lu
a
aaa-ra
Lu
aoa
vaa.i.
24
a
a
-,
Lu
a
x, --wa-a
wa
,.-a
a.--,-p--qa
a
Lu.
z.
Lu
.
o
-
a)-aLu
..J
Luwa
.a aw,aa
aa
aa --at.
--
a-..-a-ao
r
Lu-Ja
a-LuZaLu
o
oat,
a
ft La Lu Z Lu
an
.0
at.
a
0. a.. a r La. OW Lu
-x__
spat.
ta-aol
aLcoa=1
a-r
.4
ttl
a
r
a
a_aa-aL.
ClO
XaQC.ar
OIt
0 .4
a a
Lu0
a
C a--
U
a- aa
300
.4 L) La.
GEH2057
IL
IF
r
dl
LI)
It)
;A
t0
.4
a,
It
CI
+
-I
.4
Ln
In
C,
us
.r
a
-;0
c
l.a
a
J
S
.4
LI) L13L
1.3
-L
.4f.OX<
Cr
(13
t.fl
(0
O,.4l
Lfl
LL.L .4
1.. t)
.4
r-c:
(--
IXL--
4-fluJZ
us
Cr
-L
a0C
slat_I
r:
0.
or
ci
LIZ
04tL.
(.3
.45:
--Di
(13
I. 11
-a
*0(13
(4)0.4
ci
(.3
Z
.4 (0
too
4_)1l
4..
,
tF
(Is
rq-0
UI_IL) 0
L(_I.cOS
Cr;
0.
a r
a
Ut_IWO
U. (1. (0L
a
)-O
E,Cr--2__
op-u.
c,I
-
1t1.
00
(_I
I0I-
.4,0.
r -o u
0
-o
-<
Up Relays
taryOlagram for B0D16811A and
Figure 8 (026480497-1) Elemening
n
tio
ec
ot
Transformer Pr
for Three-Wind
37
GEH-2057
I--H1
i)ft
XI
II
:1
:1
-fl--
IED
I
-II
r1
a*s.
.4
1
FI
:1
HH
ri-l.a.
4-
-K
Figure9 (0264B0499-1) ElenientaryDiagram forBDD16B11A andUpRelays
for Four-Winding Transformer Protection, Using Three Restraints
38
GEH-2057
HARMc*c
RESTR.
1
Si-4ORTFIN(,E
Connections Diagram for
Figure 10 (0165A1513 [5j) Internal
Type BDD15B11A and Up Relays
39
GEH2057
HARON I C
F REQ.
RESTR.
(1)
L
D
0
=
4
c)
>:
J4
LJ
I
z
iii
LEAD NO.
TO TEFAINPL
BOARD
SHORT FINGER
40
GEH2057
L I NE
SWITCH
SI
Connections
Figure 12 (0116868011) Test
41
CD
C-,
C,
rr
(I,
CD
-1
-,
CD
-q.
Ct
cr
-s
P1
(I)
C)
rn
GEH2057
LOAD BOX
AC
TEST RECTIFIER
12
I
0148A2988
LOAD BOX
B S
2
115 VOLTS
RATED
FREQUENCY
AC
A.
TEST PLUG
(XLA12A)
Si
TEST PLUG
(XLA12A)
115 VOLTS
RATED
FREQUENCY
B.
Figure 14 (0418A0771 Sh. 2 [1]) Test Circuit for Type BOD Relays
43
GEH-2057
(I,
LJ
cD
ci
1-4
u)
L)
>-
cr\
44
(TI
CD
-a.
CD
-%
(1)
1-0
o.
bJ
cr:
ii
14++ffF
--I
1U
LL
E1E
<-J.
(I)>
Ifr
cx,
C)
1.
0i
(D
-+ll
--H__
I44-f4
-bH ++H
20
-H-
-t
FL
:i
fl
----4H--
70
tz
-H-
-1-
80
I.iff_
TT
SLOPE
4O
100
1-----
-FL
+__-*
90
4 L4J..
ZJ EEZ izLHz
+5-
JT
4-
ti
ih
iffTi-t1-1-- T
I -t
;-4--
60
THROUOH CURRENT IN PERCENT OF TAP
tt
30
44
LLL
c-n
GEH-2057
44 KV
600/5
uJ
FXA 150046
KV
600/5
LJA)
[Al
1.
FK 439115
y
13.8 KV
600/5
id
FK14.4
3000 KVA
3750 KVA
SELF COOLED
FORCED AIR COOLED
46
CEll -2057
6,625
168MM
PANEL LOCATION
SURFACE
SEMI-FLUSH
.
1 4 375
365MM
10-32 X 3/8
MTG. SCREWS
1032
STUDS
STUD
NUMBERING
97531
00000
00000
10 8
125
29MM
1/4 DRILL
4 HOLES
6MM
BACK VIEW
CUTOUT MAY REPLACE
DRILLED HOLES
5/8 DRILL
4 HOLES
4 156
5187
131MM
I
7.281
185MM
CUTIIUT
72MM
.500
12MM
(TYPICAL)
.218
5MM
3/4 DRILL
10 HOLES
19MM
PANEL DRILLING
FOR SEMI-FLUSH MOUNTING
FRONT VIEW
PANEL DRILLING
FOR SURFACE MOUNTING
FRONT VIEW
CASE
TYPICAL_DIM.
INCHES
MM
3.0
76MM
VIEW SHOWING ASSEMPLY OF HARDWARE
FUR SURFACE MTG, ON STEEL PANELS
Figure 18 (6209273
[51)
47
GE Power Management
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222
Fax: (905) 201-2098
wwwge.comlindsyslpm